Beruflich Dokumente
Kultur Dokumente
Paper 0070
Paper 0070
GPRS card) in order to upload the resulting data via the FIELD PD RESULTS
internet to the Control Center at KEMA for further
interpretation. Furthermore, in this way, the PD-OL Since various measurement systems have been installed
units can be reached via the internet for diagnostic during the year 2007 and 2008 and lots of measurement
purposes and updates. All is performed automatically results can be presented now. To do this, various
and remotely, so once installed no physical access to presentation forms are chosen in order to show the benefits
the units is needed. of doing the PD measurements on-line.
Example Circuit A
PD-OL MEASURING SEQUENCE The first result presented here originates from a cable circuit
Power cables in an on-line situation are in many cases A. The Paper Insulated Lead Covered cable circuit length is
connected to a next cable. Therefore, PD pulses do not 143 m. For illustration, only an 8 day period is shown from
reflect at all or only to a minor degree. Furthermore, in an a much longer measuring period in Fig. 2. The PD activity
on-line situation, also PD alike pulses from adjacent is very clearly varying with time; it follows the day-night
equipment arrive at the sensors. In order to discriminate load cycles, resulting in 8 clear PD concentrations with
PDs from the cable under test from other pulses and to quiet periods in between.
locate their origin, it is necessary to apply sensors at both
sides of the cable circuit, which is the chosen solution with
PD-OL. That simple fact implies that the PD-OL - CUs
installed at both cable ends do need some trick to get in time
synchronization with each other. The patented solution [5]
is that via the PD-OL - SIUs not only PDs can be measured,
but also pulses can be injected via an inductive coil (e.g.
once every minute). This pulse injection at the master PD-
OL - SIU is the accurate starting time of measuring PDs.
The slave PD-OL - SIU at the other cable end will start
doing the same immediately after receiving this injected
pulse, which is exactly the cable propagation time later.
Since the propagation time of the cable is known, accurate
time synchronization between the two PD-OL units has
become possible. Advanced signal processing techniques Fig. 2 3D plot of measured PDs from circuit A. The top
ensure that this method achieves sufficient reliability and vertical axis on the left side is charge (pC), the
accuracy. bottom left vertical axis is the location along the
cable length (143 m) and the horizontal axis is
This sequence results in time-synchronized records of data. time, which is in total ca. 8 days.
In the control unit this data is correlated with matched filter
banks in order to judge whether the measured data contains Example Circuit B
PDs. Resulting from this signal processing are tables of In Fig. 3 results from PD-OL measurements from another
detected (PD) pulses from both cable ends. Not the circuit B (2100 m in length) with Paper Insulated Lead
complete measured waveforms, but only these (much Covered cable are shown after 4 months of measurement.
smaller) resulting tables are then communicated over the Besides the increase of activity in the other cable locations
internet to the Control Center at KEMA. In this Control and the increase in magnitude of the PDs from the 1364 m
Center the results from both cable ends are combined, which joint, a completely new PD concentration of large
leads to both the elimination of pulses from other sources magnitude and high concentration has become visible.
and the determination of the location of the PD spot. Apparently, a new weak spot, next to the 1364 m joint, has
arisen, which was not or hardly visible in the first 3 months.
There are several criteria that help to eliminate other
disturbing pulses and select whether a pulse is indeed a In Fig. 4, the 3D graph of the same measurements is shown.
valid PD pulse, being discussed in detail in [4]. Also other In this graph a clear increasing trend in PD magnitude at the
particular features of the PD-OL measuring system are 1364 m joint location is shown. The PD magnitude level as
discussed extensively in [4] like the sensors applied, the such is not dangerous yet, but if this trend of increasing PD
best sensor locations, calibration matters and noise magnitude remains, degradation is very likely to exist and
suppression. In [4] also other references are mentioned, high risk levels can be reached. It is such trends that are
discussing these items in more depth. visible now and will most probably help us a lot in the
interpretation of these PD graphs, resulting in risk levels
and remaining life estimations.
Paper 0070
Paper 0070
REFERENCES
[1] P.C.J.M. van der Wielen, On-line detection and
location of partial discharges in medium-voltage
Fig. 8 2D graph of PDs measured during almost 1 month power cables, Ph.D. thesis, Eindhoven University of
on circuit F with clear PDs from a heat shrink joint Technology, Eindhoven, The Netherlands, 2005.
that failed. [2] J. Veen, On-line signal analysis of partial discharges
in medium-voltage power cables, Ph.D. thesis,
Eindhoven University of Technology, Eindhoven, The
Netherlands, 2005.
[3] P.C.J.M. van der Wielen, J. Veen, P.A.A.F. Wouters
and E.F. Steennis, “On-line partial discharge detection
of MV cables with defect localisation (PDOL) based
Fig. 9 In the XLPE insulated cable of circuit F, the
on two time synchronised sensors”, The 18th Int. Conf.
copper wire earth screen was burned away due to
on Electricity Distribution (CIRED), Session 1, Paper
excessive fault currents. These spots were found
No. 456, Turin, Italy, June 6-9, 2005.
and located with the PD-OL measuring system.
[4] P. C. J. M. van der Wielen and E. F. Steennis, “On-
Example Circuit G line PD monitoring system for MV cable connections
In Fig. 10 the 3D graph shows an increasing PD trend at with weak spot location”, IEEE Power Engineering
396 m in a 666 m long Paper Insulated Lead Covered cable. Society (PES) General Meeting, Pittsburgh,
Pennsylvania, USA, July 2008.
[5] E. F. Steennis, P. A. A. F. Wouters, P. C. J. M. van
der Wielen, and J. Veen, “Method and system for
transmitting an information signal over a power
cable”, Int. Patent No. WO 2004/013642, June 2002.
[6] E.F. Steennis and P. C. J. M. van der Wielen, "New
on-line pd monitoring system with pd location for long
mv underground power cables", 17th Conference of the
Electric Power Supply Industry (CEPSI), session 5.1,
Macau, China, October 27 – 31, 2008.
MISCELLANEOUS
Fig. 10 3D graph of PDs measured during 2 weeks on
circuit G with a clear increasing trend in PD Acknowledgments
activity in the cable at 396 m.
This work was supported by KEMA Nederland B.V. and
The cable failed at this PD spot, but a couple of days after
the Dutch utilities N.V. Continuon Netbeheer (now
the PD's reached its peak, as can be seen in Fig. 10. The
Alliander), ENECO Netbeheer B.V. (now Stedin.net) and
failure cause was the root of a tree that was pressed around
Essent Netwerk B.V. (now Enexis).
the cable, meanwhile damaging it..