Beruflich Dokumente
Kultur Dokumente
6
Draft Tariff Guidelines for Solar PV Rooftop
Plants, CERC, 2010
7
Draft Tariff Guidelines for Solar PV
Rooftop Plants, CERC, 2010 – Contd.
Power quality requirements also defined here
DC injection to be limited to 1% of the rated current of
the inverter as per IEC 61727
Use of isolation transformer at output of inverter to
achieve this
Total voltage harmonics distortion AC side <5%;
individual voltage harmonic distortion <3%; total
current harmonic distortion <8%
Adequate protection at inverter level to disconnect from
grid in no supply, under and over voltage conditions
Provision of adequate rating fuses on inverter DC side
and AC side for overload and short circuit protection
Disconnecting switches to isolate the DC and AC system
for maintenance
Manual disconnection switches at the inverter and fuses
in each solar array module to protect them against short
8
circuit
Orissa Electricity Regulatory Commission
Distribution (Conditions of Supply) Code, 2004
No direct mention of solar plants connectivity
Voltage level to depend on Connected Load for each
consumer – to be decided by Engineer of distribution
Suitable protection at connection point by developer
Connected load
Connecting Voltage
Min Max
0 (KW) 5KW / 5.55 KVA 230 V (single phase)
400 V (2Ph-3Wr or
5KW / 5.55 KVA 70 KVA
3Ph-3/4Wr)
70 KVA 555 KVA 11 KV (3Ph-3Wr)
33 KV / 11 KV (3Ph-
555 KVA 1110 KVA
9 3Wr)
MP Distribution Supply Code – voltage
levels
Connected load
Connecting
Voltage
Min Max
230 volts
0 (KW) 3 (KW)
(single phase)
Arvind Karandikar
Nexus Energytech Pvt. Ltd.
Cell: 90110 61710
14