POWER AMPLIFIER MODULE (AVLAA) 69229S906A

This module is used in Turbine control using MAX control systems for actuating
Electrohydraulic converters.

Features

• Summation and power amplifier


• Limit value monitor
• Current to voltage converter
• Load interrupt

BHEL/EDN/SAE Page 1 of 6 OM69229S906A/REV00


POWER AMPLIFIER MODULE (AVLAA) 69229S906A

LED INDICATION

A red LED (MDL) at the bottom of the module front plate is ON when limit value monitor circuits
detects output short circuits. A green LED(MDL) is ON when there is no short at the output.
A green LED (RLY) at the bottom of the module front plate is ON when the relay is not energized
A red LED (RLY) is on when relay is energized.

BUS ADDRESS

The module receives only +24V(Field Power supply) from the Bus ,other inputs and outputs are hard
wired through the front I/O connector. There is no bus communication .

MODULE OPERATION

Current to voltage conversion

Current to voltage converter converts the differential 4-20mA current signal available at the input
pins P3A-2 w.r.t P3A-1 into 0-10V voltage signal. This voltage signal is available at Jack A5. This
signal can be applied to one of the three voltage inputs of the summation amplifier stage by selecting
jumper at pin 1 & 2 of the switch S1.

Summation and power amplifier

The circuit comprises a summation unit as an integrator, two o/p amplifiers operating in a bridging
circuit and a differential amplifier stage. The load is applied to the two outputs, pin P3A-5 (Jack
A3)and P3A-6(Jack B3) each of opposite polarity. Up to three voltage signals at the input pins P3A-
3(Jack B4) , P3A-4(Jack A4) and from I/V stage can be summated. The gain is 1.1. Both outputs are
continuously short-circuit-proof relative to each other and to the zero reference voltage. The outputs
are protected against voltage surges.

Limit Value Monitor

The limit value monitor detects outputs short circuits (direct short-circuit of both outputs or short
circuit of one output to GND) by means of an analog circuit. In the event of a fault appropriate binary
signals are issued from a logic circuit and LED at the module front plate glows. Module fault will be
available at the output connector pin through potential free relay contacts at pins P3A-15(+) and P3A-
16(-).

Load Isolation
The amplifier outputs are connected via relay NC contacts for load isolation. The relay is energized by
applying high signal at pin P3A-14 through Buffer amplifier .

BHEL/EDN/SAE Page 2 of 6 OM69229S906A/REV00


POWER AMPLIFIER MODULE (AVLAA) 69229S906A
POWER SUPPLY

The module gets only field power supply available from the back plane pins P1A-18 & P1A-19
(+24V) and P1A-21 & P1A-22(GND). This power supply is protected by resetable fuse, which do
not require changing after a fault occurs . When the fault is removed and the fuse cools down, normal
operation resumes. DC-DC converter blocks are used to derive regulated -24V, +15V, -15V,
voltages required for the internal circuits and +24V is used directly from the bus.

SURGE WITHSTAND

All field inputs and outputs are protected for surges .

ELECTRICAL SPECIFICATIONS

Summation and power amplifier

Analog inputs

Pins P3A-3(B4),P3A-4(A4),
Rated voltage range : ±10V
Input resistance 33kΩ

Current input

Pins P3A-2 P3A-1


Rated current range : 4 – 20mA
Input current can be measured at jacks A1 and B1

Current output

At Jack A5(when jumper is in pins 1 & 2 of link S1)


0 to +10V(conversion accuracy 0.05%)

Analog outputs

Pin P3A-5 /jack A3 analog output


Pin P3A-6 /jack B3 analog output, inverted
The output voltage UA is the voltage between
pins P3A-5 & P3A-6 ± UA : max+24V
Output current ± IA : min.0.25A
max. 0.4A
Short circuit proof P3A-5 to P3A-6 continuous
Short circuit proof P3A-5 & P3A-6 to Gnd continuous

Jack B2 output voltage UR check back signal

BHEL/EDN/SAE Page 3 of 6 OM69229S906A/REV00


POWER AMPLIFIER MODULE (AVLAA) 69229S906A
Rated voltage range : ±3.33V

Jack A2 output voltage Us from summation amplifier.

Rated voltage range ±10V


Permissible capacitive load ≤10nF
Short circuit proof relative to GND continuous

Transfer function accuracy

a. Output voltage UA:


UA =1.1 x UE(i/p at summing ampr) UAN= ± 11V

b. Output load RL RL(max)=50R

c. Output voltage UR:


UR=-1/3UE URN =± 3.33V

d. Output voltage US :
US=1/3 UE USN =± 3.67V

e. Gain kp= UA/ UE : 1.1 ± 2.2%

f. Zero point deviation for UA: 100mV


(when inputs are connected to Gnd.)

Limit value monitor

Fault indication when limit value monitor detects o/p short circuit

Relay Contact outputs : Pin P3A-15 (+ve) & P3A-16(-ve)


Alarm (Front Plate) : MDL - Red (fault)
- Green (Healthy)
Load isolation

Binary inputs for load Isolation (by means of relay)


Pin P3A-14 : High = +24V & Low =<1V

Relay status on front plate

A green LED (RLY) ON when relay is not energized


A red LED (RLY) ON when relay is energized..

POWER SUPPLY VOLTAGE

BHEL/EDN/SAE Page 4 of 6 OM69229S906A/REV00


POWER AMPLIFIER MODULE (AVLAA) 69229S906A

Operating voltage (field PS) : +24V (Nominal )


Range : +20 to +28( P1A-18 & P1A-19)
Zero reference voltage : 0V Pin ( P1A-21 & P1A-22)
No load current consumption : 100mA
Power dissipation : 3W(no load)

MECHANICAL SPECIFICATIONS

a. Module Size : 254 X 298.5 X 42 mm


b. Edge connector : 22 pin, EB83-L22SGFW
c. Weight : 700gms

ENVIRONMENTAL SPECIFICATIONS

a. Operating temperature range : 0 to 70°C.


b. Storage temperature range : 0 to + 85°C
c. Humidity : 95%RH
d. Vibration : 0.5g with sinusoidal exitation in X,Y,Z axes
with 15 to 500 Hz.

PIN CONFIGURATION

PIN NO. FUNCTIONAL RANGE


DESCRIPTION

P1A-18 & P1A-19 Power supply +20 to +28V

P1A-21 & P1A-22 Gnd. 0V

P3A-2 w.r.t P3A-1 Current input + 4mA to +20mA

P3A-3, P3A-4 Analog I/P ±10V

P3A-5 Analog O/P non inverting, ±24V max.

P3A-6 Analog O/P inverting ±24V max.

P3A-15 Binary I/p for load isolation High- +24V


Isolation Low- < 1V
P3A-15(+) , P3A-16 Fault o/p thro relay Contacts 0.5A, 48V Max

BHEL/EDN/SAE Page 5 of 6 OM69229S906A/REV00