Beruflich Dokumente
Kultur Dokumente
com
ScienceDirect
Solar Energy 97 (2013) 460–473
www.elsevier.com/locate/solener
Received 14 February 2013; received in revised form 26 June 2013; accepted 15 August 2013
Available online 25 September 2013
Abstract
The power supply of remote sites and applications at minimal cost and with low emissions is an important issue when discussing
future energy concepts. This paper presents the modelling and optimization of a stand-alone hybrid energy system. The system consists
of photovoltaic (PV) panels and a wind turbine as renewable power sources, a diesel generator for back-up power and batteries to store
excess energy and to improve the system reliability.
For storage the technologies of lithium-ion, lead-acid, vanadium redox-flow or a combination thereof have been considered. To be
able to use different battery technologies at the same time, a battery management system (BMS) is needed. The presented BMS minimizes
operation costs while taking into account different battery operating points and ageing mechanisms.
The system is modelled and implemented in Matlab/Simulink. As input, the model uses data of the irradiation, wind speed and air
temperature measured in 10 min intervals for 10 years in Aachen – Germany. The load is assumed to be that of a rural UMTS/GSM base
station for telecommunication. For a time frame of 20 years, the performance is evaluated and the total costs have been determined.
Using a genetic algorithm, component sizes and settings have then been varied and the system re-evaluated to minimize the overall costs.
The optimization has been also done for a site in Quneitra – Syria which has very good solar radiation that allows for the comparison
between two countries, as the weather data in the two countries differ greatly (different weather data).
The optimization results show that using batteries in combination with the renewables is economical and ecological. However, the
best solution is to combine redox-flow batteries with the renewables. In addition, a power supply system consisting only of batteries,
PV and wind generators may be applicable as well to satisfy the power demand.
Ó 2013 Elsevier Ltd. All rights reserved.
Keywords: Off-grid hybrid system; Battery management system; Energy cost; Genetic algorithm
⇑ Corresponding author at: Electrochemical Energy Conversion and Storage Systems Group, Institute for Power Electronics and Electrical Drives
(ISEA), RWTH Aachen University, Jaegerstrasse 17–19, 52066 Aachen, Germany. Tel.: +49 241 80 49308; fax: +49 241 80 92203.
E-mail address: batteries@isea.rwth-aachen.de (G. Merei).
0038-092X/$ - see front matter Ó 2013 Elsevier Ltd. All rights reserved.
http://dx.doi.org/10.1016/j.solener.2013.08.016
G. Merei et al. / Solar Energy 97 (2013) 460–473 461
Nomenclature
A area swept through by rotor (m2) O&M Operation and Maintenance (€)
AC alternating current PN-DG nominal power of diesel generator (kW)
AFcycle ageing factor during cycling Pown static energy consumption (W)
AFfloat ageing factor during float life PPV output power of PV generator (W)
ANF annuity factor PV photovoltaic
ASL Above Sea Level PWind output power of wind turbine (W)
Bi benefit of battery technology i (€) R gas constant (8.314 J/mol.K)
BMS Battery Management System RBS Radio Base Station
C(s) battery capacity (Ah) Rc/d cell resistance during charge (c) and discharge
cp aerodynamic efficiency (d)
D rotor diameter (m) SOC State of Charge (%)
DC direct current SOC(s) actual state of charge (%)
EN,i nominal energy of the battery (kWh) SOC0 initial state of charge (%)
F Faraday constant (96,485 As/mol) SOCavg average state of charge (%)
GA Genetic Algorithm SOCopt optimal state of charge (%)
GSM Global System for Mobile SOH State of Health (%)
h hub height (m) T temperature (°K)
ha hectare = 10,000 m2 ti time period (a)
HAWT Horizontal Axis Wind Turbine TRX transceiver
Hdif diffuse irradiation (W/m2) UMPP voltage at maximal power point (V)
Hdir direct irradiation (W/m2) UMTS universal mobile telecommunications system
Href reflected irradiation (W/m2) Uz cell voltage (V)
Ht total irradiation on tilted surface (W/m2) v(h) wind speed [m/s] at hub height h
Hu heat value of diesel fuel (kWh/kg) v10 wind speed at height 10 m
Ia converter’s current (A) Vv output voltage (V)
Ieff(s) effective current used to charge/discharge the z number of exchanged electrons
battery (A) zp number of parallel connected panels
Iz cell current (A) Zreal net interest rate (%)
Kannuity annuity costs (€) zs number of serial connected panels
Ki amount of cash flows (€) a terrain roughness coefficient
Ki-batt deterioration cost of battery technology i (€) b tilt angle (°)
Kspez,i specific battery cost (€/kWh) d azimuth angle (°)
Ksys total system cost (€) DSOC depth of cycling (%)
Lfloat float life Dt time interval (10 min)
Lopt optimum float lifetime at SOCopt g total efficiency of generator and power converter
m_ B fuel consumption of diesel generator (kg/h) combined
MPP Maximal Power Point gDG efficiency of diesel generator
n number of the year ql air density (kg/m3)
PN nominal power of generator (W)
networks. Base stations are often studied in the context of power sources like PV by 2013, and further 40,000 base sta-
standalone energy systems since they are frequently tions will operate entirely in an off-grid mode (http://
installed at remote locations without easy access to the www.abiresearch.com, 2011).
energy grid. Another reason is that a large quantity of base Most studies about stand-alone energy systems for spe-
stations is typically needed to provide network coverage cific applications include a single storage technology (Bez-
and that their operation requires about 80% of the total malinovic et al., 2013; Borowy and Salameh, 1996;
network power consumption (Arnold et al., 2010). Koutrolouis et al., 2006; Kusakana and Vermaak, 2013;
Various articles discuss less polluting and more cost- Lagorse et al., 2009; Nfah and Ngundam, 2012; Testa
effective ways to power base stations (Arnold et al., 2010; et al., 2010), typically lead-acid batteries. However, with
Marsan et al., 2009). Some approaches have been imple- recent progress in other battery technologies, also lith-
mented. For example, in the US 295,000 grid-connected ium-ion and vanadium redox-flow batteries are viable
base stations are planned to be equipped with renewable alternatives (Vetter et al., 2005; Kaer et al., 2011). Hence,
462 G. Merei et al. / Solar Energy 97 (2013) 460–473
all three battery technologies have been included in this many (50°470 North, 6°040 East, 222 m ASL) and for
work. Furthermore, the energy management system does Quneitra – Syria (33°080 North, 35°490 East, 60 m ASL).
not control only power flow among the system compo- Using a 10 min interval, the system has been simulated
nents. It is also responsible for deciding at each time step for a time frame of 20 years. Then, system performance
which battery technology has to be charged or discharged. has been analysed and total operation cost have been com-
This paper presents a tool which has been developed to puted. Using a genetic algorithm, key parameters of the
be used for meeting the load demand in any region in the components and the system settings are then varied and
world due to the adaptability of the input data. It optimises the simulation has been repeated, with the goal to minimize
systems with different combinations of components and overall cost.
finds the optimal sizing and operation conditions. The At each point in time, the load needs to be covered and
main purpose is to supply the application with electrical therefore the equilibrium of generated, stored and used
power at the cheapest energy price. power needs to be satisfied
P PV þ P Wind þ P Batt þ P DG P P Load þ P loss ð1Þ
2. System topology and components PPV is the output power of PV generator, PWind the output
power of wind turbine, PDG the output power of diesel gen-
The system consists of a load profile representing a base erator, PBatt the input or output power of the batteries,
station, PV panels and a wind turbine as renewable power PLoad the load demand, and Ploss is the aggregated system
sources, batteries for storing excess energy and to improve power losses.
the system reliability, as well as a diesel generator for This is achieved by redirecting power from or into the
backup power. The PV panels, the wind turbine and the batteries using the control strategy implemented in the
three battery types are connected to a 48 V DC bus. A die- BMS. Furthermore the constraints for the model compo-
sel generator and the load are connected to a 230 V AC nents need to be fulfilled. In the following sections, we dis-
bus. The buses are joined through a bidirectional power cuss the components and the input and output data of the
converter. In order to use lithium-ion, lead-acid, vanadium model separately.
redox-flow batteries or a combination of them simulta-
neously, a battery management system (BMS) is needed. 2.1. Input data
It regulates the power flow by assessing the current state
of health (SOH) and the state of charge (SOC) of the bat- The input for the model uses a realistic load profile that
teries and the diesel generator (Fig. 1). the system needs to cover, as well as real environmental
The system model has been implemented with Matlab/ data to determine the contribution of the renewables
Simulink. Taking into account different battery operating towards the total power supply.
points and ageing mechanisms, the BMS chooses the cost The model uses the load profile provided by E-Plus
optimal storage technology. It also oversees the power GmbH & Co. KG, Potsdam for a GSM/UMTS base sta-
flows within the whole system and triggers the diesel tion (macro cell) with air conditioning (Menzel, 2010).
generator. The load is almost constant at 2750 W with a maximal
The load is assumed to be that of a rural UMTS/GSM deviation of 6%, see Fig. 2.
base station for telecommunication. The load profile has been provided for a time of 1 month
As further input, the model uses data of the insolation, in 15-min intervals. From this, a profile with 10 min inter-
wind speeds and air temperature for Aachen-Hörn, Ger- vals has been derived. In such systems less than 5% of the
Fig. 2. Profile of the effective power of a Flexi GSM 9 TRX & Ultra Macro 3TRX and Ericsson RBS 3106 combined GSM/UMTS base station.
0.2 0.3
0.6
0.15
0.2
0.4 0.15
0.1
0.1
0.2 0.05
0.05
0 0 0
0 200 400 600 800 1000 1200 0 3 6 9 12 15 18 -10 -5 0 5 10 15 20 25 30 35 40
Global radiation [W/m2] Wind speed [m/s] Temperature [°C]
Fig. 3. Relative frequency of the irradiation, wind speed and air temperature in Aachen.
0.2 0.25
Relative frequency [-]
0.6 0.2
0.15
0.15
0.4
0.1
0.1
0.2 0.05
0.05
0 0 0
0 200 400 600 800 1000 1200 0 3 6 9 12 15 18 -10 -5 0 5 10 15 20 25 30 35 40
Fig. 4. Relative frequency of the irradiation, wind speed and air temperature in Quneitra.
power is consumed by the AC–DC converter, where the solar radiation data have been obtained from the website
power consumption of the feeder will not be regarded. SoDa for the year 2005 (soda-is.com, 2010). The following
Power supply and battery backup needs between 10% figures illustrate the relative frequency of the weather data
and 15% of the power depending on the employed (solar irradiation, wind speed and air temperature) in both
technology. Moreover the cooling system could consume sites (see Figs. 3 and 4).
between zero and 40% according to the site (Arnold
et al., 2010). 2.2. The photovoltaic panels
It is clear that the base station in Syria will have a higher
demand for cooling compared with the Germany location. The total irradiation on a tilted surface is composed
Nevertheless it was decided to use the same profile for both from the direct, the diffuse and the reflected part of the
locations, because it makes it easier to see how the tool insolation. The actual insolation depends on the diurnal
designs for the same load profile different systems based and annual path of the sun (Eq. (2)). The three parts have
on different weather conditions. been computed from the measured data of the global and
The values used for air temperature and the solar irradi- direct insolation taking into account the surface tilt angle.
ation (direct and global) as well as the wind speeds have
H t ðb; dÞ ¼ H dir ðb; dÞ þ H ref ðb; dÞ ð2Þ
been measured over 10 years in 10-min intervals for
Aachen-Hörn, Germany and have been provided by the Ht is the total irradiation on tilted surface, Hdir, Hdif, Href
Geographical Institute of RWTH. The temperatures range the direct, diffuse and reflected irradiation, and b, d are the
between 15 °C and 35 °C. The maximal wind speed is tilt and azimuth angle.
18 m/s. It is assumed that the PV generator always operates in
For the site in Syria (Quneitra) the wind speed and tem- maximum power point (MPP) condition. The module data
perature data was provided by the faculty of Mechanical has been taken from the data sheet of a Shell SM55 PV
and Electrical Engineering in Damascus University. The module.
464 G. Merei et al. / Solar Energy 97 (2013) 460–473
Fig. 5. Typical performance of the solar module at various level of irradiance and at various temperatures.
all batteries are discharged. The generator’s efficiency depends strongly on the battery chemistry, the state of
depends strongly on the operation mode. All processes charge (SOC), the temperature and the state of health
inside the generator are optimised for full load. Here, the (SOH). Therefore for each battery an independent model
maximum efficiency is 30% and the internal combustion has been implemented. The battery models are discussed
is without residue. If the generator needs to deliver less in Sections 2.5.1–2.5.3 below. However, in all models, the
than the rated power incomplete combustion can occur state of charge (SOC) of the battery at time t has been com-
and efficiency decreases. Fuel consumption is calculated puted by the Coulomb counting method
as follows: Z
m_ B ¼ P DG =ðgðP DG =P N -DG Þ H u Þ ð6Þ SOCðtÞ ¼ SOC0 þ ðI eff ðsÞ=CðsÞÞds ð7Þ
These effects occur continuously and affect the process of (battery discharge) and power excess (battery charge) have
float ageing. Float ageing generally depends on the state been analysed separately. In the case of power shortage the
of charge (SOC) and the temperature a battery is stored at. management system chooses the battery with the least cost
In this study ageing is determined based on experimental to provide the demanded power. Battery cost has been
data for each battery technology. At different SOC levels determined with respect to cyclic battery ageing (cost of
and temperatures float ageing tests have been conducted. deterioration).
Also, batteries have been repeatedly charged and dis- K i-batt ¼ EN ;i K spez;i =zcycle ðSOCavg ; DSOCÞ ð14Þ
charged at different average SOC levels and SOC ampli-
tudes (SOCavg, DSOC) until failure (Wöhler-Matrices). In Ki-batt is the deterioration cost of battery technology i (€),
the model for both processes an ageing factor (AF) is Kspez,i the specific battery cost (€/kWh), EN,i the nominal
introduced energy of the battery (kWh), SOCavg the average state of
charge (%), and DSOC is the cycling depth.
AFfloat ¼ Dt=Lfloat ðSOC;T Þ ð10Þ
Assuming that every charged battery (SOC > SOCmin) is
AFcycle ¼ 1=zcycle ðSOCavg ; DSOC;T Þ ð11Þ able to provide enough power to meet the load, only the
one with the least operating cost is chosen. Larger batteries
Dt is the time interval (10 min), Lfloat the float life, and zcycle cause greater cost. However, in a larger battery the same
is the number of possible cycles according to ageing data. current causes a smaller SOC amplitude and hence a smal-
At each instance one of the ageing processes dominates. ler impact on battery ageing.
Hence the actual state of health (SOH) can be calculated as: In the case of power excess (due to the diesel generator
Z
or the renewables) one or more batteries will be charged.
SOHðtÞ ¼ 1 maxðAFfloat ðsÞ; AFcycle ðsÞÞds ð12Þ
The decision, which battery is charged, is made by estimat-
ing the benefit that a recharge offers. This benefit is deter-
SOH = 0 corresponds to a capacity fade of 20% and a dou- mined on the basis of float life estimation. Each battery
bled internal resistance. The battery then needs to be has a technology specific optimum state of charge, at which
replaced. the maximum float lifetime Lopt is reached. For example a
lead-acid battery will achieve a long float life when stored
2.7. Converter model fully charged, whereas the optimum float lifetime of lith-
ium-ion battery will be reached at an SOC of around
In this system three converters were considered. A DC– 20%. The benefit, a battery provides, depends therefore
DC buck-converter with MPP tracker for the PV generator on its nominal energy and the current SOC.
and an AC–DC converter for the wind turbine were mod-
Bi ¼ EN ;i K spez;i ððLopt;i Lfloat ðSOCÞÞ=Lopt;i Þ ð15Þ
elled to estimate power losses. The power losses during
converting can be classified into static and dynamic losses Bi is the benefit of battery technology i (€) and Lopt,i is the
and can be calculated to Sauer (2003): optimum float lifetime at SOCopt.
Due to limited charge acceptance rates it may be neces-
P loss-conv ¼ P own þ V v I a þ Rv I 2a ð13Þ
sary to charge two or more batteries at the same time.
Ploss-conv is the power losses of converter (W), Pown the sta- Hence, the battery with the largest benefit will be charged
tic energy consumption (W), Vv the output voltage (V), Rv first with the maximum possible charge rate. If there is still
the ohmic resistance (X), and Ia is the converter current excess power available, the next battery in line will be
(A). charged and so forth. The recharge beyond the optimum
Both converters can be optimised by varying the nomi- SOC does not normally occur. Further charging will only
nal power, which affects the efficiency and cost. take place, if all batteries have already reached their opti-
Also, a central bidirectional AC–DC converter that is mum SOC and there is still excess power.
able to transfer power in both directions has been mod- Especially for the lithium-ion battery with its low opti-
elled. It provides power at voltages of 48 V (DC) and mum SOC the algorithm would rarely lead to a charge over
230 V (AC) respectively. As mentioned above, the PV pan- SOC = 20%. Therefore, to actually use a larger share of the
els, the wind turbine and the three battery types are con- capacity an optimisable virtual state of charge is intro-
nected to a 48 V DC bus. A diesel generator and the load duced, which signals the system that the state of charge is
are connected to a 230 V AC bus. still below the optimum. According to this, regular
However, the nominal power of the central power con- recharges above the optimum SOC are possible without
verter needs to be at least as big as the maximum power changing the general algorithm.
demand and is therefore no optimization variable. For all batteries the state of health is subdivided into the
signals float ageing and cyclic ageing. If for one battery the
3. Management system accumulated factor for float ageing dominates over the fac-
tor for cyclic ageing, this particular battery will be favoured
The management system contains the control strategy for charging and discharging. This makes sure that there
for regulating the power flow. The cases of power shortage will be a guaranteed minimum usage of each battery.
468 G. Merei et al. / Solar Energy 97 (2013) 460–473
The management system also provides maintenance for The assumptions for the cost functions are summarised
the lead-acid battery. To reduce the effects of sulfation and in Table 1. In order to achieve realistic results, as much
acid stratification there will be an additional benefit in a price information as possible was accumulated. The cost
defined interval (e.g. 30 days) to fully charge the battery. functions have been derived from the collected data. The
cost of the tower of the wind turbine was computed assum-
4. Cost ing the following functions of the hub-height. Each func-
tion has been defined for a certain nominal power range
Net present value method was used to calculate the cost of the turbine.
of the entire system. This method allows for comparison of
0 < P wind 6 6 kW f ðhÞ ¼ 8:609h2 42:56h þ 2551 ð19Þ
cash flows, which are carried out at different points in time.
ð0:04492hÞ
These cash flows can be the capital (investment) cost of the 6 kW < P wind 6 15kW f ðhÞ ¼ 3724 e ð20Þ
components and the cost of operation and maintenance 15 kW < P wind 6 30 kW f ðhÞ ¼ 6543 eð0:02789hÞ ð21Þ
(O&M) as well as the cost of possible replacements. The
total cost equals the accumulated present values of The cost of the rotor (the blades) has been calculated as
payments: a function of the diameter in meters and is given in the fol-
X lowing equation:
K sys ¼ K i ð1 þ Z real ðti ÞÞti ð16Þ
f ðDÞ ¼ 44:03D2 þ 140:5D þ 72:91 ð22Þ
Ki is the amount of cash flows, Zreal the net interest rate
(5%), and ti is the time period. For the diesel consumption a relatively high price of
Annuity method has been also used to calculate the 1.6 €/l is assumed for Germany. This price was derived
energy cost. In this method the yearly amount of the pay- from a current 1.25 €/l price for the fuel and 0.35 €/l for
ment was calculated depending on the net value of the transportation and logistics.
investment. The difference between the net present value
and the annuity method is the annuity factor which 5. Optimization
depends on the interest rate and the time period (n).
Eq. (17) gives the relationship between the two methods: The concept of genetic algorithms (GAs) was first devel-
oped in the mid-seventies. It is a search method that imi-
K annuity ¼ K sys ANF ð17Þ tates the principles of biological evolution (Renner and
ANF is the annuity factor; it can be calculated accord- Ekárt, 2003). Genetic algorithm can be used to efficiently
ing to the following equation: optimise multi-dimensional, non-linear engineering prob-
n n lems as shown in Badejani et al. (2007), Shahirinia et al.
ANF ¼ Z real ð1 þ Z real Þ =ðð1 þ Z real Þ 1Þ ð18Þ (2005), and Suryoatmojo et al. (2008). This is especially
In the last equation, this factor is constant and therefore true for the case described here. With various constraints
the used calculation method does not play any role in the and no continuous derivatives this method provides an
optimization. easy way to come up with quick and feasible solutions.
Table 1
Cost assumptions of the optimised system.
Component Investment Annually cost (O&M) Replacement cost
PV system
1600 €/kWp 2% –
350 €/ha (lease)
DC–DC converter 200 €/kW 1% –
Wind turbine
Blades f(H) 2% –
Generator 2000 €/kW –
Tower f(H) –
AC–DC converter 200 €/kW 1% –
Batteries
Lead-acid 150 €/kWh 1% 80%
Lithium-ion 750 €/kWh 1% 80%
Redoxflow 150 €/kWh, 2000 €/kW (Dennenmoser, 2012) 2% 80% (stack only)
Diesel generator 1000 €/kW 2% 90%
Periphery
Installation & planning 20,000 €
Bidirectional converter 600 €/kW 1% –
G. Merei et al. / Solar Energy 97 (2013) 460–473 469
Since this method is well known and there are already Table 3
several commercial implementations available (for example Optimization options for the genetic algorithm.
Matlab, optimtool), all that is needed is to define the impor- Option Value
tant genes, a fitness function and constraints as well as to Generations 200
choose the population size, the number of generations Population size 150 individuals
and general options for the genetic operators. In Table 2 Creation function Constraint dependent
Fitness scaling Rank based, linear
the optimised genes and the constraints are listed. GA Selection function Roulette
chooses the optimal value of each parameter within the Elite count 1–3
defined upper and lower boundaries. The fitness function Crossover function Scattered
is the cost function (Eq. (16)) with the condition that the Crossover fraction 50–70%
load has to be covered at all times. Mutation rate 1–5%
All these parameters have direct or indirect impact on
the system cost. For example the installed power of the
PV panels, the nominal capacity of the batteries or
the hub height of the wind turbine have direct impact on R2011b with multiple processors on a scientific Windows
the cost and the system behaviour. Other parameters Server 2008 64-bit operating system. The applied options
like the tilt angle or the part load factor affect the system for the algorithm are shown in the following table (see
behaviour directly but have no direct influence on the cost. Table 3):
The optimization can easily be modified by changing the
constraints. For example the whole system could be 6. Results and discussion
installed in a natural reserve, where use of fossil fuel is
not allowed. Then all that is needed is to set the allowed The optimization results for different test cases are pre-
size of diesel generator to zero. Likewise, any component sented in the following sections. Firstly, the entire system
can be disregarded by changing the constraints. with all components was optimised, followed by a system
The optimization is conducted on the high performance without a diesel generator. The latter case is needed in nat-
computing (HPC)-cluster of RWTH Aachen using Matlab ural reserves and in areas where the use of diesel fuel is for-
bidden or transport is not possible and economically not
convenient. The third case does not consider batteries (no
Table 2
Optimization parameters and constraints of the system. storage system). Finally, in the last three cases, each system
uses only one battery technology (three optimizations).
Component Parameter Boundaries
Table 4 includes the different scenarios definition.
PV generator Peak power 0–30 kWp
In the following, the results for the first case will be dis-
Tilt angle 0–90°
Azimuth angle 30° to 30° cussed in detail. The results for the other cases will be all
DC–DC nominal power 0–30 kW presented in a table allowing for comparison among them.
Wind turbine Nominal power 0–30 kW
Rotor diameter 0–20 m 6.1. System with redox-flow, lead-acid and li-ion batteries –
Hub height 0–40 m scenario I
AC–DC nominal power 0–30 kW
Lead-acid battery Capacity 0–3000 Ah It is assumed that different storage technologies have
Minimum state of charge 0.05–0.6 been applied to store the excess energy and use it when it
Maximum state of charge Constant is needed (not enough energy generated by PV panels
(=1) and wind turbine to satisfy the power demand). However,
Interval between scheduled full 20–60 days
recharges
the optimization results show that the optimal storage sys-
tem is using just one battery technology which is the redox-
Lithium-ion battery Capacity 0-3000 Ah
flow battery with a capacity of 1460 Ah. The energy cost of
Minimum state of charge Constant
(=0.05) the optimal system is 0.65 €/kWh. Table 5 gives an over-
Maximum state of charge 0.7-1 view of the configuration.
Optimum state of charge 0.2-0.7
Vanadium redoxflow Capacity 0-3000 Ah
battery Table 4
Nominal power 0-10 kW Systems definition.
Minimum state of charge Constant Lead-acid Redox-flow Li-ion Diesel generator
(=0.05) p p p p
Scenario I
Maximum state of charge Constant p p p
Scenario II –
(=1) p
Scenario III – – –
p p
Diesel generator Nominal power 4–10 kW Scenario IV – –
p p
Part load factor 0–1 Scenario V – –
p p
Minimal runtime 0.5–5 h Scenario VI – –
470 G. Merei et al. / Solar Energy 97 (2013) 460–473
10 4000
8
Wind power [kW]
PV power [kW]
3000
6
2000
4
1000
2
0 0
0 10 20 30 0 10 20 30
time [day] time [day]
Load Power / kW
3
2.8
2.6
PV Power / kW
4
2
0
Wind Power / kW
10
5
0
Diesel Power / kW
5
SOC [%]
100
50
0
UPS
1
0
-1
10 20 30
time [day]
PV:
29%
Diesel:
22%
PV:
44%
Diesel:
56%
Wind: 49%
Fig. 12. Energy provided from diesel generator and the renewables in Aachen and Quneitra.
PV: 9%
PV: 14%
Wind:
23% VRB:
Diesel: 13%
47% Diesel:
63%
periphery:
VRB: 10%
15% Periphery: 6%
Fig. 13. Fraction of the component costs (investment + running costs) in Aachen and Quneitra.
costs. In addition two scenarios for Quneitra were added to It should be noted that using batteries in the hybrid sys-
compare different scenarios (scenario I and scenario III): tem makes the energy cost about 50% cheaper than depend-
The symbols used in the storage technology field indi- ing on diesel generator only. However the combination of
cate to the most important chemical component in the bat- three battery technologies is not advisable. The optimization
teries. Pb denotes lead acid, V vanadium-redox-flow and Li showed that using just one battery technology (redox-flow)
lithium-ion batteries. as a storage system is the most economical system.
472 G. Merei et al. / Solar Energy 97 (2013) 460–473
x 104
12
invest costs
running costs
10
0
Diesel PV Wind RedoxFlow Pb Li-ion Converter
Table 6
Systems properties.
Property Unit Scenario I all Scenario Scenario Scenario Scenario Scenario Syria all possible Syria
possible batteries II III IV V VI batteries scenario III
Storage technology – Pb/V/Li Pb/V/Li – Pb V Li Pb/V/Li –
Using diesel – Yes No Yes Yes Yes Yes Yes Yes
Nominal Capacity kWh 0/70/0 882/244/55 –/–/– 150 70 18.3 0/55/0 –/–/–
Peak power – PV kW 14.7 27.8 14.1 12.8 14.7 14.7 12.4 10.6
Nominal power DC–DC kW 5.9 14.5 3.2 11.1 5.9 3.7 5.2 4.7
Nominal power – wind kW 12.6 22.6 12.2 13.2 12.6 8.7 0 0
Nominal power AC–DC kW 9.6 24.5 10 11.2 9.6 7.8 0 0
Battery lifetime a 5 18/14/4 - 5 5 6 9.5 -
Replacements diesel – 2 0 5 1 2 3 5 5
Investment costs k€ 131.67 471.68 91.01 171.06 131.67 135.39 76.68 41.7
Running costs k€ 127.16 62.46 273.55 99.66 127.16 151.99 60.15 102.55
Total cost k€ 258.84 534.15 364.56 270.73 258.84 287.39 136.83 144.23
Energy cost €/kWh 0.65 1.35 0.91 0.68 0.65 0.72 0.34 0.36
Using renewable energies in combination with batteries lithium-ion batteries). The optimization was done for six
to assure the reliability is the most ecological system with different scenarios with different system configurations.
0% emission. It is however expensive (1.35 €cent/kWh). The results show that combining the batteries with the
Comparing the systems using one battery technology, renewable energy systems is effective, economical and eco-
redox-flow system is the cheapest technology (0.65 €/kWh), logical. However, using a combination of more than one
followed by the lead acid system (0.68 €/kWh) and finally battery technology as energy storage (PV, wind turbine,
the most expensive system is that with Li-ion batteries diesel and batteries) is not favourable. Instead, the optimi-
(0.72 €/kWh). zation results showed that using only redox-flow batteries
The last column shows the system properties and the is the best system (the same optimization result for Aachen
costs for a site in Quneitra with a relatively cheap energy and Quneitra).
cost of 0.34 €/kWh. In the situation where diesel generators are not allowed
(natural park or difficulty in tanking), a combination of
8. Conclusion and outlook three battery technologies is an optimal solution for the
stand-alone hybrid system.
In this study, a hybrid system consisting of PV panels The cheapest system with a low energy cost of
and a wind turbine as renewable energy sources, batteries 0.65 €/kWh in Aachen and 0.34 €/kWh for Quneitra is
for energy storage and diesel generator as a back-up system the system using redox-flow battery as a storage system.
was optimised using genetic algorithm. Initially three differ- As a future work the system needs to be validated using
ent battery technologies in combination with the renewable measured data and price data of real installations. Then,
energy sources were considered (lead acid, redox-flow and the calculation tool presented in this work is very valuable
G. Merei et al. / Solar Energy 97 (2013) 460–473 473
to “pre-design” an off-grid system in any region of the Lagorse, J., Paire, D., Miraoui, A., 2009. Hybrid stand-alone power
world and for any application. The system could be opti- supply using PEMFC, PV and battery – modeling and optimization.
In: International Conference on Clean Electrical Power, pp. 135–140.
mised also for different installation sites (different weather Magnor, D., Gerschler, J., Ecker, M., Sauer, D., 2009. Concept of a
data) and for different applications, provided the needed battery aging model for lithium-ion batteries considering the lifetime
input data are available. dependency on the operation strategy. In: 24th European Photovoltaic
Solar Energy Conference and Exhibition (EUPVSEC).
References Marsan, M., Chiaraviglio, L., Ciullo, D., Meo, M., 2009. Optimal energy
savings in cellular access networks. In: IEEE International Conference
on Communications.
Arnold, O., Richter, F., Fettweis, G., Blume, O., 2010. Power consump-
Menzel, K., 2010. Dokumentation über die Wirkleistungsprofile an
tion modeling of different base station types in heterogeneous cellular
Mobilfunkstandorten/E-Plus Mobilfunk GmbH & Co. KG. Research
networks. In: Future Network and Mobile Summit 2010 Conference
Report.
Proceedings, ISBN: 978-1-905824-18-2978.
Nfah, E., Ngundam, J., 2012. Evaluation of optimal power options for
Badejani, M., Masoum, M., Kalantar, M., 2007. Optimal Design and
base transceiver stations of Mobile Telephone Networks Cameroon.
Modeling of Stand-Alone Hybrid PV–Wind Systems. Australian
JSE 86, 2935–2949.
Universities Power Engineering, pp. 1–6.
Ozawa, K., 2009. Lithium Ion Rechargeable Batteries. Wiley-VCH Verlag
Bezmalinovic, D., Barbir, F., Tolj, I., 2013. Techno-economic analysis of
GmbH & Co. KgaA, Weinheim.
PEM fuel cells role in photovoltaic-based systems for the remote base
Perrin, M., Saint-Drenan, Y., Mattera, F., Malbranche, P., 2005. Lead-
stations. IJHE 38, 417–425.
acid batteries in stationary applications: competitors and new markets
Blanc, C., 2009. Modeling of a vanadium redox flow battery electricity
for large penetration of renewable energies. JPS 144, 402–410.
storage system. École Polytechnique Fédérale de Lausanne,
Renner, G., Ekárt, A., 2003. Genetic algorithms in computer aided design.
Dissertation.
JCAD 35, 709–726.
Blanc, C., Rufer, A., 2008. Multiphysics and energetic modeling of a
Rydh, C., 1999. Environmental assessment of vanadium redox and lead-
vanadium redox flow battery. In: IEEE International Conference on
acid batteries for stationary energy storage. JPS 80, 21–29.
Sustainable Energy Technologies, pp. 696–701.
Sauer, D., 1994. Untersuchungen zum Einsatz und Entwicklung von
Borowy, B., Salameh, Z., 1996. Methodology for optimally sizing the
Simulationsmodellen für die Auslegung von Photovoltaik-Systemen,
combination of a battery bank and PV array in a wind/PV hybrid
Diploma Thesis.
system. IEEE Trans. Energy Convers., 367–375.
Sauer, D., 2003. Optimierung des Einsatzes von Blei-Säure-Akkumulato-
Buller, S., 2002. Impedance-based simulation models for energy storage
ren in Photovoltaik-Hybrid-Systemen unter spezieller Berücksichti-
devices in advanced automotive power systems. RWTH Aachen
gung der Batteriealterung, Dissertation.
University, Dissertation.
Schiffer, J. et al., 2007. Model prediction for ranking lead-acid batteries
Buller, S., Thele, M., De Doncker, R., Kalden, E., 2005. Impedance-based
according to their expected lifetime in renewable energy systems and
simulation model of supercapacitors and Li-ion batteries for power
autonomous power supply systems. JPS 168, 66–78.
electronic applications. IEEE Trans. Ind. Appl. (41), 472–747.
Sen, C., Kar, N., 2009. Battery pack modeling for the analysis of battery
Degner, T., 1998. Energetische simulation zur Auslegung kleiner wind–
management system of a hybrid electric vehicle. In: IEEE Vehicle
diesel systeme. In: Kasseler Symposium Energie-Systemtechnik.
Power and Propulsion Conference (VPPC), pp. 207–212.
Dennenmoser, M., 2012. Status and potential of redox flow batteries. Inter
Shahirinia, A., Tafreshi, S., Gastaj, A., Moghaddomjoo, A., 2005.
Solar 2012/PV Energy World, Munich, 13 06.
Optimal sizing of hybrid power system using genetic algorithm. In:
Dürr, M., Cruden, A., Gair, S., McDonald, J., 2006. Dynamic model of a
International Conference on Future Power Systems, pp. 6–8.
lead acid battery for use in a domestic fuel cell system. JPS, 1400–1411.
Silva, S.B., de Oliveira, M.A., Severino, M.M., 2010. Economic evaluation
Georgescu, M., Barote, L., Marinescu, C., Clotea, L., 2010. Smart
and optimization of a photovoltaic–fuel cell–batteries hybrid system
electrical energy storage system for small power wind turbines. In: 12th
for use in the Brazilian Amazon. Energy Policy 38, 6713–6723.
International Conference on Optimization of Electrical and Electronic
Skyllas-Kazacos, M. et al., 1986. New all-vanadium redox flow cell. JES
Equipment (OPTIM), ISSN 1842-0133, pp. 1192–1197. <http://
133, 057–1058.
www.abiresearch.com> (05.11.11).
soda-is.com, 2010. <http://www.soda-is.com/eng/services/services_radia-
Kaer, G., Shah, A., Walsh, F., 2011. Development of the all-vanadium
tion_free_eng.php> (22.03.10).
redox flow battery for energy storage: a review of technological,
Suryoatmojo, H., Hiyama, T., Elbaset, A., Ashari, M., 2008. Optimal
financial and policy aspects. Int. J. Energy Res. 36, 1105–1120. http://
design of wind–PV–diesel–battery system using genetic algorithm. IEE
dx.doi.org/10.1002/er.1863.
J. Trans. Power Energy 129, 413–420.
Kleemann, M., Meliß, M., 1993. Regenerative Energiequellen. Springer-
Testa, A., Caro, S., Torre, R., Scimone, T., 2010. Optimal design of energy
Verlag, Berlin–Heidelberg–New York.
storage systems for stand-alone hybrid wind/PV generators. In:
Koutrolouis, E., Kolokotsa, D., Potirakis, A., Kalaitzakis, K., 2006.
International Symposium on Power Electronics, Electrical Drives,
Methodology for optimal sizing of stand-alone photovoltaic/wind-
Automation and Motion.
generator systems using genetic algorithms. JSE 80, 1072–1088.
Vetter, J. et al., 2005. Ageing mechanisms in lithium-ion batteries. JPS
Kusakana, K., Vermaak, H., 2013. Hybrid renewable power systems for
147, 269–281.
mobile telephony base stations in developing countries. Rene 51, 419–
425.