Yesterday…
• Controls were simple
• Energy was cheap
• Tower considered a ‘constant flow’ device: # towers operating = # chillers operating
Today…
• Life isn’t so simple
• Controls are much more capable
• Energy is NOT cheap
Model HP ASHRAE
efficiency
(gpm/hp)
NC8405TAN 40 hp 49.5
NC8407QAN 20 hp 92.1
NC8409PAN 15 hp 128.3
Source: Selection Software
6.5.5.4 Tower Flow Turndown. Open-circuit cooling towers used on water cooled chiller
systems that are configured with multiple- or variable-speed condenser water pumps shall
be designed so that all open-circuit cooling tower cells can be run in parallel with the
larger of:
a. the flow that is produced by the smallest pump at its minimum expected flow rate or
b. 50% of the design flow for the cell
© 2020 SPX Cooling Technologies, Inc. All Rights Reserved April 25, 2020 8
Foundation for Variable Flow – Fan Speed
© 2020 SPX Cooling Technologies, Inc. All Rights Reserved April 25, 2020 14
Using Nozzle Cups in Crossflow Designs
© 2020 SPX Cooling Technologies, Inc. All Rights Reserved April 25, 2020 15
Using Nozzle Cups in Crossflow Designs
© 2020 SPX Cooling Technologies, Inc. All Rights Reserved April 25, 2020 16
Using Nozzle Cups in Crossflow Designs
© 2020 SPX Cooling Technologies, Inc. All Rights Reserved April 25, 2020 17
Using Nozzle Cups in Crossflow Designs
Benefits:
• Eliminates risk of scaling / icing
• Uniform air-side pressure drop
• Prevents air channeling
© 2020 SPX Cooling Technologies, Inc. All Rights Reserved April 25, 2020 18
Crossflow Design – Center Inlets
© 2020 SPX Cooling Technologies, Inc. All Rights Reserved April 25, 2020 19
Crossflow Design – Center Inlets
© 2020 SPX Cooling Technologies, Inc. All Rights Reserved April 25, 2020 20
Crossflow Design – Center Inlets
Results:
• Effective air travel varies between two
extremes
• Low air rate through center
• Diminished performance
• Higher air rates through ends
• Higher risk of icing during winter operation or
free cooling
© 2020 SPX Cooling Technologies, Inc. All Rights Reserved April 25, 2020 21
Crossflow Design – Integral Inlet Louvers
Important: Make sure film fill has integral inlet louvers to minimize ice
formation
• Icing can damage fill and reduce performance
• Keep heat (water) close to louvers
air in
© 2020 SPX Cooling Technologies, Inc. All Rights Reserved April 25, 2020 25
Variable Flow in Counterflow Designs
© 2020 SPX Cooling Technologies, Inc. All Rights Reserved April 25, 2020 26
Variable Flow in Counterflow Designs
© 2020 SPX Cooling Technologies, Inc. All Rights Reserved April 25, 2020 27
Wrap Up
Wrap-Up
© 2020 SPX Cooling Technologies, Inc. All Rights Reserved April 25, 2020 29
Additional Information
Wrap-Up
© 2020 SPX Cooling Technologies, Inc. All Rights Reserved April 25, 2020 30