Sie sind auf Seite 1von 31

Variable Flow Over

Cooling Towers for Energy Savings


AHR Expo – Orlando, Florida
Gary Stauffer, Sales Engineer

© 2020 SPX Cooling Technologies, Inc. All Rights Reserved


Meet the Presenter

Gary Stauffer
Sales Engineer – West , SPX Cooling Technologies
• With SPX since 2005, has held roles including
Designer - Mechanical Components, Technical
Services Engineer, and Applications Engineer

• Previously worked as an Engineering Technician


in the aluminum casting industry

• Member of ASHRAE and ASME

Variable Flow Over Cooling Towers for Energy Savings


© 2020 SPX Cooling Technologies, Inc. All Rights Reserved April 25, 2020 2
In addition to boosting your knowledge,
today you will...

• Receive a Certificate of Completion*


• Receive a Thank You gift
• Have the opportunity to inquire about educational
programming at your facility or at SPX Cooling in
Overland Park, KS

*Be sure to get your badge scanned so we can mail your certificate!

Variable Flow Over Cooling Towers for Energy Savings


© 2020 SPX Cooling Technologies, Inc. All Rights Reserved April 25, 2020 3
Presentation Purpose & Overview

• Increase energy savings on new or existing tower


installations using variable flow over cooling towers
• Understand the differences between crossflow and
counterflow designs and how they impact variable flow

Variable Flow Over Cooling Towers for Energy Savings


© 2020 SPX Cooling Technologies, Inc. All Rights Reserved April 25, 2020 4
Variable Flow Fundamentals

© 2020 SPX Cooling Technologies, Inc. All Rights Reserved 5


Yesterday and Today

Yesterday…
• Controls were simple
• Energy was cheap
• Tower considered a ‘constant flow’ device: # towers operating = # chillers operating
Today…
• Life isn’t so simple
• Controls are much more capable
• Energy is NOT cheap

Are there opportunities to save energy by operating towers differently?

Variable Flow Over Cooling Towers for Energy Savings


© 2020 SPX Cooling Technologies, Inc. All Rights Reserved April 25, 2020 6
Foundation for Variable Flow

Less surface area requires more airflow (hp)


Trade size for horsepower
• Example: 500 ton selections (5200 GPM, 95°- 85°- 78°F)

Model HP ASHRAE
efficiency
(gpm/hp)
NC8405TAN 40 hp 49.5
NC8407QAN 20 hp 92.1
NC8409PAN 15 hp 128.3
Source: Selection Software

Variable Flow Fundamentals


© 2020 SPX Cooling Technologies, Inc. All Rights Reserved April 25, 2020 7
Another Reason to consider Variable Flow

ASHRAE 90.1-2019 Tower Flow Turndown Requirements[6]

6.5.5.4 Tower Flow Turndown. Open-circuit cooling towers used on water cooled chiller
systems that are configured with multiple- or variable-speed condenser water pumps shall
be designed so that all open-circuit cooling tower cells can be run in parallel with the
larger of:
a. the flow that is produced by the smallest pump at its minimum expected flow rate or
b. 50% of the design flow for the cell

© 2020 SPX Cooling Technologies, Inc. All Rights Reserved April 25, 2020 8
Foundation for Variable Flow – Fan Speed

Tower Cooling Capacity varies directly with


fan speed
• 100% speed provides 100% performance
• 75% speed provides 75% performance
• 50% speed provides 50% performance

Tower Fan Energy varies with the cube of the


speed ratio
• 100% speed: 1.003 = 100.0% hp
• 75% speed: 0.753 = 42.2% hp
• 50% speed: 0.503 = 12.5% hp

Variable Flow Fundamentals


© 2020 SPX Cooling Technologies, Inc. All Rights Reserved April 25, 2020 9
Traditional Example – 3000 Ton Chiller Plant

4 @ 750 ton chillers and 4-cell tower


9000 GPM, 95-85-78 Select NC8411TAN4 @ 40 hp/fan
75% Load – 3 chillers and 3 towers running

End Results: 75% of the energy @ 75% load with


traditional approach
© 2020 SPX Cooling Technologies, Inc. All Rights Reserved April 25, 2020 10
Variable Flow Example – 75% Load
3000 Ton Chiller Plant

4 @ 750 ton chillers and 4-cell tower


9000 GPM, 95-85-78 Select NC8411TAN4 @ 40 hp/fan
Now @ 75% Load – 3 chillers and 4 towers running

End Results: 67.6/120 = 44% energy savings


versus traditional
© 2020 SPX Cooling Technologies, Inc. All Rights Reserved April 25, 2020 11
Variable Flow Example – 50% Load
3000 Ton Chiller Plant

4 @ 750 ton chillers and 4-cell tower


9000 GPM, 95-85-78 Select NC8411TAN4 @ 40 hp/fan
Now @ 50% Load – 2 chillers and 4 towers running

End Results: 20/80 = 75% energy savings


versus traditional
© 2020 SPX Cooling Technologies, Inc. All Rights Reserved April 25, 2020 12
Implementing Variable Flow
in Crossflow Design

© 2020 SPX Cooling Technologies, Inc. All Rights Reserved 13


Crossflow Design – Water Distribution

1. Gravity flow water distribution basins


2. Lots of nozzles (~260 in a 400 ton
tower)
3. Nozzles are close together – easy to
distribute water over the fill
4. Min / Max water depth over nozzle
(2.5” min. – 5.4” max.)

© 2020 SPX Cooling Technologies, Inc. All Rights Reserved April 25, 2020 14
Using Nozzle Cups in Crossflow Designs

Nozzle Cups Nozzle Cups at Low Flow


• Simple passive modification • Cups restrict water distribution to
standard nozzles only

© 2020 SPX Cooling Technologies, Inc. All Rights Reserved April 25, 2020 15
Using Nozzle Cups in Crossflow Designs

Nozzle Cups at Intermediate Flow Nozzle Cups at Full Flow


• Some restriction to cupped nozzles • No restrictions

© 2020 SPX Cooling Technologies, Inc. All Rights Reserved April 25, 2020 16
Using Nozzle Cups in Crossflow Designs

Full Flow Example:


• Water overflows nozzle cups
• Entire fill volume is active
• Nozzle cups have no effect

© 2020 SPX Cooling Technologies, Inc. All Rights Reserved April 25, 2020 17
Using Nozzle Cups in Crossflow Designs

Low Flow Example:


• Reduced head in basin
• No water flows over cup
• All water is outboard

Benefits:
• Eliminates risk of scaling / icing
• Uniform air-side pressure drop
• Prevents air channeling

© 2020 SPX Cooling Technologies, Inc. All Rights Reserved April 25, 2020 18
Crossflow Design – Center Inlets

Center Inlet Design:


• Distribution flume rotated 90°
• Water distributed along entire air travel of fill

© 2020 SPX Cooling Technologies, Inc. All Rights Reserved April 25, 2020 19
Crossflow Design – Center Inlets

Center Inlet Basin Dam:


• During full flow water floods entire basin

© 2020 SPX Cooling Technologies, Inc. All Rights Reserved April 25, 2020 20
Crossflow Design – Center Inlets

Center Inlet Basin Dam:


• During low flow water floods dammed area
only

Results:
• Effective air travel varies between two
extremes
• Low air rate through center
• Diminished performance
• Higher air rates through ends
• Higher risk of icing during winter operation or
free cooling

© 2020 SPX Cooling Technologies, Inc. All Rights Reserved April 25, 2020 21
Crossflow Design – Integral Inlet Louvers

Same Day Same Facility

Integral Louvers Separate Louvers


© 2020 SPX Cooling Technologies, Inc. All Rights Reserved April 25, 2020 22
Crossflow Design – Integral Inlet Louvers

Important: Make sure film fill has integral inlet louvers to minimize ice
formation
• Icing can damage fill and reduce performance
• Keep heat (water) close to louvers

air in

Integral Louvers Separate Louvers


© 2020 SPX Cooling Technologies, Inc. All Rights Reserved April 25, 2020 23
Implementing Variable Flow
in Counterflow Design

© 2020 SPX Cooling Technologies, Inc. All Rights Reserved 24


Counterflow Design – Water Distribution

• Pressurized spray system


• Relatively few spray nozzles
(~60 in 400 ton tower)
• Nozzles much farther apart
• No modifications are available for
counterflow designs to enhance variable
flow performance
• Limited ability to run at low flow rates
• Less pressure at spray nozzle

© 2020 SPX Cooling Technologies, Inc. All Rights Reserved April 25, 2020 25
Variable Flow in Counterflow Designs

100% Nozzle Flow 50% Nozzle Flow


• Adequate Distribution • Water Channeling

© 2020 SPX Cooling Technologies, Inc. All Rights Reserved April 25, 2020 26
Variable Flow in Counterflow Designs

If you reduce flow too much (generally more


than 30%), you get uneven water loading:
• Lower air-side pressure drop in
fill sections with less water
• Air takes path of least resistance
• More air in drier sections
• Less air in wetter sections
Resulting in:
• Reduced thermal performance
• Risk of ice formation in fill
• Greater risk of fill scaling

© 2020 SPX Cooling Technologies, Inc. All Rights Reserved April 25, 2020 27
Wrap Up

© 2020 SPX Cooling Technologies, Inc. All Rights Reserved 28


Key Take-Aways

1. Variable flow offers big energy / dollar savings potential


• Remember - Tower fan energy varies with the cube of the speed
ratio
2. Inherent design differences between cooling towers:
• Crossflow – can be easily modified for variable flow
• Counterflow – cannot be practically modified and opportunity for
variable flow in counterflow towers is significantly smaller than
with crossflow towers

Wrap-Up
© 2020 SPX Cooling Technologies, Inc. All Rights Reserved April 25, 2020 29
Additional Information

• Marley Technical Report TR-14


“Variable Flow Over Cooling
Towers for Energy Savings”
• Nozzle Cups Cut sheet
• Variable Flow Over Cooling Towers
• VIDEO: Marley ST Nozzle and
Cup System

Wrap-Up
© 2020 SPX Cooling Technologies, Inc. All Rights Reserved April 25, 2020 30
Thank You! Questions?
• Get your badge scanned to ensure
you receive Certificate of Completion
• See me or a Marley representative to
share feedback on the presentation
• Inquire about lunch & learns and
other educational programming that
would benefit your team
• Pick up your gift before you head out!