Beruflich Dokumente
Kultur Dokumente
Introduction
The IMFEC11 and IMFEC12 modules can use the NTAI05 ter-
mination unit for point-to-point operation. Select the input
type of each channel using the dipshunts on the termination
unit. The FEC module can accept inputs of 4 to 20 milliam-
peres, 1 to 5 VDC, 0 to 1 VDC, 0 to 5 VDC, 0 to 10 VDC, and
-10 to +10 VDC.
NOTE: Input jumpers J6 through J20 on the IMFEC11 board must be set to the
voltage position. Refer to IMFEC11 Input Jumpers (J6 through J20) in
Section 3.
Configuring Inputs
Figure A-1 shows the input signal path through an NTAI05
dipshunt. Table A-1 shows NTAI05 dipshunt configurations.
Figure A-2 shows module to termination unit cabling and
Figure A-3 shows the NTAI05 terminal assignments.
+24 V D C
1 16
+ 2 15 M U LT IP LE X
– 3 14
4 13 C IR C U IT TO
T E R M IN A L 5 12 A /D C O N V E RT E R
6 11
B LO C K 7 10
8 9
D IP S H U N T S
X U 1-XU 16
WBPEEUI240764A0 A-1
Configuring Inputs
Externally powered 16 15 14 13 12 11 10 9
4 to 20 mA
1 2 3 4 5 6 7 8
Single-ended voltage2 16 15 14 13 12 11 10 9
1 2 3 4 5 6 7 8
Differential voltage2 16 15 14 13 12 11 10 9
1 2 3 4 5 6 7 8
Above applications: 16 15 14 13 12 11 10 9
XU17
4 to 20 mA
1 to 5 VDC 1 2 3 4 5 6 7 8
0 to 1 VDC T0 3333A
0 to 5 VDC
0 to 10 VDC
-10 to +10 VDC
NOTES:
1. XU16 is not used.
2. FSK not supported at this time.
P1
N K T U 01
IM F E C 11/12 P3 P1 N TA I0 5
P2
T03 334A
A-2 WBPEEUI240764A0
Configuring Inputs
8 7 6 5 4 3 2 1
1 1 1 1
TB 4
– + – + – + – +
16 15 14 13
8 8 8 8
X U 16 X U 15 X U 14 X U 13
1 1 1 1
8 7 6 5 4 3 2 1
8 8 8 8
X U 12 X U 11 X U 10 XU9 TB 3
E 1 (C O M M O N ) 1
– + – + – + – +
12 11 10 9
C H A S S IS P1 TE R M IN A L
GROUND B LO C K S
8 8 7 6 5 4 3 2 1
E 2 (+ 2 4 V D C ) X U 17
TB 2
1 1 1 1
– + – + – + – +
8 7 6 5
8 8 8 8
8 7 6 5 4 3 2 1
TB 1
8 8 8 8
D IP S H U N T S O C K E T A N A L O G IN P U T
(D IP S H U N T N U M B E R C O R R E S P O N D S NUM BERS
N U M E R IC A LLY TO T H E A N A LO G IN P U T N U M B E R ) T 03 33 5A
WBPEEUI240764A0 A-3