HIGH AMBIENT
AIR COOLED LIQUID CHILLER
PRODUCT CATALOGUE
STYLE A
REFRIGERANT TYPE: R22, R407C
MODELS: 50 Hz
EMEA
YORK
CONTENTS
Available Models and Nominal Cooling Capacities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Accessories and Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Operating Limitations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Refrigerant Flow Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Selection Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
YAEP R22 Cooling Capacities - Metric Data (°C kW/kW) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
YAEP R22 Cooling Capacities - Imperial Data (°F Tons/kW) . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
YAEP R407C Cooling Capacities - Metric Data (°C kW/kW) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
YAEP R407C Cooling Capacities - Imperial Data (°F Tons/kW) . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Physical Data - R22 Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Physical Data - R407C Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Electrical Data - R22 Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Electrical Data - R407C Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Nomenclature
1 2 3 4
YAEP99XD9B50PA 5 6 7 8 9 10 11 12 13
BASE PRODUCT TYPE COMPRESSOR SIZE COOLER CONDENSER FAN CODE REFRIGERANT POWER SUPPLY STARTING DESIGN LEVEL
SPECIFICATION
General The unit base and frame is of Motor - The compressor motors are
Units are completely assembled with all heavy-gauge, galvanised steel, with a refrigerant gas cooled, with integral
interconnecting refrigerant piping and baked-on enamel coloured Desert Sand temperature-sensing solid state overload
internal wiring, ready for field installation. (RAL 1019). protection in each phase. The terminal
The unit is pressure-tested, evacuated boxes are to IP55 weather protection.
Compressors
and fully charged with refrigerant and Part Winding starting is fitted as standard.
The unit has accessible, semi-hermetic,
includes an initial oil charge. After
reciprocating compressors. All rotating Housing - The compressor housing is
assembly, a full run test is performed, with
parts are statically and dynamically cast iron, and contains: removable
water flowing through the cooler, to verify
balanced. cylinder heads with internal muffling,
that each refrigeration circuit operates
correctly. discharge service valve, optional suction
service valve, crankcase sight glass and
heater, oil and suction strainers, and
internal relief valves.
Page 1
Doc. No. PCYAEP-50/03.04/GB
Crankshaft - The crankshaft is ductile The fan guards are constructed of Controls
(nodular) iron, drilled for positive oil heavy-gauge wire hot dipped galvanized The microprocessor based control
distribution, with integral counterweights coated steel. After construction the fan system is capable of multi-circuit control
for balancing. The main bearings are deck and cowl are hot dipped galvanized to maintain chilled liquid temperature.
insert type, steel-backed babbitt. The prior to assembly. (Colour co-ordinated Compressor starting/stopping and
thrust bearing is bronze. paint finish is available as an extra). All loading/ unloading decisions are
blades are dynamically and statically performed by the microprocessor to
Cylinder Assemblies - Suction and balanced for vibration-free operation. maintain leaving water temperature.
discharge valves are high-quality, These decisions are a function of
non-flexing, stainless steel. The pistons Motors - The fan motors are Totally
temperature deviation from setpoint and
are aluminium alloy with two piston rings. Enclosed Air-Over, squirrel-cage type,
rate of change of temperature.
The connecting rods are aluminium alloy current protected. They feature ball
with integral bearing surfaces on both bearings that are double sealed and Control System Keypad and Display
ends. Cylinder liners are removable. permanently lubricated. (main power and control panel only)
The backlit 40 character display (LCD, 2
Lubrication - The lubrication is force-fed Refrigerant Circuits
lines of 20 characters) allows the operator
by a reversible oil pump to all crankshaft Unit piping is ACR copper with brazed joints.
to view system operating parameters as
and bearing surfaces and filtered through The liquid line includes: a shut off valve with
well as access programmed information
a fine mesh stainless steel oil strainer. charging port, sightglass with
already in memory.
moisture-indicator, thermal expansion valve
Capacity Control - Capacity control is (direct acting, max-operating pressure), The keypad is provided for programming
provided by, solenoid-actuated, capacity solenoid valve, and filter drier. The entire and accessing setpoints, pressures,
control valves which are controlled by the suction line, the liquid line between the temperatures, motor current, cut-outs,
microprocessor centre. These inject high expansion valve and the cooler, are daily schedule, options and fault
pressure oil to lift pins that close the insulated with flexible, UV stable colour information.
cylinder suction valves when a load coordinated closed-cell, foam insulation.
requirement exists. Gas flow is sufficient The standard controls shall include:
at all times to cool the motor. Compressor low, high and oil pressure automatic pump down at shutdown and
transducers plus manual high pressure recycling pumpdown, run signal contacts,
Isolation - Each compressor is mounted cut-outs are located on the compressor demand load limit from external building
on isolator pads to reduce vibration and system pipework with Econoseal all automation system input, remote reset
transmission to the structure. weather electrical connectors. liquid temperature reset input, unit alarm
Cooler(s) contacts, chilled liquid pump control,
Power And Control Panel(s)
The single/multi-circuit cooler is the automatic or manual reset after power
All controls and motor starting equipment
direct- expansion type, with the failure, automatic system optimisation to
necessary for full unit operation are
refrigerant in the tubes and chilled liquid match operating conditions, software
factory wired and functionally tested. One
flowing through the baffled shell. stored in non-volatile memory (EPROM)
and two refrigerant circuit units have a
to eliminate chiller failure due to AC power
The design working pressure of the shell sigle power and control panel and four
failure. Programmed Setpoint shall be
is 10.3 bar (150 psi), and 16.2 bar (235 circuit units have a two power and control
retained in a lithium battery backed RTC
psi) for the tube side. The refrigerant side panels (main and auxiliary).
memory for a minimum of 5 years.
is constructed and tested in accordance Each panel is divided into sections; with
with CE/PED pressure vessel code For each circuit, the following items shall
seperate power sections serving each
requirements. ASME pressure vessels be displayed in Metric (°C and Bar) or
refrigerant ciruit, a conrol section and a
are available on two and four refrigerant Imperial (°F and psi) units :
common input section.
circuit models. • Return and leaving chilled liquid, and
Components are mounted on galvanised
The water baffles are constructed of ambient temperature.
steel back plates, and enclosed in the
galvanised steel to resist corrosion. The relevant section of the galvanised steel • Day, date and time. Daily start/stop
removable heads allow access to the enclosure. times. Holiday and Manual Override
internally enhanced, seamless, copper status.
tubes. Vent and drain connections are Separate doors are provided for each • Compressor operating hours and
included. Standard cooler connections section. All doors are hinged, lockable starts. Automatic or manual lead/lag.
are Victaulic nozzles. with door stays and are designed to IP55 Lead compressor identification.
weather protection. Enclosure and doors • Run permissive status. No cooling load
The cooler is covered with 19 mm (3/4 are finished in zinc phosphate pre-treated
inch) flexible, closed-cell, UV stable, condition. Compressor run status.
baked enamel coloured Desert Sand. • Anti-recycle timer and anti-coincident
colour co-ordinated foam insulation. Each
circuit is protected by a relief valve. Each Power Section Contains: start timer status per compressor.
Partwind compressor starting contactors, • System suction (and suction
An optional cooler heater mat, controlled system fuses, fan contactors, fan manual superheat), discharge, and oil
by a separate thermostat, provides freeze motor starters and control interface relays pressures and temperatures.
protection for the cooler down to -29°C (CE Compliant). • Percent full load compressor motor
ambient. current. Compressor capacity control
The Common Input Section Contains: valve input steps.
Condenser Non-fused disconnect switch for
Coils - The condenser coils are seamless • Cut-out status and set-points for:
customer single point power supply
copper tubes, arranged in staggered supply fluid temperature, low suction
connection. Transformer and wiring to
rows, mechanically expanded into ripple pressure, high discharge pressure and
allow control voltage to be internally
profile aluminium fins. Integral subcooling temperature, high oil temperature, low
derived (CE Compliant).
is included. The design working pressure and high ambient, high and low current,
of the coil is 31 bar (450 psi). The Control Section Contains: and low leaving liquid temperature.
microprocessor board, power supply • Unloading limit setpoints for high
Fans - The condenser fans are U.V. board and relay board. The relay board discharge pressure and compressor
stable polypropylene, high efficiency, contains the control circuit serving motor current.
airfoil-type fan blades directly driven by compressor solenoids, crankcase • Liquid pull-down rate sensitivity (0.3°C
independent motors, and positioned for heaters and compressor and fan to 3°C/minute in 0.05°C increments).
vertical air discharge. contactor coils.
Page 2
Doc. No. PCYAEP-50/03.04/GB
• Status of: evaporator heater, temperature cut-out, high motor current Remote cycling, unloading and chilled
condenser fans, chilled liquid pump. unload, anti-recycle time (300 - 600 water temperature reset can be
• “Out of range” message. seconds), local remote control, lead lag accomplished by voltage free customer
• Up to 6 fault shut down conditions. control, power failure reset and average contacts.
motor current cut-out.
The following settings can be Settings for liquid temperature set-point
programmed by the operator: high reset signal from YORK ISN or building
discharge pressure cut-out, high automation system.
discharge pressure unload, suction
pressure cut-out, high ambient cut-out,
low ambient cut-out, leaving liquid
Page 3
Doc. No. PCYAEP-50/03.04/GB
TABLE 1 OPERATING LIMITATIONS
All YAEP Models Min. °C (°F) Max. °C (°F)
Leaving Chilled Liquid Temperature - R22 Units 4 (39) 12 (54)
Leaving Chilled Liquid Temperature - R407C Units 6 (43) 12 (54)
Chilled Liquid Temperature Difference 3.3 (6) 8 (15)
Air Entering Standard Units -4 (25) 52 (125)
Condenser Units with Low Ambient Kit -18*(0) 52 (125)
Electrical Power Supply 380/400/415 V, 3Ø, 50 Hz V 342 440
4 Circuit Units
Model YAEP 5555S 6666S 7777X 8888X 8899X 9999X
Minimum Cooler Flow l/s (gpm) 9.4 (150) 9.4 (150) 15.8 (250) 15.8 (250) 15.8 (250) 15.8 (250)
Maximum Cooler Flow l/s (gpm) 40.5 (640) 40.5 (640) 50.7 (805) 50.7 (805) 50.7 (805) 50.7 (805)
Minimum Unit Flow l/s (gpm) 18.8 (300) 18.8 (300) 31.6 (500) 31.6 (500) 31.6 (500) 31.6 (500)
Maximum Unit Flow l/s (gpm) 81 (1280) 81 (1280) 101.4 (1610) 101.4 (1610) 101.4 (1610) 101.4 (1610)
Minimum System Volume l (Usg) 3235 (920) 3735 (1065) 4335 (1235) 5140 (1465) 5910 (1680) 6265 (1785)
4 circuit units are fitted with 2 coolers. The table details flow rate for each cooler and total flow rate for the unit.
Altitude Comp.
COOLER Capacity
Comp. Input
Fouling Factor Capacity Metres Feet Factor
Input Factor
m²°C/kW ft²°F hr/Btu Factor 0 0 1.000 1.000
Factor
0.018 0.00012 1.000 1.000 600 1970 0.987 1.010
0.044 0.00025 0.994 0.998 1200 3940 0.973 1.020
0.088 0.00050 0.981 0.993 1800 5905 0.958 1.029
0.176 0.00100 0.958 0.983 2400 7075 0.943 1.038
0.352 0.00200 0.910 0.960
Condenser Coil
Refrigerant
Circuit No 2
Condenser Coil
Refrigerant
Circuit No 1
High Pressure
superheated vapour
Compressor
Fusible
Plug Optional
Suction
Service
High pressure Valve
sub-cooled liquid
Low pressure liquid refrigerant enters the cooler and is
evaporated and superheated by the heat energy absorbed from
the chilled water passing through the cooler shell. Low pressure Low pressure superheated vapour
vapour enters the compressor where pressure and superheat
are increased. Heat is rejected via the air cooled condenser coil Sight TEV
and fans. The fully condensed and subcooled liquid refrigerant Glass
then enters the expansion valve where pressure reduction and Filter
further cooling takes place before returning to the cooler. Low pressure
Drier Cooler
sub-cooled
liquid/vapour
Refrigerant Circuit No 2
Page 4
Doc. No. PC010HA/02.02/GB
SELECTION GUIDE
DATA REQUIRED From Pressure Drop Graph (Figure 2). YAEP77XC9C cooler
To select a YORK YAEP chiller the following information is water pressure drop = 30.5 kPa (4.4 psi) at the calculated flow of
required: 25.7 l/s. (410 gpm)
1. Required cooling capacity.
2. Required refrigerant.
3. Design chilled water entering and leaving temperatures.
FIGURE 2 COOLER WATER PRESSURE DROP
4. Design water flow rate if one of the temperatures in item 3 are
unknown. 140
5. Design condenser entering air temperature. This will normally 120
be the design summer ambient air temperature unless
location or other factors have an influence. 100
44M
6. Altitude above sea level.
80
7. Design cooler fouling factor.
Note: Items 1, 3 and 4 must be linked by the following formulae: 77X
Cooling Capacity (kW) = Range (°C) x Flow (litre/sec) x 4.18 60 88X
Where Range = Entering liquid temperature - Leaving liquid 99X
50
temperature.
SELECTION METHOD 40
Ambient air entering condenser: 35°C (95°F) Note: Pressure drop applies to each cooler on 4 Circuit Models
Fouling Factor: 0.044m² °C/kW (i.e. the total unit flow should be divided by 2 to obtain the flow
(0.00025 ft²°F hr/Btu) rate through each cooler).
Altitude: Sea level
From a cursory examination of capacity Table 4, a model Model Pressure Drop Calculation
YAEP77XC9C gives approximately the required capacity: 08L,
Pressure Drop [kPa] = 0.2133 x (Flow Rate [l/s]1.7018)
No correction factors apply therefore, after calculating the flow 09L
rate, the conditions will be as follows:
44M Pressure Drop [kPa] = 0.2920 x (Flow Rate [l/s]1.6730)
Cooling Capacity: 537 kW (153 Tons)
Water temperature: 12 to 7°C (Range = 5 °C) 55S,
53 to 44 °F (Range = 9 °F) Pressure Drop [kPa] = 0.2101 x (Flow Rate [l/s]1.6914)
66S
Water flow rate: 25.7 l/s (410 gpm)
Compressor Power: 173 kW 77X,
Pressure Drop [kPa] = 0.1103 x (Flow Rate [l/s]1.7282)
88X, 99X
All values are within the operating limits in Table 1.
Page 5
Doc. No. PCYAEP-50/03.04/GB
YAEP R22 COOLING CAPACITIES - METRIC DATA (°C KW/KW) TABLE 4a
Power (kW) is for compressors only, Power consumption of all fans running: 08L, 44M, 55S = 8.8 kW; 09L, 66S, 77X = 15.2 kW;
88X, 99XB, 5555S = 17.6 kW; 99XD, 6666S, 7777X =30.4 kW; 8888X, 9999XB = 35.2 kW; 9999XD = 60.8 kW.
Page 6
Doc. No. PCYAEP-50/03.04/GB
TABLE 4b YAEP R22 COOLING CAPACITIES - IMPERIAL DATA (°F TONS/KW)
Power (kW) is for compressors only, Power consumption of all fans running: 08L, 44M, 55S = 8.8 kW; 09L, 66S, 77X = 15.2 kW;
88X, 99XB, 5555S = 17.6 kW; 99XD, 6666S, 7777X =30.4 kW; 8888X, 9999XB = 35.2 kW; 9999XD = 60.8 kW.
Page 7
Doc. No. PCYAEP-50/03.04/GB
YAEP R407C COOLING CAPACITIES - METRIC DATA (°C KW/KW) TABLE 4c
Power (kW) is for compressors only, Power consumption of all fans running: 08L, 44M = 8.8 kW; 09L, 55S, 66S, 77XC = 15.2 kW;
77XF = 13.2 kW; 88X =17.6 kW; 99XD, 5555S, 6666S, 7777XC =30.4 kW; 7777XF = 26.4 kW; 8888X, 8899X = 35.2 kW; 9999XD = 60.8 kW.
Page 8
Doc. No. PCYAEP-50/03.04/GB
TABLE 4d YAEP R407C COOLING CAPACITIES - IMPERIAL DATA (°F TONS/KW)
Power (kW) is for compressors only, Power consumption of all fans running: 08L, 44M = 8.8 kW; 09L, 55S, 66S, 77XC = 15.2 kW;
77XF = 13.2 kW; 88X =17.6 kW; 99XD, 5555S, 6666S, 7777XC =30.4 kW; 7777XF = 26.4 kW; 8888X, 8899X = 35.2 kW; 9999XD = 60.8 kW.
Page 9
Doc. No. PCYAEP-50/03.04/GB
PHYSICAL DATA - YAEP R22 UNITS TABLE 5a
4 Circuit Units
YAEP 5555SC7C 6666SC9C 7777XC9C 8888XB7C 8899XB7C 9999XD9C
Unit Number of Capacity Steps 8 8 8 12 12 12
Number of Compressors 4 4 4 4 4 4
Compressor Cylinders per Compressor 4 6 6 8 8 8
Oil Capacity per Compressor l 11 11 11 11 11 11
Coolers per Unit 2 2 2 2 2 2
Cooler Refrigerant Circuits per Cooler 2 2 2 2 2 2
Water Capacity per Cooler l 150 150 205 205 205 205
Condenser Face Area m2 23.8 23.8 23.8 47.6 47.6 47.6
Quantity 8 8 8 16 16 16
Fans Power (each) kW 2.2 3.8 3.8 2.2 2.2 3.8
Total Airflow m3/s 60.8 69.6 69.6 121.6 121.6 139.2
Systems 1/2 kg 49.0 49.0 49.0 57.0 57.0 64.0
Refrigerant Charge
Systems 3/4 kg 49.0 49.0 49.0 57.0 57.0 64.0
Ship (Main) kg 4200 4350 4495 5222 5222 5422
Aluminium Fins Ship (Aux.) kg 4200 4350 4495 5222 5222 5422
Operating kg 8700 9000 9400 10854 10854 11254
Weight
Ship (Main) kg 4490 4640 4785 5797 5797 5997
Copper Fins Ship (Aux.) kg 4490 4640 4785 5797 5797 5997
Operating kg 9280 9580 9980 12004 12004 12404
Length mm 6128 6128 6128 11705 11705 11705
Dimensions Width mm 2241 2241 2241 2241 2241 2241
Height mm 2466 2466 2466 2466 2466 2466
Page 10
Doc. No. PCYAEP-50/03.04/GB
TABLE 5b PHYSICAL DATA - YAEP R407C UNITS
1 Circuit Units 2 Circuit Units
YAEP 08LC7B 09LC9B 44MC7B 55SC9B 66SC9B 77XC9B 77XF7B 88XD7B 99XD9B
Unit Number of Capacity Steps 3 3 4 4 4 4 4 6 6
Number of Compressors 1 1 2 2 2 2 2 2 2
Compressor Cylinders per Compressor 8 8 4 4 6 6 6 8 8
Oil Capacity per Compressor l 11 11 11 11 11 11 11 11 11
Coolers per Unit 1 1 1 1 1 1 1 1 1
Cooler Refrigerant Circuits per Cooler 1 1 2 2 2 2 2 2 2
Water Capacity per Cooler l 90 90 135 150 150 205 205 205 205
Condenser Face Area m2 11.9 11.9 11.9 11.9 11.9 11.9 17.8 23.8 23.8
Quantity 4 4 4 4 4 4 6 8 8
Fans Power (each) kW 2.2 3.8 2.2 3.8 3.8 3.8 2.2 2.2 3.8
Total Airflow m3/s 30.4 34.8 30.4 34.8 34.8 34.8 44.7 60.8 69.6
Systems 1 kg 39.0 42.0 42.0 49.0 49.0 49.0 53.0 57.0 64.0
Refrigerant Charge
Systems 2 kg 42.0 49.0 49.0 49.0 53.0 57.0 64.0
Shipping kg 3550 3665 4000 4200 4350 4495 4985 5222 5422
Aluminium Fins
Operating kg 3640 3640 4135 4350 4500 4700 5190 5427 5627
Weight
Shipping kg 3740 3955 4190 4490 4640 4785 5400 5797 5997
Copper Fins
Operating kg 3830 4045 4325 4640 4790 4990 5605 6002 6202
Length mm 2969 2969 2969 2969 2969 2969 4193 5703 5703
Dimensions Width mm 2241 2241 2241 2241 2241 2241 2241 2241 2241
Height mm 2466 2466 2466 2466 2466 2466 2466 2466 2466
4 Circuit Units
YAEP 5555SC9B 6666SC9B 7777XC9B 7777XF7B 8888XD7B 8899XD7B 9999XD9B
Unit Number of Capacity Steps 8 8 8 8 12 12 12
Number of Compressors 4 4 4 4 4 4 4
Compressor Cylinders per Compressor 4 6 6 6 8 8 8
Oil Capacity per Compressor l 11 11 11 11 11 11 11
Coolers per Unit 2 2 2 2 2 2 2
Cooler Refrigerant Circuits per Cooler 2 2 2 2 2 2 2
Water Capacity per Cooler l 150 150 205 205 205 205 205
Condenser Face Area m2 23.8 23.8 23.8 35.6 47.6 47.6 47.6
Quantity 8 8 8 12 16 16 16
Fans Power (each) kW 3.8 3.8 3.8 2.2 2.2 2.2 3.8
Total Airflow m3/s 69.6 69.6 69.6 89.4 121.6 121.6 139.2
Systems 1/2 kg 49.0 49.0 49.0 53.0 57.0 57.0 64
Refrigerant Charge
Systems 3/4 kg 49.0 49.0 49.0 53.0 57.0 57.0 64
Ship (Main) kg 4200 4350 4495 4985 5222 5222 5422
Aluminium Fins Ship (Aux.) kg 4200 4350 4495 4985 5222 5222 5422
Operating kg 8700 9000 9400 10380 10854 10854 11254
Weight
Ship (Main) kg 4490 4640 4785 5400 5797 5797 5997
Copper Fins Ship (Aux.) kg 4490 4640 4785 5400 5797 5797 5997
Operating kg 9280 9580 9980 11210 12004 12004 12404
Length mm 6128 6128 6128 8586 11705 11705 11705
Dimensions Width mm 2241 2241 2241 2241 2241 2241 2241
Height mm 2466 2466 2466 2466 2466 2466 2466
Page 11
Doc. No. PCYAEP-50/03.04/GB
ELECTRICAL DATA - YAEP R22 UNITS TABLE 6a
Power Requirement per Panel - 1, 2 and 4 Refrigerant Circuit Units with Single Point Power Supply - Disconnect Switch (CE) or Terminal Block Option (Non CE)
(Data includes one/both compressors and associated fans)
Note: To obtain the total unit power requirements on four circuit models 5555SC7C / 6666SC9C / 7777XC9C / 8888XB7C / 9999XD9C multiply the panel values by 2.
Note: To obtain the total unit power requirements on four circuit model 8899XB7C the panel values should be added together.
YAEP Model 35°C/7°C Nominal. Amps Maximum. Amp Part Wind Inrush
Circuits
Nom. kW Max. kW 380 V 400 V 415 V 342 V 380 V 400 V 415 V 380 V 400 V 415 V
08LA7C 1 101 144 195 194 193 293 268 266 264 689 725 752
09LC9C 1 122 150 228 226 224 293 268 266 264 689 725 752
44MC7C 2 107 125 197 195 193 275 231 225 221 398 409 420
(55)55SC7C 2/4 137 163 239 237 235 315 289 285 279 500 518 532
(66)66SC9C 2/4 149 185 278 276 274 356 336 332 328 626 648 674
(77)77XC9C 2/4 189 227 348 344 342 422 408 404 400 753 780 802
(88)88XB7C 2/4 228 300 410 408 406 580 530 526 522 954 988 1015
99XB7C 2 270 300 480 470 466 580 530 526 522 954 988 1015
228 300 410 408 406 580 530 526 522 954 988 1015
8899XB7C 2+2
270 300 480 470 466 580 530 526 522 954 988 1015
(99)99XD9C 2/4 250 300 469 463 461 595 545 541 537 961 995 1020
Power Requirement per Refrigeration Circuit - 2 and 4 Refrigerant Circuit Units with Multi Point Power Supply Option (Non CE)
(Data includes each circuit compressor and associated fans)
YAEP Model 35°C/7°C Nominal. Amps Maximum. Amp Part Wind Inrush
Circuits
Nom. kW Max. kW 380 V 400 V 415 V 342 V 380 V 400 V 415 V 380 V 400 V 415 V
44MC7C 2 53 62 98 97 96 137 115 112 110 283 297 308
55SC7C 2 69 82 119 118 117 157 144 142 139 356 376 390
66SC9C 2 75 93 139 138 137 178 168 166 164 458 482 508
77XC9C 2 95 114 174 172 171 211 204 202 200 549 578 600
88XB7C 2 114 150 205 204 203 290 265 263 261 689 725 752
99XB7C 2 135 150 240 235 233 290 265 263 261 689 725 752
99XD9C 2 125 150 234 231 230 297 272 270 268 689 725 752
5555SC7C 4 65 82 119 118 117 157 144 142 139 356 376 390
6666SC9C 4 71 93 139 138 137 178 168 166 164 458 482 508
7777XC9C 4 91 114 174 172 171 211 204 202 200 549 578 600
8888XB7C 4 114 150 205 204 203 290 265 263 261 689 725 752
8899XB7C Main 2 114 150 205 204 203 290 265 263 261 689 725 752
8899XB7C Aux 2 135 150 240 235 233 290 265 263 261 689 725 752
9999XD9C 4 125 150 234 227 230 297 272 270 268 689 725 752
Power Requirement per Panel - 1, 2 and 4 Refrigerant Circuit Units with Single Point Power Supply - Disconnect Switch (CE) or Terminal Block Option (Non CE)
(Data includes one/both compressors and associated fans)
Note: To obtain the total unit power requirements on four circuit models 5555SC9B / 6666SC9B / 7777XC9B / 7777XF7B / 8888XB7B / 9999XD9B multiply the panel values by 2.
Note: To obtain the total unit power requirements on four circuit model 8899XB7B the panel values should be added together.
YAEP Model 35°C/7°C Nominal. Amps Maximum. Amp Part Wind Inrush
Circuits
Nom. kW Max. kW 380 V 400 V 415 V 342 V 380 V 400 V 415 V 380 V 400 V 415 V
08LC7B 1 97 144 190 189 188 293 268 266 264 689 725 752
09LC9B 1 123 150 228 226 224 293 268 266 264 689 725 752
44MC7B 2 105 125 197 195 193 275 231 225 221 398 409 418
(55)55SC9B 2/4 137 163 246 244 242 322 296 292 286 504 522 533
(66)66SC9B 2/4 149 185 280 278 276 356 336 332 328 626 648 672
(77)77XC9B 2/4 187 227 348 346 342 422 412 406 400 755 781 800
(77)77XF7B 2/4 177 225 331 329 327 427 417 411 405 758 784 803
(88)88XB7B 2/4 200 288 386 380 374 580 530 526 522 954 988 1013
200 288 386 380 446 580 530 526 522 954 988 1013
(88)99XB7B 2+2
244 288 450 448 446 580 530 526 522 954 988 1013
(99)99XD9B 2/4 250 300 457 455 453 595 545 541 537 961 995 1020
Power Requirement per Refrigeration Circuit - 2 and 4 Refrigerant Circuit Units with Multi Point Power Supply Option (Non CE)
(Data includes each circuit compressor and associated fans)
YAEP Model 35°C/7°C Nominal. Amps Maximum. Amp Part Wind Inrush
Circuits
Nom. kW Max. kW 380 V 400 V 415 V 342 V 380 V 400 V 415 V 380 V 400 V 415 V
44MC7B 2 52 62 98 97 96 137 115 112 110 283 297 308
55SC9B 2 69 82 123 122 121 161 148 146 143 356 376 390
66SC9B 2 75 93 140 139 138 178 168 166 164 458 482 508
77XC9B 2 94 114 174 173 171 211 206 203 200 549 578 600
77XF7B 2 89 113 166 165 164 214 209 206 203 549 578 600
88XB7B 2 100 144 193 190 187 290 265 263 261 689 725 752
99XD9B 2 125 150 228 227 226 297 272 270 268 689 725 752
5555SC9B 4 65 82 123 122 121 161 148 146 143 356 376 390
6666SC9B 4 71 93 140 139 138 178 168 166 164 458 482 508
7777XC9B 4 90 114 174 173 171 211 206 203 200 549 578 600
7777XF7B 4 91 113 166 165 164 214 209 206 203 549 578 600
8888XB7B 4 100 144 193 190 187 290 265 263 261 689 725 752
8899XB7B Main 2 100 144 193 190 187 290 265 263 261 689 725 752
8899XB7B Aux 2 122 144 225 224 223 290 265 263 261 689 725 752
9999XD9B 4 125 150 228 227 226 297 272 270 268 689 725 752
Page 12
Doc. No. PCYAEP-50/03.04/GB
POWER SUPPLY CONNECTIONS
(Main Panel and Auxiliary Panel when fitted)
Common
Input
Section
Control
Section
Power Power
Section 1 Section 2
Common
Input
Section
Common
Input
Section
1 PS 2 PS
One supply per panel to a common terminal block (QCSITB) with
internal power distribution to fuses, control supply to non-fused AMB ARB
disconnect switch (QCSD/ESD) derived internally.
CS
Compressor CIS Compressor
3
1 PS 2 PS
Contactor 4 Contactor
CIS
U V W U V W
F F F F F F QCSD/ESD PE
QCSITB PE PE
U V W
PE 3 4
QRESB
PE
L1 L2 L3 QRESB
3 50 Hz 380/400 V
PE PE PE
L1 L2 L3 L1 L3 L1 L2 L3
3 50Hz 2 50Hz 3 50Hz
380/400V 380/400V 380/400V
Page 13
Doc. No. PCYAEP-50/03.04/GB
CONTROL CONNECTIONS
(Main Panel and Auxiliary Panel when fitted)
YAEP 08L-09L YAEP 44M-77X & 5555S-7777X YAEP 88X-99X & 8888X-9999X
Common Common
Input Common Input
Section Input Section
Section
Control Section
Communication Link 34
(4 Circuit Units Only) APB
33
} Chilled Liquid Pump Start
}
36
Unit Run Signal
AMB 35
} Open on Alarm
}
ARB 37
MAIN System
PANEL 38
Close on Alarm No. 2 / 4
39 }
30
} Open on Alarm
}
BLACK
WHITE
31 System
AUXILIARY
PANEL Mixed Water
Temperature
(4 Circuit Units Only)
DESIGNATION DESCRIPTION
Note 1 AMB MICROPROCESSOR BOARD
APB POWER SUPPLY BOARD
13 10 11 14 12 15 16 13 17 18 10 13 ARB RELAY BOARD
Communications Link Cable CS CONTROL SECTION
to be field run and CIS COMMON INPUT SECTION
connected to Main Panel TB7
PS POWER SECTION
during installation
Remote Lead/Lag
Note 1: Fit link between terminals 14 and 15 and connect a voltage free contact to terminals 11 and 14
for combined Remote Start/Stop of systems 1 / 2 (2 circuit units) and systems 3 / 4 (4 circuit units).
Page 14
Doc. No. PCYAEP-50/03.04/GB
2969
2466
1990
DIMENSIONS YAEP 08L & 09L
840
520
335
946 493 AVM 1911 AVM C
L 148 446
2897 2241
Page 15
Doc. No. PCYAEP-50/03.04/GB
Page 16
Doc. No. PCYAEP-50/03.04/GB
2969
2466.4
DIMENSIONS YAEP 44M - 77XC
407
(382 on 44M and 446 on 77XC)
2241
2467
446
Page 17
Doc. No. PCYAEP-50/03.04/GB
Page 18
Doc. No. PCYAEP-50/03.04/GB
5700 1800
221
40
8" (200 mm) 8" (200 mm)
1153
Outlet Inlet
2426
124
DIMENSIONS YAEP 88X - 99X
838
446
634 2108 702
2166 AVM POSITIONS
COMPRESSOR
199 AVM 2438 AVM POSITIONS 1220 AVM 1257 AVM 292 AVM
2241 SYSTEM 2
5407
SYSTEM 1 COMPRESSOR
REMOVED FOR DRAWING CLARITY
6232
2241
8" (200 mm) 8" (200 mm) 8" (200 mm) 8" (200 mm)
Inlet Outlet Outlet Inlet
1150
2466
DIMENSIONS YAEP 5555S - 7777XC
840
1911 AVM POS. 493 493 1911 AVM POS. 2172 AVM POSITIONS
406
Page 19
Doc. No. PCYAEP-50/03.04/GB
Page 20
Doc. No. PCYAEP-50/03.04/GB
8812
300 2241
8" (200 mm) 8" (200 mm) 8" (200 mm) 8" (200 mm)
Inlet Outlet Outlet Inlet
DIMENSIONS YAEP 7777XF
2467
446
2108 1631 1631 2108 702
493 1707 1676 312 312 1676 1707 2172
4187 4187
8675
MULTI POINT
MULTI POINT CABLE ENTRY
CABLE ENTRY SYSTEM 2
SYSTEM 3
SINGL POINT
SINGL POINT CABLE ENTRY
CABLE ENTRY SYSTEMS 1 & 2
1800
SYSTEMS 3 & 4
MULTI POINT
CABLE ENTRY
MULTI POINT SYSTEM 1
CABLE ENTRY
SYSTEM 4
11700
221
40
8" (200 mm) 8" (200 mm)
Inlet Outlet
1153
2426
838
446
DIMENSIONS YAEP 8888X - 9999X
Page 21
Doc. No. PCYAEP-50/03.04/GB
EMEA
YORK
YORK INTERNATIONAL
GB