"Failure" refers to Failure Mode in reference to the root cause

Severity Rating Probability Rating Detection Rating


# Activity Detail Guideline # Activity Detail Guideline # Activity Detail Guideline
Failure potential is obvious (visual
Failure unlikely. History shows no
1 No effect No effect of failure 1 Almost never 1 Almost Certain inspection); no parameter deviations
failures
occur
Automatic process control occurs
Rare number of failures likely (> 60
2 Very slight effect Minor impact on local efficiency 2 Remote 2 Very High when process parameters go out of
months)
range
Major impact of local efficiency but
Failures repeated at a moderate Automatic alarm is triggered when
3 Slight effect negligible impact on overall 3 Very slight 3 High
frequency (36 - 60 months) process parameters go out of range
efficiency
Process parameters indicating
Failures repeated at a moderate potential of failure are tracked in
4 Minor effect Major impact on overall efficiency 4 Slight 4 Moderately High
frequency (24 - 36 months) DCS / SCADA and online Condition
monitoring
Minor equipment damage Failure potential is detectable but
Failures repeated at a moderate
5 Moderate effect (equipment repair) but no generation 5 Low 5 Moderately High only through interval based PM &
frequency (18 - 24 months)
/ no availability loss time bound Condition Monitoring
Major equipment damage Process parameters indicating
(equipment replacement) but no Failures repeated at a moderate occurrence of failures are
6 Significant effect 6 Medium 6 Low
generation / no availability loss or frequency (12 - 18 months) measurable, but not in DCS /
minor HSE impact or both SCADA
Failue is detected immediately after
Partial generation loss / partial Failures repeated at a moderate – it occurs, but no generation loss /
7 Major effect 7 Moderately high 7 Very Low
availability loss / grid incentive loss high frequency (9 - 12 months) efficiency loss / availability loss / grid
incentive loss
Failure is detected some time after it
Partial generation loss / partial
Failures repeated at a moderate – occurs, but no generation loss /
8 Extreme effect availability loss / grid incentive loss 8 High 8 Remote
high frequency (6 – 9 months) efficiency loss / availability loss / grid
with major equipment damage
incentive loss
Failure is detected only after partial
Unit trip / Complete grid failure or Failures repeated at a moderate –
9 Serious effect 9 Very high 9 Very Remote generation loss / availability loss /
serious HSE Impact high frequency (3 – 6 months)
grid incentive loss
Unit trip / Complete grid network Failure tends to be repeated at a Absolute Failure is detected only after unit
10 Hazardous effect 10 Almost certain 10
failure and serious HSE Impact high frequency (< 3 months) Uncertainty trip / complete grid network failure
Process/ Equipment Process/ Equipment Description
Department Component
Description & Function & Function

LV / MV SWITCHGEAR Circuit Breaker

LV / MV SWITCHGEAR Circuit Breaker

LV / MV SWITCHGEAR Circuit Breaker

LV / MV SWITCHGEAR Circuit Breaker

LV / MV SWITCHGEAR Circuit Breaker

LV / MV SWITCHGEAR Circuit Breaker

LV / MV SWITCHGEAR Circuit Breaker

LV / MV SWITCHGEAR Circuit Breaker

LV / MV SWITCHGEAR Circuit Breaker

LV / MV SWITCHGEAR Circuit Breaker

LV / MV SWITCHGEAR Bus Bar compartment

LV / MV SWITCHGEAR Bus Bar compartment

LV / MV SWITCHGEAR Bus Bar compartment

LV / MV SWITCHGEAR Cable compartment

LV / MV SWITCHGEAR PT/ CT

LV / MV SWITCHGEAR PT/ CT

LV / MV SWITCHGEAR PT/ CT

LV / MV SWITCHGEAR PT/ CT

LV / MV SWITCHGEAR Protection Relay

LV / MV SWITCHGEAR MCB

LV SWITCHGEAR MCCB
LV SWITCHGEAR MPCB / Overload relays
LV SWITCHGEAR LV modules
LV SWITCHGEAR LV modules

Boiler Pressure parts CGPL-MMD

Boiler Pressure parts CGPL-MMD

Boiler Pressure parts CGPL-MMD


Boiler Pressure parts CGPL-MMD

Boiler Pressure parts CGPL-MMD

Boiler Pressure parts CGPL-MMD

Boiler Pressure parts CGPL-MMD

Boiler Pressure parts CGPL-MMD

Boiler Pressure parts CGPL-MMD


Boiler Pressure parts CGPL-MMD

Boiler Pressure parts CGPL-MMD

Boiler Pressure parts CGPL-MMD

Boiler Pressure parts CGPL-MMD

Boiler Pressure parts CGPL-MMD

Boiler Pressure parts CGPL-MMD


CGPL-MMD

Boiler Pressure parts CGPL-MMD

Boiler Pressure parts CGPL-MMD

Boiler Pressure parts CGPL-MMD

Boiler Pressure parts CGPL-MMD

Boiler Pressure parts CGPL-MMD


Boiler Pressure parts CGPL-MMD

Boiler Pressure parts CGPL-MMD

Boiler Pressure parts CGPL-MMD

Boiler Pressure parts CGPL-MMD

Boiler Pressure parts CGPL-MMD

Boiler Pressure parts CGPL-MMD


Boiler Pressure parts CGPL-MMD

Boiler Pressure parts CGPL-MMD

Boiler Pressure parts CGPL-MMD

Boiler Pressure parts CGPL-MMD

Boiler Pressure parts CGPL-MMD


Boiler Pressure parts CGPL-MMD

Boiler Pressure parts CGPL-MMD

Boiler Pressure parts CGPL-MMD

Boiler Pressure parts CGPL-MMD

Boiler Pressure parts CGPL-MMD

Boiler Pressure parts CGPL-MMD


Boiler Pressure parts CGPL-MMD

Boiler Pressure parts CGPL-MMD

Boiler Pressure parts CGPL-MMD

Boiler Pressure parts CGPL-MMD


Boiler Pressure parts CGPL-MMD

Boiler Pressure parts CGPL-MMD

Boiler Pressure parts CGPL-MMD

Boiler Pressure parts CGPL-MMD


Boiler Pressure parts CGPL-MMD

Boiler Pressure parts CGPL-MMD

Boiler Pressure parts CGPL-MMD

Boiler Pressure parts CGPL-MMD


Boiler Pressure parts CGPL-MMD

Boiler Pressure parts CGPL-MMD


Boiler Pressure parts CGPL-MMD

CGPL-MMD
Function Functional failure

Switches and disconnects electrical


Vacuum Bottle Failure
power source from load
Switches and disconnects electrical
Vacuum Bottle Failure
power source from load
Switches and disconnects electrical
Breaker mechanishm failure
power source from load
Switches and disconnects electrical
Spring charge motor failure
power source from load
Switches and disconnects electrical
Spring charge motor failure
power source from load
Switches and disconnects electrical
power source from load Fails to open on command
Switches and disconnects electrical Fails to open on command – Opens
power source from load but fails to interrupt

Switches and disconnects electrical Fails to open on command – Opens


power source from load but fails to maintain open contact
insulation
Switches and disconnects electrical
power source from load Closes without command

Switches and disconnects electrical


power source from load
Fails to provide insulation
Provides interconnection between
Partial Discharge
parallel feeders
Provides interconnection between
Insulator Failure
parallel feeders
Provides interconnection between
Improper bus bar connection
parallel feeders
Provides connection to Outgoing
Improper Cable termination
feeders via power cable
For measurement of Current &
Failure of CT / PT
voltages and protection
For measurement of Current &
Improper Cable termination
voltages and protection
For measurement of Current &
Improper bus bar connection
voltages and protection
For measurement of Current &
Partial Discharge
voltages and protection

For tripping of Breaker during fault


Failure of Relay
condition

Loss of power to control &


For control and measurement circuit
measurement circuits
Switches and disconnects electrical
power source from load
For protection of motor
Switches and disconnects electrical
Power connection failed
power source from load
Switches and disconnects electrical
Control connection failed
power source from load
Failure Mode Root Cause of failure L1

Loss of vacuum Aging

Flashover across the external portion Dirt and contamination

Jam in mechanishm Inappropriate or inadequate lubrication


Motor winding failure Insulation failure

Motor continous operation Limit switch operation failed

Flashover Open or shorted trip coil

Flashover Loss of vacuum

Flashover Loss of vacuum

Flashover Stray current in close circuit

Flashover Excessive temperature of insulating materials


Detoriation of Insulation Tracking via moisture,Dirt and contamination

Flashover Void within insulation

Overheating Loose connection

Overheating Loose connection

Flashover Insulation failure

Maloperation of Relays Loose connection of cables in terminals

Overheating Loose connection

Detoriation of Insulation Tracking via moisture,Dirt and contamination

Fails to open circuit breaker Didn’t operate during fault

Short circuit in control circuit

Flashover Aging
Aging
Male & female sliding contact of power module
Flashover
improper
Male & female sliding contact of control module
Problem in control circuit
improper
Root Cause of failure
Root Cause of failure L2 Root Cause of failure L3
L4

Aging

Wear out of charging mechanishm

Inappropriate or inadequate lubrication Loss of stored interrupting energy Mechanical failure

Arc chute failure Mechanical failure Contact ablation

Mechanism does not travel complete


distance

Unwanted power on intertrip signaling Spring release mechanism worn

Ionization of surrounding insulating air Water / moisture infiltration Dirt or pollution


Void within insulation
Tracking via moisture,Dirt and
contamination

Void within insulation

Wrong protection
Loose connections Software problems (booting errors) settings /
configuration
inulation failure of wires used in Loose connections
Aging
control circuit at terminals
Male & female contact of power Loose connections
Insulation failure of cable
module improper at terminals
Insulation failure of motor / cable Loose connections at terminals
Root Cause of failure L5 Root Cause of failure L6 Root Cause of failure L7 Effect on the Equipment

Failure

Failure

Failure

Failure

Failure

Failure

Failure

Deterioration of interrupter
exterior surfaces caused by Failure
partial discharge
Failure

Failure

Failure

Wrong connections Failure

Failure

Failure
Local effect of failure Overall effect of failure ( Unit / Process control mechanisms for Severity
(Immediate System) Station / Grid) detection Rating

Switchgear outage Unit / station 8

Switchgear outage Unit / station 8

Switchgear outage Unit / station 8

Switchgear outage Unit / station 9

Switchgear outage Unit / station 9

Switchgear outage Unit / station 9

Switchgear outage Unit / station 9

Switchgear outage Unit / station 10

Switchgear outage Unit / station 8

Switchgear outage Unit / station 8

Switchgear outage Unit / station 8

Switchgear outage Unit / station 9

Switchgear outage 7
6
Switchgear outage 7
4
Probability
Detection Rating RPN Number
Rating

2 9 144

3 9 216

2 9 144

2 9 108

2 9 108

5 8 360

5 6 270

5 6 270

5 6 270

2 2 40

2 8 128

2 3 48

2 6 72

2 6 72

2 2 32

2 6 72

2 6 72

2 8 128

2 5 90

3 7 126

2 8 112
3 7 126
2 5 70
5 6 120