Sie sind auf Seite 1von 52

Refrigeration

Retrofit Guidelines

R-12 to: 134a


MP39 /401A
MP66 /401B
409A

R- 502 to: AZ-50 507


HP80 /402A
404A
408A
Safety Tips
1. Never mix refrigerants in a refrigeration system or recovery cylinder. Any
refrigerant mixing creates a non-reclaimable mixture that will cost you or
your customer more money to dispose of.

2. Never leak test a system using air, oxygen or other oxidizing materials. When
combined with HFCs and HCFCs under pressure, these mixtures can become
combustible.

3. Always read the label and Material Safety Data Sheet (MSDS) before working
with the refrigerant(s).

4. Never “top-off” a system with a refrigerant other than what is already in that
system. If you aren’t sure what’s in a system, either recover the full charge
or have the refrigerant tested.

5. Always make sure systems you work on are properly labeled with the
refrigerant and oil when you leave.

6. Do not store refrigerant cylinders in direct sunlight or in areas where


temperatures could exceed 125° F or 51.7° C.

7. Keep smaller cylinders from becoming a rolling hazard by keeping them in


their cartons while storing or transporting them.

8. Always recover the contents of non-refillable refrigerant cylinders to 0 psig or


less before disposing of them. Whenever possible, recycle non-refillable
cylinders at a local metal recycling center or scrapyard.
Table of Contents
HFC Retrofit Guidelines 2
Genetron HFC Refrigerants 3
General HFC Retrofit Procedures 4
Genetron AZ-50 Retrofit Specifics 10
Genetron 404A Retrofit Specifics 12
Genetron 134a Retrofit Specifics 14

HCFC Retrofit Guidelines 16


Genetron HCFC Refrigerants 17
General HCFC Retrofit Procedures 19
Genetron MP39 Retrofit Specifics 24
Genetron MP66 Retrofit Specifics 26
Genetron 409A Retrofit Specifics 28
Genetron HP80 Retrofit Specifics 30
Genetron 408A Retrofit Specifics 32

Pressure -Temperature Data 34


English Units 34
R-12 and R-12 Replacements
Pressure-Temperature Table 34
Temperature-Pressure Table 36
R-502 and R-502 Replacements
Pressure-Temperature Table 38
Temperature-Pressure Table 40

Standard International Units 42


R-12 and R-12 replacements
Pressure-Temperature Table 42
Temperature-Pressure Table 44

R-502 and R-502 Replacements


Pressure-Temperature Table 46
Temperature-Pressure Table 48

How to Use These Guidelines


This booklet is broken into three sections: HFC Guidelines, HCFC
Guidelines and Pressure-Temperature Tables
The HFC and HCFC guidelines begin with a General Procedures
section that provides general guidelines for working with any
Genetron HFC or HCFC refrigerant. The table below indicates the
categories for each retrofit fluid. In the pages following each
General Procedures section, you will find guidelines specific to the
refrigerant you intend to retrofit into the system. In the back pages
of the booklet are tables of Pressure and Temperature data for
R-12 replacements and R-502 replacements. Both Pressure-
Temperature and Temperature-Pressure tables are provided to
help you to work faster.

Recommended
Retrofit Refrigerants HFC-Based HCFC-Based
R-12 Retrofits 134a MP39 (401A)
MP66 (401B)
409A
R-502 Retrofits AZ-50 (507) HP80 (402A)
404A 408A

HFC Retrofit Guidelines 1


HFC Retrofit Guidelines
With the phaseout of CFCs continuing,
and the phaseout of HCFCs on the horizon,
retrofitting existing systems to non-ozone
depleting HFCs can be a cost-effective
alternative to complete system replacement.
By following equipment manufacturers’
recommendations and the guidelines in
this publication, service technicians can
readily retrofit many CFC-12 refrigeration
systems to Genetron 134a, or convert
R-502 systems to Genetron 404A or
Genetron AZ-50 refrigerants.

Although the information in this booklet can


be helpful as a general guide, it should not
be used as a substitute for the equipment
manufacturer’s specific recommendations.
For this reason, Honeywell strongly
recommends contacting the equipment
manufacturer for detailed information on
retrofitting the specific model under
consideration. Also, refer to the Material
Safety Data Sheet (MSDS) for safety
information on the specific Genetron
Refrigerant you will use.

2 HFC Retrofit Guidelines


Genetron HFC Refrigerants
Genetron AZ-50, Genetron 404A and Genetron 134a are HFC
refrigerants and are not scheduled for phaseout under current law.
Descriptive information including refrigerant type, ASHRAE
number, constituents and applications appear in the table below.

Applications
Genetron
Refrigerant Type Replaces Applications & Comments
AZ-50 (R-507) Azeotrope R-502 Supermarket freezer cases,
reach-in coolers, display cases,
ice machines.
404A (R-404A) Blend R-502 Supermarket freezer cases,
reach-in coolers, display cases,
transport refrigeration, ice machines.
134a (R-134a) Pure R-12 Supermarket display cases,
walk-in coolers, beverage dispensers,
vending machines, water coolers and
domestic refrigerators. Use where
temperature is above -10°F (-23°C).

When Should an HFC refrigerant be used?


Where feasible, the preferred replacement for CFC-12 is
Genetron 134a. Likewise, the preferred replacement for R-502 is
an HFC such as Genetron AZ-50. Although these non-ozone-
depleting HFC refrigerants are being used in many OEM
applications, there are instances where retrofitting to an HFC may
be difficult because nearly all of the mineral oil in the system must
be removed. In these situations, an interim service fluid such as a
Genetron MP blend, Genetron HP blend, Genetron 408A or
Genetron 409A may be preferred.

Service technicians should keep in mind that future regulations


may further restrict the use of HCFC refrigerants and dictate the
ultimate use of HFC refrigerants such as Genetron AZ-50,
Genetron 404A and Genetron 134a.

HFC Refrigerants are not “Drop-in” Replacements


The HFC refrigerants are not “drop-in” replacements for CFC or
HCFC refrigerants. Mineral oils and alkylbenzene lubricants, which
have been used traditionally with R-502 and R-12, are immiscible
with HFC refrigerants such as Genetron AZ-50, Genetron 404A
and Genetron 134a. These HFC refrigerants require the use of a
lubricant that is miscible with the refrigerant, such as a polyol
ester (POE) lubricant. The retrofit procedures listed here have
been developed by Honeywell to address these issues and to help
technicians perform successful retrofits of R-502 and R-12
systems utilizing positive-displacement (reciprocating, rotary,
scroll or screw) compressors.

HFC Retrofit Guidelines 3


General HFC Retrofit Procedures
A word about system preparation: In retrofitting an existing
refrigeration system, the condition of the existing seals and
gaskets must be taken into account. Heat set, compression set,
and seal shrinkage can all impact the condition of an existing seal
or gasket. When the system is put under vacuum, the sealing
device can be displaced, creating the potential for leakage.
Whenever possible, gaskets and seals should be replaced in
order to minimize the chances of an old seal or gasket becoming
a source of a leak.

1. Record Baseline Data


Before making any hardware changes, compare current system
operating data with normal operating data. Correct any
deficiencies and record final data as a performance baseline.
Data should include temperature and pressure measurements
throughout the system including the evaporator, compressor
suction and discharge, condenser and expansion device. These
measurements will be useful when adjusting the system with an
alternative Genetron Refrigerant.

2. Isolate CFC Refrigerant Charge


The CFC refrigerant charge should be isolated from the system
by pumping it down into the receiver. If no receiver is present,
the refrigerant must be removed from the system using a
recovery machine capable of meeting or exceeding the required
levels of evacuation.

The charge must be collected in a recovery cylinder dedicated to


that refrigerant (e.g., CFC-12 or CFC-502). Do not mix the
recovered material with other refrigerants in a recovery tank, as
this will result in a mixture that cannot be reclaimed. Do not vent
the refrigerant to the atmosphere.

Knowing the recommended CFC refrigerant charge size for the


system is helpful. If it is not known, weigh the entire amount of
refrigerant removed. This amount can be used as a guide for
calculating the initial quantity of alternative Genetron Refrigerant
to be charged to the system.

3. Choose Compressor Lubricant


Mineral oil or alkylbenzenes are typically used as the lubricants
for R-12 and R-502 compressors. To achieve miscibility of
Genetron AZ-50, Genetron 404A or Genetron 134a (stationary
applications), a polyol ester lubricant may be used. Honeywell
recommends using a lubricant approved by the compressor
manufacturer. Differences among polyol ester-based
lubricants make it difficult to assume that they are
interchangeable. Check with the compressor manufacturer for
the correct viscosity grade and brand for the compressor in the
system being retrofitted.

4. Drain the Lubricant


Many small hermetic compressors do not have oil drains,
making it necessary to remove the compressor from the system
to drain the lubricant. In this case, the best point in the system
to drain the lubricant is the suction line of the compressor.
Small hand-operated pumps are available which permit
insertion of a tube into the compressor suction line. For
compressors with an access port, the same hand-operated

4 HFC Retrofit Guidelines


pump can be used to remove lubricant without removing the
compressor from the system.

For larger systems, the mineral oil should be drained from


multiple points in the system. Particular attention should be paid
to low spots around the evaporator where lubricant often
collects. The mineral oil should also be drained from oil
separators and/or suction accumulators.

5. Measure Existing Lubricant


Measure and record the volume of the lubricant removed from the
system. Compare this amount with the amount recommended by
the manufacturer to ensure that the majority of lubricant has been
removed. This volume also will be used as a guide to determine
the amount of replacement lubricant to add in the next step.
Properly dispose of the old lubricant.

6. Recharge Compressor with Replacement Lubricant


Add to the compressor the same volume of HFC-compatible
lubricant as the volume of mineral oil drained in Step 5. Follow the
lubricant manufacturer’s suggestion for handling. For example, it
is recommended that polyol ester lubricant be pumped rather
than poured to avoid absorption of atmospheric moisture.
Likewise, systems charged with polyol ester lubricant should not
be left open to the atmosphere for more than 10 to 15 minutes.

7. Reinstall the Compressor


Reinstall the compressor following standard service practices
recommended by the manufacturer.

8. Recharge the CFC Refrigerant


If the system charge was pumped into the receiver, the balance
of the system should be evacuated and then the receiver valves
opened. If the original charge was collected in a recovery
cylinder, the system should be evacuated and then recharged
with the original CFC refrigerant. It may be necessary to “top off”
the refrigerant charge to compensate for the small amount lost in
draining the oil.

9. Run the Compressor


Run the compressor with the replacement lubricant and the CFC
refrigerant for at least 24 hours. Next, drain the lubricant and
recharge with fresh lubricant. Check the lubricant that was
drained. Be sure the residual mineral oil or alkylbenzene content
is below 5%. Test kits are available from several lubricant
suppliers for this purpose. It usually requires about three changes
to get the residual oil content under 5%.

10. Continue to Flush the System


Repeat steps 4 through 9 until the residual mineral oil or
alkylbenzene content is below 5%. The lubricant that was
removed from the compressors in the flushing procedure must
be disposed of properly.

11. Evaluate the Expansion Device


Most R-502 and R-12 systems with thermostatic expansion
valves will operate satisfactorily with the appropriate
replacement HFC; however, it may be necessary to adjust the
superheat. For R-502 and R-12 systems equipped with a
capillary tube, in most cases the unit can be operated

HFC Retrofit Guidelines 5


satisfactorily with the original capillary tube by undercharging
the unit (as long as ambient conditions are relatively constant).
In cases where Genetron 134a has replaced R-12 and
operation of the original R-12 capillary tube is expected over a
wide range of condensing temperatures, unsatisfactory
performance may result at both high and low condensing
temperatures. The potential problems would include liquid
floodback and motor overload at high condensing
temperatures or loss of liquid seal entering the capillary tube at
low condensing temperatures.

In R-12 systems equipped with a capillary tube, the capillary


tube will have to be replaced in order to achieve satisfactory
performance with Genetron 134a over the entire range of
design conditions. Honeywell recommends consulting with
the equipment manufacturer before replacing the capillary
tube. If the manufacturer’s information is not available, consult
the table below to determine capillary tube length at the same
diameter. Although the need to change an R-502 capillary tube
is less likely, comparative tube length information for
Genetron AZ-50 and Genetron 404A is also included in the
table below. These figures are based on ASHRAE method for
capillary tube sizing.

Capillary Tube Sizing – Relative Length


• R-502 = 100% R-12 = 100%
Evaporating Temp
°F (°C) AZ-501 404A1 R-134a2
-25 (-32) 130% 140% –
-10 (-23) 125% 140% 200%
0 (-18) 125% 130% 195%
20 (-7) – – 180%
40 (4) – – 165%

1
110°F (43°C) condensing temperature, no significant difference at 130°F (54°C) condensing.
2
110°F (43°C) condensing temperature, 10-30% increase in length required at 130°F (54°C)
condensing.

12. Replace the Filter Drier


Following system maintenance, a recommended service practice is
to replace the filter drier. There are two types of filter driers
commonly used in refrigeration equipment: loose-fill and solid-core.

Many, but not all, of the standard loose-fill and solid-core driers
used with CFC refrigerants are compatible with the
corresponding alternative Genetron Refrigerants. Check with
your wholesaler to make sure the replacement filter drier is
compatible with the Genetron Refrigerant being used.

13. Reconnect the System and Evacuate


Use normal service practices to reconnect and evacuate the
system. To remove air and other non-condensables, Honeywell
recommends evacuating the system to a full vacuum of 1,000
microns or less from both sides of the system. However,
attempting to evacuate a system with the pump connected only
to the low-side of the system will not adequately remove moisture
and non-condensables such as air. Use a good electronic gauge
to measure the vacuum. An accurate reading cannot be made
with a refrigeration gauge.

6 HFC Retrofit Guidelines


14. Check the System for Leaks
Check the system for leaks using normal service practices. No
leak testing should be performed using mixtures of HFCs and air,
oxygen, or other oxidizing materials.

15. Charge System with Genetron HFC Refrigerant


When replacing CFC-12 with Genetron 134a, or replacing R-502
with Genetron AZ-50, use the same charging procedures that you
would use for the refrigerant being replaced. When replacing R-
502 with Genetron 404A, it is important to remember that 404A is
a blend, not an azeotrope. It is essential that Genetron 404A be
liquid-charged by removing only liquid from the cylinder. Never
vapor charge the system with vapor from a Genetron 404A
cylinder. Vapor-charging may result in the wrong refrigerant
composition and could damage the system.

If the Genetron 404A cylinder is equipped with a dip tube, keep


the cylinder upright for liquid removal. If the Genetron 404A
cylinder does not have a dip tube, invert the cylinder for liquid
removal. A throttling valve should be used to control the flow of
refrigerant to the suction side to ensure that a liquid slug does not
enter the compressor. NOTE: To prevent compressor damage,
do not charge liquid into the suction line of the unit.

Systems being charged with Genetron 134a, Genetron AZ-50 or


Genetron 404A require a smaller charge size than the CFC
refrigerants they replace. For expansion valves or optimized
capillary tube systems, the typical charge size relative to the CFC
being replaced appears below.

Relative Charge Size


Genetron
Refrigerant R-12 Replacement R-502 Replacement
R-134a 90% not applicable
AZ-50, 404A not applicable 85%

If the original capillary tube is used, it will generally be necessary


to undercharge the system to prevent liquid floodback to the
compressor—particularly where Genetron 134a is used to replace
CFC-12.

As part of general procedure, Honeywell recommends initially


charging the system with 75 percent by weight of the original
CFC charge. For example, if the original CFC charge was 100
pounds (45 kg), initially charge 75 pounds (35 kg) of the
appropriate replacement HFC refrigerant. If, for example, the
original CFC charge was 300 grams, initially charge 225 grams of
the replacement HFC refrigerant.

16. Check System Operation


Start the system and allow conditions to stabilize. If the system is
undercharged, add refrigerant in increments of 5 percent by weight
of the original CFC charge. For example, if the original charge was
100 pounds (45 kg), charge increments of 5 pounds (2.5 kg).
Continue until desired operating conditions are achieved. If the
original CFC charge was 300 grams, charge in increments of 15
grams. Continue until desired operating conditions are achieved.

Compressor suction and discharge pressures for the HFC


refrigerants relative to the CFC refrigerants they replace are
provided here.

HFC Retrofit Guidelines 7


Comparative Suction and Discharge Pressure
• Versus R-502
Suction Discharge
AZ-50 2 psi (15 kPa) higher 18-25 psi (125-170 kPa) higher
404A 2 psi (15 kPa) higher 18-25 psi (125-170 kPa) higher

• Versus R-12
Suction Discharge
R-134a 2 psi (15 kPa) higher 3-10 psi (20-70 kPa) higher

It may be necessary to reset the high-pressure cutout to


compensate for the higher discharge pressures of the
replacement refrigerant. This procedure should be done carefully
to avoid exceeding the recommended operating limits of the
compressor and other system components. The use of an
unoptimized capillary tube will make the system more sensitive to
charge and/or operating conditions. As a result, system
performance will change more quickly if the system is
overcharged or undercharged. To avoid overcharging, it is best to
charge the system by first measuring the operating conditions
(including discharge and suctions pressures, suction line
temperature, compressor amps, superheat) instead of using the
liquid line sight glass as a guide.

17. Label Components and System


After retrofitting the system with the appropriate HFC-based
Genetron Refrigerant, label the system components to identify
the type of refrigerant (for example, Genetron AZ-50) and specify
the type of lubricant (by brand name and grade) in the system.
This will help ensure that the proper refrigerant and lubricant will
be used to service the equipment in the future.

Retrofit Checklist for HFC-based Genetron Refrigerants


1. Record baseline data on original system performance. __________
2. Recover CFC refrigerant charge using appropriate recovery
equipment or pump down into receiver. __________
* Record the identity (e.g., R-502) and amount of CFC removed. __________
3. Choose compressor lubricant. __________
4. Drain as much of the lubricant from the compressor as possible. __________
5. Measure the amount of lubricant removed. __________
6. Recharge compressor with HFC-compatible lubricant. __________
* Use the same amount that was removed from existing system. __________
7. Reinstall compressor. __________
8. Recharge the System using the original CFC refrigerant. __________
9. Run the System. __________
10. Repeat flushing steps 4-9 until at least 95% pure
replacement lubricant. __________
11. Check expansion device. __________
12. Replace filter drier with new filter drier approved for use with
the newly charged alternative Genetron Refrigerant. __________
13. Reconnect system and evacuate. __________
14. Check system for leaks. __________
15. Recharge system with the alternative Genetron Refrigerant. __________
* For Genetron 404A, remove liquid only from cylinder. __________
* Initial charge 75 percent by weight of the original CFC
refrigerant charge. __________
* Record amount of refrigerant charged. __________

continued on next page

8 HFC Retrofit Guidelines


16. Check system operation. __________
* Adjust charge to achieve desired operating conditions. __________
* If low, charge in increments of 5 percent of original CFC
refrigerant charge. For Genetron 404A, liquid charge only. __________
* Record the amount of refrigerant added. __________
17. Label components and systems for refrigerant and lubricant
by brand name and grade/type. __________

Convenient Pressure-Temperature tables can be found at the


back of this booklet.

HFC Retrofit Guidelines 9


Genetron AZ-50 Retrofit Specifics
(To be used in conjunction with the Genetron HFC Refrigerant
Retrofit Guidelines).

Applications
Genetron
Refrigerant Type Replaces Applications & Comments
AZ-50 (R-507) Azeotrope R-502 Supermarket freezer cases,
reach-in coolers, display cases,
transport refrigeration, ice machines.

Lubricant
A lubricant miscible with HFC refrigerants must be used with
Genetron AZ-50. Honeywell recommends using a lubricant such
as polyol ester (POE) that has been approved by the compressor
manufacturer. Differences among polyol ester-based lubricants
make it difficult to assume that they are interchangeable. Check
with the compressor manufacturer for the correct viscosity grade
and brand for the compressor in the system being retrofitted.

Expansion Device
Most R-502 systems with any common expansion device will
operate satisfactorily with Genetron AZ-50; however, it may be
necessary to adjust the superheat. For R-502 systems equipped
with a capillary tube, in most cases the unit can be operated
satisfactorily with the original capillary tube by undercharging the
unit as long as ambient conditions are relatively constant.

Honeywell recommends consulting with the equipment


manufacturer before replacing the capillary tube. If the
manufacturer’s information is not available, consult the table below
based on ASHRAE method for capillary tube sizing to determine
capillary tube length at the same diameter. Although the need to
change an R-502 capillary is unlikely, comparative tube length
information for Genetron AZ-50 is given in the table below.

Capillary Tube Sizing – Relative Length


• R-502 = 100%
Evaporating Temperature
°F (°C) AZ-501
-25 (-32) 130%
-10 (-23) 125%
0 (-18) 125%

1
110°F (43°C) condensing temperature, no significant difference at 130°F (54°C) condensing.

Charge Size
Systems being charged with Genetron AZ-50 require a smaller
charge size than the R-502 being replaced. For expansion valves
or optimized capillary tube systems, the AZ-50 charge size will
typically be 85 percent by weight of the original R-502 charge. If
the original capillary tube is used, it will generally be necessary to
undercharge the system to prevent liquid floodback to the
compressor.

Comparative Suction and Discharge Pressure


• Versus R-502
Suction Discharge
AZ-50 2 psi (15 kPa) higher 18-25 psi (125-170 kPa) higher

10 HFC Retrofit Guidelines


Example: For a box temperature of -15°F (and a 15°F leaving
difference), the suction pressure would be about 11 psig. This
corresponds to a saturated suction temperature of -30°F. If the
measured temperature of the suction-line is -15°F, there is a 15°F
superheat (the difference between measured suction-line
temperature and saturated suction temperature).

To determine superheat for different conditions than above, first


note the measured suction pressure. Using the temperature-
pressure chart for Genetron AZ-50, locate the measured suction
pressure. Find the corresponding saturated temperature on the
chart. The difference between the measured suction-line
temperature and the saturated temperature is the superheat.

The expected box temperature can be found by adding the


leaving difference (usually 15-20°F) to the saturated suction
temperature.

For a head pressure of 279 psig, the condensing temperature is


about 110°F. To determine the condensing temperature at a
different head pressure, find the temperature corresponding to
the measured head pressure in the Genetron AZ-50 temperature-
pressure chart.

Convenient Pressure-Temperature tables can be found at the


back of this booklet.

HFC Retrofit Guidelines 11


Genetron 404A Retrofit Specifics
(To be used in conjunction with the Genetron HFC Refrigerant
Retrofit Guidelines).

Applications
Genetron
Refrigerant Type Replaces Applications & Comments
404A (R-404A) Blend R-502 Supermarket freezer cases,
reach-in coolers, display cases,
transport refrigeration, ice machines.

Lubricant
A lubricant miscible with HFC refrigerants must be used with
Genetron 404A. Honeywell recommends using a lubricant such
as polyol ester (POE) that has been approved by the compressor
manufacturer. Differences among polyol ester-based lubricants
make it difficult to assume that they are interchangeable. Check
with the compressor manufacturer for the correct viscosity grade
and brand for the compressor in the system being retrofitted.

Expansion Device
Most R-502 systems with any common expansion device will
operate satisfactorily with Genetron 404A, however, it may be
necessary to adjust the superheat. For R-502 systems equipped
with a capillary tube, in most cases the unit can be operated
satisfactorily with the original capillary tube by undercharging the
unit (as long as ambient conditions are relatively constant).

Honeywell recommends consulting with the equipment


manufacturer before replacing the capillary tube. If the
manufacturer’s information is not available, consult the table below
to determine capillary tube length at the same diameter. Although
the need to change an R-502 capillary is unlikely, comparative tube
length information for Genetron 404A based on ASHRAE method
for capillary tube sizing is given in the table below.

Capillary Tube Sizing – Relative Length


• R-502 = 100%
Evaporating Temperature
°F (°C) Genetron 404A1
-25 (-32) 140%
-10 (-23) 130%
0 (-18) 130%

1
110°F (43°C) condensing temperature, no significant difference at 130°F (54°C) condensing.

Charge Size
Systems being charged with Genetron 404A require a smaller
charge size than the R-502 being replaced. For expansion valves
or optimized capillary tube systems, the Genetron 404A charge
size will typically be 85 percent by weight of the original R-502
charge. If the original capillary tube is used, it will generally be
necessary to undercharge the system to prevent liquid floodback
to the compressor.

Genetron 404A must be liquid-charged.


A throttling valve should be used to control the flow of refrigerant
to the suction side to ensure that a liquid slug cannot enter the
compressor. NOTE: To prevent compressor damage, do not
directly charge liquid into the suction line of the unit.

12 HFC Retrofit Guidelines


Comparative Suction and Discharge Pressure
• Versus R-502
Suction Discharge
404A 2 psi (15 kPa) higher 18-25 psi (125-170 kPa) higher

Example: For a box temperature of -15°F (and a 15°F leaving


difference), the suction pressure would be about 10 psig and the
average evaporating temperature -31°F. This corresponds to a
saturated suction temperature of -30°F. If the measured
temperature of the suction-line is -15°F, there is a 15°F superheat
(the difference between measured suction-line temperature and
saturated suction temperature).

To determine superheat for different conditions than above, first note


the measured suction pressure. Using the temperature-pressure
chart for Genetron 404A, locate the measured suction pressure in
the “dew” pressure column. Find the corresponding saturated
temperature on the chart. Subtract the saturated temperature from
the measured suction-line temperature to determine the superheat.

The average evaporating temperature is the average of the


temperatures corresponding to the suction pressure from both
the “bubble” and “dew” pressure columns in the Genetron 404A
temperature-pressure chart. The expected box temperature can
be found by adding the leaving difference (usually 15-20°F) to the
average evaporating temperature.

For a head pressure of 272 psig, the average condensing


temperature is about 110°F. To determine the average
condensing temperature at a different head pressure, average
the temperatures corresponding to the head pressure from both
the “bubble” and “dew” pressure columns of the Genetron 404A
temperature-pressure chart.

Convenient Pressure-Temperature tables can be found at the


back of this booklet.

HFC Retrofit Guidelines 13


Genetron 134a Retrofit Specifics
(To be used in conjunction with the Genetron HFC Refrigerant
Retrofit Guidelines).

Applications
Genetron
Refrigerant Type Replaces Applications Comments
134a (R-134a) Pure R-12 Supermarket display Use where
cases, evaporator temperature is
fluid, walk-in coolers, above -10°F
beverage dispensers, (-23°C)
vending machines,
water coolers,
domestic refrigerators.

Lubricant
A lubricant miscible with HFC refrigerants must be used with
Genetron 134a. Honeywell recommends using a lubricant such
as polyol ester (POE) that has been approved by the compressor
manufacturer. Differences among polyol ester-based lubricants
make it difficult to assume that they are interchangeable. Check
with the compressor manufacturer for the correct viscosity grade
and brand for the compressor in the system being retrofitted.

Expansion Device
Most R-12 systems with thermostatic expansion valves will work
satisfactorily with Genetron 134a. A capillary tube will need to be
replaced with one of greater restriction to achieve satisfactory
performance over the complete range of design conditions.
Using the original capillary tube may result in liquid floodback and
motor overload at high-condensing temperatures and loss of
liquid seal at low-condensing temperatures. Where ambient
conditions are relatively constant, in most cases R-12 systems
equipped with the original capillary tube can be operated
satisfactorily by undercharging the unit with Genetron 134a.

Honeywell recommends consulting with the equipment


manufacturer before replacing the capillary tube. If the
manufacturer’s information is not available, consult the table below
to determine capillary tube length at the same diameter. These
figures are based on ASHRAE method for capillary tube sizing.

Capillary Tube Sizing – Relative Length


• R-12 = 100%
Evaporator Temperature
°F (°C) R-134a1
-10 (-23) 200%
0 (-18) 195%
20 (-7) 180%
40 (4) 165%

1
110°F (43°C) condensing temperature, 10-30% increase in length required at 130°F (54°C)
condensing.

Charge Size
Systems being charged with Genetron 134a require a smaller
charge size than the R-12 being replaced. For expansion valves
or optimized capillary tube systems, the Genetron 134a charge
size will typically be 90 percent by weight of the original R-12

14 HFC Retrofit Guidelines


charge. If the original capillary tube is used, it will generally be
necessary to undercharge the system to prevent liquid floodback
to the compressor.

Comparative Suction and Discharge Pressure


• Versus R-12
Suction Discharge
R-134a 2 psi (15 kPa) higher 3-10 psi (20-70 kPa) higher

Example: For a box temperature of 35°F (and a 15°F leaving


difference), the suction pressure would be about 18 psig. This
corresponds to a saturated suction temperature of 20°F. If the
measured temperature of the suction-line is 30°F, there is a 10°F
superheat (the difference between measured suction-line
temperature and saturated suction temperature).

To determine superheat for different conditions than above, first


note the measured suction pressure. Using the temperature-
pressure chart for Genetron 134a, locate the measured suction
pressure. Find the corresponding saturated temperature on the
chart. The difference between the measured suction-line
temperature and the saturated temperature is the superheat.

The expected box temperature can be found by adding the


leaving difference (usually15-20°F) to the saturated suction
temperature.

For a head pressure of 146 psig, the condensing temperature is


about 110°F. To determine the condensing temperature at a
different head pressure, find the temperature corresponding to
the measured head pressure in the Genetron 134a temperature-
pressure chart.

Convenient Pressure-Temperature tables can be found at the


back of this booklet.

HFC Retrofit Guidelines 15


HCFC Retrofit Guidelines
Although HCFCs (hydrochlorofluorocarbons)
will be phased out over the next several
decades in many countries, retrofitting
existing CFC equipment to refrigerant
blends that contain HCFCs may still remain
a cost-effective alternative to complete
equipment replacement. By following
equipment manufacturers’ recommendations
and the guidelines in this publication,
service technicians can readily retrofit many
existing CFC-12 refrigeration systems to use
Genetron MP39 or Genetron 409A. Likewise,
many R-502 systems can be retrofit to use
Genetron HP80 or Genetron 408A.

When possible, refrigeration systems should


be retrofit to use non-ozone depleting HFC
(hydrofluorocarbon) refrigerants in order to
reduce the environmental impact in the
case of accidental discharge. Also, there
are no current plans to phase out HFCs in
the United States or most other countries,
and so HFCs are considered a long-term
refrigerant solution. These HCFC guidelines
are meant to provide guidance in those
situations where an HFC retrofit is not
possible or economical.

Although the information in this booklet can


be helpful as a general guide, it should not
be used as a substitute for the equipment
manufacturer’s specific recommendations.
For this reason, Honeywell strongly
recommends contacting the equipment
manufacturer for detailed information on
retrofitting the specific model under
consideration. Also, refer to the Material
Safety Data Sheet (MSDS) for safety
information on the specific Genetron
Refrigerant you will use.

16 HCFC Retrofit Guidelines


Genetron HCFC Refrigerants
Genetron MP39, Genetron MP66, and Genetron 409A are alterna-
tive refrigerants to replace CFC-12 in many medium temperature
refrigeration systems. Genetron HP80 and Genetron 408A are alter-
native refrigerants designed to replace R-502 in low- and
medium-temperature commercial refrigeration applications. These
blends contain ozone-depleting hydrochlorofluorocarbons (HCFCs),
chemicals subject to phaseout in the United States and other coun-
tries. The constituents of the refrigerant mixtures, ASHRAE numbers,
refrigerant type, and applications are given below.

Applications
Genetron
Refrigerant Type Replaces Applications Comments
MP39 (R-401A) Blend CFC-12 Supermarket display Applications
cases, walk-in limited to
coolers, beverage evaporator
dispensers, vending temperatures
machines, water > -10°F (-23°C).
coolers, home
refrigerators.
MP 66 (R-401B) Blend CFC-12 Transport Consult equipment
refrigeration, mfg’r where high
domestic and compression ratios
commercial exist, may be
freezers. excessive discharge
temperature and
capacity reduction.
409A (R-409A) Blend CFC-12 Supermarket display
cases, walk-in coolers,
beverage dispensers,
vending machines,
water coolers, domestic/
commercial refrigerators/
freezers, transport
refrigeration.
HP80 (R-402A) Blend R-502 Supermarket freezer
cases, reach-in coolers,
display cases, ice
machines.
408A (R-408A) Blend R-502 Same as for HP80 To avoid high
above. discharge
temperature, use
when evaporator
temperature > -30°F
and superheat
not exceeding 10°F.

Service technicians should keep in mind that future regulations


may restrict the use of HCFC refrigerants and dictate the ultimate
use of an HFC refrigerant. Where feasible, the preferred replace-
ment for CFC-12 is Genetron 134a. Likewise, the preferred
replacement for R-502 is an HFC such as Genetron AZ-50. Although
these non-ozone-depleting HFC refrigerants are being used in
many OEM applications, there are instances where retrofitting to
an HFC may be difficult because nearly all of the mineral oil in the
system must be removed. In these situations, an interim service
fluid such as a Genetron MP Blend or Genetron 409A may be

HCFC Retrofit Guidelines 17


preferred as an R-12 replacement. Similarly, an interim service
fluid such as a Genetron HP80 or Genetron 408A may be pre-
ferred as a replacement for R-502.

HCFC Refrigerants are not “Drop-in” Replacements


The HCFC refrigerants are not “drop-in” replacements for the
CFC refrigerants. Genetron MP39, Genetron MP66, Genetron
HP80, Genetron 408A, and Genetron 409A, are blends and can
segregate. As a result, service technicians must acquaint them-
selves with modified service procedures to perform each retrofit
effectively. The retrofit procedures listed here have been devel-
oped by Honeywell to address these issues and to help
technicians perform successful retrofits of R-12 and R-502 sys-
tems utilizing positive-displacement (reciprocating, rotary, scroll
or screw) compressors.

18 HCFC Retrofit Guidelines


General HCFC Retrofit Procedures
A word about system preparation: In retrofitting an existing refrig-
eration system, the condition of the existing seals and gaskets
must be taken into account. Heat set, compression set, and seal
shrinkage can all impact the condition of an existing seal or gas-
ket. When the system is put under vacuum, the sealing device can
be displaced, creating the potential for leakage. Whenever possi-
ble, gaskets and seals should be replaced in order to minimize the
chances of an old seal or gasket becoming a source of a leak.

1. Record Baseline Data


Before making any hardware changes, compare current system
operating data with normal operating data. Correct any deficien-
cies and record final data as a performance baseline. Data should
include temperature and pressure measurements throughout the
system including the evaporator, compressor suction and dis-
charge, condenser and expansion device. These measurements
will be useful when adjusting the system with an alternative
Genetron Refrigerant.

2. Recover CFC Refrigerant Charge


The CFC refrigerant charge should be recovered from the system
using a recovery machine capable of meeting or exceeding the
required levels of evacuation.

The charge must be collected in a recovery cylinder dedicated to


that refrigerant (e.g., CFC-12 or CFC-502). Do not mix the recov-
ered material with other refrigerants in a recovery tank, as this will
result in a mixture that cannot be reclaimed. Do not vent the
refrigerant to the atmosphere.

Knowing the recommended CFC refrigerant charge size for the


system is helpful. If it is not known, weigh the entire amount of
refrigerant removed. This amount can be used as a guide for the
initial quantity of alternative Genetron Refrigerant to be charged
to the system.

3. Drain the Lubricant


Genetron 409A has sufficient mineral oil solubility for most appli-
cations, however, at evaporating temperatures below -20°F
(-29°C), at least 50% of the mineral oil should be replaced with
alkylbenzene lubricant. Genetron MP39 and Genetron MP66
have sufficient mineral oil solubility for most medium temperature
(20°F or higher evaporating) applications where piping runs are
not exceedingly long. If piping runs are lengthy or for low-tem-
perature evaporating conditions with MP blends, at least 50% of
the mineral oil should be replaced with alkylbenzene lubricant.
Recall that for evaporating temperatures below -10°F (-7°C),
Genetron MP66 is recommended in favor of Genetron MP39.
When retrofitting low temperature R-502 systems to Genetron
HP80 or Genetron 408A, at least 50% of the mineral oil should be
replaced with alkylbenzene lubricant.

If the system being retrofitted requires removal of the existing


mineral oil, continue with Step 3. If operating conditions permit
the use of mineral oil, and the existing oil is in acceptable condi-
tion, proceed to step 7.

Many small hermetic compressors do not have oil drains, making


it necessary to remove the compressor from the system to drain
the lubricant. In this case, the best point in the system to drain the

HCFC Retrofit Guidelines 19


lubricant is the suction line of the compressor. Small hand-oper-
ated pumps are available which permit insertion of a tube into the
compressor suction line. For compressors with an access port,
the same hand-operated pump can be used to remove lubricant
without removing the compressor from the system.

For larger systems, the mineral oil should be drained from


multiple points in the system. Particular attention should be paid
to low spots around the evaporator where lubricant often
collects. The mineral oil should also be drained from oil
separators and/or suction accumulators.

4. Measure Existing Lubricant


Measure and record the volume of the lubricant removed from the
system. Compare this amount with the amount recommended by
the manufacturer to ensure that the majority of lubricant has been
removed. This volume also will be used as a guide to determine the
amount of alkylbenzene lubricant to add in the next step.

5. Recharge Compressor with Alkylbenzene Lubricant


Add to the compressor the same volume of alkylbenzene lubricant
as the volume of mineral oil drained in Step 4. Honeywell
recommends using a commercially available alkylbenzene lubricant
of the same viscosity as the mineral oil. Check with the compressor
manufacturer for the correct viscosity grade.

6. Reinstall the Compressor


If the compressor was removed to drain the oil, reinstall the
compressor following standard service practices recommended
by the manufacturer.

7. Evaluate the Expansion Device


Most R-502 and R-12 systems with thermostatic expansion valves
will operate satisfactorily with the appropriate interim HCFC blend,
however, it may be necessary to adjust the superheat.

In most cases, an existing R-502 capillary tube can be expected to


operate satisfactorily with HP80. In the case of Genetron 408A,
the mass flow is about 75% of that for R-502. The mass flows of
the R-12 replacements are measurably lower than R-12. Hence for
R-408A and likewise, for the R-12 replacements, a more restrictive
capillary is required to achieve satisfactory performance over the
entire range of design conditions.

Honeywell recommends consulting with the equipment manufacturer


before replacing the capillary tube. If the manufacturer’s information
is not available, consult the table on the following page to determine
capillary tube length at the same diameter. These figures are based
on ASHRAE method for capillary tube sizing.

When considering the R-12 replacements or R-408A (for


replacement of R-502), if operation of the original capillary tube
is expected over a wide range of condensing temperatures,
unsatisfactory performance may result at both high and low
condensing temperatures. The potential problems would
include liquid floodback and motor overload at high
condensing temperatures and loss of liquid seal entering the
capillary tube at low condensing temperatures. Only in a
situation where ambient conditions are expected to be
relatively constant can using the original capillary tube and
undercharging the unit be considered.

20 HCFC Retrofit Guidelines


Capillary Tube Sizing- Relative Length
• R-502 = 100% • R-12 = 100%
Evaporating
Temperature
°F (°C) HP801 408A1 MP392 MP662 409A2
-25 (-32) 115% 205% – – –
-10 (-23) 115% 205% 215% 250% 190%
0 (-18) 110% 200% 205% 230% 170%
20 (-7) 110% 200% 190% 200% 150%
40 (4) – – 180% 195% 150%
1
110°F (43°C) condensing temperature, no significant difference at 130°F (54°C) condens-
ing.
2
110°F (43°C) condensing temperature, 10-30% increase in length required at 130°F (54°C)
condensing.

8. Replace the Filter Drier


Following system maintenance, a recommended service practice is
to replace the filter drier. There are two types of filter driers
commonly used in refrigeration equipment; loose-fill and solid-core.

Many, but not all, of the standard loose-fill and solid-core


driers used with CFC refrigerants are compatible with the
corresponding alternative Genetron Refrigerants. Check with your
wholesaler to make sure the replacement filter drier is compatible
with the Genetron Refrigerant being used.

9. Reconnect the System and Evacuate


Use normal service practices to reconnect and evacuate the
system. To remove air and other non-condensables, Honeywell
recommends evacuating the system to a full vacuum of 1,000
microns or less from both sides of the system. However,
attempting to evacuate a system with the pump connected only
to the low-side of the system will not adequately remove
moisture and non-condensables such as air. Use a good
electronic gauge to measure the vacuum. An accurate reading
cannot be made with a refrigeration gauge.

10. Check the System for Leaks


Check the system for leaks using normal service practices.

11. Charge System with Alternative Genetron Refrigerant Blend


When charging an R-12 system with either Genetron MP39,
Genetron MP66, or Genetron 409A or when charging an R-502
system with Genetron HP80 or Genetron 408A, it is important to
remember that these products are blends and not azeotropes. This
means the composition of the vapor is not the same as the
composition of the liquid. It is essential that these refrigerants be
liquid-charged by removing only liquid from the cylinder. Never
charge the system with vapor from a refrigerant blend cylinder.
Doing so will result in the wrong refrigerant composition and may
lead to a loss of system performance. Cylinders for the refrigerant
blends that are equipped with a dip tube should be kept upright for
liquid removal. Cylinders for the refrigerant blends that do not
contain a dip tube should be inverted in order to withdraw liquid. A
throttling valve should be used to control the flow of refrigerant to
the suction side to ensure that a liquid slug cannot enter the
compressor. NOTE: To prevent compressor damage, do not directly
charge liquid into the suction line of the unit.

HCFC Retrofit Guidelines 21


12. Use Correct Charge Size
Systems being charged with Genetron MP blends or Genetron
409A will require a smaller charge size than those using R-12.
Genetron HP80 and Genetron 408A charge sizes are smaller than
the R-502 charge size being replaced. For expansion valves or
optimized capillary tube systems, the typical charge size relative
to the CFC being replaced appears below.

Relative Charge Size


Genetron
Refrigerant R-12 Replacement R-502 Replacement
MP39, MP66 90% not applicable
409A 93% not applicable
HP80 not applicable 95%
408A not applicable 85%

Where MP39, MP66, or 409A has replaced CFC-12 or when 408A


has replaced R-502 and the original capillary tube is used, it will
generally be necessary to undercharge the system to prevent
liquid floodback to the compressor. As part of general procedure,
Honeywell recommends initially charging the system with 75
percent by weight of the original CFC charge. For example, if the
original CFC charge was 100 pounds (45 kg), initially charge 75
pounds (35 kg) of the appropriate replacement blend. If, for
example, the original CFC charge was 300 grams, initially charge
225 grams of the replacement blend.

13. Check System Operation


Start the system and allow conditions to stabilize. If the system is
undercharged, add refrigerant in increments of 5 percent by weight
of the original CFC charge. For example, if the original charge was
100 pounds (45 kg), charge increments of 5 pounds (2.5 kg).
Continue until desired operating conditions have been achieved.

Compressor suction and discharge pressures for the HCFC


refrigerants relative to the CFC refrigerants they replace is given
below.

Comparative Suction and Discharge Pressure


• Versus R-12
Suction Discharge
MP39 Within 1 psi (5-10 kPa) 10-20 psi (70-150 kPa) higher
MP66 Comparable at -20°F (-29°C) Up to 70 psi (450-500 kPa) higher
Evaporator 8-9 psi higher with extreme ambient conditions
at 25°F (-4°C) evaporator
409A 4 psi (25-30 kPa) higher 15-20 psi (100-175 kPa) higher

• Versus R-502
Suction Discharge
HP80 5 psi (35 kPa) higher 40-50 psi (275-350 kPa) higher
408A 1-2 psi (7-14 kPa) higher 1-10 psi (7-70 kPa) higher

It may be necessary to reset the high-pressure cutout to


compensate for the higher discharge pressures of the replacement
refrigerant. This procedure should be done carefully to avoid
exceeding the recommended operating limits of the compressor
and other system components. The use of the original capillary
tube will make the system more sensitive to charge and/or
operating conditions. As a result, system performance will change

22 HCFC Retrofit Guidelines


more quickly if the system is overcharged or undercharged. To
avoid overcharging, it is best to charge the system by first
measuring the operating conditions (including discharge and
suctions pressures, suction line temperature, compressor amps,
superheat) instead of using the liquid line sight glass as a guide.

14. Label Components and System


After retrofitting the system with the appropriate HCFC-based
Genetron Refrigerant, label the system components to identify
the type of refrigerant (for example, Genetron MP39) and specify
the type of alkylbenzene lubricant (by brand name) in the system.
This will help ensure that the proper refrigerant and lubricant will
be used to service the equipment in the future.

Retrofit Checklist for HCFC-based Genetron Refrigerants


1. Record baseline data on original system performance. __________
2. Recover CFC refrigerant charge using appropriate
recovery equipment. __________
* Record the identity (e.g., R-502) and amount of
CFC removed. __________
3. Drain most of the lubricant from the compressor. __________
4. Measure the amount of lubricant removed. __________
5. Recharge compressor with alkylbenzene lubricant. __________
* Use the same amount that was removed from
existing system. __________
6. Reinstall compressor. __________
7. Check expansion device. __________
* Adjust the setting of the valve as necessary. __________
8. Replace filter drier with new filter drier approved for use
with the newly charged alternative Genetron Refrigerant. __________
9. Reconnect system and evacuate. __________
10. Check system for leaks. __________
11. Recharge system with the alternative Genetron Refrigerant. __________
* Remove liquid only from cylinder. Charge using a
throttling device. __________
12. Use correct charge size. __________
* Initial charge 75 percent by weight of the original CFC
refrigerant charge. __________
* Record amount of refrigerant charged. __________
13. Check system operation. __________
* Adjust charge to achieve desired operating conditions. __________
* If low, remove liquid only from cylinder in increments of
5 percent of original CFC refrigerant charge. __________
* Record the amount of refrigerant added. __________
14. Label components and systems for refrigerant and lubricant
by brand name. __________

Convenient Pressure-Temperature tables can be found at the


back of this booklet.

HCFC Retrofit Guidelines 23


Genetron MP39 Retrofit Specifics
(To be used in conjunction with the General HCFC Retrofit
Procedures on page 19.)

Applications
Genetron
Refrigerant Type Replaces Applications Comments
MP39 (R-401A) Blend CFC-12 Supermarket Applications
display cases, limited to
walk-in coolers, evaporator
beverage dispensers, temperatures
vending machines, > -10°F (-23°C).
water coolers,
home refrigerators.

Lubricant
Alkylbenzene lubricant is required with Genetron MP39. Mineral
oil may have sufficient miscibility with Genetron MP39 to achieve
adequate oil return to the compressor at medium temperature
conditions (above 20°F or -7°C evaporator) unless extremely long
lines exist.

Expansion Device
Most R-12 systems with thermostatic expansion valves will work
satisfactorily with Genetron MP39. A capillary tube will need to be
replaced with one of greater restriction to achieve satisfactory
performance over the complete range of design conditions.
Using the original capillary tube may result in liquid floodback and
motor overload at high-condensing temperatures and loss of
liquid seal at low-condensing temperatures. Where ambient
conditions are relatively constant, R-12 systems equipped with
the original capillary tube, can, in most cases, be operated
satisfactorily by undercharging the unit with MP39.

Honeywell recommends consulting with the equipment


manufacturer before replacing the capillary tube. If the
manufacturer’s information is not available, consult the table below
to determine capillary tube length at the same diameter. These
figures are based on ASHRAE method for capillary tube sizing.

Capillary Tube Sizing — Relative Length


• R-12 = 100%
Evaporating Temperature
°F (°C) MP39 1
-10 (-23) 215%
0 (-18) 205%
20 (-7) 190%
40 (4) 180%

1 110°F (43°C) condensing temperature, 10-30% increase in length required at 130°F (54°C)
condensing.

Charge Size
Genetron MP39 charge size is typically about 90 percent of the
CFC-12 charge for systems with expansion valves or optimized
capillary tubes. Initially charge the system with MP39 at 75
percent by weight of the original CFC charge. (Refer to General
HCFC Retrofit procedures on page 19 for more information.)
Genetron MP39 must be liquid-charged. A throttling valve should

24 HCFC Retrofit Guidelines


be used to control the flow of refrigerant to the suction side to
ensure that a liquid slug cannot enter the compressor. NOTE: To
prevent compressor damage, do not directly charge liquid into the
suction line of the unit.

Comparative Suction and Discharge Pressure


• Versus R-12
Suction Discharge
MP39 Within 1 psi (5-10 kPa) 10-20 psi (70-150 kPa) higher

If necessary, reset high-pressure cutout to compensate for higher discharge pressures.

Example: For a box temperature of 35°F (and a 15°F leaving


difference), the suction pressure would be about 24 psig and the
average evaporating temperature 20°F. This corresponds to a
saturated suction temperature of 25°F. If the measured
temperature of the suction-line is 35°F, there is a 10°F superheat
(the difference between measured suction-line temperature and
saturated suction temperature).

To determine superheat for different conditions than above, first


note the measured suction pressure. Using the temperature-
pressure chart for Genetron MP39, locate the measured suction
pressure in the “dew” pressure column. Find the corresponding
saturated temperature on the chart. Subtract the saturated
temperature from the measured suction-line temperature to
determine the superheat.

The average evaporating temperature is the average of the


temperatures corresponding to the suction pressure from both
the “bubble” and “dew” pressure columns in the MP39
temperature-pressure chart.

The expected box temperature can be found by adding the


leaving difference (usually 15-20°F) to the average evaporating
temperature.

For a head pressure of 160 psig, the average condensing


temperature is about 110°F. To determine the average
condensing temperature at a different head pressure, average
the temperatures corresponding to the head pressure from both
the “bubble” and “dew” pressure columns of the Genetron MP39
temperature-pressure chart.

Convenient Pressure-Temperature tables can be found at the


back of this booklet.

HCFC Retrofit Guidelines 25


Genetron MP66 Retrofit Specifics
(To be used in conjunction with the General HCFC Retrofit
Procedures on page 19.)

Applications
Genetron
Refrigerant Type Replaces Applications Comments
MP66 (R-401B) Blend CFC-12 Transport Consult equipment
refrigeration, mfg’r. where high
domestic and compression
commercial (Evaporator < -10°F)
freezers. ratios exist, may be
excessive discharge
temperature and
capacity reduction.

Lubricant
Alkylbenzene lubricant is required with Genetron MP66.

Expansion Device
Most R-12 systems with thermostatic expansion valves will work
satisfactorily with Genetron MP66. A capillary tube will need to be
replaced with one of greater restriction to achieve satisfactory
performance over the complete range of design conditions.
Using the original capillary tube may result in liquid floodback and
motor overload at high-condensing temperatures and loss of liq-
uid seal at low-condensing temperatures. Where ambient
conditions are relatively constant, R-12 systems equipped with
the original capillary tube, can, in most cases, be operated satis-
factorily by undercharging the unit with MP66.

Honeywell recommends consulting with the equipment manufac-


turer before replacing the capillary tube. If the manufacturer’s
information is not available, consult the table below to determine
capillary tube length at the same diameter. These figures are
based on ASHRAE method for capillary tube sizing.

Capillary Tube Sizing – Relative Length


• R-12 = 100%
Evaporating Temperature
°F (°C) MP661
-25 (-32) –
-10 (-23) 250%
0 (-18) 230%
20 (-7) 200%
40 (4) 195%

1 110°F (43°C) condensing temperature, 10-30% increase in length required at 130°F (54°C)
condensing.

Charge Size
Genetron MP66 charge size is typically about 90 percent of the
CFC-12 charge for systems with expansion valves or optimized
capillary tubes. Initially charge the system with MP66 at 75 percent
by weight of the original CFC charge. (Refer to General HCFC
Retrofit Procedures on page 19 for more information.) Genetron
MP66 must be liquid-charged. A throttling valve should be used to
control the flow of refrigerant to the suction side to ensure that a

26 HCFC Retrofit Guidelines


liquid slug cannot enter the compressor. NOTE: To prevent
compressor damage, do not directly charge liquid into the suction
line of the unit.

Comparative Suction and Discharge Pressure


• Versus R-12
Suction Discharge
MP66 Comparable at -20°F (-29°C) Up to 70 psi (450-500 kPa)
Evaporator 8-9 psi higher higher with extreme
at 25°F (-4°C) evaporator. ambient conditions.

If necessary, reset high pressure cutout to compsensate for higher discharge pressures.

Example: For a box temperature of -5°F (and a 15°F leaving


difference), the suction pressure would be about 1.5 psig and the
average evaporating temperature -20°F. This corresponds to a
saturated suction temperature of -15°F. If the measured
temperature of the suction-line is -5°F, there is a 10°F superheat
(the difference between measured suction-line temperature and
saturated suction temperature).

To determine superheat for a different box temperature, first note


the measured suction pressure. Using the temperature-pressure
chart for MP66, locate the measured suction pressure in the “dew”
pressure column. Find the corresponding saturated temperature
on the chart. Subtract the saturated temperature from the
measured suction-line temperature to determine the superheat.

The average evaporating temperature is the average of the


temperatures corresponding to the suction pressure from both
the “bubble” and “dew” pressure columns in the MP66
temperature-pressure chart.

The expected box temperature can be found by adding the leaving


difference (usually15-20°F) to the average evaporating temperature.

For a head pressure of 170 psig, the average condensing


temperature is about 110°F. To determine the average
condensing temperature at a different head pressure, average
the temperatures corresponding to the head pressure from both
the “bubble” and “dew” pressure columns in the MP66
temperature-pressure chart.

Convenient Pressure-Temperature tables can be found at the


back of this booklet.

HCFC Retrofit Guidelines 27


Genetron 409A Retrofit Specifics
(To be used in conjunction with the General HCFC Retrofit
Procedures on page 19.)

Applications
Genetron
Refrigerant Type Replaces Applications & Comments
409A (R-409A) Blend CFC-12 Supermarket display cases,
walk-in coolers, beverage
dispensers, vending machines,
water coolers, domestic/commercial
transport refrigeration.

Lubricant
Mineral oil may have sufficient miscibility with Genetron 409A to
achieve adequate oil return to the compressor down to
evaporating temperatures of -20°F (-29°C) unless piping is
extremely long. For systems operating with Genetron 409A at
evaporating temperatures below -20°F (-29°C), at least 50% of
the mineral oil should be replaced with alklybenzene lubricant.
Likewise, if piping runs are extremely long, at least 50% of the
mineral oil should be replaced with alkylbenzene lubricant.

Expansion Device
Most R-12 systems with thermostatic expansion valves will work
satisfactorily with Genetron 409A. A capillary tube will need to
be replaced with one of greater restriction to achieve satisfactory
performance over the complete range of design conditions.
Using the original capillary tube may result in liquid floodback and
motor overload at high-condensing temperatures and loss of
liquid seal at low-condensing temperatures. Where ambient
conditions are relatively constant, R-12 systems equipped with
the original capillary tube, can, in most cases, be operated
satisfactorily by undercharging the unit with Genetron 409A.

Honeywell recommends consulting with the equipment


manufacturer before replacing the capillary tube. If the
manufacturer’s information is not available, consult the table below
to determine capillary tube length at the same diameter. These
figures are based on ASHRAE method for capillary tube sizing.

Capillary Tube Sizing – Relative Length


• R-12 = 100%
Evaporating Temperature
°F (°C) R-409A1
-25 (-32) –
-10 (-23) 190%
0 (-18) 170%
20 (-7) 150%
40 (4) 150%

1 110°F (43°C) condensing temperature, 10-30% increase in length required at 130°F (54°C)
condensing.

Charge Size
Genetron 409A charge size is typically about 93 percent of the
CFC-12 charge for systems with expansion valves or optimized
capillary tubes. Initially charge the system with Genetron 409A at
75 percent by weight of the original CFC charge. (Refer to General

28 HCFC Retrofit Guidelines


HCFC Retrofit Procedures on page 19 for more information.)
Genetron 409A must be liquid-charged. A throttling valve should
be used to control the flow of refrigerant to the suction side to
ensure that a liquid slug cannot enter the compressor. NOTE: To
prevent compressor damage, do not directly charge liquid into the
suction line of the unit.

Comparative Suction and Discharge Pressure


• Versus R-12
Suction Discharge
409A 4 psi higher. 15-20 psi higher.
(25-30 kPa) higher. (100-175 kPa) higher.

If necessary, reset high pressure cutout to compsensate for higher discharge pressures.

Example: For a box temperature of 35°F (and a 15°F leaving


difference), the suction pressure would be about 25 psig and the
average evaporating temperature 20°F. This corresponds to a
saturated suction temperature of 27°F. If the measured
temperature of the suction-line is 37°F, there is a 10°F superheat
(the difference between measured suction-line temperature and
saturated suction temperature).

To determine superheat for a different box temperature, first note


the measured suction pressure. Using the temperature-pressure
chart for Genetron 409A, locate the measured suction pressure in
the “dew” pressure column. Find the corresponding saturated
temperature on the chart. Subtract the saturated temperature from
the measured suction-line temperature to determine the superheat.

The average evaporating temperature is the average of the


temperatures corresponding to the suction pressure from both
the “bubble” and “dew” pressure columns in the Genetron 409A
temperature-pressure chart. The expected box temperature can
be found by adding the leaving difference (usually15-20°F) to the
average evaporating temperature.

For a head pressure of 160 psig, the average condensing


temperature is about 110°F. To determine the average
condensing temperature at a different head pressure, average
the temperatures corresponding to the head pressure from both
the “bubble” and “dew” pressure columns of the Genetron 409A
temperature-pressure chart.

Convenient Pressure-Temperature tables can be found at the


back of this booklet.

HCFC Retrofit Guidelines 29


Genetron HP80 Retrofit Specifics
(To be used in conjunction with the General HCFC Retrofit
Procedures on page 19.)

Applications
Genetron
Refrigerant Type Replaces Applications & Comments
HP80 (R-402A) Blend R-502 Supermarket, freezer cases,
22/125/290 reach-in coolers, display cases,
ice machines.

Lubricant
Alkylbenzene lubricant is required with Genetron HP80.

Expansion Device
Most R-502 systems with thermostatic expansion valves will operate
satisfactorily with Genetron HP80, however, it may be necessary to
adjust the superheat. In most cases, an existing R-502 capillary tube
can be expected to operate satisfactorily with HP80. Although the
need to change an R-502 capillary is unlikely, comparative tube
length information for Genetron HP80 is given below.

Capillary Tube Sizing – Relative Length


• R-502 = 100%
Evaporating Temperature
°F (°C) HP801
-25 (-32) 115%
-10 (-23) 115%
0 (-18) 110%
20 (-7) 110%

1 110°F (43°C) condensing temperature, no significant difference at 130°F (54°C) condensing.

Charge Size
Genetron HP80 charge size is typically about 95 percent of the R-
502 charge for systems with expansion valves or optimized capillary
tubes. Initially charge the system with HP80 at 75 percent by weight
of the original CFC charge. (Refer to General HCFC Retrofit
Procedures on page 19 for more information.) Genetron HP80 must
be liquid-charged. A throttling valve should be used to control the
flow of refrigerant to the suction side to ensure that a liquid slug
cannot enter the compressor. NOTE: To prevent compressor
damage, do not directly charge liquid into the suction line of the unit.

Comparative Suction and Discharge Pressure


• Versus R-502
Suction Discharge
HP80 5 psi higher. 40-50 psi higher.
(35 kPa) higher. (275-350 kPa) higher.

If necessary, reset high pressure cutout to compsensate for higher discharge pressures.

Example: For a box temperature of -15°F (and a 15°F leaving


difference), the suction pressure would be about 11 psig and the
average evaporating temperature -32°F. This corresponds to a
saturated suction temperature of -31°F. If the measured
temperature of the suction-line is -16°F, there is a 15°F superheat
(the difference between measured suction-line temperature and
saturated suction temperature).

30 HCFC Retrofit Guidelines


To determine superheat for a different box temperature, first
note the measured suction pressure. Using the temperature-
pressure chart for Genetron HP80, locate the measured suction
pressure in the “dew” pressure column. Find the corresponding
saturated temperature on the chart. The difference between
the saturated temperature and the measured suction-line
temperature is the superheat.

The average evaporating temperature is the average of the


temperatures corresponding to the suction pressure from both
the “bubble” and “dew” pressure columns in the Genetron HP80
temperature-pressure chart. The expected box temperature can
be found by adding the leaving difference (usually15-20°F) to the
average evaporator temperature.

For a head pressure of 285 psig, the average condensing


temperature is about 110°F. To determine the average
condensing temperature at a different head pressure, average
the temperatures corresponding to the head pressure from both
the “bubble” and “dew” pressure columns of the Genetron HP80
temperature-pressure chart.
Convenient Pressure-Temperature tables can be found at the
back of this booklet.

HCFC Retrofit Guidelines 31


Genetron 408A Retrofit Specifics
(To be used in conjunction with the General HCFC Retrofit
Procedures on page 19.)

Applications
Genetron
Refrigerant Type Replaces Applications & Comments
408A (R-402A) Blend R-502 Supermarket freezer
cases, reach-in coolers,
display cases, ice machines.

Lubricant
Alkylbenzene lubricant is required with Genetron 408A.

Expansion Device
The capacity of an existing R-502 thermostatic expansion valve
(TXV) will be oversized but may be acceptable when using R-
408A. However, the superheat setting should be checked and
may have to be readjusted after the system is put back into
operation. If hunting of the TXV cannot be minimized by
adjustment, the valve should be replaced with a smaller one.
Honeywell recommends consulting with the TXV manufacturer
for correct sizing and superheat setting.

An existing capillary tube will be unsatisfactory with R-408A. If


operation of the original capillary tube is expected over a wide
range of condensing temperatures, unsatisfactory performance
may result at both high and low condensing temperatures. The
potential problems would include liquid floodback and motor
overload at high condensing temperatures and loss of liquid seal
entering the capillary tube at low condensing temperatures. Only
in a situation where ambient conditions are expected to be
relatively constant can using the original capillary tube and
undercharging the unit be considered.

The mass flow rate of R-408A is about 75% of that for R-502. R-
408A will require a more restrictive capillary tube in order to
achieve satisfactory performance over the entire range of design
conditions. Honeywell recommends consulting with the
equipment manufacturer before replacing the capillary tube. If the
manufacturer’s information is unavailable, it is recommended that
a new capillary tube of the same diameter but twice the length of
the original be used.

Capillary Tube Sizing – Relative Length


R-502 = 100%
Evaporating Temperature,
°F (°C) R-408A1
-25 (-32) 205%
-10 (-23) 205%
0 (-18) 205%
20 (-7) 205%
1 110°F (43 °C) condensing temperature, no significant difference at 130°F (54°C) condensing.

Charge Size
Genetron 408A charge size is typically about 85 percent of the R-502
charge for systems with expansion valves or optimized capillary
tubes. Initially charge the system with R-408A at 75 percent by
weight of the original CFC charge. (Refer to General HCFC Retrofit
Procedures on page 19 for more information.) Genetron 408A must

32 HCFC Retrofit Guidelines


be liquid-charged. A throttling valve should be used to control the
flow of refrigerant to the suction side to ensure that a liquid slug
cannot enter the compressor. NOTE: To prevent compressor
damage, do not directly charge liquid into the suction line of the unit.

Comparative Suction and Discharge Pressure


• Versus R-502
Suction Discharge
R-408A 1-2 psi (7-14 kPa) higher 1-10 psi higher (10-70 kPa) higher

It may be necessary to reset the high-pressure cutout to


compensate for higher discharge pressures.

Example: For a box temperature of -15°F (and a 15°F leaving


difference), the suction pressure would be about 9 psig and the
average evaporating temperature -30°F. This corresponds to a
saturated suction temperature of -30°F. If the measured
temperature of the suction-line is -15°F, there is a 15°F superheat
(the difference between measured suction-line temperature and
saturated suction temperature).

To determine superheat for a different box temperature, first note the


measured suction pressure. Using the temperature-pressure chart for
Genetron 408A, locate the measured suction pressure in the “dew”
pressure column. Find the corresponding saturated temperature on
the chart. The difference between the saturated temperature and the
measured suction-line temperature is the superheat.

The average evaporating temperature is the average of the


temperatures corresponding to the suction pressure from both
the “bubble” and “dew” pressure columns in the Genetron 408A
temperature-pressure chart. The expected box temperature can
be found by adding the leaving difference ( usually 15-20°F) to the
average evaporating temperature.

For a head pressure of 259 psig, the average condensing


temperature is about 110°F. To determine the average
condensing temperature at a different head pressure, average
the temperatures corresponding to the head pressure from both
the “bubble” and “dew” pressure columns of the Genetron 408A
pressure-temperature table.
Convenient Pressure-Temperature tables can be found at the
end of this booklet.

HCFC Retrofit Guidelines 33


R-12 Retrofit
Pressure-Temperature Table (English units)
Units are in Pounds Per Square Inch Gauge vs. Degrees Fahrenheit

Temperature (°F)
Bubble Dew Bubble Dew Bubble Dew
Pressure (liquid) (vapor) (liquid) (vapor) (liquid) (vapor)
(psig) 12 134a MP39 MP66 409A
0 -22 -15 -28 -18 -31 -21 -32 -17
2 -16 -10 -23 -13 -25 -16 -26 -12
4 -11 -5 -18 -8 -21 -12 -22 -7
6 -7 -1 -13 -4 -16 -7 -17 -3
8 -2 3 -9 0 -12 -3 -13 1
10 2 7 -6 4 -9 1 -9 5
12 5 10 -2 7 -5 4 -6 8
14 9 13 1 11 -2 7 -2 12
16 12 16 5 14 2 10 1 15
18 16 19 8 17 4 13 4 18
20 19 22 10 19 7 16 7 21
22 21 25 13 22 10 19 10 23
24 24 27 16 25 13 21 12 26
26 27 30 18 27 15 24 15 29
28 30 32 21 30 18 26 17 31
30 32 35 23 32 20 29 20 33
32 34 37 25 34 22 31 22 36
34 37 39 28 36 24 33 24 38
36 39 41 30 38 26 35 26 40
38 41 43 32 40 29 37 28 42
40 43 45 34 42 31 39 31 44
42 45 47 36 44 32 41 33 46
44 47 49 38 46 34 43 34 48
46 49 51 39 48 36 45 36 50
48 51 52 41 50 38 46 38 52
50 53 54 43 52 40 48 40 53
52 55 56 45 53 41 50 42 55
54 57 57 46 55 43 51 43 57
56 59 59 48 57 45 53 45 58
58 60 60 50 58 46 55 47 60
60 62 62 51 60 48 56 48 62
65 66 66 55 63 52 60 52 65
70 70 69 59 67 55 63 56 69
75 74 73 62 70 59 67 59 72
80 77 76 66 74 62 70 63 76
85 81 79 69 77 65 73 66 79
90 84 82 72 80 68 76 69 82
95 87 85 75 83 71 79 72 85
100 90 88 78 86 74 82 75 88
105 93 90 80 88 77 85 78 91
110 96 93 83 91 80 87 81 93
115 99 96 86 94 82 90 83 96
120 102 98 88 96 85 92 86 98
125 104 100 91 99 87 95 89 101
130 107 103 93 101 90 97 91 103
135 109 105 96 103 92 99 93 106
140 112 107 98 105 94 101 96 108
145 114 109 100 108 96 104 98 110
150 117 112 102 110 99 106 100 112
155 119 114 104 112 101 108 102 114
160 121 116 107 114 103 110 105 116

34 Pressure-Temperature Data
Temperature (°F)
Bubble Dew Bubble Dew Bubble Dew
Pressure (liquid) (vapor) (liquid) (vapor) (liquid) (vapor)
(psig) 12 134a MP39 MP66 409A
165 123 118 109 116 105 112 107 118
170 126 120 111 118 107 114 109 120
175 128 121 113 120 109 116 111 122
180 130 123 115 122 111 118 113 124
185 132 125 116 124 113 119 115 126
190 134 127 118 125 114 121 117 128
195 136 129 120 127 116 123 118 130
200 138 130 122 129 118 125 120 132
205 140 132 124 131 120 127 122 133
210 141 134 125 132 122 128 124 135
215 143 135 127 134 123 130 126 137
220 145 137 129 136 125 131 127 138
225 147 139 131 137 127 133 129 140
230 149 140 132 139 128 135 131 142
235 150 142 134 140 130 136 132 143
240 152 143 135 142 131 138 134 145
245 154 145 137 143 133 139 136 146
250 155 146 138 145 134 141 137 148
255 157 148 140 146 136 142 139 149
260 159 149 141 148 137 144 140 151
265 160 151 143 149 139 145 142 152
270 162 152 144 151 140 147 143 154
275 163 153 146 152 142 148 145 155
280 165 155 147 154 143 149 146 157
285 166 156 149 155 145 151 148 158
290 168 157 150 156 146 152 149 159
295 169 159 151 158 147 153 151 161
300 171 160 153 159 149 155 152 162
305 172 161 154 160 150 156 153 163
310 174 163 156 162 151 157 155 165
315 175 164 157 163 153 158 156 166
320 176 165 158 164 154 160 157 167
325 178 166 159 165 155 161 159 169
330 179 167 161 167 157 162 160 170
335 180 169 162 168 158 163 161 171
340 182 170 163 169 159 165 163 172
345 183 171 164 170 160 166 164 173
350 184 172 166 171 161 167 165 175
355 186 173 167 173 163 168 166 176
360 187 174 168 174 164 169 168 177
365 188 176 169 175 165 170 169 178
370 189 177 170 176 166 172 170 179
375 191 178 172 177 167 173 171 180
380 192 179 173 178 168 174 172 182
385 193 180 174 179 170 175 174 183
390 194 181 175 180 171 176 175 184
395 196 182 176 181 172 177 176 185
400 197 183 177 183 173 178 177 186

Pressure-Temperature Data 35
R-12 Retrofit
Temperature-Pressure Table (English units)
Units are in Degrees Fahrenheit vs Pounds Per Square Inch Gauge
* = Inches of Mercury Vacuum

Pressure (psig)
Bubble Dew Bubble Dew Bubble Dew
Temperature (liquid) (vapor) (liquid) (vapor) (liquid) (vapor)
(°F) 12 134a MP39 MP66 409A
-40 11.0 * 14.8 * 8.1* 13.2* 6.5* 11.8* 5.7* 13.6*
-38 10.0 * 13.9 * 6.9* 12.3* 5.3* 10.7* 4.4* 12.6*
-36 8.9 * 12.9 * 5.7* 11.2* 3.9* 9.7* 3.1* 11.6*
-34 7.8 * 12.0 * 4.4* 10.2* 2.6* 8.5* 1.7* 10.6*
-32 6.7 * 10.9 * 3.1* 9.1* 1.2* 7.3* 0.3* 9.5*
-30 5.5 * 9.8 * 1.7* 7.9* 0 6.1* 1 8.4*
-28 4.3 * 8.7 * 0.2* 6.7* 1 4.8* 1 7.2*
-26 3.0 * 7.5 * 1 5.5* 2 3.5* 2 6.0*
-24 1.7 * 6.3 * 1 4.2* 3 2.1* 3 4.7*
-22 0.3 * 5.0 * 2 2.8* 3 0.6* 4 3.4*
-20 1 3.7 * 3 1.4* 4 1 5 2.0*
-18 1 2.3 * 4 0 5 1 6 0.6*
-16 2 0.8 * 5 1 6 2 7 1
-14 3 0 6 2 7 3 8 1
-12 4 1 7 2 8 4 9 2
-10 5 2 8 3 9 5 10 3
-8 5 3 9 4 10 6 11 4
-6 6 4 10 5 11 7 12 5
-4 7 5 11 6 13 8 13 6
-2 8 6 12 7 14 9 14 7
0 9 7 13 8 15 10 16 8
2 10 8 14 9 16 11 17 9
4 11 9 16 10 18 12 18 10
6 12 10 17 11 19 13 19 11
8 13 11 18 13 21 15 21 12
10 15 12 20 14 22 16 22 13
12 16 13 21 15 24 17 24 14
14 17 14 23 16 25 19 25 16
16 18 16 24 18 27 20 27 17
18 20 17 26 19 28 21 29 18
20 21 18 27 20 30 23 30 20
22 22 20 29 22 32 25 32 21
24 24 21 31 23 34 26 34 22
26 25 23 33 25 36 28 36 24
28 27 25 35 27 38 30 38 26
30 28 26 36 28 40 31 40 27
32 30 28 38 30 42 33 42 29
34 32 30 40 32 44 35 44 31
36 33 31 42 34 46 37 46 32
38 35 33 45 36 48 39 48 34
40 37 35 47 38 50 41 50 36
42 39 37 49 40 53 43 52 38
44 41 39 51 42 55 46 55 40
46 43 41 54 44 58 48 57 42
48 45 43 56 46 60 50 60 44
50 47 45 59 48 63 52 62 46
52 49 48 61 51 66 55 65 49
54 51 50 64 53 68 57 68 51
56 53 52 66 55 71 60 70 53
58 55 55 69 58 74 63 73 56

36 Temperature-Pressure Data
Pressure (psig)
Bubble Dew Bubble Dew Bubble Dew
Temperature (liquid) (vapor) (liquid) (vapor) (liquid) (vapor)
(°F) 12 134a MP39 MP66 409A
60 58 57 72 60 77 65 76 58
62 60 60 75 63 80 68 79 61
64 62 63 78 66 83 71 82 63
66 65 65 81 69 86 74 85 66
68 68 68 84 72 90 77 88 69
70 70 71 87 74 93 80 91 72
72 73 74 90 77 96 83 95 75
74 76 77 94 81 100 87 98 78
76 78 80 97 84 104 90 102 81
78 81 83 101 87 107 93 105 84
80 84 87 104 90 111 97 109 87
82 87 90 108 94 115 100 112 90
84 90 94 112 97 119 104 116 94
86 93 97 116 101 123 108 120 97
88 96 101 119 104 127 112 124 101
90 100 104 123 108 131 116 128 104
92 103 108 128 112 135 120 132 108
94 106 112 132 116 140 124 136 112
96 110 116 136 120 144 128 141 115
98 113 120 140 124 149 132 145 119
100 117 124 145 128 153 137 149 123
102 121 128 149 133 158 141 154 128
104 124 133 154 137 163 146 159 132
106 128 137 159 141 168 151 163 136
108 132 142 164 146 173 155 168 140
110 136 146 169 151 178 160 173 145
112 140 151 174 155 184 165 178 150
114 144 156 179 160 189 171 183 154
116 149 161 184 165 194 176 189 159
118 153 166 189 170 200 181 194 164
120 157 171 195 176 206 187 199 169
122 162 177 200 181 212 192 205 174
124 166 182 206 186 217 198 210 179
126 171 187 212 192 224 204 216 185
128 176 193 218 198 230 210 222 190
130 181 199 224 203 236 216 228 196
132 186 205 230 209 242 222 234 201
134 191 211 236 215 249 228 240 207
136 196 217 242 221 255 234 246 213
138 201 223 249 227 262 241 253 219
140 206 229 255 234 269 248 259 225
142 211 236 262 240 276 254 266 231
144 217 242 269 247 283 261 272 237
146 223 249 276 254 290 268 279 244
148 228 256 283 260 298 276 286 250
150 234 263 290 267 305 283 293 257

Temperature-Pressure Data 37
R-502 Retrofit
Pressure-Temperature Table (English units)
Units are in Pounds Per Square Inch Gauge vs. Degrees Fahrenheit

Temperature (°F)
Bubble Dew Bubble Dew Bubble Dew
Pressure AZ-50 (liquid) (vapor) (liquid) (vapor) (liquid) (vapor)
(psig) 502 507 404A HP80 408A
0 -49 -53 -52 -50 -56 -53 -50 -49
2 -44 -48 -47 -46 -52 -48 -45 -44
4 -40 -44 -43 -41 -47 -44 -40 -40
6 -35 -39 -38 -37 -43 -40 -36 -36
8 -32 -36 -35 -33 -39 -36 -32 -32
10 -28 -32 -31 -30 -36 -32 -29 -28
12 -25 -29 -28 -27 -33 -29 -26 -25
14 -21 -26 -25 -23 -29 -26 -22 -22
16 -18 -23 -22 -20 -26 -23 -19 -19
18 -15 -20 -19 -18 -24 -20 -17 -16
20 -13 -17 -16 -15 -21 -18 -14 -13
22 -10 -15 -14 -12 -18 -15 -11 -11
24 -8 -12 -11 -10 -16 -13 -9 -8
26 -5 -10 -9 -8 -14 -10 -6 -6
28 -3 -8 -7 -5 -11 -8 -4 -3
30 -1 -5 -4 -3 -9 -6 -2 -1
32 2 -3 -2 -1 -7 -4 0 1
34 4 -1 0 1 -5 -2 2 3
36 6 1 2 3 -3 0 4 5
38 8 3 4 5 -1 2 6 7
40 10 4 6 7 1 4 8 9
42 12 6 8 9 3 6 10 11
44 13 8 9 10 5 7 12 13
46 15 10 11 12 6 9 14 14
48 17 11 13 14 8 11 15 16
50 19 13 14 15 10 12 17 18
52 20 15 16 17 11 14 19 19
54 22 16 18 19 13 16 20 21
56 23 18 19 20 14 17 22 22
58 25 19 21 22 16 19 23 24
60 26 21 22 23 17 20 25 25
65 30 24 26 27 21 24 28 29
70 34 28 29 30 24 27 32 32
75 37 31 32 33 28 30 35 36
80 40 34 35 36 31 33 38 39
85 43 37 38 39 34 36 41 42
90 46 40 41 42 37 39 44 45
95 49 43 44 45 39 42 47 48
100 52 46 47 48 42 44 50 50
105 55 48 50 50 45 47 52 53
110 57 51 52 53 47 50 55 56
115 60 53 55 55 50 52 58 58
120 62 55 57 58 52 54 60 60
125 65 58 59 60 54 57 62 63
130 67 60 61 62 57 59 65 65
135 69 62 64 65 59 61 67 67
140 71 64 66 67 61 63 69 70
145 74 66 68 69 63 65 71 72
150 76 69 70 71 65 67 73 74
155 78 71 72 73 67 69 75 76
160 80 72 74 75 69 71 77 78

38 Pressure-Temperature Data
Temperature (°F)
Bubble Dew Bubble Dew Bubble Dew
Pressure AZ-50 (liquid) (vapor) (liquid) (vapor) (liquid) (vapor)
(psig) 502 507 404A HP80 408A
165 82 74 76 77 71 73 79 80
170 84 76 78 79 73 75 81 82
175 86 78 80 80 75 77 83 83
180 87 80 81 82 77 78 85 85
185 89 82 83 84 78 80 87 87
190 91 83 85 86 80 82 88 89
195 93 85 87 87 82 84 90 90
200 94 87 88 89 83 85 92 92
205 96 88 90 91 85 87 93 94
210 98 90 92 92 87 89 95 95
215 100 92 93 94 88 90 97 97
220 101 93 95 95 90 92 98 99
225 103 95 96 97 91 93 100 100
230 104 96 98 98 93 95 101 102
235 106 98 99 100 94 96 103 103
240 107 99 101 101 96 98 104 105
245 109 101 102 103 97 99 106 106
250 110 102 104 104 99 100 107 108
255 112 103 105 106 100 102 109 109
260 113 105 106 107 102 103 110 111
265 115 106 108 108 103 105 112 112
270 116 108 109 110 104 106 113 113
275 117 109 111 111 106 107 114 115
280 119 110 112 112 107 109 116 116
285 120 112 113 114 108 110 117 117
290 121 113 114 115 110 111 118 119
295 123 114 116 116 111 112 119 120
300 124 115 117 118 112 114 121 121
310 127 118 119 120 115 116 123 124
320 129 120 122 122 117 118 126 126
330 132 122 124 125 119 121 128 128
340 134 125 126 127 122 123 130 131
350 136 127 129 129 124 125 133 133
360 138 129 131 131 126 127 135 135
370 141 131 133 134 128 130 137 137
380 143 133 135 136 130 132 139 140
390 145 135 137 138 133 134 141 142
400 147 137 139 140 135 136 143 144
410 149 139 141 142 137 138 146 146
420 151 141 143 144 139 140 148 148
430 153 143 145 145 140 142 149 150
440 155 145 147 147 142 143 151 152
450 157 147 149 149 144 145 153 154

Pressure-Temperature Data 39
R-502 Retrofit
Temperature-Pressure Table (English units)
Units are in Degrees Fahrenheit vs. Pounds Per Square Inch Gauge
* = Inches of Mercury Vacuum

Pressure (psig)
Bubble Dew Bubble Dew Bubble Dew
Temperature AZ-50 (liquid) (vapor) (liquid) (vapor) (liquid) (vapor)
(°F) 502 507 404A HP80 408A
-40 4 6 5 5 8 6 4 4
-38 5 7 6 6 9 7 5 5
-36 6 8 7 7 10 8 6 6
-34 7 9 8 8 11 9 7 7
-32 8 10 10 9 12 10 8 8
-30 9 11 11 10 14 11 9 9
-28 10 13 12 11 15 13 11 10
-26 11 14 13 12 16 14 12 11
-24 12 15 15 14 18 15 13 13
-22 14 17 16 15 19 17 14 14
-20 15 18 17 16 21 18 16 15
-18 16 20 19 18 22 20 17 17
-16 18 21 20 19 24 21 18 18
-14 19 23 22 21 26 23 20 19
-12 21 24 23 22 27 25 21 21
-10 22 26 25 24 29 26 23 22
-8 24 28 27 26 31 28 25 24
-6 25 30 29 27 33 30 26 26
-4 27 31 30 29 35 32 28 28
-2 29 33 32 31 37 34 30 29
0 31 35 34 33 39 36 32 31
2 32 37 36 35 41 38 34 33
4 34 40 38 37 43 40 36 35
6 36 42 40 39 46 42 38 37
8 38 44 43 41 48 45 40 39
10 40 46 45 44 51 47 42 41
12 43 49 47 46 53 50 44 43
14 45 51 50 48 56 52 46 46
16 47 54 52 51 58 55 49 48
18 49 56 55 53 61 57 51 50
20 52 59 57 56 64 60 54 53
22 54 62 60 59 67 63 56 56
24 57 64 63 61 70 66 59 58
26 59 67 66 64 73 69 62 61
28 62 70 68 67 76 72 64 64
30 65 73 71 70 79 75 67 66
32 68 77 74 73 82 78 70 69
34 71 80 78 76 86 81 73 72
36 74 83 81 79 89 85 76 75
38 77 86 84 83 93 88 80 79
40 80 90 88 86 96 92 83 82
42 83 94 91 89 100 95 86 85
44 86 97 95 93 104 99 90 89
46 90 101 98 97 108 103 93 92
48 93 105 102 100 112 107 97 96
50 97 109 106 104 116 111 100 99
52 100 113 110 108 120 115 104 103
54 104 117 114 112 124 119 108 107
56 108 121 118 116 129 124 112 111
58 112 125 122 121 133 128 116 115

40 Temperature-Pressure Data
Pressure (psig)
Bubble Dew Bubble Dew Bubble Dew
Temperature AZ-50 (liquid) (vapor) (liquid) (vapor) (liquid) (vapor)
(°F) 502 507 404A HP80 408A
60 116 130 127 125 138 133 120 119
62 120 134 131 129 142 137 124 123
64 124 139 136 134 147 142 129 128
66 128 144 140 139 152 147 133 132
68 133 149 145 143 157 152 138 137
70 137 154 150 148 162 157 142 141
72 142 159 155 153 168 162 147 146
74 146 164 160 158 173 168 152 151
76 151 169 165 163 179 173 157 156
78 156 175 171 169 184 179 162 161
80 161 180 176 174 190 184 167 166
82 166 186 182 180 196 190 173 171
84 171 192 187 185 202 196 178 177
86 176 198 193 191 208 202 184 182
88 182 204 199 197 214 208 189 188
90 187 210 205 203 220 215 195 194
92 193 216 211 209 227 221 201 200
94 199 223 218 216 234 228 207 206
96 205 229 224 222 240 234 213 212
98 210 236 231 229 247 241 219 218
100 217 243 237 235 254 248 226 224
102 223 250 244 242 261 255 232 231
104 229 257 251 249 269 263 239 237
106 236 264 258 256 276 270 246 244
108 242 272 266 263 284 278 253 251
110 249 279 273 271 292 286 260 258
112 256 287 281 278 300 293 267 265
114 263 295 288 286 308 301 274 273
116 270 303 296 294 316 310 282 280
118 277 311 304 302 324 318 289 288
120 285 319 313 310 333 327 297 296
122 292 328 321 319 341 335 305 303
124 300 337 329 327 350 344 313 312
126 308 346 338 336 359 353 321 320
128 316 355 347 345 369 362 330 328
130 324 364 356 354 378 372 338 337
132 332 373 365 363 388 381 347 345
134 341 383 375 372 397 391 356 354
136 349 393 384 382 407 401 365 363
138 358 403 394 392 417 411 374 372
140 367 413 404 402 428 422 383 382
142 376 423 414 412 438 432 393 391
144 385 434 424 422 449 443 403 401
146 395 445 435 433 460 454 412 411
148 404 456 446 444 471 465 423 421
150 414 467 457 455 482 477 433 431

Temperature-Pressure Data 41
R-12 Retrofit
Pressure-Temperature Table (Standard International)
Units are kiloPascals vs. Degrees Celsius

Temperature (°C)
Bubble Dew Bubble Dew Bubble Dew
Pressure (liquid) (vapor) (liquid) (vapor) (liquid) (vapor)
(kPa) 12 134a MP39 MP66 409A
100 -30.1 -26.4 -33.4 -28.1 -35.0 -29.9 -35.7 -27.6
110 -27.8 -24.3 -31.3 -26.0 -32.8 -27.7 -33.5 -25.5
120 -25.7 -22.3 -29.3 -24.0 -30.9 -25.8 -31.5 -23.5
130 -23.7 -20.5 -27.4 -22.2 -29.0 -23.9 -29.6 -21.6
140 -21.9 -18.8 -25.7 -20.5 -27.3 -22.2 -27.8 -19.9
150 -20.1 -17.1 -24.0 -18.8 -25.6 -20.6 -26.1 -18.2
160 -18.5 -15.6 -22.4 -17.2 -24.0 -19.0 -24.5 -16.6
170 -16.9 -14.1 -20.9 -15.8 -22.5 -17.6 -23.0 -15.1
180 -15.3 -12.7 -19.5 -14.3 -21.1 -16.1 -21.5 -13.7
190 -13.9 -11.4 -18.1 -13.0 -19.7 -14.8 -20.1 -12.3
200 -12.5 -10.1 -16.8 -11.7 -18.4 -13.5 -18.8 -11.0
210 -11.1 -8.8 -15.5 -10.4 -17.2 -12.3 -17.5 -9.7
220 -9.8 -7.6 -14.3 -9.2 -15.9 -11.1 -16.3 -8.5
230 -8.6 -6.5 -13.1 -8.0 -14.8 -9.9 -15.1 -7.3
240 -7.4 -5.4 -11.9 -6.9 -13.6 -8.8 -13.9 -6.2
250 -6.2 -4.3 -10.8 -5.8 -12.5 -7.7 -12.8 -5.1
260 -5.1 -3.2 -9.8 -4.8 -11.5 -6.6 -11.7 -4.0
270 -4.0 -2.2 -8.7 -3.7 -10.4 -5.6 -10.6 -3.0
280 -2.9 -1.2 -7.7 -2.7 -9.4 -4.6 -9.6 -2.0
290 -1.8 -0.3 -6.7 -1.8 -8.4 -3.7 -8.6 -1.0
300 -0.8 0.7 -5.7 -0.8 -7.5 -2.7 -7.6 0.0
310 0.2 1.6 -4.8 0.1 -6.6 -1.8 -6.7 0.9
320 1.2 2.5 -3.9 1.0 -5.6 -0.9 -5.8 1.8
330 2.1 3.4 -3.0 1.9 -4.8 0.0 -4.9 2.7
340 3.0 4.2 -2.1 2.8 -3.9 0.8 -4.0 3.6
350 3.9 5.0 -1.3 3.6 -3.1 1.7 -3.1 4.5
360 4.8 5.8 -0.4 4.4 -2.2 2.5 -2.3 5.3
380 6.5 7.4 1.2 6.0 -0.6 4.1 -0.6 6.9
400 8.2 8.9 2.7 7.5 0.9 5.6 1.0 8.4
420 9.8 10.4 4.2 9.0 2.4 7.0 2.5 9.9
440 11.3 11.8 5.7 10.4 3.8 8.5 3.9 11.4
460 12.8 13.2 7.1 11.8 5.2 9.8 5.4 12.8
480 14.3 14.5 8.4 13.1 6.6 11.1 6.7 14.1
500 15.7 15.7 9.7 14.4 7.9 12.4 8.1 15.4
520 17.0 17.0 11.0 15.7 9.1 13.6 9.3 16.7
540 18.3 18.2 12.2 16.9 10.3 14.9 10.6 17.9
560 19.6 19.3 13.4 18.1 11.5 16.0 11.8 19.1
580 20.8 20.5 14.6 19.2 12.7 17.2 13.0 20.3
600 22.1 21.6 15.7 20.3 13.8 18.3 14.2 21.4
620 23.2 22.7 16.8 21.4 14.9 19.4 15.3 22.5
640 24.4 23.7 17.9 22.5 16.0 20.4 16.4 23.6
660 25.5 24.7 19.0 23.5 17.0 21.4 17.5 24.6
680 26.6 25.7 20.0 24.5 18.1 22.4 18.5 25.7
700 27.7 26.7 21.0 25.5 19.1 23.4 19.5 26.7
720 28.8 27.7 22.0 26.5 20.1 24.4 20.6 27.6
740 29.8 28.6 23.0 27.5 21.0 25.3 21.5 28.6
760 30.8 29.5 23.9 28.4 22.0 26.3 22.5 29.6
780 31.8 30.4 24.9 29.3 22.9 27.2 23.5 30.5
800 32.8 31.3 25.8 30.2 23.8 28.1 24.4 31.4
820 33.8 32.2 26.7 31.1 24.7 28.9 25.3 32.3

42 Pressure-Temperature Data
Temperature (°C)
Bubble Dew Bubble Dew Bubble Dew
Pressure (liquid) (vapor) (liquid) (vapor) (liquid) (vapor)
(kPa) 12 134a MP39 MP66 409A
840 34.7 33.1 27.5 31.9 25.6 29.8 26.2 33.2
860 35.6 33.9 28.4 32.8 26.4 30.6 27.1 34.0
880 36.6 34.7 29.3 33.6 27.3 31.5 27.9 34.9
900 37.5 35.5 30.1 34.4 28.1 32.3 28.8 35.7
920 38.3 36.3 30.9 35.2 28.9 33.1 29.6 36.5
940 39.2 37.1 31.7 36.0 29.7 33.9 30.5 37.3
960 40.1 37.9 32.5 36.8 30.5 34.6 31.3 38.1
980 40.9 38.6 33.3 37.6 31.3 35.4 32.1 38.9
1000 41.7 39.4 34.1 38.3 32.0 36.2 32.9 39.6
1050 43.7 41.2 36.0 40.2 33.9 38.0 34.8 41.5
1100 45.7 43.0 37.8 42.0 35.7 39.7 36.6 43.3
1150 47.6 44.7 39.5 43.7 37.5 41.5 38.4 45.1
1200 49.4 46.3 41.3 45.3 39.2 43.1 40.2 46.7
1250 51.2 47.9 42.9 47.0 40.8 44.7 41.9 48.4
1300 52.9 49.5 44.5 48.5 42.4 46.3 43.5 50.0
1350 54.6 51.0 46.1 50.0 43.9 47.8 45.1 51.5
1400 56.2 52.4 47.6 51.5 45.4 49.2 46.6 53.0
1450 57.8 53.9 49.1 53.0 46.9 50.7 48.1 54.5
1500 59.3 55.2 50.5 54.4 48.3 52.1 49.6 55.9
1550 60.8 56.6 51.9 55.7 49.7 53.4 51.1 57.3
1600 62.3 57.9 53.3 57.1 51.1 54.8 52.5 58.6
1650 63.8 59.2 54.6 58.4 52.4 56.1 53.8 60.0
1700 65.2 60.5 55.9 59.7 53.7 57.3 55.2 61.3
1750 66.5 61.7 57.2 60.9 55.0 58.6 56.5 62.5
1800 67.9 62.9 58.5 62.1 56.3 59.8 57.8 63.8
1850 69.2 64.1 59.7 63.3 57.5 61.0 59.1 65.0
1900 70.5 65.2 60.9 64.5 58.7 62.2 60.3 66.2
1950 71.8 66.4 62.1 65.7 59.9 63.3 61.5 67.4
2000 73.0 67.5 63.3 66.8 61.0 64.4 62.7 68.5

Gauge Pressure = Absolute Pressure - 101.3 kPa


1 Bar = 101.3 kPa

Pressure-Temperature Data 43
R-12 Retrofit
Temperature-Pressure Table (Standard International)
Units are in Degrees Celsius vs kiloPascals
Pressure (kPa)
Bubble Dew Bubble Dew Bubble Dew
Temperature (liquid) (vapor) (liquid) (vapor) (liquid) (vapor)
(°C) 12 134a MP39 MP66 409A
-40 64 51 74 57 79 61 82 55
-39 67 54 77 60 83 65 86 58
-38 70 57 81 63 87 68 90 61
-37 74 60 85 66 91 71 94 64
-36 77 63 89 69 96 75 99 68
-35 81 66 93 73 100 79 103 71
-34 84 70 98 76 105 82 108 74
-33 88 73 102 80 109 86 112 78
-32 92 77 107 84 114 91 117 82
-31 96 80 112 88 119 95 122 86
-30 100 84 116 92 125 99 128 90
-29 105 88 122 96 130 104 133 94
-28 109 93 127 101 136 109 139 98
-27 114 97 132 105 142 114 145 103
-26 119 102 138 110 148 119 151 108
-25 123 106 144 115 154 124 157 112
-24 129 111 150 120 160 130 163 117
-23 134 116 156 126 167 135 170 123
-22 139 122 163 131 174 141 177 128
-21 145 127 169 137 181 147 184 134
-20 151 133 176 143 188 154 191 139
-19 157 139 183 149 196 160 198 145
-18 163 145 191 155 203 167 206 151
-17 169 151 198 162 211 174 214 158
-16 176 157 206 168 220 181 222 164
-15 182 164 214 175 228 189 231 171
-14 189 171 222 183 237 196 239 178
-13 196 178 231 190 246 204 248 185
-12 204 185 240 198 255 212 257 192
-11 211 193 248 205 265 221 267 200
-10 219 201 258 213 274 229 276 208
-9 227 209 267 222 284 238 286 216
-8 235 217 277 230 295 247 296 224
-7 243 225 287 239 305 257 307 233
-6 252 234 297 248 316 266 317 242
-5 261 243 308 258 327 276 328 251
-4 270 253 319 267 339 286 340 260
-3 279 262 330 277 351 297 351 270
-2 288 272 342 287 363 308 363 280
-1 298 282 353 298 375 319 375 290
0 308 293 365 309 388 330 388 300
1 318 304 378 320 401 342 401 311
2 329 315 391 331 414 354 414 322
3 340 326 404 343 428 367 427 333
4 351 338 417 355 442 379 441 345
5 362 350 431 367 457 392 455 357
6 374 362 445 380 472 406 469 369
7 385 375 459 393 487 419 484 381
8 398 388 474 406 502 434 499 394
9 410 401 489 420 518 448 515 407
10 423 415 504 434 534 463 530 421
11 436 429 520 448 551 478 547 435
44 Temperature-Pressure Data
Pressure (kPa)
Bubble Dew Bubble Dew Bubble Dew
Temperature (liquid) (vapor) (liquid) (vapor) (liquid) (vapor)
(°C) 12 134a MP39 MP66 409A
12 449 443 536 463 568 494 563 449
13 463 458 553 478 585 510 580 463
14 476 473 570 493 603 526 597 478
15 491 488 587 509 621 543 615 494
16 505 504 605 525 640 560 633 509
17 520 521 623 542 659 577 651 525
18 535 537 642 559 679 595 670 542
19 551 554 661 576 699 614 689 558
20 566 572 680 594 719 632 709 576
21 583 590 700 612 740 652 729 593
22 599 608 720 631 761 671 750 611
23 616 627 741 650 783 691 770 629
24 633 646 762 669 805 712 792 648
25 651 665 783 689 827 733 814 667
26 668 685 805 710 850 754 836 687
27 687 706 828 731 874 776 858 707
28 705 727 850 752 898 799 881 727
29 724 748 874 774 922 822 905 748
30 744 770 898 796 947 845 929 770
31 763 793 922 818 973 869 953 792
32 784 815 947 842 999 893 978 814
33 804 839 972 865 1025 918 1004 837
34 825 863 998 889 1052 944 1030 860
35 846 887 1024 914 1080 970 1056 883
36 868 912 1051 939 1108 996 1083 908
37 890 937 1078 965 1137 1023 1110 932
38 913 963 1106 991 1166 1051 1138 958
39 935 990 1134 1018 1195 1079 1166 983
40 959 1017 1163 1045 1226 1107 1195 1009
41 983 1044 1193 1073 1256 1137 1225 1036
42 1007 1072 1223 1101 1288 1166 1254 1063
43 1031 1101 1253 1130 1320 1197 1285 1091
44 1057 1130 1284 1159 1352 1228 1316 1119
45 1082 1160 1316 1190 1385 1259 1347 1148
46 1108 1190 1348 1220 1419 1291 1379 1178
47 1135 1221 1381 1251 1453 1324 1412 1208
48 1161 1253 1414 1283 1488 1358 1445 1238
49 1189 1285 1448 1315 1524 1392 1479 1269
50 1217 1318 1482 1348 1560 1426 1513 1301
51 1245 1351 1518 1382 1596 1461 1548 1333
52 1274 1385 1553 1416 1634 1497 1583 1366
53 1303 1420 1590 1451 1672 1534 1619 1400
54 1333 1455 1627 1487 1710 1571 1656 1434
55 1363 1492 1664 1523 1749 1609 1693 1468
56 1394 1528 1702 1559 1789 1647 1731 1504
57 1425 1566 1741 1597 1830 1687 1769 1540
58 1457 1604 1781 1635 1871 1727 1808 1576
59 1489 1642 1821 1674 1913 1767 1848 1613
60 1522 1682 1861 1713 1956 1809 1888 1651
61 1555 1722 1903 1753 1999 1851 1929 1690
62 1589 1763 1945 1794 2043 1893 1970 1729
63 1624 1804 1988 1836 2087 1937 2012 1769
64 1659 1847 2031 1878 2133 1981 2055 1809
65 1694 1890 2075 1921 2179 2026 2098 1850

Gauge Pressure = Absolute Pressure - 101.3 kPa


1 Bar = 101.3 kPa
Temperature-Pressure Data 45
R-502 Retrofit
Pressure-Temperature Table (Standard International)
Units are in kiloPascals vs. Degrees Celsius

Temperature (°C)
Bubble Dew Bubble Dew Bubble Dew
Pressure AZ-50 (liquid) (vapor) (liquid) (vapor) (liquid) (vapor)
(kPa) 502 507 404A HP80 408A
100 -45.3 -47.4 -46.8 -46.1 -49.4 -47.3 -45.7 -45.3
110 -43.3 -45.4 -44.8 -44.1 -47.4 -45.3 -43.7 -43.3
120 -41.4 -43.5 -43.0 -42.2 -45.6 -43.5 -41.8 -41.4
130 -39.6 -41.8 -41.2 -40.5 -43.8 -41.8 -40.1 -39.6
140 -37.9 -40.1 -39.6 -38.8 -42.2 -40.2 -38.4 -38.0
150 -36.3 -38.6 -38.0 -37.3 -40.6 -38.6 -36.8 -36.4
160 -34.8 -37.1 -36.5 -35.8 -39.1 -37.2 -35.3 -34.9
170 -33.4 -35.7 -35.1 -34.4 -37.7 -35.8 -33.9 -33.5
180 -32.0 -34.4 -33.8 -33.1 -36.4 -34.5 -32.5 -32.1
190 -30.7 -33.1 -32.5 -31.8 -35.1 -33.2 -31.2 -30.8
200 -29.4 -31.8 -31.2 -30.5 -33.8 -32.0 -30.0 -29.6
210 -28.2 -30.7 -30.0 -29.4 -32.6 -30.8 -28.8 -28.4
220 -27.0 -29.5 -28.9 -28.2 -31.5 -29.7 -27.6 -27.2
230 -25.9 -28.4 -27.8 -27.1 -30.4 -28.6 -26.5 -26.1
240 -24.8 -27.3 -26.7 -26.0 -29.3 -27.5 -25.4 -25.0
250 -23.7 -26.3 -25.7 -25.0 -28.3 -26.5 -24.4 -24.0
260 -22.7 -25.3 -24.7 -24.0 -27.3 -25.5 -23.3 -22.9
270 -21.7 -24.3 -23.7 -23.0 -26.3 -24.5 -22.4 -22.0
280 -20.7 -23.4 -22.7 -22.1 -25.4 -23.6 -21.4 -21.0
290 -19.8 -22.4 -21.8 -21.2 -24.4 -22.7 -20.5 -20.1
300 -18.8 -21.5 -20.9 -20.3 -23.5 -21.8 -19.5 -19.2
310 -17.9 -20.7 -20.0 -19.4 -22.7 -20.9 -18.7 -18.3
320 -17.1 -19.8 -19.2 -18.5 -21.8 -20.1 -17.8 -17.4
330 -16.2 -19.0 -18.3 -17.7 -21.0 -19.3 -16.9 -16.6
340 -15.4 -18.2 -17.5 -16.9 -20.1 -18.5 -16.1 -15.7
350 -14.6 -17.4 -16.7 -16.1 -19.3 -17.7 -15.3 -14.9
375 -12.6 -15.5 -14.8 -14.2 -17.4 -15.8 -13.4 -13.0
400 -10.7 -13.6 -13.0 -12.4 -15.6 -14.0 -11.5 -11.2
425 -8.9 -11.9 -11.2 -10.6 -13.9 -12.3 -9.8 -9.4
450 -7.2 -10.2 -9.5 -9.0 -12.2 -10.6 -8.1 -7.7
475 -5.6 -8.6 -7.9 -7.4 -10.6 -9.1 -6.5 -6.1
500 -4.0 -7.1 -6.4 -5.8 -9.1 -7.5 -4.9 -4.6
525 -2.5 -5.6 -4.9 -4.4 -7.6 -6.1 -3.4 -3.1
550 -1.0 -4.2 -3.5 -2.9 -6.1 -4.7 -2.0 -1.6
575 0.4 -2.8 -2.1 -1.6 -4.8 -3.3 -0.6 -0.2
600 1.8 -1.5 -0.8 -0.2 -3.4 -2.0 0.8 1.1
625 3.1 -0.2 0.5 1.1 -2.1 -0.7 2.1 2.4
650 4.4 1.1 1.8 2.3 -0.9 0.5 3.4 3.7
675 5.7 2.3 3.0 3.5 0.3 1.7 4.6 4.9
700 6.9 3.5 4.2 4.7 1.5 2.9 5.8 6.1
725 8.1 4.6 5.4 5.9 2.7 4.1 7.0 7.3
750 9.2 5.7 6.5 7.0 3.8 5.2 8.1 8.4
775 10.4 6.8 7.6 8.1 4.9 6.2 9.2 9.5
800 11.5 7.9 8.7 9.2 6.0 7.3 10.3 10.6
825 12.5 9.0 9.7 10.2 7.0 8.3 11.4 11.7
850 13.6 10.0 10.7 11.2 8.1 9.4 12.4 12.7
875 14.6 11.0 11.7 12.2 9.1 10.3 13.4 13.7
900 15.6 12.0 12.7 13.2 10.0 11.3 14.4 14.7
925 16.6 12.9 13.7 14.2 11.0 12.3 15.4 15.7
950 17.6 13.9 14.6 15.1 11.9 13.2 16.3 16.6
975 18.5 14.8 15.6 16.0 12.9 14.1 17.3 17.6

46 Pressure-Temperature Data
Temperature (°C)
Bubble Dew Bubble Dew Bubble Dew
Pressure AZ-50 (liquid) (vapor) (liquid) (vapor) (liquid) (vapor)
(kPa) 502 507 404A HP80 408A
1000 19.5 15.7 16.5 16.9 13.8 15.0 18.2 18.5
1050 21.3 17.4 18.2 18.7 15.5 16.7 20.0 20.3
1100 23.0 19.1 19.9 20.4 17.2 18.4 21.7 22.0
1150 24.7 20.8 21.6 22.0 18.9 20.0 23.4 23.6
1200 26.4 22.4 23.2 23.6 20.5 21.6 25.0 25.2
1250 28.0 23.9 24.7 25.1 22.0 23.1 26.5 26.8
1300 29.5 25.4 26.2 26.6 23.5 24.6 28.1 28.3
1350 31.0 26.8 27.7 28.1 25.0 26.1 29.5 29.8
1400 32.5 28.3 29.1 29.5 26.4 27.5 31.0 31.2
1450 33.9 29.6 30.5 30.9 27.8 28.8 32.4 32.6
1500 35.3 31.0 31.8 32.2 29.1 30.1 33.7 34.0
1550 36.6 32.3 33.1 33.5 30.4 31.4 35.0 35.3
1600 37.9 33.5 34.4 34.8 31.7 32.7 36.3 36.6
1650 39.2 34.8 35.6 36.0 32.9 33.9 37.6 37.8
1700 40.5 36.0 36.9 37.2 34.2 35.1 38.8 39.1
1750 41.7 37.2 38.1 38.4 35.4 36.3 40.1 40.3
1800 42.9 38.4 39.2 39.6 36.5 37.5 41.2 41.5
1850 44.1 39.5 40.4 40.7 37.7 38.6 42.4 42.6
1900 45.3 40.6 41.5 41.8 38.8 39.7 43.5 43.8
1950 46.4 41.7 42.6 42.9 39.9 40.8 44.7 44.9
2000 47.5 42.8 43.7 44.0 41.0 41.9 45.7 46.0
2050 49.1 43.8 44.7 45.1 42.1 42.9 46.8 47.0
2100 50.1 44.9 45.8 46.1 43.1 44.0 47.9 48.1
2150 51.2 45.9 46.8 47.1 44.1 45.0 48.9 49.1
2200 52.2 46.9 47.8 48.1 45.1 46.0 49.9 50.1
2250 53.3 47.9 48.8 49.1 46.1 46.9 50.9 51.1
2300 54.3 48.8 49.7 50.0 47.1 47.9 51.9 52.1
2350 55.3 49.8 50.7 51.0 48.0 48.8 52.9 53.1
2400 56.2 50.7 51.6 51.9 49.0 49.8 53.8 54.0
2450 57.2 51.6 52.6 52.8 49.9 50.7 54.8 55.0
2500 58.2 52.5 53.5 53.7 50.8 51.6 55.7 55.9
2550 59.1 53.4 54.4 54.6 51.7 52.5 56.6 56.8
2600 60.0 54.3 55.2 55.5 52.6 53.3 57.5 57.7
2650 60.9 55.1 56.1 56.4 53.5 54.2 58.4 58.6
2700 61.8 56.0 56.9 57.2 54.3 55.0 59.2 59.4
2750 62.7 56.8 57.8 58.0 55.2 55.9 60.1 60.3
2800 63.5 57.6 58.6 58.9 56.0 56.7 61.0 61.1
2850 64.4 58.4 59.4 59.7 56.8 57.5 61.8 62.0
2900 65.2 59.2 60.2 60.5 57.6 58.3 62.6 62.8
2950 66.1 60.0 61.0 61.2 58.4 59.1 63.4 63.6
3000 66.9 60.8 61.8 62.0 59.2 59.9 64.2 64.4
3050 67.1 61.6 62.6 62.8 60.0 60.6 65.0 65.2
3100 67.9 62.3 63.3 63.5 60.8 61.4 65.8 66.0
3150 68.7 63.1 64.1 64.3 61.5 62.1 66.6 66.7
3200 69.4 63.8 64.8 65.0 62.3 62.9 67.3 67.5
3250 70.2 64.5 65.6 65.7 63.0 63.6 68.1 68.2
3300 71.0 65.2 66.3 66.4 63.8 64.3 68.8 69.0
3350 71.7 65.9 67.0 67.1 64.5 65.0 69.5 69.7
3400 72.4 66.6 67.7 67.8 65.2 65.7 70.3 70.4

Gauge Pressure = Absolute Pressure - 101.3 kPa


1 Bar = 101.3 kPa

Pressure-Temperature Data 47
R-502 Retrofit
Temperature-Pressure Table (Standard International)
Units are in Degrees Celsius vs. kiloPascals
Pressure (kPa)
Bubble Dew Bubble Dew Bubble Dew
Temperature AZ-50 (liquid) (vapor) (liquid) (vapor) (liquid) (vapor)
(°C) 502 507 404A HP80 408A
-40 127 141 137 133 154 141 130 128
-39 133 147 144 139 161 148 136 134
-38 139 154 150 145 168 154 142 140
-37 145 161 157 152 175 161 149 146
-36 152 168 164 159 183 168 155 152
-35 159 175 171 166 191 176 162 159
-34 165 183 178 173 199 184 169 166
-33 172 191 186 180 207 192 176 173
-32 180 199 194 188 216 200 184 181
-31 187 207 202 196 224 208 192 188
-30 195 216 210 204 234 217 200 196
-29 203 224 219 213 243 226 208 205
-28 211 234 228 222 253 235 217 213
-27 220 243 237 231 263 245 225 222
-26 229 253 247 240 273 255 234 231
-25 238 263 257 250 284 265 244 240
-24 247 273 267 260 295 276 253 250
-23 257 284 277 270 306 287 263 259
-22 267 295 288 281 318 298 274 270
-21 277 306 299 292 329 309 284 280
-20 287 318 310 303 342 321 295 291
-19 298 330 322 315 354 333 306 302
-18 309 342 334 326 367 346 318 313
-17 321 355 346 339 381 359 329 325
-16 332 368 359 351 394 372 341 337
-15 345 381 372 364 408 386 354 349
-14 357 395 386 377 423 400 367 362
-13 370 409 399 391 438 414 380 375
-12 383 423 414 405 453 429 393 388
-11 396 438 428 419 468 444 407 402
-10 410 453 443 434 484 460 421 416
-9 424 469 458 449 501 476 436 431
-8 438 485 474 465 518 492 451 446
-7 453 502 490 481 535 509 466 461
-6 468 518 507 497 552 526 482 477
-5 484 536 523 514 571 544 498 493
-4 500 553 541 531 589 562 515 509
-3 516 572 559 549 608 581 532 526
-2 533 590 577 567 628 600 549 543
-1 550 609 596 585 648 619 567 561
0 568 629 615 604 668 639 585 579
1 586 649 634 624 689 660 604 598
2 604 669 654 643 710 681 623 617
3 623 690 675 664 732 702 643 636
4 642 711 696 685 754 724 663 656
5 662 733 717 706 777 746 683 676
6 682 756 739 728 800 769 704 697
7 703 779 762 750 824 793 725 719
8 724 802 785 773 849 817 747 740
9 745 826 808 796 874 841 770 763
10 767 851 832 820 899 866 793 786
11 790 876 856 844 925 892 816 809
48 Temperature-Pressure Data
Pressure (kPa)
Bubble Dew Bubble Dew Bubble Dew
Temperature AZ-50 (liquid) (vapor) (liquid) (vapor) (liquid) (vapor)
(°C) 502 507 404A HP80 408A
12 813 901 882 869 952 918 840 833
13 836 927 907 895 979 945 864 857
14 860 954 933 921 1007 972 889 882
15 885 981 960 947 1035 1000 915 907
16 909 1009 987 974 1064 1029 941 933
17 935 1038 1015 1002 1093 1058 968 960
18 961 1067 1044 1030 1123 1088 995 987
19 988 1096 1073 1059 1154 1118 1022 1014
20 1015 1126 1102 1089 1185 1149 1051 1043
21 1042 1157 1132 1119 1217 1181 1080 1071
22 1070 1189 1163 1150 1250 1213 1109 1101
23 1099 1221 1195 1181 1283 1246 1139 1131
24 1129 1254 1227 1213 1317 1279 1170 1161
25 1158 1287 1260 1246 1351 1313 1201 1192
26 1189 1321 1293 1279 1387 1348 1233 1224
27 1220 1356 1327 1313 1423 1384 1265 1257
28 1252 1391 1362 1347 1459 1420 1298 1290
29 1284 1427 1397 1383 1496 1457 1332 1323
30 1317 1464 1433 1419 1534 1495 1367 1358
31 1350 1502 1470 1455 1573 1533 1402 1393
32 1384 1540 1507 1493 1612 1572 1437 1428
33 1419 1579 1546 1531 1652 1612 1474 1464
34 1455 1618 1584 1570 1693 1653 1511 1501
35 1491 1659 1624 1609 1735 1694 1549 1539
36 1527 1700 1664 1649 1777 1736 1587 1577
37 1565 1742 1706 1690 1820 1779 1626 1617
38 1603 1785 1747 1732 1864 1823 1666 1656
39 1642 1828 1790 1775 1909 1867 1707 1697
40 1681 1873 1834 1818 1954 1913 1748 1738
41 1721 1918 1878 1862 2001 1959 1790 1780
42 1762 1964 1923 1907 2048 2006 1833 1823
43 1804 2011 1969 1953 2096 2054 1877 1866
44 1846 2058 2015 2000 2144 2102 1921 1911
45 1889 2107 2063 2047 2194 2152 1966 1956
46 1933 2156 2111 2096 2245 2202 2012 2002
47 1977 2206 2160 2145 2296 2254 2059 2048
48 2023 2258 2210 2195 2348 2306 2106 2096
49 2069 2310 2261 2246 2401 2359 2155 2144
50 2115 2363 2313 2298 2455 2413 2204 2193
51 2163 2417 2366 2351 2510 2468 2254 2243
52 2212 2472 2420 2405 2566 2524 2305 2294
53 2261 2528 2475 2459 2623 2581 2356 2346
54 2311 2584 2530 2515 2681 2639 2409 2398
55 2362 2642 2587 2572 2740 2698 2463 2452
56 2414 2701 2645 2630 2800 2758 2517 2506
57 2467 2761 2703 2688 2860 2819 2572 2562
58 2520 2822 2763 2748 2922 2881 2629 2618
59 2575 2885 2824 2809 2985 2944 2686 2675
60 2630 2948 2886 2871 3049 3008 2744 2733
61 2686 3013 2949 2934 3114 3074 2803 2792
62 2743 3078 3013 2999 3180 3140 2863 2852
63 2802 3145 3078 3064 3248 3208 2924 2914
64 2861 3214 3144 3131 3316 3277 2987 2976
65 2921 3283 3212 3199 3385 3347 3050 3039

Gauge Pressure = Absolute Pressure - 101.3 kPa


1 Bar = 101.3 kPa
Temperature-Pressure Data 49
Further Information
For additional information, call your nearest Genetron
refrigerants wholesaler, or contact us at 1-800-631-8138,
or fax us at 1-973-455-6395.

To request a Material Safety Data Sheet (MSDS) or additional product


information call 1-800-707-4555 or download it from www.genetron.com.

For more information contact us at:


Internet: www.genetron.com
Phone: 1-800-631-8138
Mail: Genetron Refrigerants
Honeywell International
P.O. Box 1053
Morristown, NJ 07962-1053

Disclaimer
All statements, information and data given herein are believed to be
accurate and reliable but are presented without guaranty, warranty
or responsibility of any kind, expressed or implied. Statements or
suggestions concerning possible use of our products are made
without representation or warranty that any such use is free of patent
infringement and are not recommendations to infringe any patent.
The user should not assume that all safety measures are indicated,
or that other measures may not be required.
Genetron, AZ-20, and AZ-50 are registered trademarks of Honeywell.
©2001 Honeywell Genetron Refrigerants
G525-100
03/01 5K
Printed in the U.S.A.

Das könnte Ihnen auch gefallen