Sie sind auf Seite 1von 2

Air System Sizing Summary for AHU-G-01

Project Name: FACULTY OF MEDICINE-ALBAHA 04/20/2020


Prepared by: SAJMEP 10:45AM

Air System Information


Air System Name AHU-G-01 Number of zones 1
Equipment Class CW AHU Floor Area 6566.0 ft²
Air System Type SZCAV Location ALBAHA, Saudi Arabia

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 36.2 Tons Load occurs at Jul 1600
Total coil load 434.2 MBH OA DB / WB 96.3 / 61.0 °F
Sensible coil load 434.2 MBH Entering DB / WB 86.5 / 58.2 °F
Coil CFM at Jul 1600 15327 CFM Leaving DB / WB 54.5 / 46.2 °F
Max block CFM 15327 CFM Coil ADP 51.0 °F
Sum of peak zone CFM 15327 CFM Bypass Factor 0.100
Sensible heat ratio 1.000 Resulting RH 50 %
ft²/Ton 181.5 Design supply temp. 53.0 °F
BTU/(hr-ft²) 66.1 Zone T-stat Check 0 of 1 OK
Water flow @ 10.0 °F rise 86.89 gpm Max zone temperature deviation 0.1 °F

Central Heating Coil Sizing Data


Max coil load 111.5 MBH Load occurs at Des Htg
Coil CFM at Des Htg 15327 CFM BTU/(hr-ft²) 17.0
Max coil CFM 15327 CFM Ent. DB / Lvg DB 52.7 / 60.9 °F
Water flow @ 20.0 °F drop N/A

Humidifier Sizing Data


Max steam flow at Jan 0700 327.98 lb/hr Air mass flow 56491.04 lb/hr
Airflow Rate 15327 CFM Moisture gain .00581 lb/lb

Supply Fan Sizing Data


Actual max CFM 15327 CFM Fan motor BHP 0.00 BHP
Standard CFM 12554 CFM Fan motor kW 0.00 kW
Actual max CFM/ft² 2.33 CFM/ft² Fan static 0.00 in wg

Return Fan Sizing Data


Actual max CFM 15327 CFM Fan motor BHP 0.00 BHP
Standard CFM 12554 CFM Fan motor kW 0.00 kW
Actual max CFM/ft² 2.33 CFM/ft² Fan static 0.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM 14561 CFM CFM/person 108.66 CFM/person
CFM/ft² 2.22 CFM/ft²

Hourly Analysis Program v4.90 Page 1 of 2


Zone Sizing Summary for AHU-G-01
Project Name: FACULTY OF MEDICINE-ALBAHA 04/20/2020
Prepared by: SAJMEP 10:45AM

Air System Information


Air System Name AHU-G-01 Number of zones 1
Equipment Class CW AHU Floor Area 6566.0 ft²
Air System Type SZCAV Location ALBAHA, Saudi Arabia

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (MBH) (CFM) (CFM) Peak Load (MBH) (ft²) CFM/ft²
Zone 1 228.9 14561 14561 Jun 1600 8.9 6566.0 2.22

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
01-G-CO-019 1 2.1 Jul 1600 127 0.0 86.1 1.48
01-G-CO-021 1 6.5 Jul 2100 394 0.0 419.8 0.94
01-G-CO-022 1 15.4 Jun 1600 937 0.6 322.9 2.90
01-G-LA-016 1 18.4 Dec 1100 1116 0.5 441.3 2.53
01-G-LA-017 1 18.4 Dec 1100 1116 0.5 441.3 2.53
01-G-LA-020 1 15.8 Jun 1600 958 0.6 333.7 2.87
01-G-LA-021 1 108.9 Jun 1600 6617 3.4 3024.7 2.19
01-G-LA-025 1 33.7 Dec 1400 2050 2.0 1001.0 2.05
01-G-OF-026 1 9.0 Jun 1600 545 0.6 172.2 3.16
01-G-VA-014 1 11.5 Jun 1600 700 0.6 322.9 2.17

Hourly Analysis Program v4.90 Page 2 of 2