Beruflich Dokumente
Kultur Dokumente
TIL 1287-1
GE ENERGY SERVICES
PRODUCT SERVICE
8/23/2000
BACKGROUND / DISCUSSION
P2
In July and August 1999, two MS7001B units (psig)
20VG-1
were removed from service due to uncontrolled (GAS SYSTEM VENT VALVE)
GAS
GE identified several contributing factors SRV GCV NOZZLES
including out-of-calibration servo control cards, (SPEED / RATIO VALVE) (GAS CONTROL VALVE)
GAS MANIFOLD
worn position sensors (LVDT’s), evidence of
P1 - GAS SUPPLY INLET PRESSURE
contaminated hydraulics with servo fouling, and P2 - SPEED REGULATED GAS PRESSURE TO GVC
P3 - TURBINE CONTROL GAS PRESSURE
COPYRIGHT 2000, GE
The information published in this Technical Information Letter is offered to you by GE in consideration of its ongoing sales and service
relationship with your organization. However, since the operation of your plant involves many factors not within our knowledge, and since
operation of the plant is in your control and ultimate responsibility for its continuing successful operation rests with you, GE specifically
disclaims any responsibility for liability based on claims for damage of any type, i.e. direct, consequential or special that may be alleged to
have been incurred as result of applying this information regardless of whether it is claimed that GE is strictly liable, in breach of contract,
in breach of warranty, negligent, or is in other respects responsible for any alleged injury or damage sustained by your organization as a
result of applying this information.
TIL1287-1
Page 2
TIL1287-1
Page 2
– Determine root cause and perform
corrective action prior to next start
DIAGNOSTIC MONITORING attempt.
Customers should use the following four (4)
diagnostic monitoring guidelines during start-up
to ensure safe, reliable operation.
As a reference, Figure 2 demonstrates the characteristic 4) LONG START - It is GE fleet experience for
P2 pressure and GCV positioning for a typical start. the fuel gas fired turbine that ignition
initiation – to flame indication nominally
Guideline P2 values can be determined using
takes less than 10 seconds. Any start which
information listed in Table I at the end of this document.
requires 15 seconds or more should be
1) P2 HIGH (greater than P2H psig ) considered a warning indicator. Upon any
long start, the gas turbine and gas fuel
PRIOR to the ignition sequence – Fuel gas
supply systems should be closely evaluated
may be passing the SRV before it is permitted
for maintenance / corrective action.
– ABORT the start immediately Abnormal noises during startup should be
considered an indicator and should be
– Review the calibration and operation
investigated immediately.
of the SRV, LVDT(s) servo valve, and P2
pressure transducer
– Determine root cause and perform 110
FSNL
IGNITION WARMUP
corrective action prior to next start 100
attempt. 90
P2 PRESSURE
60
correctly P2 PRESSURE
40
TURBINE SPEED
TABLE I
P2 Guideline Values
by Frame size:
P2H P2VH P2L
MS9001F
6 PSIG 1.25 X P2F 0.8 X P2F
Classes
Notes:
1. Measured P2 pressure before the ignition sequence should be zero (0) psig. The
P2H limits are valued at levels that should allow a clear determination using the existing
pressure transducer.
2. P2F is the site-specific P2 gas pressure at firing. P2F will vary with firing speed.
P2F can be found in the latest revision of the site specific Control Specifications (Control
System Settings). Note that modifications, upgrades and system changes may affect the
site-specific P2F gas pressure at firing. Contact GE representative for clarification if there
is any uncertainty.
3. Additional information concerning the maintenance of the gas fuel system can be
found in TIL-331CR1: LEAKAGE PAST THE GAS FUEL STOP VALVE.