TECHNICAL SPECIFICATION
STORAGE
Storage in the origine packaging, protected against shock.
MAINTENANCE / SERVICING
Visual inspection every six months.
Check that the drilled holes are not blocked (e.g. due to corrosion,
or deposits of foreign material) and that the drilled holes comply
with the installation drawings.
Verify that there are no loose objects placed in close proximity to
the nozzles and that there are no obstructions which would inhibit
the correct diffusion of the extinguishant.
Not applicable
DESCRIPTION INSTALLATION
The drilled hole diameters are calculated from the following formula: The nozzle is fitted to a pipe which has been screwed with a pipe
thread to EN 10226-1 R; apply PTFE tape to the thread before
fitting the nozzle.
M* = ωhom . A . ρhom with 1 / ρhom = (XL / ρL) + (XG / ρG) Particular care must be paid to the orientation of the nozzle drillings
in order to optimize the diffusion of the gas into the protected
Where
volume.
M* : Total flow (kg/s) The rules governing the positioning and orientation of this type of
ω : Velocity (m/s) nozzle are defined in the technical instructions of the relevant
hom : Homogeneous extinguishing system.
A : Nozzle opening area (m²)
ρk : Density of phase k ( (kg/m³)
Xk : Weight fraction of phase k k
A
A-A ( 1 : 2 )
50°
°
50
50°
45°
A
The drilled holes can be placed in the
following ways:
- 2 drilled holes at 180°
- 4 drilled holes at 50°
- 4 drilled holes at 90°
B
C Modification of the maximum working pressure: 60 to 100 bar / Translation correction 20/02/2012
B Additional information : Nozzle used with Sinorix CO2 - Approval System VdS 04/02/2010
ISSUE DESCRIPTION DATE