Sie sind auf Seite 1von 3

Heat Loss Calculation Sheet

Data Input PROJECT NAME

Room: ROOM NAME

Length Width Height Room Design


L (m) W (m) H (m) tc 22 oC
Outside Design
10 8.5 2.4 tao -4 oC
Infiltration Rate
N 1.2 AC/hr
Emitter Radiant
Proportion R 0.1
Initial Calculations

Room Volume V =L⋅W⋅H 204 m3


Ventilation Conductance Cv
N⋅V
= 81.6
3

Surface tcmod Area U Umod A*U Umod


External Wall N/A 85 0.8 N/A 68.000 (t −t )
Window N/A 2.1 1.8 N/A 3.780 U '=U⋅ c c '
(t c−t ao )
N/A N/A 0.000
N/A N/A 0.000
N/A N/A 0.000
0 0.000
0 0.000
0 0.000
0 0.000
0 0.000

= 87.1 = 71.7800

Main Calculations
3( C v +6 ∑ A )
F1cu =
∑ ( AU )+ 18 ∑ A + 1. 5 R {3 C v−∑ ( AU ) } = 1.0883

F2cu =
∑ ( AU )+18 ∑ A
∑ ( AU )+ 18 ∑ A + 1. 5 R {3 C v−∑ ( AU ) } = 0.9844

Steady State Heat Loss


Ф = { F1 cu ∑ ( AU )+ F 2cu C v }( t c−t ao )
= 4119.61 Watts

= 48.47 W/m2
t c−t c ' )
t c−t ao )