BANGLADESH UNIVERSITY OF ENGINEERING AND TECHNOLOGY (BUET)

DEPARTMENT OF CIVIL ENGINEERING


Mobile: 01819 557 964; PABX: 966 5650-80 Ext. 7226; www.buet.ac.bd/ce/ 1l 1! 1' '~
Bureau of Research ,
Testing & Consultation
CONCRETE L ABORATORY

BRTC No. 1102-02394/19·20/CE; Dt: 10/12/2019


Client : Akij Cement Ready Mix Concrete
Ref.No. : ACRMC/TSD/CORE/1 0/DEC/2019; Dt: 10/12/2019
Project : Splash Works Water Park ltd.,Gozaria, Munshigonj.

Sample : Concrete Cylindrical Core [Mix Proportion (as quoted}: Not Mentioned, Aggregate Type: Stone Chips]
Date of Casting : Not Mentioned Date of Sample Collection: 13/01 /2020
Test : Compressive Strength of Concrete Cylindrical Core [ASTM C 42/C 42M)
Date of Test : 8/212020

TEST REPORT

Average
Sample
Length of Diameter of Cross Crushing
SI. No. Location Identification Ultimate Load Type of Failure
Sample Sample Sectional Strength
Mark
Area
in. in. sq. in. lb.

Mat 3150 psi


1 2 5.2 2.72 5.81 18,302 Combined•
(21 .7 MPa}
6190 psi
2 Mat 3 5.2 2.72 5.81 35,950 Combined•
(42.7 MPa}

Mat 4190 psi


3 4 5.2 2.72 5.81 24,322 Combined•
(28.9 MPa}

Mat 4700 psi


4 2/1 5.2 2.72 5.81 27,335 Combined•
(32.4 MPa}
7580 psi
5 Mat 212 5.2 2.72 5.81 44,051 Combined•
(52.3 MPa)
6230 psi
6 Mat 213 5.2 2.72 5.81 36,220 Combined• '"
(43 MPa}

• Combined = Mortar and Aggregate failure

NOTE 1 - The diameter of core specimens for the determination of compressive strength in load bearing structural members shall be at least
3.70 in. [94 mm]. For non-load bearing structural members or when it is impossible to obtain cores with length-diameter ratio (UD} greater than or
equal to 1, core diameters less than 3.70 in. [94 mm] are not prohibited.

NOTE 2 - The compressive strengths of nominal 2-in. (50-mm] diameter cores are known to be somewhat lower and more variable than those of
nominal 4-in. [100-mm] diameter cores. In addition, smaller diameter cores appear to be more sensitive to the effect of the length-diameter ratio.

COMMEi'ff - Please compare the results with your corresponding design value~nd consult with your design engineer.

2
Countersigned by: ,. Test Performed by:

~ . ? .... '

Radin Md Mahirul Hoque


Professor Assistant Professor
Department of Civil Engineering Department of Civtt Engineering
SUET, Dhaka-1000, Bangladesh BUET, Dhaka-1000, Bangladesh

Warning: Samples as supplied to us have been testedin our laboratory. BRTC does not have any responsibility as to the representative character of the samples required tobe
tested. It is recommended that samples are sent in asecure and sealed cover/packet/container under signature of the competent authority. In order to avoid fraudulent
fabrication of test results, It isrecommended that all test reports are collected by duly authorized person, and not by the Contractor/Supplier.

Authenticity of this page is


verifiable from
http://verltv.ce.buet.ac.bd
with the QR Q9dt or 10