Dimensional
Weight w/o Weight with Roof
Qty Accessories Accessories Opening
(lb) (lb) (in)
1 245 284 32.5 x 32.5
Performance
Requested Actual Requested Actual Operating Airstream Drive Tip
Fan Elevation SE
Volume Volume SP SP Power Temperature Loss Speed
RPM (ft) (%)
(CFM) (CFM) (in wg) (in wg) (hp) (F) (%) (ft/min)
8,329 8,329 1.5 1.5 813 3.57 1,752 70 4.2 6,493 57.5
Notes:
All dimensions shown are in units of in.
*FLA - based on tables 150 or 148 of National Electrical
Code 2002. Actual motor FLA may vary, for sizing thermal
overload, consult factory.
LwA - A weighted sound power level, based on ANSI S1.4
dBA - A weighed sound pressure level, based on 11.5 dB
attenuation per Octave band at 5.0 ft - dBA levels are not
licensed by AMCA International