PDVSA
RESISTANCE TEMPERATURE SENSORS

ITEM N° QUANTITY OFF PROJECT REFERENCE SHEET OF

SPECIFICATION REFERENCES N° By REVISED DATE


I.S.A S
PDVSA–K–

XMTR 1. Assy RTD and thermowell only RTD and T/W. complete with trans
And R.T.D. 2. Mounting Integral with R.T.D assembly Remote from R.T.D. assy. on yoke

3. Enclosure Safe area Classified Class Group Div

Weatherproof Ex. Proof Intr. safe STD.


Temp. Class T1 T2 T3 T4 T5 T6

4. Output 4–20 m.A.d.c. Other Powered ext.

5. Type Pt–100 Other 2–wire 3–wire 4–wire


ELEMENT
Sheathed O.D. Material: 316 ST.ST. Herm. sealed
Screw cap and chain Cond. conn. 1/2” N.P.T.F.

6. Thermowell Material I.D. Shall suit sheath O.D.


Construction: Drilled Tapered Straight

7. Notes See notes 1 and 2 Notes 3 and 4 only applicable when specified

MFR 8. Model N°

TERMINAL EXTENSION PROCESS SOLID BARSTOCK DRILLED PROCESS


HEAD NIPPLE CONNECTION CONNECTION
AND UNION 1” NPTM

INTERNAL INTERNAL
CONNECTION ID OD CONNECTION ID OD

LAGGING
EXTENSION
T U U

ELEMENT LENGTH

Item Tag. N° RTD Single Element Thermowell Details


N° Type Duplex length Type
X S – screwed Process U T
inches Connection Notes
F – flanged inches inches

Notes: 1. All items shall be corrosion resistant to marine atmosphere and tropicalised.
2. For remote transmitter supply 2 metres cable with connectors between R.T.D. head and instr.
3. R.T.D. and thermowell assembly only.
4 Special extension leads protection for high ambient temperature.
20.13a
To fill the data sheet, click here

PDVSA

ITEM N° QUANTITY OFF PROJECT REFERENCE SHEET OF

SPECIFICATION REFERENCES N° By REVISED DATE


I.S.A S
PDVSA–K–

Item Tag. N° RTD Single Element Thermowell Details


N° Type Duplex length Type Process U T
X S – screwed
inches Connection inches inches Notes
F – flanged

Notes:

20.13b
ENGINEERING SPECIFICATION PDVSA 20.13

PDVSA
REVISION DATE
INSTRUCTIONS TO FILL FORMS
20.13A AND 20.13B 0 AUG.94
Page 1
Menú Principal Indice manual Indice volumen Indice norma

RESISTANCE TEMPERATURE SENSORS

Refer to Scientific Apparatus Manufacturers Association (SAMA) Tentative


Standard on Resistance RC 5–10–1955.
1. Complete assembly includes head, element, and well; as shown in sketch.
5. Give size and pipe schedule of nipple. Check if union is required.
7. The ice point resistance in ohms usually defines the resistance vs.
temperature curve. If not, provide additional data as an attachment.
8. Give maximum range over which the elements will be used.
9. Specify sealing of leads.
11. This thread is on the element termination, not the well.
12. It is necessary to specify the number of wires, depending on the
compensation required. The other items refer to the element termination.
14. A built–up well has a welded tip and connection.
16. Internal thread of flange if well flange is threaded.

Instructions for the tabulation:


17. Process Connection is the connection on the element or well which is
connected to the pipe or vessel. Well dimensions are illustrated in the sketch.
It is not necessary to specify ‘‘Element Length’’ if well dimensions are already
given. Single or Dual elements are assumed to be within the same sheath.