PRE-COMMISSIONING TEST
80 MVA, Station Transformer #4
REPORT OF TRANSFORMER
Date : 20/11/15
Insulation Resistance Test Before Tan-Delta Test :-

SIDE TEST VOLTAGE MEASURE VALUE


HV TO EARTH 14.1 GΩ

LV1 TO EARTH 14.5 GΩ

LV2 TO EARTH 14.1 GΩ


5 KV DC
HV TO LV1 19.9 GΩ

HV TO LV2 27.6 GΩ

LV1 TO LV2 14.7 GΩ

Capacitance & Tan-Delta Measurement (GST Mode) :-HV TO EARTH


Leakage Value of C Value of Tan-Delta
Applied Voltage Value of Watt
Current(mA) (PF) (DF)
5.12 KV 16.69 10381 0.5613 0.66%

10.01 KV 32.63 10381 2.142 0.66%

Capacitance & Tan-Delta Measurement (GST Mode) :- LV1 TO EARTH


Leakage Value of C Value of Tan-Delta
Applied Voltage Value of Watt
Current(mA) (PF) (DF)
5.14 KV 16.81 10413 0.4508 0.52%

10.15 KV 33.17 10413 1.817 0.54%

Capacitance & Tan-Delta Measurement (GST Mode) :- LV1 TO EARTH


Leakage Value of C Value of Tan-Delta
Applied Voltage Value of Watt
Current(mA) (PF) (DF)
5.20 KV 16.12 9875.5 0.4053 0.48%

10.01 KV 31.04 9875.6 1.519 0.49%

NAME SIGNATURE & DATE.


WITNESS BY
Mr. P.DAS
PEPL
WITNESS BY
PROJECT SG T P P Mr. S B SARKAR
BHEL
WITNESS BY
UNIT NO. UNIT# 4
WBPDCL(Construction)
WITNESS BY
RATING 500MW Sheet 3 of 4
WBPDCL(Commissioning)
TESTED BY
PHASE 2 REPORT NO.5
WBPDCL(TECIT)
SL. NO. - 2034289
PRE-COMMISSIONING TEST
80 MVA, Station Transformer #4
REPORT OF TRANSFORMER
Date : 20/11/15

Capacitance & Tan-Delta Measurement (UST Mode) :-HV TO LV1


Leakage Value of C Value of Tan-Delta
Applied Voltage Value of Watt
Current(mA) (PF) (DF)
5.12 KV 4.808 2804.7 0.6900 0.30%

10.10 KV 8.892 2804.8 0.2691 0.30%

Capacitance & Tan-Delta Measurement (UST Mode) :- HV TO LV2


Leakage Value of C Value of Tan-Delta
Applied Voltage Value of Watt
Current(mA) (PF) (DF)
5.08 KV 3.952 2477.1 0.0915 0.46%

10.12 KV 7.869 2477.3 0.3645 0.46%

Capacitance & Tan-Delta Measurement (UST Mode) :- LV1 TO LV2


Leakage Value of C Value of Tan-Delta
Applied Voltage Value of Watt
Current(mA) (PF) (DF)
5.07 KV 0.246 154.52 0.0079 0.63%

10.06 KV 0.487 154.54 0.0310 0.63%

NAME SIGNATURE & DATE.


WITNESS BY
Mr. P.DAS
PEPL
WITNESS BY
PROJECT SG T P P Mr. S B SARKAR
BHEL
WITNESS BY
UNIT NO. UNIT# 4
WBPDCL(Construction)
WITNESS BY
RATING 500MW Sheet 4 of 4
WBPDCL(Commissioning)
TESTED BY
PHASE 2 REPORT NO.5
WBPDCL(TECIT)