NOTE: TERMINAL L1 MUST 120V. 50/60HZ.

BE POWERED BEFORE FUSED POWER SUPPLY


TERMINAL 12 L1 L2
UV
FORM 6642 VT GROUP MP3101 NOT USED
SEE
PROTECTOFIER E FLAME RELAY (F)
INTERCONNECTION FLAME-PAK
SINGLE BURNER, MANUAL DIAGRAM BELOW ELECT. COIL IS ENERGIZED
G NETWORK WHEN FLAME IS
OPERATION, INCLUDES TIMER ESTABLISHED AND
ACF
FOR PURGE AND IGNITION DETECTED.
TRIAL. D.C. ua TEST JACK 13 F 12
SS100A FLAME PAK LS 12 F 5 6
POC CTP1 (CHECK) ACF
C - CHECK RELAY C
ACF F - FLAME RELAY
1 4
PROOF OF 3 9 13 12
F CLOSURE SW. C
**
POC - PROOF OF CLOSURE 1 7 1 7 TIMER
CONTACT(S) FROM CTP2 C
MAIN VALVE(S) START
1 4
3 10 4
TIMER
13 11 MOTOR
CTP
NO CONNECTION * 7 1

- JUMPER IN U300M MANUAL F 7 PURGED


* TIMOFIER FOR IGNITION
TRIAL UNITS ONLY. 2 5 CTP3 (MUST BE NEON)
SEE OFF-ON
TIMING PURGE 12
** - FUEL
SAFETY INTLK.SERIES CIRCUIT.
AND AIR PRESS.SWS., SCHEDULE IGN.
F 11
6
C 4
IGNITION TRANS.
VENT,FANS,ETC. AS REQ'D. IT
NOTE: TIMER CAMS (CTP) SHOWN BURNER/ALARM 2 8 2 8 SPARK
IN ZERO TIME POSITION. SEL.SW. IGNITOR
CTP2 CLOSES BEFORE
CTP1 OPENS. PILOT VALVE(S) PV

INTERNAL WIRING 9 F C 8 MAIN VALVE(S)


N.C.
MV
EXTERNAL WIRING 3 9 3 9 N.C.
FLAME ON
WIRING DIAGRAM (NEON LIGHT ON CHASSIS)
F 10 AH
3 6 ALARM HORN

SINGLE BURNER PROTECTOFIER


NOTE: 120V.
TERMINAL L1 MUST L1 (FORM 6642 VT GROUP MP3101) ua
50/60HZ. L1 D.C.
BE POWERED BEFORE L2 TEST
TERMINAL 12
FUSED L2 JACK
LS FLAME
POWER 3
PAK
SUPPLY 4 U300M
NOTES: PROOF OF MANUAL
5 G
FLAME WIRE TO BE NO. 14 TYPE TW. ** CLOSURE
SW.
POC
6
TIMOFIER
600V. INSULATED WIRE OR EQUAL. FLAME TIMER 7 TRANS.
WIRE MUST NOT BE IN SAME CONDUITS 8
WITH POWER WIRING. PURGED UV
9
IGNITION CABLE MUST BE RUN IN SEPARATE 10
CONDUIT TO SPARK ELECTRODE. BURNER/
ALARM 11 ACF ACF
(DO NOT MIX WITH 120V.WIRING.) E
OFF-ON 12
ALL WIRING AND EQUIPMENT EXTERNAL TO SEL.SW. 13
PROTECTOFIER TO BE FURNISHED BY (CHECK) (FLAME)
OTHERS UNLESS OTHERWISE SPECIFIED.
INSTALLATION, OPERATION AND MAINTENANCE FLAME ELECTRODE
SHALL CONFORM WITH NATIONAL FIRE ASSY. (IF USED) FLAME OPERATING
PROTECTION ASSOCIATION STANDARDS, WIRE SIGNAL
BURNER E FROM
NATIONAL AND LOCAL CODES AND
AUTHORITIES HAVING JURISDICTION.ANY P-C II OR
POC PURPLE UV FLAME
MODIFICATION VOIDS APPROVAL. PROOF OF CLOSURE ROD
CONTACT(S) FROM
MAIN VALVE(S) GAS YELLOW
PILOT
START P-C II ULTRA- G
P.B. VIOLET SCANNER
U300M MANUAL (IF USED) ALARM HORN
AH
TIMOFIER TIMING
RANGE PURGE(MIN.) IGN.(SEC.) IGN. TRANS. IT
SPARK IGNITOR
M MIN. SEC.
IGN. CABLE MV
PROTECTION CONTROLS, INC. N.C.
MAIN VALVE(S)
SKOKIE, ILLINOIS
PILOT VALVE(S) PV
WIRING DIAGRAM FOR: N.C.
PROTECTOFIER FORM 6642VT GROUP MP3101
JOB NO. REVISED DRAWING NO. INTERCONNECTION DIAGRAM
1-05 X-379