Sie sind auf Seite 1von 271

India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 1


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

1) Mr. Sameer Gaikwad (Regional sales manager)


2) Mr. Kamin Dave (Relay Application Engineer)
3) Mr. B.Sundaram (Relay Application Engineer)

1) Mr. Mike O’Dowd (Regional sales manager)

4) Mr. Jay Gosalia (Vice-President-Engineering & Marketing)


5) Mr. Denis Tierney (Product Manager-F6 & F2 series)
6) Mr. Yakov knobel (Sr. Application Engineer-Protective relaying)
7) Mr. Jun Verzosa (Sr. Application Engineer-Protective relaying)
8) Mr. He fang (Application Engineer-Protective relaying)

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 2


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Important considerations when design protection system:


1. Types of fault and abnormal Conditions to be protected against
2. Quantities available for measurement
3. Types of protection available
4. Speed
5. Fault position discrimination
6. Dependability / reliability
7. Security / stability
8. Overlap of protections
9. Phase discrimination / selectivity
10. CT’s and VT’s ratio required
11. Auxiliary supplies
12. Back-up protection
13. Cost
14. Duplication of protection

Types of protection
A - Fuses
For LV Systems, Distribution Feeders and Transformers, VT’s, Auxiliary Supplies

B - Over current and earth fault


Widely used in All Power Systems
1. Non-Directional
2. Directional

C - DIFFERENTIAL
For feeders, Bus-bars, Transformers, Generators etc
1. High Impedance
2. Low Impedance
3. Restricted E/F
4. Biased
5. Pilot Wire

D - Distance
For transmission and sub-transmission lines and distribution feeders, also used as back-
up protection for transformers and generators without signaling with signaling to provide
unit protection e.g.:

1. Time-stepped distance protection


2. Permissive under-reach protection (PUP)
3. Permissive overreach protection (POP)
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 3
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
4. Unblocking overreach protection (UOP)
5. Blocking overreach protection (BOP)
6. Power swing blocking
7. Phase comparison for transmission lines
8. Directional comparison for transmission lines

E - Miscellaneous:
1. Under and over voltage
2. Under and over frequency
3. A special relay for generators, transformers, motors etc.
4. Control relays: auto-reclose, tap change control, etc.
5. tripping and auxiliary relays

Speed
Fast operation: minimizes damage and danger
Very fast operation: minimizes system instability discrimination and security can be
costly to achieve.
Examples:
1. differential protection
2. differential protection with digital signaling
3. distance protection with signaling
4. directional comparison with signaling

Fault position discrimination


Power system divided into protected zones must isolate only the faulty equipment or
section

Dependability / reliability
Protection must operate when required to Failure to operate can be extremely damaging
and disruptive Faults are rare. Protection must operate even after years of inactivity
Improved by use of:
1. Back-up Protection and
2. duplicate Protection

Security / Stability
Protection must not operate when not required to e.g. due to:
1. Load Switching
2. Faults on other parts of the system
3. Recoverable Power Swings

Overlap of protections
1. No blind spots
2. Where possible use overlapping CTs

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 4


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Phase discrimination / selectivity


Correct indication of phases involved in the fault Important for Single Phase Tripping and
auto-Reclosing applications

Auxiliary supplies

Required for:
1. Tripping circuit breakers
2. Closing circuit breakers
3. Protection and trip relays
• AC. auxiliary supplies are only used on LV and MV systems.
• DC. auxiliary supplies are more secure than ac supplies.
• Separately fused supplies used for each protection.
• Duplicate batteries are occasionally provided for extra security.
• Modern protection relays need a continuous auxiliary supply.
• During operation, they draw a large current which increases due to
operation of output elements.
Relays are given a rated auxiliary voltage and an operative auxiliary voltage range. The
rated value is marked on the relay. Refer to relay documentation for details of operative
range. it is important to make sure that the range of voltages which can appear at the
relay auxiliary supply terminals is within the operative range.
IEC recommended values (IEC 255-6):
Rated battery voltages:
12, 24, 48, 60, 11 0, 125, 220, 250, 440
Preferred operative range of relays:
80 to 10% of voltage rated
AC. component ripple in the dc supply:
<10% of voltage rated

COST
The cost of protection is equivalent to insurance policy against damage to plant, and loss
of supply and customer goodwill.
Acceptable cost is based on a balance of economics and technical factors. Cost of
protection should be balanced against the cost of potential hazards there is an economic
limit on what can be spent.

Minimum cost:
Must ensure that all faulty equipment is isolated by protection
Other factors:
1. Speed
2. Security/Stability
3. Sensitivity:
Degree of risk in allowing a low level fault to develop into a more severe fault
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 5
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
4. Reliability

Total cost should take account of:


1. Relays, schemes and associated panels and panel wiring
2. Setting studies
3. Commissioning
4. CT’s and VT’s
5. Maintenance and repairs to relays
6. Damage repair if protection fails to operate
Lost revenue if protection operates unnecessarily

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 6


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Cautions for Use: Check List

Check list
1) Is the correct rated voltage applied?
2) Is the applied coil voltage within the allowable continuous
voltage limit?
3) Is the ripple in the coil voltage within the allowable level?
4) For voltage applied to a polarized coil, is polarity observed?
5) When hot start is required, is the increase in coil resistance
resulting from coil temperature rise taken into account in setting
Coil Drive Input coil voltage?
6) Is the coil voltage free from momentary drop caused by load
current?
(Special attention for self-holding relays.)
7) Is supply voltage fluctuation taken into account when setting
the rated coil voltage?
8) The relay status may become unstable if the coil voltage (current)
is gradually increased or decreased. Was the relay tested in a
real circuit or with a real load?

1) Is the load rated within the contact ratings?


2) Does the load exceed the contacts minimum switching capacity?
3) Was the relay tested with a real load?
A DC load may cause contact lock-up due to large contact
transfer. Was the relay tested with a real load?
4) For an inductive load, is a surge absorber used across the
contacts?
5) When an inductive load causes heavy arc discharge across
the relay contacts, the contacts may be corroded by chemical
reaction with nitrogen in the atmosphere. Was the relay tested
Load with a real load?
(Relay contacts) 6) Is the contact switching frequency below the specification?
7) When there are more than two sets of contacts (2T) in a relay,
metallic powder shed from one set of contacts may cause a
contact failure on the other set (particularly for light loads). Was
the relay tested in a real circuit?
8) A delay capacitor used across relay contacts may cause
contact welding. Was the relay tested with a real load?
9) For an AC relay, a large contact bounce may cause contact
welding. Was the relay tested in a real circuit or with a
real load?

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 7


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
1) Is the ambient temperature in the allowable operating
temperature range?
2) Is relative humidity below 85 percent?
3) Is the operating atmosphere free from silicon gas? Depending on
the load type, silicon gas may cause a black substance to from
on the contacts, leading to contact failure.
Operating 4) Is the operating atmosphere free from excessive airborne dust?
Environment 5) Is the relay protected from oil and water splashes?
6) Is the relay protected from vibration and impact which may
cause poor contact with the socket?
7) Is the relay free from mechanical shocks after it is installed in
position?
10) Is insulation coating applied to the relay along with the PC
board? Depending on the load type, a black substance may form
to cause contact failure.

Storage and 1) Is the relay subject to freezing or condensation (especially when


Transport shipping)?
2) Is the temperature in the allowable temperature range?
3) Is the humidity in the allowable humidity range?
4) Is the storing atmosphere free from excessive airborne dust?
5) Is the relay protected from oil and water splashes?
6) When shipping does vibration and impact exceed the
allowable range?

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 8


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

CHAPTER-1 DISTRIBUTION FEEDER


PROTECTION
CHAPTER-2 POWER SYSTEM MODEL:
SHORT CIRCUIT STUDY,
O/C & E/F RELAY CO-
ORDINATION
CHAPTER-3 TRANSFORMER
PROTECTION
CHAPTER-4 SHUNT CAPACITOR BANK
PROTECTION
CHAPTER-5 BASIC FUNDAMENTAL OF
POWER FACTOR
IMPROVEMENT
CHAPTER-6 BASIC FUNDAMENTAL OF
HARMONICS

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 9


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

“MULTIPLICATION OF THIS DOCUMENT IS STRICTLY PROHIBITED”

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 10


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

TABLE OF CONTENTS:

TITLE Sr.No. PAGE NUMBER


Introduction 1.1 12
IDMT OC & E/F Prot. 1.2 12
DMT & IDMTL 1.2.1 13
characteristics variations &
their Applications
Functional characteristics 1.3 19
Non-directional phase & 1.4 21
earth fault OC relays
Advantage of Three OC & 1.4.1. 22
E/F scheme against two
OC & E/F scheme
Non-directional IDMTL 1.4.2 26
relay with highest
Application in TR feeder
Directional Phase & earth 1.5 27
fault OC relays
Connection for Directional 1.5.1 31
Phase OC relays
Directional E/F OC 1.5.2 36
elements
Non-directional standby E/F 1.6 38
Protection
Sensitive E/F Protection 1.7 43
using CBCT
E/F Protection in 3-phase & 1.8 44
4-wire system
2-O/C & 1-E/F scheme in 1.9 45
same parallel feeder
operation
Unit Protection 2.0 46
Circulating Current system 2.1 46
Balanced voltage system 2.2 47
Summation arrangement 2.3 48
Supervision of pilots 2.4 49

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 11


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

1.1 INTRODUCTION:

Industrial power distribution systems make extensive use of cable feeder for
example, between “captive generation bus” or “grid supply bus” to load center /
power control center. These feeders are too often radial or sometimes form part
of ring main system. While IDMTL OC / E/F protection is mostly used for radial
distribution feeders particularly in the tail end, unit type protection such as a pilot
wire protection, are also sometimes used on critical feeders.

The unit protections are highly selective, sensitive & fast in operation but don’t
have any backup capabilities. The IDMTL protections on the contrary, are simple
& economical but slower in operation to necessities time co-ordination between
adjacent sections for selective tripping. IDMTL relays, however provide excellent
backup protection to the downstream system.

1.2 IDMT OVER CURRENT & EARTH FAULT PROTECTION:

Application of relay is used as a primary protection as well as backup protection


of transformer/motor/capacitor/cable feeders.

Primary Protection & Backup Protection:


-Æ Primary Protection: Device Closest to the Fault or Main Protection
-Æ Backup Protection: Device next in the line, if main protection fails
Definition : A device which operates, usually after slight delay, if the
normal relay does not operate to trip its circuit breaker
-Æ Backup Protection should be operate, if the primary protection fails.
-Æ Reason for providing Backup Protection;
1) Failure of Primary Protection due to;
-Æ No operation of relay
-Æ Incorrect system design
-Æ Wrong selection of the relay
-Æ Improper installation & maintenance
2) Circuit Breaker failure (Stuck breaker)

-ÆMainly Three kinds of back up relays:


1) Relay which trip the same breaker if the main relay fails (Relay back
up)
2) Relay which open the next nearest circuit breakers on the same bus
in case one of the local breakers fails to open (Breaker back up)
3) Relay which operate from a neighboring station so as to back-up both
relays and breakers and their supplies (Remotes Back-up) in case of

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 12


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
the failure of any local supply including the battery, or in case a circuit
breaker or relay fails to function.

While at the lower end of the distribution system (particularly at low voltage
levels), fuses or series connected trip coils operating on switching devices, are
used for short circuit protection, IDMT over phase/earth current relays find wide
application at medium voltage levels.

As the name implies, IDMTL relays have an inverse time OC characteristic (i.e.
the operating time is inversely proportional to the current) and a definite minimum
time (DMT) for high multiples of setting current. The time /current curve is usually
represented on a logarithmic scale and gives the operating time at different
multiples of setting current, for the maximum “Time Multiple Setting” (TMS). The
TMS is continuously adjustable giving a range of time/current characteristic.

1.2.1 DMT & IDMTL CHARACTERISTIC VARIATIONS AND THEIR APPLICATIONS:

There are different variation of IDMTL characteristics. These are

i) IEC Standard Inverse


t = (0.14*TMS)/((PSM)0.02 - 1)

ii) IEC Very Inverse


t = (13.5*TMS)/((PSM) – 1)

iii) IEC Extremely Inverse


t = (80*TMS)/((PSM)2 – 1)

iv) UK Long Inverse


t = (120*TMS)/((PSM) – 1)

v) IEEE Moderately Inverse


t = (TD/7)*{((0.0515)/(PSM0.02 – 1)) + 0.114}

vi) IEEE Very Inverse


t = (TD/7)*{((19.61)/(PSM2 – 1)) + 0.491}

vii) IEEE Extremely Inverse


t = (TD/7)*{((28.2)/(PSM2 – 1)) + 0.1217}

viii) IEEE US C08 Inverse


t = (TD/7)*{((5.95)/(PSM2 – 1)) + 0.18}

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 13


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

ix) US C02 Short Time Inverse


t = (TD/7)*{((0.02394)/(PSM0.02 – 1)) + 0.01694}

Where,
PSM = Plug setting multiplier = If/Is
TMS = Time multiplier setting
TD = Time dial setting

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 14


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
Below figure shows the above characteristics at the maximum time multiplier
setting of 1.0

Figure (1A):- IEC60255 CURVES at TMS1.0

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 15


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Figure (1B):- IEEE CURVES at TD=7.0

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 16


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Definite Time Current Relays (DMT):


In radial or loop circuits, where there are several line sections in series, there is
no difference in current magnitude between a fault at the end of one section and
a fault at the beginning of the next section as shown below;

G1 TR
F1 F2 F3

R1 R2
1.0s
0.75s
0.5s
0.2s

Disadvantage: Relay “R1” will operate after 1.0s on “F1”, “F2” & “F3”

Where there are many section in series the tripping time for a fault near the
power source may be dangerously high. This is obviously un-desirable because
such faults involve large currents and are destructive if not removed quickly. In
fact, the disadvantage of time-graded over current relays is the heaviest faults
are cleared slowest.

Standard Inverse Definite Minimum Time lag (IDMTL) over current relays:
It’s a combination curve of Inverse time + Definite minimum time. This relay
covers majority of the application in power system

Very Inverse Time Current relays:


Application of this relay is suitable in cases where there is a substantial reduction
of fault current as the distance from the power source increases.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 17


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
Extremely Inverse Time Current relays:
Application of this relay is suitable in grading with fuses & at the same time to
remain inoperative on the switching current. As shown in formula the operating
time of relay is inversely proportional to the square of the applied current.

Long Inverse Time Current relays:


Application of this relay is mainly for over load protection of NGR (Neutral
grounding resistor).

The IDMTL relays provide both time & current grading to achieve discrimination
between successive stage in the distribution system.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 18


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

1.3 Functional Characteristics:

Three essential characteristics of the protective relaying:


1) Sensitivity
2) Selectivity
3) Speed

1) Sensitivity:

-Æ Pickup Setting must be greater than maximum load current in circuit.


-Æ Lower the pickup of the relay more will be the sensitivity.
-Æ Relay should be able to detect minimum fault current.

Example:
----Æ Fault current magnitude = 35kA
----Æ CTR = 3000/1
----Æ Relay Pickup, set at 75%
Relay Operating current on Primary side = (75/100)*(3000) = 2250 Amp
Relay Operating current on Secondary side = (75/100)*(1) = 0.75 Amp
Sensitivity of relay during a fault = (2250/35000)*100 = 6.42%

----Æ Relay Pickup, set at 100%


Relay Operating current on Primary side = (100/100)*(3000) = 3000 Amp
Relay Operating current on Secondary side = (100/100)*(1) = 1.0 Amp
Sensitivity of relay during a fault = (3000/35000)*100 = 8.57%

Thus, lower the setting, higher will be the sensitivity for fault detection.

2) Selectivity:

Three methods to achieve the discrimination


1) Discrimination by Time
2) Discrimination by current
3) Discrimination by both Time & current
4) Direction of the fault current

1) Discrimination by Time:
• Basically used with definite time relays
• Time of operation is independent of current magnitude
• Discrimination time between successive relays say 0.3 sec

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 19


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
EXAMPLE:
• For fault on one outgoing feeder3
• Fuse Operates in 0.01s
• Next feeder2 relay operates in 0.25s
• Next feeder1 relay operates in 0.50s
• All upstream relays are graded accordingly

DISADVANTAGE:
• Operating time of the upstream relays will be very high
• The fault closest to the source takes longest time to clear

ADVANTAGE:
• Defined operating time for variable source operating condition.

2) Discrimination by Current:
• Applicable only when substantial difference between the fault
current magnitudes exist for the faults on the two ends of the
equipment.
• The impedance of the equipment shall be substantial that will
create the above difference.

EXAMPLE:
• For the fault on the L.T. side of transformer TR
• Fault current = 40,000 A @ 415V
= 1509.09 A @ 11kV (Reflected fault on 11kV side)
• For the fault on the H.T. side of Transformer TR
• Fault current = 13.5 kA @ 11kV
• IDMTL unit of Transformer Primary side (11kV) relay should be
operate as a backup protection on L.T. fault
• HIGHSET unit of Transformer Primary side (11kV) relay should be
operate on H.T. fault

DISADVANTAGE:
• The discrimination is obtained but no backup ensured

3) Discrimination by both Time & Current:


• Obtained using Inverse time relays (IDMTL)
• IDMTL – Inverse definite minimum time lag
• Relay operating time varied by adjusting time dial & current setting

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 20


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
• Relay operating time depends on fault current. Higher fault, less
operating time. Operating time inversely proportional to current
magnitude
• Discrimination achieved by both current & time

EXAMPLE:
• For a given fault current magnitude, discrimination time is 0.3s for
all the successive relays
• Pickup value for all the relays set below the fault current level
• For the fault on the outgoing feeder-1
• Fault current = 40,000 A @ 415V
= 1509.2 A @ 11kV (Reflected fault current on H.T.
side)
• 250 A fuse operates in 0.01s
• Next feeder-2 relay operates in 0.25s on L.T. side fault
• Next feeder-3 relay operates in 0.5s on L.T. side fault
• Next feeder-4 relay operates in 0.75s on L.T. side fault
• For H.T. side of the Transformer TR
• Fault current = 13.5 kA @ 11kV
• Same Feeder-4 relay operates in 0.25s on H.T. faults

ADVANTAGE:
• With the same Pickup & Time dial settings, lower Tome of
operating for near end faults and higher operating times for near
end faults inherently achieved.
• In case of the difference in the fault current magnitude along
system, IDMTLL relays are superior to the DMT relays
• In case of same fault current magnitude along system, desired
operating time can be achieved by adjusting pickup & time dial

4) SPEED:
• Speed: the clearance time of the fault
• Fault clearing time < 100ms, high speed tripping
• Necessity of high speed tripping:
• Minimizing the damage of the equipment
• Increasing stability margin for synchronous machines
• Avoiding unwanted tripping of voltage sensitive loads

• Speed without sensitivity: Unsatisfactory co-ordination

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 21


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
• Methods to achieve high speed tripping:
• Unit protection:
1) Protection provide to trip instantaneously for faults only within
unit
under protection
2) No co-ordination with external protections
• Example:
• Bus differential protection
• Feeder pilot wire protection
• Transformer or motor protection
• Directional protection
• Restricted earth fault protection

1.4 Mainly Two types of Phase & Earth fault Over current relays:

[A] Non-directional Phase & Earth fault Over current relays:

Non-directional means when the fault current can flows on both direction
through relay & fault current magnitude is more than threshold level of relay, it
gives trip command to Circuit breaker.

F1 F2

G1

F1
F2

R1

Where,
R1 = Non-directional OC relay
F1 = In zone fault
F2 = Out zone fault

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 22


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
During fault “F1” , the fault current can flows through the relay towards the source
G1 & fault “F2”, the fault current can flows through the relay away from source
G1. So, relay R1 seen the magnitude of fault current which flows in both
directions.

1.4.1 Non-directional Three Over current and One Earth Fault Scheme of
Protection of a “DY1” & “DY11” Transformer’s feeder

If the relays are protecting a transformer feeder, two over current and one earth fault

scheme of protection will give inadequate protection.

Why two over current & one earth fault scheme of Protection is inadequate?

For the “Y-B” fault as shown in figure-2, the directions and magnitudes of fault currents
are shown. If “Y-B” fault occurs on the secondary side of a transformer having vector
group “DY1”, the magnitude of the current will be Iy, 2Iy & Iy in the R, Y & B lines of
primary side respectively. The magnitude of the fault current is maximum in “Y-ph” &
in “Y-ph” there is no over current element in this scheme as shown in figure-3.
The tripping of the circuit breaker will be delayed because of low current (Iy) flows in “R-
ph” & “B-ph”. Thus two over current and one earth fault scheme is inadequate protection
for this particular case.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 23


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

FIGURE:-2

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 24


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Figure-3

RECOMMENDATION:
IT IS BETTER TO PUT 3-OC & 1-E/F SCHEME INSTEAD OF 2-OC & 1-E/F SCHEME
FOR CRITICAL TRANSFORMER WHICH HAVE “DY-1” OR “DY-11” VECTOR GROUP.

RECOMMENDED RELAYS FOR 3-OC & 1-E/F SCHEME:


-ÆCDG-61 & CDG-11 LOWER COST ELECTROMECHANICAL RELAYS
-ÆICM-21 LOWER COST ELECTROMECHANICAL RELAY
-ÆSPAJ-141/142 ABB MAKE NUMERICAL RELAYS
-Æ7SJ61X SIEMENS MAKE NUMERICAL RELAYS
-ÆP124/125/126 ALSTOM MAKE NUMERICAL RELAYS

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 25


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

1.4.2 Non-directional “IDMT” RELAYS WITH “HIGHSET INSTANTANEOUS OVER


CURRENT UNIT” APPLICATION FOR TRANSFORMER PRIMARY FEEDER

Particularly on any Transformer primary feeder required Two Over current elements;

[A] Inverse definite Minimum time lag (IDMTL) Over current Unit

Application of IDMTL Unit is for Backup Protection of any down stream faults

on Secondary side & primary faults on primary side. It is always co-ordinate with

IDMTL relay of transformer secondary feeders for through faults or down

stream faults only.

Here as shown in figure-1, IDMTL unit should be operated as backup protection

on fault (F1 & F2).

[B] Highset or Instantaneous Over current Unit

Application of Highset Unit is for Primary protection of fault on primary side.

Due to the co-ordination problem, operation of IDMTL unit is very sluggish

(take more time) for fault on primary side & it may chance to damage the

transformer to sustain the fault current for longer time (Say 400ms or more). That

is why the highest unit is required to operate instantaneously (Say 50ms) for

primary feeder.

Here as shown in figure-4, highest unit should be operated as primary protection

on fault (F1).

The setting of an instantaneous over current unit on the primary side of transformer
should be little above asymmetrical value of the fault current for three phase fault on
the secondary of the transformer & it should be lesser than minimum value of the
fault current on the primary side.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 26
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

EXAMPLE SETTING OF HIGHSET UNIT:

CTR = 150 / 1A
RELAY TYPE = CDG-61
PLUG SETTING RANGE OF IDMETL UNIT = 0.5 – 2.0A
PLUG SETTING OF IDMTL UNIT = 1.0A
PLUG SETTING RANGE OF HIGHSET UNIT = 2.0 – 20A
FAULT CURRENT (F2) = 40Ka on 415V BUS
“F2” FAULT CURRENT REFLECTED ON 11Kv = 1.509kA

[A]
PLUG SETTING MULTIPLIER DURING “F2” FAULT = 1.509 *1000 / 150
PSM = 10.06

[B]
PLUG SETTING MULTIPLIER DURING “F1” FAULT = 4.000 *1000 / 150
PSM = 26.66

[C]
HIGHSET UNIT SHOULD NOT BE OPERATED ON FAULT “F2”. THEREFORE,
HIGHSET SETTING is > PSM “10.06” other wise it will immediately tripped on
through fault (F2) & isolate whole system.

HIGHSET SETTING is < PSM “26.66”.

RECOMMENDED HIGHSET SETTING = 10.06 * 1.3 (Safety margin) = 13A

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 27


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Figure-4: Example system diagram

RECOMMENDED RELAY (R2) ON PRIMARY SIDE IS “CDG-61 or EQUIVALENT”.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 28


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

1.5 Directional Phase & Earth fault Over current relays:

Directional Over current relays are combinations of directional & over


current units in the same enclosing case. Any combination of directional relay,
inverse-time over current relay, and instantaneous over current relay is available
for phase- or ground-fault protection.

When fault current can flow in both directions through the relay location, it may
be necessary to make the response of the relay directional by the introduction of
a directional control facility. The facility is provided by use of additional voltage
inputs or Polarizing voltage inputs to the relay.

Relays that must respond to power are generally used for protecting against
conditions other than short circuits. Such relays are connected to be polarized by
a voltage of a circuit, and the current connections and the relay characteristics
are chosen so that maximum torque in the relay occurs when unity-power-factor
load is carried by the circuit. The relay will then pick up for power flowing in one
direction through the circuit and will reset for the opposite direction of power flow.

If a single-phase circuit is involved, a directional relay is used having maximum


torque when the relay current is in phase with the relay voltage. The same relay
can be used on a three-phase circuit if the load is sufficiently well balanced; in
that event, the polarizing voltage must be in phase with the current in one of the
three phases at unity-power-factor load. (For simplicity, the term “phase” will be
used frequently where the term “phase conductor” would be more strictly
correct.) Such an in-phase voltage will be available if phase voltage is available;
otherwise, a connection like that in neutral voltage is not available.

Directional Element of OC relay checks the phase angle between current &
voltage and threshold magnitude of current. If the phase angle is reverse & fault
magnitude crosses it’s threshold then it allows to operation of relay.

Application:
• Generally the Protection is applied for parallel feeders, cables, lines
& transformers in ring main system.
• Sometimes it is more helpful while relay co-ordination is not
possible through non-directional IDMTL OC relays.
• Protection should be able to offered with higher sensitivity while
using the directional control. This is not possible with non-
directional OC relays.
• Selective tripping
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 29
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
• Protection is not applied for radial distribution system.

“F1” FAULT FEED BY


“SOURCE – G2

G1

F1

R1 CB

G2

F2
“F2” FAULT FEED BY
“SOURCE – G1
R2

Where,
R1 = Directional OC relay on Line-1
R2 = Directional OC relay on Line-2
F1 = In zone fault of Line-1
F2 = In zone fault of Line-2

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 30


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
Here as shown in figure below; relay R1 is connected on line-1 & relay R2 is
connected on line-2. Relay “R1” seen fault current at “F1” location & “R2” seen
fault current at “F2” location.

1.5.1 CONNECTION FOR DIRECTIONAL OVERCURRENT RELAYS:

Two separate Elements:


1) DIRECTIONAL PHASE FAULT OVER CURRENT ELEMENT
2) DIRECTIONAL EARTH FAULT OVER CURRENT ELEMENT

1.5.1a DIRECTIONAL PHASE FAULT OVER CURRENT ELEMENT:

RELAY CONNECTIONS:

There are mainly three possibilities for a connectional connections of voltage and
current inputs & these connections are dependent on the phase angle, at unity
system power factor, by which the current and voltage applied to the relay are
displaced.

1) 90o RELAY QUADRATURE CONNECTION

“Ia” current & “Vbc” voltage.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 31


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

2) 30o RELAY ADJACENT CONNECTION

“Ia” current & “Vac” voltage.

3) 60o RELAY CONNECTION

“Ia” current & “(Vbc+Vac)” voltage.

Circuit diagram of most commonly method for phase over current element is 90o
quadrature connection as shown below;

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 32


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Fig.5 Connections and vector diagram for a directional relay where phase-to-
neutral voltage is not available.

This is the standard connection for Electromechanical, static, digital or numerical


relays. Depending on the angle by which the applied voltage is shifted to produce
maximum relay sensitivity (the Relay Characteristic Angle, or RCA for numerical
relays & MTA for Electromechanical & static relays ) two types are available.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 33


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

1) 30o MTA LEAD (Maximum torque angle) or 30o RCA LEAD (Relay
characteristic angle)

Fig.6 Vector diagram for the 30° connection (phase A element)

The A phase relay element is supplied with Ia current and Vbc voltage displaced
by 30° in an anti-clockwise direction. In this case, the relay maximum sensitivity
is produced when the current lags the system phase to neutral voltage by 60°.
This connection gives a correct directional tripping zone over the current range of
30° leading to 150° lagging; see Figure 6. The relay sensitivity at unity power
factor is 50% of the relay maximum sensitivity and 86.6% at zero power factor
lagging. This characteristic is recommended when the relay is used for the
protection of plain feeders with the zero sequence source behind the relaying
point.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 34


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

2) 45o MTA LEAD (Maximum torque angle) or 30o RCA LEAD (Relay
characteristic angle)

Fig.7 Vector diagram for the 45° connection (phase A element)

The A phase relay element is supplied with current Ia and voltage Vbc displaced
by 45° in an anti-clockwise direction. The relay maximum sensitivity is produced
when the current lags the system phase to neutral voltage by 45°. This
connection gives a correct directional tripping zone over the current range of 45°
leading to 135° lagging. The relay sensitivity at unity power factor is 70.7% of the
maximum torque and the same at zero power factor lagging; see Figure 7.

This connection is recommended for the protection of transformer feeders or


feeders that have a zero sequence source in front of the relay. It is essential in
the case of parallel transformers or transformer feeders, in order to ensure
correct relay operation for faults beyond the star/delta transformer. This
connection should also be used whenever single-phase directional relays are
applied to a circuit where a current distribution.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 35
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

1.5.2 DIRECTIONAL EARTH FAULT OVER CURRENT ELEMENT:

PRINCILAL:
The directional earth-fault unit measures the neutral current “I0”, the residual
voltage “U0” from open delta PT and the phase angle(pHi) between residual
voltage(U0) and neutral current(I0). An earth-fault stage starts if all of the three
criteria below are fulfilled at the same time:

- the residual voltage U0 exceeds the threshold or set level


- the neutral current I0 exceeds the set value
- if the phase angle between residual voltage and neutral current falls
within the operation area

RELAY CONNECTIONS:

The residual current is extracted as shown in Figure 8. Since this current may be
derived from any phase, in order to obtain a directional response it is necessary
to obtain an appropriate quantity to polarize the relay.

Residual voltage:

A suitable quantity is the residual voltage of the system. This is the vector sum of
the individual phase voltages. If the secondary windings of a three-phase, five
limb voltage transformer or three single-phase units are connected in broken
delta, the voltage developed across its terminals will be the vector sum of the
phase to ground voltages and hence the residual voltage of the system, as
illustrated in Figure 8. The primary star point of the VT must be earthed.
However, a three-phase, three limb VT is not suitable, as there is no path for the
residual magnetic flux.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 36


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Figure 8. Residual voltage connection for Earth fault element by using open delta PT

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 37


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

RESIDUAL CONNECTION DIAGRAM OF “CDD21” EARTH FAULT UNIT:

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 38


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

CHARACTERISTIC ANGLES FOR EARTH FAULT UNIT:

The characteristic angles are varies from relay to relay but, most commonly are
as shown below;

Characteristics are available in ELECTROMECHANICAL & STATIC RELAYS


(CDD21, 2TJM12 etc) are;

1) 30o MTA LAG or 30o RCA LAG FOR SOLIDLY EARTHED SYSTEM
2) 45o MTA LAG or 45o RCA LAG FOR SOLIDLY EARTHED SYSTEM
3) 12.5o MTA or 14o MTA FOR RESISTIVE EARTHED SYSTEM

Characteristics are available in NUMERICAL RELAYS (SPAS348, MICOMP140


etc) are;

1) o to 90 degree RCA LAG.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 39


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

2) WATTMETRIC “Io*COS(pHi)” FOR RESISTIVE EARTHED SYSTEM

If the watt-metric component of zero sequence power is detected in the forward


direction, it indicates a fault on that feeder, while a power in the reverse
direction indicates a fault elsewhere on the system. This method of protection is
more popular than the sensitive earth fault method while system is resistive
earthed, and can provide greater security against false operation due to spurious
CBCT output under non-earth fault conditions.

Watt-metric power is calculated in practice using residual quantities instead of


zero sequence ones. The resulting values are therefore nine times the zero
sequence quantities as the residual values of current and voltage are each three
times the corresponding zero sequence values. The equation used is:

3Vo * 3Io * COS(φ- φc) = Vres * Ires * COS(φ -φc)

where:
Vres = residual voltage
Ires = residual current
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 40
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
Vo = zero sequence voltage
Io = zero sequence current
φ = angle between Vres and Ires
φc = relay characteristic angle setting

3) VARMETRIC “Io*SIN(pHi)” FOR REACTIVE EARTHED SYSTEM

If the Var-metric component of zero sequence power is detected in the forward


direction, it indicates a fault on that feeder, while a power in the reverse
direction indicates a fault elsewhere on the system. This method of protection is
more popular than the sensitive earth fault method while system is reactive
earthed, and can provide greater security against false operation due to spurious
CBCT output under non-earth fault conditions.

Watt-metric power is calculated in practice using residual quantities instead of


zero sequence ones. The resulting values are therefore nine times the zero
sequence quantities as the residual values of current and voltage are each three
times the corresponding zero sequence values. The equation used is:

3Vo * 3Io * SIN(φ- φc) = Vres * Ires * SIN(φ -φc)

where:
Vres = residual voltage
Ires = residual current
Vo = zero sequence voltage
Io = zero sequence current
φ = angle between Vres and Ires
φc = relay characteristic angle setting

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 41


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

1.6 Non-directional stand by earth fault Protection:

• Protection is mainly used for Star-Star transformer or Star side of


Delta-Star transformer.
• Time dial setting of Protection is require to co-ordinate with down
stream feeder’s relay.
• Protection is work as a main protection for small transformer &
backup protection of medium & large transformer.
• CTR is independent of load current.

R-ph

Y-ph

B-ph

IDMT /
DMT E/F
3Iao

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 42


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

1.7 Sensitive Earth fault protection using Core Balance C.T. (CBCTs):

• Normally applied when the earth fault current magnitude is very


very low (10mA or 20mA).
• Where low infeed earth faults are excepted, requiring a very
sensitive earth fault protection, CBCTs can be used in conjunction
with sensitive earth fault relay.

The CBCT surrounds all 3-phases (and neutral also in case of 4-core cables) and
is excited by the primary residual current. Better sensitivities are achieved due to
reduced number of secondary turns since the turns ratio is independent of the
load current. Usually static relays with sensitive setting and low ohmic burdens
should be used with CBCTs to limit the output voltage requirement in view of low
turns ratio.

The CBCTs are used on cables which are usually armoured. The earthing of the
cable sheath/armour should be such that the earth return current carried by the
armour should not offset the earth fault current in the phase conductor as it would
adversely affect the sensitivity. Typical earthing arrangement of the
sheath/armour at load and source end is shown in figure ANNEXURE:-1

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 43


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

1.8 Earth Fault Protection in 3-phase 4-wire System:

• 3-phase 4-wire means, 3-phase + Neutral.


• Normally, it is seen in LT (415V) distribution system.
• 4-CT connections are require because of high unbalanced loads.
• In 3-phase 4-wire system having substantial single phase
unbalanced loads, conventional residually connected earth fault
relays using 3-phase CTs cannot provide adequate sensitive
against earth faults. This is because the earth fault relay is required
to be set above the max. single phase unbalanced current. If a
sensitive E/F setting is desirable, independent of the single phase
unbalanced loads a 4th C.T. in the neutral becomes necessary as
shown in figure below;

E/F O/C

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 44


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

1.9 Non-operation of two O/C and one E/F scheme for Parallel Feeder:

Here as shown in figure below; two O/C and E/F scheme of protection as applied
to a parallel feeder where the phase relays are provided in “R” & “B” phases. Let
us consider “R-Y” phase fault as shown in figure below. The instantaneous
directions of currents are as shown. For the case of the “R-Y” fault as shown in
figure(), the relay in “R-phase” gets practically zero current (if fault current is of
the order of the normal load current of feeder) while “Y-phase” carries practically
double the fault current. The relay “R” will not operate because of insignificance
current flow through its element and since there is no relay element in “Y-phase”
this fault is not cleared.

Solution:
Three O/C & one E/F relay protection scheme take care of this.

IF2

IF2

IF1 IF2

2IF2

IF2 = IF1

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 45


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

2.0 Pilot wire Unit Protection:

There are mainly three types of pilot relaying relays:


1) DC Pilot Wire relay
2) AC Pilot Wire relay

1) DC PILOT WIRE RELAYING SCHEME:


Mainly two schemes:
1) Series DC PILOT wire relaying scheme
2) Shunt DC PILOT wire relaying scheme

1) Series DC Pilot Wire Relaying scheme:


Here as shown in figure below;
Where, D = Poly-phase mho relay (Directional comparison)
T = Tripping relay
O = N/C contact of Over current fault detector
S = Alarm relay for pilot wire open circuit indication

• The supervisory alarm relays (S) are energized through DC circuit.


• Relay (S) de-energized while pilot wire circuit break & it gives an
alarm.

Scheme for Internal Faults:


• When the internal fault occurs, the over current fault detector pick
up.
• Contact “O” will open
• De-energized “S” relay
• Mho relay contact “D” will close while power flow in to the protected
section
• Finally Relay “T” will energize to gives a trip command to their
circuit breakers

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 46


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Scheme for External Faults:


• When external fault occurs then one end Mho relay will energize
but other end relay will not energize because of power flow
direction & it will not gives a trip command to circuit breakers

2) Shunt DC Pilot Wire Relaying Scheme:


Here as shown in figure below;
Where, D = Poly-phase mho relay (Directional comparison)
TC = Tripping relay or trip coil of CB
O = N/C contact of Over current fault detector
B = Blocking relay
PW = Pilot Wire

Scheme for External Faults:


• External faults or Normal condition (Under load), Main relay (both
end) contact “D” will energize because of the power flow
directions
• Blocking relay “B” will pick up
• Now, N/C contact of “B” will open & it blocks the tripping

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 47


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Scheme for Internal Faults:


• Internal fault condition, one end directional comparison relay will
de-energize.
• Now, DC supply at relay “B” will break.
• Relay “B” contact close & it permits a trip command to circuit
breakers.

2) AC Pilot Wire relaying scheme:

The principal of unit protection was first established by merz-price. This


fundamental differential system have formed the basis of many highly developed
protective arrangements for feeders & many plant equipments.

Two forms of Pilot differential schemes are available.


a) Circulating current system
b) Balanced voltage system

2.1 Circulating current system:

In this arrangement current transformers of identical ratio & ratings are provided
at each end of the protected zone & are interconnected by secondary pilot as
shown in figure:2.1 below;

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 48


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

CABLE

CT1 CT2

PILOT CHANNEL

87 R1 87 R2

Figure:2.1

For external faults, the two end CT’s see equal inflow & out flow producing a
circulating current between the CT secondary & Pilots, with no differential current
through the relay. For an in zone fault, however, the secondary current have an
additive polarity & hence the summated current flows through the relay, causing
operation.

In practice, unequal saturation of the CTs can cause increased spill current
through the relay on external faults, producing instability. The problem is normally
overcome by making the relay branch “high impedance” by adding series
stabilizing resistor.

2.2 Balanced voltage system:

In balanced voltage system, CT secondary outputs are opposed for through fault
so that no current flows in series connected relays. An in zone fault however,
produce a circulating current, causing operation. The arrangement is shown in
figure 2.2

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 49


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

CABLE

CT1 CT2

PILOT CHANNEL

87 R1 87 R2

Figure: 2.2

In above arrangement, external faults would, in effect, cause a CT open circuit


conditions, as no secondary current would flow. To avoid excessive saturation of
the core. The core is provided with non-magnetic gaps to absorb the maximum
primary m.m.f. the secondary winding therefore would produce an e.m.f. & can
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 50
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
be regarded a voltage source. The inherent CT error & Pilot capacitance would
produce a substantial spill current through the relay on external fault, causing
instability. The problem is overcome by providing a through current bias
(restraint) which increases the differential pickup, approximately proportional to
the through fault current, there by ensuring stability.

2.3 Summation arrangement:

In three phase system, independent protection can be provided for each phase
using phase by phase comparison of the two end currents. This would however a
require a minimum for core pilot adding up to the cost. An alternative is to
combine the separate phase current in to a single quantity for comparison over a
pair of Pilots. This achieved by using summation current transformer. A typical
summation CT is shown in figure 2.3

R-ph

Y-ph

B-ph

The interface section of the summation winding (i.e. A-B & B-C) usually have
equal number of turns & the neutral end winding (C-N) having greater number of
turns. The above summation arrangement would produce output for balanced as
well as un balanced faults. However, the relay offers a different sensitive for
different types of faults depending upon the phases involved. In the summation
arrangement illustrated, the associated relay will have highest sensitive for A-C &
A-N faults.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 51


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
2.4 Supervision of Pilots:

The pilot circuits are subjected to various hazards, which can cause open circuit
or short circuit of the pilot cores. While overhead pilots are vulnerable to storms,
buried pilots may be damaged during excavation. The pilot failure may lead to
either mal operation or non-operation of the protection and hence continuous
supervision of the healthiness of the pilots becomes necessary.

This is achieved by injecting a small d.c. current through the pilot from one end
and monitoring its presence at the other end by energizing an auxiliary relay. The
auxiliary relay resets in the event of any discrepancy in the pilots and sounds an
alarm. A small time delay is introduced to prevent transient operation due to
primary system faults causing momentary dip in the auxiliary supply.

Over current check feature may also be incorporated to prevent tripping on load
in the event of a pilot open circuit condition as it may lead to instability. A typical
pilot supervision arrangement is shown in figure-ANAXURE-2.

The supervision arrangement detects any discrepancy in the pilot including open
circuit, short circuit & cross pilot conditions.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 52


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

“MULTIPLICATION OF THIS DOCUMENT IS STRICTLY PROHIBITED”

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 53


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

TABLE OF CONTENTS:

TITLE Sr.No. PAGE NUMBER


Introduction 3.1 55
Parameter Conversions 3.2 55
Two winding Transformer 3.2.1 58
Parameter conversions
3-winding Transformer 3.2.2 62
Parameter conversions
Transmission line 3.2.3 66
Parameter conversions
Motor Parameter 3.2.4 67
conversions
Series Reactor Parameter 3.2.5 70
conversions
Shunt Capacitor Parameter 3.2.6 70
conversions
Shunt Reactor Parameter 3.2.7 71
conversions
Series Capacitor Parameter 3.2.8 71
conversions
Generator Parameter 3.2.9 71
conversions
Perunit & Percentage Qty 3.2.10 76
Basic consideration for 3.3 78
short circuit study
Asymmetrical fault current 3.3.1 79
3-ph SC on unloaded 3.3.2 81
synchronous m/c
Symmetrical fault current 3.3.3 84
Effect of low zero seq. 3.3.4 88
impedance of generators
ANSI/IEEE calculations 3.3.5 94
Importance of X/R ratio 3.3.6 102
PU method for SC 3.3.7.1 108
calculations
Ohmic method for SC 3.3.7.2 125
calculations

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 54


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

TITLE Sr.No. PAGE NUMBER


Point-to-Point method for 3.3.7.3 134
SC calculations
1-ph SC current for 1-ph TR 3.3.7.4 139
system
Introduction relay co- 3.3.7.5 149
ordination study
Functional characteristics 3.3.7.6 154
Criterias for Pickup setting 3.3.7.7 157
& time dial
Data required for O/C & E/F 3.3.7.8 159
relay co-ordination
Example for Phase fault 3.3.7.9 162
relay setting
Example calculation for 3.3.3.10 170
DMT relays

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 55


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

3.1 INTRODUCTION:
Successful Operation of a power system depends largely on the engineer’s
ability to provide reliable and uninterrupted service to loads. The reliability of the
power supply implies much more than merely being available. Ideally, the loads
must be fed at constant voltage and frequency at all times. In practical terms this
means that consumer’s equipment may operate satisfactorily. For example, a
drop in voltage of 10-15% or a reduction of the system frequency of only a few
hertz may lead to stalling of the motor loads on the system.

As electrical utilities have grown in size, and the number of interconnections has
increased, planning for future expansion has become increasingly complex. The
increasing cost of additions and modifications has made it imperative that utilities
consider a range of design options, and perform detailed studies of the effects on
the system of each option, based on the number of assumptions: like normal and
abnormal operating conditions, peak and off-peak loadings, and present and
future years of handled.

Future transmission and distribution systems will be far more complex than those
of today. This means that the power system planner’s task will be more complex.
If the systems being planned are to be optional with respect to construction cost,
performance, and operating efficiency, better planning tools are required.

3.2 Parameter Conversion:


Power transmission lines are operated at voltage levels where kilovolts is the
most convenient unit to express voltage. The amount of power transmitted is in
terms of kilowatts or megawatts and kilo amperes or mega amperes. However
the quantities, current and Ohms are often expressed as a percent or per unit of
base value. The per unit value of any quantity is defined as the ratio of the
quantity to its base value expressed as a decimal. Both the per unit (p.u.) and
percent methods of calculation are simpler than the use of actual amperes,
Ohms, and voltage values.

The per unit method has an advantage over the percent method because the
product of two quantities expressed in per unit is expressed in per unit itself, but
the product of two quantities expressed in percent must be divided by 100 to
obtain the result in percent.

The per unit value of a line to neutral voltage on the line to neutral voltage base
is equal to the per unit value of the line to line voltage at the same point on the
line to line voltage base if the system is balanced. Similarly, the three-phase kVA
is three times the kVA/phase and the three-phase kVA base is three times the

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 56


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
base kVA per phase. Therefore the per unit value of the three-phase kVA on the
three-phase kVA base is identical to the per unit value of the kVA per phase on
the kVA per phase base.

Base impedance and base current value can be computed directly from three-
phase values of base kilovolts and base kilo-amperes.

Base Current = {Base kVA (3-ph) / 1.7325*Base kV}

Where, Base kV is the line-to-line voltage.

Base Z = { (Base kV / 1.7325)2*1000 / (Base kVA) / 1.7325 }

Base Z = { (Base kV)2 / (Base MVA) }

Sometimes the per unit impedance of a component of a system is expressed on


a base other than the one selected as base for the part of the system in which
the component is located. Since all impedances in any one part of a system must
be expressed on the same impedance base when making computations, it is
necessary to have a means of converting per unit impedances from one base to
another. The per unit impedance is given by following equation;

Per unit Z = { ( Actual Z in Ohms*Base MVA ) / ( Base kV )2 }

Which shows that per unit impedance is directly proportional to “base MVA” and
inversely proportional to the square of the base voltage. Therefore, to change
from per unit impedance on a given base to per unit impedance on a new base,
the following equation is used,
Per unit Znew = ( Per unit Zgiven )*( Base kVgiven / Base kVnew )2*( Base MVAnew / Base MKVAgiven )

The Ohmic values of resistance and leakage reactance of a transformer depends


on whether they are measured from the LT side or HT side of a transformer. If
they are expressed in “p.u.”, the base MVA rating of the transformer which is
same as referred from HT side or LT side. The base kV is selected as the voltage
of LT winding, if the ohmic values are referring to LT side, else it is selected as
voltage of HT winding, if the ohmic values are referring to HT side of transformer.
Whereas the “PU” values remains same regardless of whether they are
determined from HT side or LT side.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 57


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

The advantages of the “PU” method are;


• The “PU” impedance of machines of same type and widely different ratings
usually lie within a narrow range, although the ohmic values differ for machines
of different ratings. For this reason, when the impedance is not known definitely,
it is generally possible to select from the tabulated values a “PU” impedance
which will be reasonably correct.

• When impedance in ohms is specified in an equivalent circuit, each impedance


must be referred to the same circuit by multiplying it by the square of the ratio of
rated voltages of the two sides of a transformer. The “PU” impedance, once
expressed in proper base, remains same either referring from HT side or LT side.

• The way in which transformers are connected in three phase circuits does not
affect the “PU” impedances of the equivalent circuit, although the transformer
connection does determine the relation between the voltage bases on the two
sides of the transformer.

3.2.1 Two winding Transformer Parameter Conversions:


Manufacturers usually specify the impedance of a piece of apparatus in percent
or per on the base of the nameplate rating. It is converted to common base using
MVA rating and the voltage rating of transformer. Sometimes the voltage ratings
of the transformer does not match exactly with the base voltage on their
respective sides, in case the transformer parameters are converted to the base
values of voltage and MVA. To begin with, assuming that transformer tap is on
primary side ( HV side ), the given impedance is converted to common base as;

Znewpu = { (Zoldpu)*(MVAnew / MVAold)*(Rated kVsec / Base kVsec)2 }

If the transformer parameters are given in actual units (ohms). Then the values
are converted to common base as;

Zpu = (Zohms)*(Base MVA / BasekV2)

Base kV is the voltage referred to the side at which measurements are made.

The transformer R/X ratio is used to separate the transformer resistance and
reactance values from the impedance. If number of units are in parallel then the
effective equivalent impedance is computed by dividing the impedance by units.

X = [ {√Z2 / { 1 + ( R / X )2 }} / Units ]

R = (X)*(R / X)

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 58


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
The minimum tap value is computed as;

Tapmin(pu) = [ { VTap min kV / Base kVpri }*{ Base kVsec / Rated kVsec } ]

The maximum tap value is computed as;

Tapmax(pu) = [ { VTap max kV / Base kVpri }*{ Base kVsec / Rated kVsec } ]

The tap step value (pu) is computed as;

Tap step(pu) = [ { VTap max kV – VTap min kV } / { NTap max – NTap min } ]

Nominal tap value (pu) is computed as;

Tap nom = [ { VTap min kV + { ( NTap nom – NTap min )*Tap step kV } } ]*[ Base kV sec / Rated kV sec ]

The vector groups shows the connection of phases of two windings of a


transformer and the numerical index for the phase displacement of the vectors of
the two star-voltages. The numerical index shows by what multiples of 30o the
low voltage vector lags ( anti-clockwise rotation of vectors ) behind the high
voltage vector with the corresponding terminal designation. For example the
groups are interpreted as;

• Vector Group Dy5 – High voltage in Delta and low voltage in star connection.
• Vector Group Yz11 – High voltage in Star and low voltage in zigzag connection.

The transformer vector group information is required for 3-phase load flow and
unbalanced fault studies. The different vector groups used are;

• Star with neutral isolated.


• Star with neutral grounded.
• Star with neutral impedance.
• Delta connected.

The zero sequence impedances differ greatly depending on the type of


connection and the construction of the transformers. Conductors connected to
transformer windings with delta connection or with star with an insulated neutral
point cannot carry a zero sequence current. The zero sequence impedance is
therefore infinite. When the neutral point of star winding is earthed or connected,
zero sequence can flow in the associated system. If the transformer is star

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 59


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
connected on primary side and delta connected on secondary side, then shunt
impedance will exists from primary node to ground and vice-versa.

The neutral impedance given in ohms, converted to common base as;

Base Zpri = ( Base kVpri2 / Base MVA ) in Ohm

Base Zsec = ( Base kVsec2 / Base MVA ) in Ohm

Rpu neutral pri = ( ROhm neutral pri / Base Z pri )

Rpu neutral sec = ( ROhms neutral sec / Base Zsec )

EXAMPLE:
Rated MVA = 315
Primary Voltage = 420 kV
Secondary Voltage = 240 kV
Positive sequence impedance = 0.125PU or 12.5%
Zero sequence impedance = 0.100PU or 10%
TAPmin = 1.0
TAPmax = 17.0
TAPnormal = 12.0
Minimum TAP Voltage = 360 kV
Maximum TAP Voltage = 440 kV
Neutral Rpri = Rsec = 2.0 Ohm.
Connection = YnYn0

The transformer is connected to a bus on HT side with voltage 400 kV and on LT side is
connected to a bus with voltage 220 kV. Hence primary base voltage = 400 kV and the
secondary base voltage is 220 kV.
The common base MVA = 100

Zpositive seq. in PU = (%Z / 100)*(Base MVA / Rated MVA)*(Rated kV / Base kV)2


= (12.5 / 100)*(100 / 315)*(240/220)2
= 0.047225 PU

Xpositive seq. in PU = [ {√Z2 / { 1 + ( R / X )2 }} / Units ]


= [ {√(0.047225)2 } / { 1 + (0.05)2 } ]
= 0.047166 PU

Rpositive seq. in PU = (0.04766 * 0.05)


= 0.002358 PU

Zzero seq. in PU = (%Z / 100)*(Base MVA / Rated MVA)*(Rated kV / Base kV)2


= (10 / 100)*(100 / 315)*(240/220)2

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 60


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
= 0.0377804 PU

Xzero seq. in PU = [ {√Z2 / { 1 + ( R / X )2 }} / Units ]


= [ {√(0.0377804)2 } / { 1 + (0.05)2 } ]
= 0.0377332 PU

Rzero seq. in PU = (0.0377332 * 0.05)


= 0.00188666 PU

Tapmin(pu) = [ { VTap min kV / Base kVpri }*{ Base kVsec / Rated kVsec } ]
= [ { 360 / 400 }*{ 220 / 240 } ]
= 0.82500 PU

Tapmax(pu) = [ { VTap max kV / Base kVpri }*{ Base kVsec / Rated kVsec } ]
= [ { 440 / 400 }*{ 220 / 240 } ]
= 1.00833 PU

Tap step(pu) = [ { VTap max kV – VTap min kV } / { NTap max – NTap min } ]
= [ { 440 – 360 } / { (17 – 1)*400 } ]
= 0.0125 PU

Tap nom = [ { VTap min kV + { ( NTap nom – NTap min )*Tap step kV } } ]*[ Base kV sec / Rated kV sec ]
= [ { 360 + { (12 – 1)*5 } } / 400 ]*[ 220 / 240 ]
= 0.95104 PU
The neutral impedance values are computed as;

Base Zpri = ( Base kVpri2 / Base MVA ) in Ohm


= ( 400 )2 / 100
= 1600 Ohm.

Base Zsec = ( Base kVsec2 / Base MVA ) in Ohm


= ( 220 )2 / 100
= 484 Ohm.

Rpu neutral pri = ( ROhm neutral pri / Base Z pri )


= ( 2 / 1600 )
= 0.00125 PU

Rpu neutral sec = ( ROhms neutral sec / Base Zsec )


= ( 2 / 484 )
= 0.004132 PU

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 61


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
3.2.2 Three Winding Transformer Parameter Conversions:
The MVA rating of a two-winding transformer is same on primary and secondary
side, whereas all the three windings of a three winding transformer may have
different MVA ratings. The impedance of each winding of a three-winding
transformer may be given in percent or PU based on the rating of its own
winding. The transformer impedance values, which are measured by short circuit
test, are

• Impedance measured in primary with secondary short circuited and tertiary open
(Z ps).
• Impedance measured in primary with tertiary short circuited and secondary open
(Z pt).
• Impedance measured in secondary with tertiary short circuited and primary open
(Z st).

If the three impedances measured in Ohms are referred to the voltage of one of
the windings, the impedance of each separate winding referred to that same
winding are related to the measured impedances as;

Z ps = Zp + Zs
Z pt = Zp + Zt
Zst = Zs + Zt

Where Zp, Zs, and Zt are the impedance of primary, secondary and tertiary windings
referred to primary circuit. If Zps, Zpt, Zst are the measured impedances refer to
primary circuit, the real and reactive parts are separated as;

X ps = [ { √Z ps2 } / {( R / X ps )2 + 1} ] / Units

X pt = [ { √Z pt2 } / {( R / X pt )2 + 1} ] / Units

X st = [ { √Z st2 } / {( R / X st )2 + 1} ] / Units

Solving the above impedance simultaneous equations for Rp, Rs, & Rt, Xp, Xs & Xt
yields,

Rp = [ R ps + R pt – R st ] / 2

Rs = [ R ps + R st – R pt ] / 2

Rt = [ R pt + R st – R ps ] / 2

Xp = [ X ps + X pt – X st ] / 2
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 62
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Xs = [ X ps + X st – X pt ] / 2

Xt = [ X pt + X st – X ps ] / 2

The impedance of the three windings are connected in star (Y) to represent the single
phase equivalent circuit of the three winding transformer. Since the ohmic values of the
impedances must be referred to the same voltage, it follows that conversion to PU
requires the same MVA base for all the three circuits and requires voltage bases in three
circuits of the transformer.
The neutral impedances, if present is converted to per unit values on common base as;

Base Z pri = ( Base kV pri )2 / Base MVA

Base Z sec = ( Base kV sec )2 / Base MVA

Base Z ter = ( Base kV ter )2 / Base MVA

Rpu neutral pri = Rohm neural pri / Base Z pri

Rpu neutral sec = Rohm neutral sec / Base Z sec

Rpu neutral ter = Rohm neutral ter / Base Z ter

EXAMPLE:
Rated Primary MVA = 15
Primary Voltage = 66 kV
Rated Secondary MVA = 10
Secondary Voltage = 13.2 kV
Rated tertiary MVA = 5.0
Tertiary Voltage = 2.3 kV
Zps = 7% on 15 MVA, 66 kV
RX-Ratio-ps = 0.05
Zpt = 9% on 15 MVA, 66 kV
RX-Ratio-pt = 0.05
Zst = 8% on 15 MVA, 66 kV
RX-Ratio-st = 0.05
TAPmin = 1.0
TAPmax = 17.0
TAPnormal = 12.0
Minimum TAP Voltage = 59.4 kV
Maximum TAP Voltage = 72.6 kV
Rpri = Rsec = Rtertiary = 2.0 Ohm.
Connection = YYnYn0
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 63
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Assuming the common base values as 15MVA and 66 kV. First step is to convert
all the impedance to common base on primary side. Zps & Zpt are measured at
primary ratings, need no conversion while the Zst measured at different ratings it
is converted to common base values as;

Zst in PU = (%Z / 100)*(Base MVA / Rated MVA)*(Rated kV / Base kV)2


= (8.0 / 100)*(15 / 10)*(13.2 / 13.2 )2
= 0.12 PU

Zps in PU = (%Z / 100)*(Base MVA / Rated MVA)*(Rated kV / Base kV)2


= (7.0 / 100)*(15 / 15)*(13.2 / 13.2 )2
= 0.07 PU

Zpt in PU = (%Z / 100)*(Base MVA / Rated MVA)*(Rated kV / Base kV)2


= (9.0 / 100)*(15 / 15)*(13.2 / 13.2 )2
= 0.09 PU

X ps = [ { √Z ps2 } / {( R / X ps )2 + 1} ] / Units
= [ { √(0.07)2 } / {( 0.05 )2 + 1} ] / Units
= 0.06991 PU

X pt = [ { √Z pt2 } / {( R / X pt )2 + 1} ] / Units
= [ { √(0.09)2 } / {(0.05)2 + 1} ] / Units
= 0.0898877 PU

X st = [ { √Z st2 } / {( R / X st )2 + 1} ] / Units
= [ { √(0.12)2 } / {(0.05)2 + 1} ] / Units
= 0.1198503 PU

Rst = Xst * RXRatio-st


= 0.1198503 * 0.05
= 0.0059925 PU

Rps = Xps * RXRatio-ps


= 0.06991 * 0.05
= 0.0034955 PU

Rpt = Xpt * RXRatio-pt


= 0.0898877 * 0.05
= 0.00449438 PU

Rp = [ R ps + R pt – R st ] / 2

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 64


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
= [ 0.0034955 + 0.00449438 – 0.0059925 ] / 2
= 0.00099865 PU

Rs = [ R ps + R st – R pt ] / 2
= [ 0.0034955 + 0.0059925 – 0.00449438 ] / 2
= 0.00249685 PU

Rt = [ R pt + R st – R ps ] / 2
= [ 0.00449438 + 0.0059925 – 0.0034955 ] / 2
= 0.00349565 PU

Xp = [ X ps + X pt – X st ] / 2
= [ 0.06991 + 0.0898877 – 0.1198503 ] / 2
= 0.0199737 PU

Xs = [ X ps + X st – X pt ] / 2
= [ 0.06991 + 0.1198503 – 0.0898877 ] / 2
= 0.0499363 PU

Xt = [ X pt + X st – X ps ] / 2
= [ 0.0898877 + 0.1198503 – 0.06991 ] / 2
= 0.069914 PU

Tapmin(pu) = [ { VTap min kV / Base kVpri }*{ Base kVsec / Rated kVsec } ]
= [ { 59.4 / 66 }*{ 13.2 / 13.2 } ]
= 0.9 PU

Tapmax(pu) = [ { VTap max kV / Base kVpri }*{ Base kVsec / Rated kVsec } ]
= [ { 72.6 / 66 }*{ 13.2 / 13.2 } ]
= 1.10 PU

Tap step(pu) = [ { VTap max kV – VTap min kV } / { NTap max – NTap min } ]
= [ { 72.6 – 59.4 } / { (17 – 1)*66 } ]
= 0.0125 PU

Tap nom = [ { VTap min kV + { ( NTap nom – NTap min )*Tap step kV } } ]*[ Base kV sec / Rated kV sec ]
= [ { 59.4 + { (12 – 1)*0.825 } } / 66 ]*[ 13.2 / 13.2 ]
= 1.0375 PU

The neutral impedance values are computed as;

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 65


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
Base Zpri = ( Base kVpri2 / Base MVA ) in Ohm
= ( 66 )2 / 15
= 290.4 Ohm.

Base Zsec = ( Base kVsec2 / Base MVA ) in Ohm


= ( 13.2 )2 / 15
= 11.616 Ohm.

Base Zter = ( Base kVter2 / Base MVA ) in Ohm


= ( 2.3 )2 / 15
= 0.35267 Ohm.

Rpu neutral pri = ( ROhm neutral pri / Base Z pri )


= ( 2 / 290.4 )
= 0.00688 PU

Rpu neutral sec = ( ROhms neutral sec / Base Zsec )


= ( 2 / 11.616 )
= 0.172176 PU

Rpu neutral ter = ( ROhms neutral ter / Base Zter )


= ( 2 / 0.35267 )
= 5.671 PU

3.2.3 Transmission Line Parameter Conversions:


For a transmission line, line resistance, reactance and the susceptance of the
line are given in actual units (Ohms) per km length of the line per circuit. Zero
sequence impedance denotes the impedance of zero sequence system of a
three phase line per phase in which equal and in-phase currents are flowing
through the three phase conductors of the system. The operative zero sequence
impedance is affected by, among other things, the electrical conductivity of the
earth and the presence of earth wires. The same formula are used for both
positive and zero sequence parameter conversion. The line positive sequence
parameters are converted to per unit on common base values as;

Base Z = ( Base kV )2 / Base MVA

R1pu = ( R1ohm / Base Z )*( Length / Circuits )

X1pu = ( X1ohm / Base Z )*( Length / Circuits )

B1pu = ( B1mho * Base Z )*( Length * Circuits )

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 66


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

EXAMPLE:
Number of Circuits = 1.0
Length of Line = 181km.
Positive sequence R = 0.0288864 Ohm/km.
Zero sequence R = 0.072216 Ohm/km.
Positive sequence X = 0.32704 Ohm/km.
Zero sequence X = 0.8176 Ohm/km.
Positive sequence B = 1.78087E-06 mho/km.
Zero sequence B = 1.52374E-06 mho/km.
Common base MVA = 100 and Base voltage = 400.0 kV.

Base Z = ( Base kV )2 / Base MVA


= ( 400 )2 / 100
= 1600 Ohm.

R1pos. pu = ( R1ohm / Base Z )*( Length / Circuits )


= ( 0.0288864 / 1600 )*(181 / 1)
= 0.003267 PU

X1pos.pu = ( X1ohm / Base Z )*( Length / Circuits )


= ( 0.32704 / 1600 )*(181 / 1)
= 0.03699 PU

B1pos.pu = ( B1mho * Base Z )*( Length * Circuits )


= (1.78087E-06 * 1600)*(181*1)
= 0.51574 PU

R1zero. pu = ( R0ohm / Base Z )*( Length / Circuits )


= ( 0.072216 / 1600 )*(181 / 1)
= 0.008169 PU

X1zero.pu = ( X0ohm / Base Z )*( Length / Circuits )


= ( 0.8176 / 1600 )*(181 / 1)
= 0.09249 PU

B1zero.pu = ( B0mho * Base Z )*( Length * Circuits )


= (1.52374E-06 * 1600)*(181*1)
= 0.44127 PU

3.2.4 Motor Parameter Conversions:


The induction motor parameters are given in PU on its own rating. The motor is
represented as a shunt impedance between node to which motor is connected
and ground. The shunt impedance value is obtained after simplifying the exact
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 67
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
equivalent circuit as shown in fig below. The motor parameters are converted to
common base by using formula.

Rmotor = Rold ( Base kV old / Base kV new )2*( MVA new / MVA old )

Rmotor = Rmotor / Units

Xmotor = Xold ( Base kV old / Base kV new )2*(MVA new / MVA old )

Xmotor = Xmotor / Units

By using above formula, stator resistance, rotor resistance, stator reactance,


rotor reactance and magnetizing reactance are converted to common base. On
simplifying the equivalent circuit, we obtain equations for the equivalent
resistance and reactance as denoted below;

Rmotorq = Rstator + [ { ( Slip * Rrotor * ( Xmag )2 ) } / { Rrotor2 + ( Slip2 ( Xrotor + Xmag )2 } ]


2 2 2 2 2
Xmotorq = Xstator + [ ( Rrotor *Xmag ) + ( Slip *Xrotor*Xmag ( Xrotor + Xmag ) ) ] / [ Rrotor + ( Slip ( Xrotor + Xmag ) ) ]

Type of motor winding connection is used for zero sequence network calculations
only. The motor neutral impedance, value is converted to common base and 3-
times of it is added to the zero sequence impedance value of the motor to get the
effective zero sequence impedance.

EXAMPLE:
Number of Units = 1.0
Voltage Rating = 2.3 kV
Rating = 1.6785 MW, 0.8 P.F.
Stator resistance = 0.029 Ohm.
Stator reactance = 0.226 Ohm.
Rotor resistance = 0.022 Ohm.
Rotor reactance = 0.226 Ohm.
Magnetizing reactance = 13.04 Ohm.
Winding type = Delta.
Common base = 100 MVA and base volt = 2.3 kV.
Motor Zbase = (Base kV)2 / (Base MVA)

= (2.3)2 / (2.098125)

= 2.5213 Ohm.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 68


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
Rstator = Rold ( Base kV old / Base kV new )2*( MVA new / MVA old )

= (0.029 / 2.5213)*( 2.3 / 2.3 )2 *(100 / 2.098125)

= 0.5482 PU.
Xstator = Xold ( Base kV old / Base kV new )2*(MVA new / MVA old )

= (0.226 / 2.5213)*( 2.3 / 2.3 )2 *(100 / 2.098125)

= 4.2722 PU.
Rrotor = Rold ( Base kV old / Base kV new )2*( MVA new / MVA old )

= (0.022 / 2.5213)*( 2.3 / 2.3 )2 *(100 / 2.098125)

= 0.41588 PU.
Xrotor = Xold ( Base kV old / Base kV new )2*(MVA new / MVA old )

= (0.226 / 2.5213)*( 2.3 / 2.3 )2 *(100 / 2.098125)

= 4.2722 PU.
Xmagnetizing = Xold ( Base kV old / Base kV new )2*(MVA new / MVA old )

= (13.04 / 2.5213)*( 2.3 / 2.3 )2 *(100 / 2.098125)

= 246.504 PU.
Rmotorq = Rstator + [ { ( Slip * Rrotor * ( Xmag )2 ) } / { Rrotor2 + ( Slip2 ( Xrotor + Xmag )2 } ]
= 0.5482 + [{ (0.0077*0.41588*(246.504)2 )} / {(0.41588)2 + ( (0.0077)2 ( 4.2722 + 246.504)2 }]
= 50.010 PU.

Xmotorq = Xstator + [ ( Rrotor2*Xmag ) + ( Slip2*Xrotor*Xmag ( Xrotor + Xmag ) ) ] / [ Rrotor2 + ( Slip2 ( Xrotor + Xmag )2 ) ]

= 4.2722+[ (0.415882*246.504)+(0.00772*4.2722*246.504 (4.2722+246.504))] / [ 0.415882(4.2722+246.504)2) ]

= 19.215899 PU.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 69


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
3.2.5 Series Reactor Parameter Conversions:
The reactors are used as branch elements to limit the current during fault
conditions, to cyclic voltage fluctuations caused by repetitive loads (Cyclic loads)
in conjunction with condensers and to limit the motor starting currents. The series
reactor resistance and reactance values are given in PU on its own rating. The
values are converted to common base as:

R new = (R old)* (Base kV old / Base kV new)2* (MVA new / MVA old)

X new = (X old)* (Base kV old / Base kV new)2* (MVA new / MVA old)

EXAMPLE:
Rated Voltage = 11 kV.
Rated Current = 262 Amp.
kVar = 256.

Reactor MVA = 1.7325 * 11*262 = 5 MVA

X in Ohm = (kVar) / (3* I2)


= (256*1000) / (3*2622)
= 1.2431 Ohm/Phase

X in PU = (1.2431 *5) / (11)2


= 0.0514 PU

Common base MVA = 100, Base Voltage = 11kV.

Rreactor = 0.0 PU.

Xreactor = (0.514)*(100/5)*(11/11)2
= 1.028 PU

3.2.6 Shunt Capacitor Parameter Conversions:


The shunt capacitor banks are used extensively to correct power factors and as
results, improve voltage regulation at the point of connection. The shunt
capacitor conductance and susceptance values are given in PU on its own rating.
The values are converted to common base as:

G new = (G old)* (Base kV new / Base kV old)2 * (MVA old / MVA new)

B new = (B old)* (Base kV new / Base kV old)2 * (MVA old / MVA new)

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 70


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
3.2.7 Series Capacitor Parameter Conversions:
The series capacitors are sometimes used on transmission and distribution lines
to compensate for the inductive reactance drop or to improve the system stability
by increasing the amount of power that can be transmitted on tie lines. The
series capacitor conductance and susceptance values are given in PU on its own
rating. The values are converted to common base as:

G new = (G old)* (Base kV new / Base kV old)2 * (MVA old / MVA new)

All series elements are molded in impedance form, hence the parameters are
converted to impedance form by inverting the admittance.

R pu = (G pu) / (G2 pu + B2 pu)

X pu = (B pu) / (G2 pu + B2 pu)

3.2.8 Shunt Reactor Parameter Conversions:


The shunt reactor resistance and reactance values are given in PU on its own
rating. The values are converted to common base as:

R new = (R old)* (Base kV old / Base kV new)2* (MVA new / MVA old)

X new = (X old)* (Base kV old / Base kV new)2* (MVA new / MVA old)

All shunt elements are molded in admittance form; its data is converted to
admittance form by using the formula-

G pu = (R pu) / (R2 pu + X2 pu)

B pu = (X pu) / (R2 pu + X2 pu)

3.2.9 Generator Parameter Conversions:


The generator resistance, direct axis sub-transient & transient reactance,
quadrature axis sub-transient & transient reactance etc., is specified in PU on its
own rating. The reactance values are converted to PU on common base as:

R gen = (R old)* (Base kV old / Base kV new)2* (MVA new / MVA old)

R gen = (R gen) / Units

X gen = (X old)* (Base kV old / Base kV new)2* (MVA new / MVA old)
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 71
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

X gen = (X gen) / Units

X 2(Neg.) = (X d” + X q”) / 2

T d’ = (X d” / Xd)* T do’, T do’ = Transient OC time constant

T q’ = T d’ / 2

T a = (X 2(Neg.)) / (w*Ra), Ra = Stator Resistance in Ohm.

By using the above formula, the Sub-transient, Transient, & Steady-state direct
axis reactance, negative sequence reactance and the zero sequence reactance
values are converted to PU on common base.

The generator specified voltage is in actual units (kV). It is converted to PU by


dividing it by the base voltage.

V gen pu = (V gen kV) / (Base kV)

Type of generator winding connection is used for zero sequence network


calculations only. The neutral impedance is given in actual units (Ohms), it is
converted to PU on common base as:

Base Z = (Base kV)2 / (Base MVA)

R neutral pu = (R neutral Ohms) / (Base Z)

The generator neutral impedance value is converted to common base and 3


times of it is added to the zero sequence impedance value of the generator to get
the effective zero sequence impedance.

Tdo’ = No load time constant determines the excitation and de-magnetisation with Open
stator circuit.

Td” = Sub-transient time constant determines the excitation and de-magnetization with
three phase short circuit.
Td’ = Transient time constant determines the excitation and de-magnetization with three
phase short circuit.

EXAMPLE:
Number of units = 1.0
Voltage Rating = 11.0 kV
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 72
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
Rated MVA = 260 MVA
Positive sequence resistance = 0.00154 PU.
Steady state direct axis reactance = 2.22 PU.
Transient direct axis reactance = 0.265 PU.
Negative sequence reactance = 0.225 PU.
Zero sequence reactance = 0.125 PU.
Winding connection = Star connection.
Neutral resistance = 2.0 Ohms.
Neutral reactance = 0.0 Ohms.

Common base = 100 MVA and base voltage = 11 kV.

R gen = (R old)* (Base kV old / Base kV new)2* (MVA new / MVA old)
= (0.00154)*(11 / 11)2* (100 / 260)
= 0.00059 PU.

X gen pos. = (X old)* (Base kV old / Base kV new)2* (MVA new / MVA old)
= (2.22)*(11 / 11)2* (100 / 260)
= 0.8538 PU.

X gen Neg. = (X old)* (Base kV old / Base kV new)2* (MVA new / MVA old)
= (0.225)*(11 / 11)2* (100 / 260)
= 0.08654 PU

X d’ = (X old)* (Base kV old / Base kV new)2* (MVA new / MVA old)


= (0.265)*(11 / 11)2* (100 / 260)
= 0.10192 PU.

Base Impedance = (Base Voltage)2 / Base MVA


= (11)2 / 100
= 3.24 Ohm.

Generator technical data-sheet of Brush Electric Machine, USA are as shown


below which is installed in Search-Chem industries ltd, Bharuch;

Rated MVA = 35
Terminal Voltage = 11.0kV
Frequency = 50Hz
Speed = 3000RPM
Power Factor = 0.85
Applicable national standard = IEC 34-3
Rated Air inlet temperature = 15 deg.
Unsaturated Direct axis Synchronous Reactance (Xd) = 243.9%
Saturated Direct axis Synchronous Reactance (Xd) = 243.9%
Saturated Direct axis Transient Reactance (Xd’) = 25.1%
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 73
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
Unsaturated Direct axis Transient Reactance (Xd’) = 33.9%
Saturated Direct axis Sub-transient Reactance (Xd”) = 18%
Unsaturated Direct axis Sub-transient Reactance (Xd”) = 24.1%
Unsaturated Quadrature axis Synchronous Reactance (Xq) = 224.1%
Saturated Quadrature axis Synchronous Reactance (Xq) = 224.1%
Unsaturated Quadrature axis Transient Reactance (Xq’) = 48.2%
Saturated Quadrature axis Sub-transient Reactance (Xq”) = 17.7%
Unsaturated Quadrature axis Sub-transient Reactance (Xq”) = 24.1%
Saturated Negative sequence Reactance (X2) = 17.3%
Unsaturated Negative sequence Reactance (X2) = 23.2%
Saturated Zero Sequence Reactance (X0) = 10.2%
Unsaturated Zero Sequence Reactance (X0) = 12.9%
Leakage Reactance, Overexcited (XLM,OEX) = 21.2%
Leakage Reactance, Underexcited (XLM,UEX) = 21.2%
Short Circuit Ratio = 0.43
Open Circuit Time constant (Td0’) = 6.016second
3-ph Short-circuit transient time constant (Td3’) = 0.620second
Line to Line short-circuit transient time constant (Td2’) = 0.975second
Line to Neutral short-circuit transient time constant (Td1’) = 1.165second
Short-circuit sub-transient time constant (Td”) = 0.015second
Open Circuit Sub-transient time constant (Td0”) = 0.021second
Open Circuit Time constant (Tq0’) = 0.522second
3-ph Short-circuit transient time constant (Tq’) = 0.522second
Short-circuit sub-transient time constant (Tq”) = 0.015second
Open Circuit Sub-transient time constant (Tq0”) = 0.041second

Generator technical data-sheet of Brush Electric Machine, USA are as shown


below which is installed in Search-Chem industries ltd, Bharuch;

Rated MVA = 60
Terminal Voltage = 11.0kV
Frequency = 50Hz
Speed = 3000RPM
Power Factor = 0.85
Applicable national standard = IEC 34-3
Rated Air inlet temperature = 15 deg.
Unsaturated Direct axis Synchronous Reactance (Xd) = 257%
Saturated Direct axis Transient Reactance (Xd’) = 22.7%
Saturated Direct axis Sub-transient Reactance (Xd”) = 15.9%
Unsaturated Zero Sequence Reactance (X0) = 10.4%
Unsaturated Negative sequence Reactance (X2) = 19.4%
Short Circuit Ratio = 0.41

Generator technical data-sheet of ALSTOM Electric Machine, UK are as shown


below which is installed in Sanghi industries ltd, Kuttch;

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 74


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
Rated MVA = 15
Terminal Voltage = 11.0kV
Frequency = 50Hz
Speed = 600RPM
Power Factor = 0.80
Applicable national standard = IEC 60034
Ambient temperature = 50 deg.
Unsaturated Direct axis Synchronous Reactance (Xd) = 169.4%
Saturated Direct axis Synchronous Reactance (Xd) =-
Saturated Direct axis Transient Reactance (Xd’) = 28.1%
Unsaturated Direct axis Transient Reactance (Xd’) = 34.7%
Saturated Direct axis Sub-transient Reactance (Xd”) = 18.7%
Unsaturated Direct axis Sub-transient Reactance (Xd”) = 23.1%
Unsaturated Quadrature axis Synchronous Reactance (Xq) = 100.2%
Saturated Quadrature axis Synchronous Reactance (Xq) = -
Saturated Quadrature axis Sub-transient Reactance (Xq”) = 21.5%
Unsaturated Quadrature axis Sub-transient Reactance (Xq”)= 25.6%

Unsaturated Negative sequence Reactance (X2) = 24.5%


Unsaturated Zero Sequence Reactance (X0) = 6.5%
Unsaturated Zero Sequence Resistance (R0) = 0.914%

Short Circuit Ratio = 0.637


Open Circuit Time constant (Td0’) = 3.63second
3-ph Short-circuit transient time constant (Td’) = 0.743second
3-ph Short-circuit saturated transient time constant (Td’) = 0.590second
Short-circuit sub-transient time constant (Td”) = 0.05second
Short-circuit saturated sub-transient time constant (Td”) = 0.035second
Maximum kVAr available at zero p.f. under-excited = 0.51 PU
Maximum kVAr available at zero p.f. over-excited = 0.76 PU
Over speed = 720RPM

Typical Parameters Considered for fault study:

Generator:
• Transient (Xd’) or sub-transient (Xd”) reactance is considered for positive
sequence.
• Negative sequence reactance which is approximately equal to (Xd”).
• Zero sequence reactance, which is comparatively small around 0.1 to 0.7 times
of (Xd”).
• Assume Short Circuit Ratio = 1 / Xd while value of Xd is not given in data-sheet

Transformer:
• Positive sequence, Negative sequence, & Zero sequence impedances are equal.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 75


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

3.2.10 Per Unit (PU) and Percentage Quantity (%):

Per Unit Quantity = Percentage Quantity / 100

• Quantity => Voltage, Current, MVA, Impedance


• E.g. Z = 10% => Z = 0.10 PU; V = 105% => V = 1.05PU
• Per Unit Computation is slightly advantageous over percentage computation.
• Product of two quantities expressed in PU. Result also in PU.
• Product of two quantities expressed in percent. Result shall be divided by 100 to
get percent.
• Fault level calculations are generally performed using PU only.

Per Unit Quantity:

Q(PU) = Q (ACTUAL) / Q (BASE)

e.g. Vbase = 6.6kV; Vactual = 3.3kV; => V = 0.5 PU

e.g. Pbase = 100 MVA; Pactual = 200 MW; => P = 2 PU

Choosing Base:

In general, MVA (3-ph) & Voltage (L to L) chosen as base

Base Current = Base MVA / 1.7325 * Base Voltage

Base Impedance = Base Voltage / 1.7325 * Base Current

= {Base Voltage / (1.7325 * Base MVA / 1.7325 * Base Voltage) }

= (Base Voltage)2 / Base MVA

Base Voltage changes on either side of Transformer:

• Choose Base Voltage as 11 kV and Base Power as 100 MVA


• Let there be 11 / 132 kV Transformer.
• On the HT side of Transformer, base voltage is Automatically 132 kV.
• You can not independently choose another base voltage on other side of
Transformer.
• Base Power is 100 MVA on either side of Transformer.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 76


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

On Low voltage side:

Base voltage = 11 kV (Always L to L )

Base MVA = 100 (Always 3-ph Power)

Base Current = 100 / 1.7325 * 11 = 5.2486 kA

Base Impedance = (11)2 / 100 = 1.21 Ohms

On High voltage side:

Base Voltage = 132 kV (Always L to L)

Base MVA = 100 (Always 3-ph Power)

Base Current = 100 / 1.7325 * 132 = 0.4374 kA

Base Impedance = (132)2 / 100 = 174.24 Ohms

Advantages of Calculations in Per Unit System:

Per Unit Impedance of Transformer is same whether referred to Primary or


Secondary.

e.g. 11 / 33 kV, 50 MVA, Z = 10% (0.1PU)

• In PU, Z = 0.1 on either 11 kV or 33 kV side

• In Ohms, on 11 kV side:
Z base = (Base Voltage)2 / Base MVA = (11)2 / 50 = 2.42 Ohms
Z 11 = (Z base * Z pu) = (2.42)* (0.1) = 0.242 Ohms.

On 33 kV side:

Z base = (Base Voltage)2 / Base MVA = (33)2 / 50 = 21.78 Ohms


Z 33 = (Z base* Z pu) = (21.78)* (0.1) = 2.178 Ohms

• Per Unit Impedance lie within a Narrow Band while Ohmic values can be
widely different.
• Transformer 415 V to 400 kV and 500 kVA to 500 MVA.
Z lies between 5% (0.05PU) to 15% (0.15PU)
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 77
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
• Generator 1 MVA to 500 MVA,
X’d lies between 20% (0.2PU) to 30% (0.3PU)

PU = only realistic way to solve big and practical problems.

3.3 Basic Considerations of Short-Circuit Calculations:

Why Short-Circuit Calculations?

Several sections of the National Electrical Code relate to proper over-current


protection. Safe and reliable application of over-current protective devices based
on these sections mandate that a short circuit study and a selective coordination
study be conducted.

The protection for an electrical system should not only be safe under all service
conditions but, to insure continuity of service, it should be selectively coordinated
as well. A coordinated system is one where only the faulted circuit is isolated
without disturbing any other part of the system. Over-current protection devices
should also provide short-circuit as well as overload protection for system
components, such as bus, wire, motor controllers, etc.

To obtain reliable, coordinated operation and assure that system components are
protected from damage, it is necessary to first calculate the available fault current
at various critical points in the electrical system.

Once the short-circuit levels are determined, the engineer can specify proper
interrupting rating requirements, selectively coordinate the system and provide
component protection.

General Comments on Short-Circuit Calculations:


Short Circuit Calculations should be done at all critical points in the system.
These would include:
- Service Entrance
- Panel Boards
- Motor Control Centers
- Motor Starters
- Transfer Switches
- Load Centers
Normally, short circuit studies involve calculating a bolted 3-phase fault condition.
This can be characterized as all three phases “bolted” together to create a zero
impedance connection. This establishes a “worst case” condition that results in

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 78


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
maximum thermal and mechanical stress in the system. From this calculation,
other types of fault conditions can be obtained.

Sources of short circuit current that are normally taken under consideration
include:
- Utility Generation
- Local Generation
- Synchronous Motors and
- Induction Motors
Capacitor discharge currents can normally be neglected due to their short time
duration. Certain IEEE (Institute of Electrical and Electronic Engineers)
publications detail how to calculate these currents if they are substantial.

3.3.1 Asymmetrical Components:


Short circuit current normally takes on an asymmetrical characteristic during the
first few cycles of duration. That is, it is offset about the zero axis, as indicated in
Figure 1.

Figure 1.

In Figure 2, note that the total short-circuit current Ia is the summation of two
components - the symmetrical RMS current IS, and the DC component, IDC. The
DC component is a function of the stored energy within the system at the
initiation of the short circuit. It decays to zero after a few cycles due to I2R losses
in the system, at which point the short circuit current is symmetrical about the
zero axis. The RMS value of the symmetrical component may be determined
using Ohm’s Law. To determine the asymmetrical component, it is necessary to
know the X/R ratio of the system. To obtain the X/R ratio, the total resistance and
total reactance of the circuit to the point of fault must be determined. Maximum
thermal and mechanical stress on the equipment occurs during these first few
cycles. It is important to concentrate on what happens during the first half cycle
after the initiation of the fault.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 79
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Figure 2.

Where,
Ia = Asymmetrical RMS Fault Current in kA.
IDC = DC component depend on X/R in kA
Is = Asymmetrical RMS Fault Current in kA.
Ip = Instantaneous Peak Current in kA.

Figure 2 illustrates a worst case waveform that 1 phase of the 3 phase system
will assume during the first few cycles after the fault initiation.

The key portions are:


- Symmetrical RMS Short Circuit Current = Is
- Instantaneous Peak Current = Ip
- Asymmetrical RMS Short Circuit Current
(worst case single phase) = Ia

Interrupting Rating, Interrupting Capacity and Short-Circuit Currents:


Interrupting Rating can be defined as “the maximum short-circuit current that a
protective device can safely clear, under specified test conditions.”
Interrupting Capacity can be defined as “the actual short circuit current that a
protective device has been tested to interrupt.”

Interrupting Rating:
Equipment intended to break current at fault levels shall have an interrupting
rating sufficient for the system voltage and the current, which is available at the
line terminals of the equipment.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 80
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Available Short-Circuit Current:


Service Equipment shall be suitable for the short circuit current available at its
supply terminals.

Low voltage fuses have their interrupting rating expressed in terms of the
symmetrical component of short-circuit current, IS. They are given an RMS
symmetrical interrupting rating at a specific power factor. This means that the
fuse can interrupt any asymmetrical current associated with this rating. Thus only
the symmetrical component of short-circuit current need be considered to
determine the necessary interrupting rating of a low voltage fuse. For U.L. listed
low voltage fuses, interrupting rating equals its interrupting capacity.

Low voltage molded case circuit breakers also have their interrupting rating
expressed in terms of RMS symmetrical amperes at a specific power factor.
However, it is necessary to determine a molded case circuit breaker’s
interrupting capacity in order to safely apply it. The reader is directed to Buss
bulletin PMCB II for an understanding of this concept.

Three Phase fault through Impedance:

Fault MVA = Base MVA / (Z1 + Zf)


Ia1 = Fault MVA / 1.7325*(Rated kV), Ia2 = 0, Ia0 = 0

Let, Ia1 = Positive sequence Fault Current in kA,


Ia2 = Negative sequence Fault Current in kA
Ia0 = Zero sequence Fault Current in kA
Z1 = Positive sequence impedance in PU.
Zf = Fault impedance in PU.

Example: (Z1 + Zf) = 0.2 PU., Base MVA = 15, Rated kV = 11, Base kV = 11.

PU method:
Step:-1
Fault MVA = 15 / 0.2 = 75 MVA

Step:-2
Ia1 = 75 / 1.7325*(11) = 3.93kA.

Ohm method:
Step:-1
Find Base Impedance value in Ohm
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 81
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
Z base = (Base Voltage)2 / Base MVA = (11) / 15 = 8.066 Ohms
2

Step:-2
Find Z value in Ohm
Z in Ohm = (Z base * Z pu) = (8.066)* (0.2) = 1.613 Ohms.

Step:-3
Find Fault current
Ia1 = Rated kV / 1.7325*(Z in Ohm) = 3.93kA.

Single-line to ground fault:

(Z1’ + Z2’ + Z0’) = (Z1 + Z2 + Z0) / 3


Fault MVA = Base MVA / (Z1’ + Z2’ + Z0’)
Ia0 = Fault MVA / 1.7325*(Rated kV)

Let, Ia1 = Positive sequence Fault Current in kA,


Ia2 = Negative sequence Fault Current in kA
Ia0 = Zero sequence Fault Current in kA
Z1 = Positive sequence impedance in PU.
Zf = Fault impedance in PU.

Example: Z1 = 1.35 PU., Z2 = 1.35 PU, Z0 = 1.0 PU, Base MVA = 100, Rated kV = 6.6,
Base kV = 6.6.

PU method:
Step:-1
(Z1’ + Z2’ + Z0’) = (Z1 + Z2 + Z0) / 3 = (1.35 + 1.35 + 1.0) / 3 = 1.23 PU

Step:-1
Fault MVA = 100 / 1.23 = 81.30 MVA

Step:-2
Ia0 = 81.30 / 1.7325*(6.6) = 7.11kA.

Ohm method:
Step:-1
Find Base Impedance value in Ohm
Z base = (Base Voltage)2 / Base MVA = (6.6)2 / 100 = 0.4356 Ohms

Step:-2
Find Z value in Ohm
Z in Ohm = (Z base * Z pu) = (0.4356)* (1.23) = 0.5357 Ohms.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 82


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
Step:-3
Find Fault current
Ia1 = Rated kV / 1.7325*(Z in Ohm) = 7.11kA.

3.3.2 Sudden three-phase short circuit on an unloaded synchronous


generator:

A sudden three-phase short circuit on an initially unloaded synchronous


generator will have several types of current components: a unidirectional (or DC)
transient current, an AC transient current, and an AC steady state current. Upon
close examination, the AC transient current is seen to decay first rapidly, then
more slowly. The initial rapid decay is called the sub-transient (Xd”) part and the
slower decay is called the transient part. The AC component is symmetrical,
since all three phases will have essentially the same RMS current values at any
time, but the DC transients are asymmetrical. Thus the symmetrical short-circuit
current excludes the DC terms and the asymmetrical current includes both the
AC and the DC terms.

Figure 2.1.1 shows plots that resemble actual short-circuit currents in the three
armature phases. The phase a current is completely offset in the negative
direction, while the b and c phase currents are offset half as much in the positive
direction. The exact offsets will depend on the instant at which the fault occurs
relative to the pre-fault voltage waveform.

DC offsets:

The physical reason for the existence of the DC offsets is that the current and
flux waveforms of an inductive circuit cannot change instantly. Since the pre-fault
current is zero, the DC offset in any given phase must take on a value equal in
magnitude and opposite in sign to the value of the AC waveform just after the
fault. Since the AC currents are shifted by 120o from each other, the DC
components of the three phases will always add to zero.

The maximum DC offset in a phase current is the peak value of the AC initial
component. This occurs in one phase at most, since the three DC offsets must
add to zero as discussed above. That means that the maximum DC offset is
1.414 times the initial RMS AC waveform.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 83


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

View of DOBLE “DATC” software which is shown a DC OFFSET with L/R=300ms

3.3.3 Symmetrical short-circuit current:

In most short-circuit current calculations, the AC (or symmetrical) current is


needed. We consider a sudden three-phase short circuit on an unloaded
synchronous generator.
The sub-transient component of this current decays with a time constant that is
determined by the time constant of the damper windings, which are windings on
the pole faces of salient-pole synchronous motors and generators. Cylindrical-
rotor machines usually have no damper windings, but eddy currents in their solid-
iron rotors have much the same effect. Just after the short circuit, the RMS value
of the current is I" = E / Xd" where E is the pre-fault voltage and Xd" is the
generator sub-transient reactance. If E is in volts (line- neutral) and Xd" is in
ohms, then I" will be in amps. If E and Xd" are in per-unit, then I" will be in per
unit. Since Xd" is usually tabulated in percent or per unit, and since E is
approximately 1.00 per unit, we will use per-unit equations for our calculations.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 84


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Figure 2.1.1 Synchronous machine armature short-circuit currents for sudden 3-ph Fault

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 85


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
The transient component decays with a much longer time constant (about 1
second compared to several cycles for the sub-transient) that is due to the time
constant of the field winding. A few cycles after the fault occurs, the RMS value
of the current is I' = E / Xd' where Xd' is the generator transient reactance.

Figure 2.1.2(below) shows the rms ac (or symmetrical) short-circuit current for
the same case that is illustrated in the previous figure.

If the short circuit is left on until the transients die out, the steady-state short-
circuit current may be determined. We subtract the steady-state current from the
ac component, and plot the result on semi-log paper, as shown in Figure 2.1.3
(below), to determine transient and sub-transient time constants and reactances.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 86


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Figure 2.1.3 The transient time constant Td' is the slope of the line fitted by
ignoring the initial part of this curve. The excess current for the first few cycles
may be plotted on a similar graph to obtain the sub-transient time constant Td".

Calculation:
According to ANSI/IEEE Std. 242-1996, the total AC component of armature
current consists of the steady-state (Id) value and two components that decaying
at a rate according to their respective time constant.
Iac = (Id” – Id’)*(e(2*3.14*f*t)/(Td”) ) + (Id’ – Id)*(e(2*3.14*f*t)/(Td’) ) + Id-----------(1)

(1) Subtransient Component, Id”

Id” = (e”/Xd”) p.u. where e” = (et + Xd” Sin(theta) )----------------(2)


When machine is at no-load, e”=et
(2) Transient component, Id’

Id’ = (e’/Xd’) p.u.


(3) Steady-state component, Id

Id = (et/Xd)* (If/Ifg)----------------------------------------------------------(3)
(4) The DC component of the armature current is controlled by the sub-transient
reactance and the armature time constant:

Idc = (1.414)* (Id”)* (e(2*3.14*f*t)/(X/R) )


= (1.414)* (Id”)* (e(t/(L/R)) )---------------------------------------------(4)

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 87


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

General Description of Calculation Methodology:

3.3.4 EFFECT OF LOW ZERO-SEQUENCE IMPEDANCES ON GENERATORS:

Good design practice dictates that short circuit calculations be performed to


ensure that the IEC rating specified for equipment is higher than the anticipated
fault currents. Properly rated equipment is not only a code requirement but can
impact the cost of a project. Equipment that is underrated must be replaced, and
overrated equipment costs more than properly rated equipment.

Short circuit calculations during the design phase require some assumptions and
generalizations, which are validated or corrected when a detailed study is
completed. The detailed study is usually completed prior to the review of
equipment submittals. Underrated equipment identified in the study can be
changed before orders are released or factories prepare the equipment for
shipment.

In the case study mentioned in the introduction, the detailed short circuit study
was not completed until after the equipment had been installed. Since the
engineer had used the positive sequence impedance of the generator for his
calculations (or used generator decrement curve data, which is based on the
positive sequence impedance), some of the equipment was underrated. As will
be discussed below, the lower zero sequence impedance of a generator can
result in line-to-ground fault currents that can be as high as one and a half times
the phase fault currents.

ANALYSIS
To graphically illustrate the variation in magnitude between line-to-ground faults
and phase faults, we will begin by looking at the one-line diagram for a typical
installation. This is shown in Figure below. The service transformers are 2500
kVA and the generators are 1500 kW.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 88


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Table 1 summarizes the impedance values for the transformers and generators
shown. All values are shown in per unit for each phase. The kVA base is 10,000
and the kV base for the primary is 13.8 and 0.48 for the secondary. Note that the
values for the generator reactance are sub-transient values.

As can be seen by observation, the generator zero-sequence X(0) impedance is


somewhat lower than the positive-sequence X(+ve). This contrasts markedly with
the transformers and the utility source impedance, where the zero-sequence
impedance X(0) is essentially the same as the positive sequence impedance
X(+ve).

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 89


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

TABLE:-1: SOURCE & TRANSFORMER DATA


For the purpose of this analysis, we will assume that the utility and generators
will never be paralleled. As such, there is no need to consider the implications of
the lower generator zero-sequence impedance being in parallel with the utility
transformer zero-sequence impedance.

To determine the available three-phase fault currents, the pre-fault voltage


(usually taken to be the nominal voltage) would be divided by the equivalent
positive sequence impedance of the network, as seen from the faulted bus.

Using the impedance values for the conductors shown in Table 2, for a fault at
the ATS, the positive sequence network, with the generator as the source, would
be as shown in Figure. (Since the line-to-ground fault current magnitudes for the
transformer source are the same as the phase fault current magnitudes, we will
confine our analysis to the generator source.)

TABLE:-2: CONDUCTOR IMPEDANCE VALUE

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 90


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

POSITIVE SEQUENCE DIAGRAM OF NETWORK

The equivalent impedance of the positive sequence network would then be the
parallel combination of the series combination of generators and their conductors
in series with the conductor to the ATS.

Neglecting the impedance of the conductors, neglecting the resistance of the


generators, and using only the positive sequence impedance would yield the
following results:

We now turn our attention to the available line-to-ground fault currents. For this
calculation, the pre-fault voltage would be divided by the equivalent zero
sequence impedance of the network, as seen from the faulted bus. Looking at
the impedance seen at the ATS for a line-to-ground fault, the following sequence
network is generated.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 91


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 92


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Sequence Network for Line-to-Ground Faults

As before, we will neglect the impedance of the conductors and the resistance of
the generators. This would yield the following results:

As can be seen from this calculation, the line-to-ground fault current is almost
125% of the three-phase fault current. If the model were expanded to include five
generators, the three-phase fault current would be approximately 27.75 kA and
the line-to-ground fault current would be 34.5 kA. If the AIC rating of the
equipment to be used were based on the three phase currents, the equipment
would be underrated. Of course, in a case with fewer and/or smaller machines,
the disparity between the phase fault currents and the ground fault currents may
not be a problem, that is, 125% of the phase fault currents may still be well below
the minimum IEC rating of equipment in a given voltage rating. However, it is
always important to check before the equipment is approved for manufacture and
shipment.

CONCLUSIONS
This simple, two machine model demonstrates the higher magnitudes that can be
anticipated for line-to-ground faults when a facility is fed from a generator source.
When specifying the IEC rating of equipment, it is important to consider the
source of the fault and the nature of that source.

Although simple installations with small machines may not be affected, good
design practice would dictate that consideration be given to the calculation of
line-to-ground fault currents. Failure to compare the equipment short circuit
ratings to the calculated line-to-ground fault currents can cause construction
delays and expensive equipment replacement.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 93


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

3.3.5 ANSI/IEEE CALCULATION METHODS:

In ANSI/IEEE short-circuit calculations, an equivalent voltage source at the fault location,


which equals the pre-fault voltage at the location, replaces all external voltage sources
and machine internal voltage sources.

All machines are represented by their internal impedances. Line capacitances and static
loads are neglected. Transformer taps can be set at either the nominal position or at the
tapped position, and different schemes are available to correct transformer impedance
and system voltages if off-nominal tap setting exists. It is assumed the fault is bolted,
therefore, arc resistances are not considered. System impedances are assumed to be
balanced three-phase, and the method of symmetrical components is used for
unbalanced fault calculations.

Three different impedance networks are formed to calculate momentary, interrupting,


and steady-state short-circuit currents, and corresponding duties for various protective
devices. These networks are: ½ cycle network (sub-transient network), 1.5-4.0 cycle
network (transient network), and 30-cycle network (steady-state network).

ANSI/IEEE standards recommend the use of separate “R” and “X” networks to calculate
X/R values. An X/R ratio is obtained for each individual faulted bus and short-circuit
current. This X/R ratio is then used to determine the multiplying factor to account for the
system DC OFFSET.

½ Cycle Fault:

It is used to calculate momentary short-circuit and protective device duties at the ½


Cycle after the fault. The following table shows the type of device and its associated
duties using the ½ cycle fault.

Type of Device Duty

High Voltage Circuit breaker Closing & Latching capability

Low Voltage Circuit breaker Interrupting capability

Fuse Interrupting capability

Switch gear & MCC Bus bracing

Relay Instantaneous settings

½ cycle fault is also consider as a sub-transient period fault, primarily because all
rotating machines are represented by their sub-transient reactances, as shown in table:

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 94


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
Type of Machine Xsc

Utility X”

Turbo generator Xd”

Hydro generator with amortisseur winding Xd”

Hydro generator without amortisseur 0.75*Xd”


winding

Condenser Xd”

Synchronous motor Xd”

Induction machine >1000hp @ 1800rpm or Xd” = 1/LRC (LRC = Locked rotor current)
less

Induction machine >250hp @ 3600rpm Xd” = 1/LRC

Induction machine >50hp 1.2*Xd”

Induction machine <50hp 1.67*Xd”

1.5 – 4.0 Cycle Fault:

It is used to calculate the interrupting short-circuit and protective device duties 1.5 – 4.0
Cycle after the fault. The following table shows the type of device and its associated
duties using the 1.5 – 4.0 cycle fault.

Type of Device Duty

High Voltage Circuit breaker Interrupting capability

Low Voltage Circuit breaker N/A

Fuse N/A

Switch gear & MCC N/A

Relay IDMTL Over current relay settings

1.5 – 4.0 cycle fault is also consider as a transient period fault, because all rotating
machines are represented by their transient reactances, as shown in table:

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 95


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
Type of Machine Xsc

Utility X”

Turbo generator Xd”

Hydro generator with amortisseur winding Xd”

Hydro generator without amortisseur 0.75*Xd”


winding

Condenser Xd”

Synchronous motor 1.5*Xd”

Induction machine >1000hp @ 1800rpm or 1.5*Xd” = 1/LRC (LRC = Locked rotor


less current)

Induction machine >250hp @ 3600rpm 1.5*Xd” = 1/LRC

Induction machine >50hp 3.0*Xd”

Induction machine <50hp Infinite

30 Cycle Fault:

It is used to calculate the steady state short-circuit current and duties for some of the
protective devices 30 Cycle after the fault. The following table shows the type of device
and its associated duties using the 1.5 – 4.0 cycle fault.

Type of Device Duty

High Voltage Circuit breaker N/A

Low Voltage Circuit breaker N/A

Fuse N/A

Switch gear & MCC N/A

Relay IDMtL Over current relay settings

The type of rotating machine and its representation in the 30-cycle fault is shown in
following table. Note that induction machines, synchronous motors, and condensers are
not considered in the 30-cycle fault calculation.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 96
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
Type of Machine Xsc

Utility X”

Turbo generator Xd’

Hydro generator with amortisseur winding Xd’

Hydro generator without amortisseur Xd’


winding

Condenser Infinite

Synchronous motor Infinite

Induction machine >1000hp @ 1800rpm or Infinite


less

Induction machine >250hp @ 3600rpm Infinite

Induction machine >50hp Infinite

Induction machine <50hp Infinite

ANSI Multiplying Factor (MF):

The ANSI (American National Standards & Institute) multiplying factor is determined by
the equivalent system X/R ratio at a particular fault location. The X/R ratio is calculated
by the separate “R” and “X” networks.

Momentary (1/2 Cycle) short-circuit current calculation (Buses & HV CB):

The momentary short-circuit current at the ½ cycle represents the highest or maximum
value of the short-circuit current (before its AC & DC components decay toward the
steady state value). Although, in reality, the highest or maximum short-circuit current
actually occurs slightly before the ½ cycle, the ½ cycle network is used for this
calculation.

The following procedure is used to calculate momentary short-circuit current:

Step:-1

Calculate the symmetrical rms value of momentary short-circuit current using the
following formula:

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 97


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
Imom,rms,symm = ( Vpre-fault ) / ((1.7325)*Zeq)

Where Zeq is the equivalent impedance at the faulted bus from the ½ cycle fault.

Step:-2

Calculate the Asymmetrical rms value of momentary short-circuit current using the
following formula:

Imom,rms,Asymm = (MFm)*( Imom,rms,symm )

Step:-3

Calculate the Multiplying or Asymmetrical factor using the following formula:

(MFm) = Under root( 1 + (2e)-2*3.14/(X/R))


Step:-4

Calculate the Peak value of momentary short-circuit current using the following formula:

Imom,Peak = (MFP)*( Imom,rms,Asymm )

Step:-5

Calculate the Peak Multiplying factor using the following formula:

(MFP) = 1.414*(Under root( 1 + (e)-3.14/(X/R)))


In both equations for MFm and MFP calculation, X/R is the ratio of X to R at the fault
location obtained from separate X and R networks at ½ cycle. The value of the fault
current calculated by this method can be used for following purpose:

• Check closing & latching capabilities of high voltage circuit breakers.

• Check bus-bar capacity.

• Adjust relay instantaneous settings.

• Check interrupting capabilities of fuses and low voltage circuit breakers.

High voltage Circuit breaker Interrupting short-circuit current calculation:

The interrupting fault currents for high voltage circuit breakers correspond to the 1.5 –
4.0 cycle short-circuit for high voltage circuit breakers:

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 98


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

The following procedure is used to calculate the interrupting short-circuit current:

Step:-1

Calculate the symmetrical rms value of the interrupting short-circuit current using the
following formula:

Iint,rms,symm = ( Vpre-fault ) / ((1.7325)*Zeq)

Where Zeq is the equivalent impedance at the faulted bus from the 1.5 – 4.0 cycle fault.

Step:-2

Calculate the short-circuit current contributions to the fault location from the surrounding
buses.

Step:-3

If contribution is from a Remote bus, the symmetrical value is corrected by the factor of
MFr, calculated from

MFr = Under root( 1 + (2e)-4*3.14*t/(X/R))

Where t is the circuit breaker contact parting time in cycles, as given in the following
table:
Circuit breaker rating in Cycles Contact Parting time in Cycles
8 4.0
5 3.0
3 2.0
2 1.5

Low voltage Circuit breaker Interrupting short-circuit current calculation:

Due to the instantaneous action of low voltage circuit breakers at maximum short-circuit
values, the ½ cycle network is used for calculating the interrupting short-circuit current.

The following procedure is used to calculate the interrupting short-circuit current:

Step:-1

Calculate the symmetrical rms value of the interrupting short-circuit current using the
following formula:

Iint,rms,symm = ( Vpre-fault ) / ((1.7325)*Zeq)

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 99


PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
Where Zeq is the equivalent impedance at the faulted bus from the ½ cycle fault.

Step:-2

Calculate the adjusted asymmetrical rms value of the interrupting short-circuit current
duty using the following formula:

Iint,rms,adj = MF * Iint,rms,symm

Step:-3
(MF) = {1.414*(Under root( 1 + (e)-3.14/(X/R)))} / {1.414*(Under root( 1 + (e)-3.14/(X/R)TEST))} for
unfused power breakers.

(MF) = {1.414*(Under root( 1 + (2e)-2*3.14/(X/R)))} / {1.414*(Under root( 1 + (2e)-2*3.14/(X/R)TEST))} for


fused power or molded case breakers.

Where (X/R)test is calculated based on the test power factor. The manufacturer
maximum testing power factors given in the following table are used as the default
values:
Circuit breaker type Max Design %PF (X/R)test
Power breaker (Unfused) 15 6.59
Power breaker (fused) 20 4.90
Molded case (>20000A) 20 4.90
Molded case (10001-20000A) 30 3.18
Molded case (<10000A) 50 1.73

IEC CALCULATION METHODS:

Initial Symmetrical Short-circuit current (I”k):


This is the rms value of the ac symmetrical component of an available short-circuit
current applicable at the instant of short-circuit if the impedance remains at zero time
value.

Peak Short-circuit current (ip):


This is the maximum possible instantaneous value of the available short-circuit current.

Symmetrical Short-circuit Breaking current (Ib):


This is the rms value of an integral cycle of the symmetrical ac component of the
available short-circuit at the instant of contact separation of the first pole of a switching
device.

Steady state Short-circuit current (Ik):


This is the rms value of the short-circuit current which remains after the decay of the
transient phenomena.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 100
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Sub-transient Voltage (E”) of a Synchronous machine:


This is the rms value of the symmetrical internal voltage of a synchronous machine
which is active behind the sub-transient reactance Xd” at the moment of short-circuit.

Sub-transient Reactance (Xd”) of a Synchronous machine:


This is the effective reactance at the moment of short-circuit. For the calculation of short-
circuit currents, the saturated value of (Xd”) is taken.

According to IEC Standard 909, the synchronous motor impedance used in IEC short-
circuit calculations is calculated in the same way as the synchronous generator.

Zk = KG(R+Xd”)

KG = (kVn * Cmax) / kVr* {1 + (Xd”)*(SIN(pHi))}

Where kVn and kVr are the nominal voltage of the terminal bus and the motor rated
voltage respectively, Cmax is determine based on machine rated voltage, Xd” is
machine sub-transient reactance (Per unit in motor base), and “pHi” is the machine rated
power factor angle.

Minimum time delay (Tmin) of a Circuit breaker:


This is the shortest time between the beginning of the short-circuit current and the first
contact separation of one pole of the switching device.

Voltage factor C:
This is the factor used to adjust the value of the equivalent voltage source for minimum
and maximum current calculation according to the following table:

Nominal Voltage Vn Cmax Cmin


Low voltage; 100V to 1.05 1.00
1000V
Medium voltage:>1kV to 1.05 1.00
35kV
230V/400V 1.00 0.95
High voltage:>35kV to 1.10 1.00
230kV

Initial symmetrical short-circuit current calculation:


I”k = (C * Vn) / {(1.7325)*Zk}

Where Zk is the equivalent impedance at the fault location.

Peak short-circuit current calculation:


IP = 1.414* (I”k)* (R/X)

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 101
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
DC component of short-circuit current calculation:
(2*3.14*f*t)/(X/R)
IDC = 1.414* (I”k)* (e )

Asymmetrical Short-circuit current calculation for MV CB:


(-4*3.14*f*t)/(X/R)
IK,ASYMM. = (I”k)*{1 + (2e )}

DC component of short-circuit current calculation for MC CB:


(2*3.14*f*t)/(X/R)
IDC = 1.414* (I”k)* (e )

Asymmetrical Short-circuit current calculation for LV CB:


(-4*3.14*f*t)/(X/R)
IK,ASYMM. = (I”k)*{1 + (2e )}

Asymmetrical Short-circuit current calculation for FUSE:


(-4*3.14*f*t)/(X/R)
IK,ASYMM. = (I”k)*{1 + (2e )}

3.3.6 The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies:

Introduction:

In some short circuit studies, the X/R ratio is ignored when comparing the short
circuit rating of the equipment to the available fault current at the equipment.
What is not always realized is that when low-voltage gear is tested, it is tested at
a certain X/R ratio. The X/R ratio is important because it determines the peak
asymmetrical fault current. The asymmetrical fault current can be much larger
than the symmetrical fault current. The purpose of this article is to introduce such
terms as the X/R ratio and asymmetrical fault current and to relate the
importance of the X/R ratio to the rating of low-voltage equipment.

X/R Ratio and Asymmetrical Fault Current:

In AC electrical systems, impedance has two components. The first is called


reactance (X). Reactance depends on two things: (1) the inductance and (2) the
frequency. Inductance reflects how hard it is to change the current. All
conductors have some inductance, but a more useful example of a component
having inductance is a coil of wire. Frequency is fixed at either 60 or 50Hz,
depending upon where in the world the electrical system is, so the reactance is
solely dependent upon the inductance.

The second component of impedance is the familiar resistance (R). Resistance is


a measure of how hard it is for current to flow. When current flows through a
material having resistance, heat is transferred from the material to the
surroundings.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 102
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

The resistance and reactance of a circuit establishes a power factor. The power
factor (p.f.) is given by the following equation:

p.f. = cos(tan-1(X/R))

If the power factor is unity (1), then the impedance only has resistance. If the
power factor is zero, then the impedance only has reactance.

The power factor also determines how much the voltage and current waveforms (sine
waves) are out of phase. Remember that both voltage and current are sine waves in
linear AC electrical systems. For purely resistive systems, the voltage and current are in
phase. For purely reactive systems, the voltage and current are 90-degress (one-quarter
of a cycle) out of phase, with the voltage leading the current. Figure 2 below illustrates
this.

Effect of P.F. upon Voltage (------) and Current (------) waveform

The above equation means that the power factor and X/R ratio are related.
Therefore, power factor and X/R ratio are different ways of saying the same
thing. Please note that as power factor decreases, the X/R ratio increases.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 103
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
Right after a fault occurs, the current waveform is no longer a sine wave. Instead,
it can be represented by the sum of a sine wave and a decaying exponential.
Figure 3 below illustrates this phenomenon.

Sine-wave (-----) , Decaying Exponential (-----), and their Sum (-----)

Please note that the decaying exponential added to the sine wave causes the
current to reach a much larger value than that of the sine wave alone. The
waveform that equals the sum of the sine wave and the decaying exponential is
called the asymmetrical current because the waveform does not have symmetry
above and below the time axis. The sine wave alone is called the symmetrical
current because it does have symmetry above and below the time axis.

The actual waveform of the asymmetrical fault current is hard to predict because
it depends on what time in the voltage cycle waveform the fault occurs. However,
the largest asymmetrical fault current occurs when a fault happens at a point
when the voltage is zero. Then, the asymmetrical fault current depends only on
the X/R ratio, or power factor, and the magnitude of the symmetrical fault current.

Figure 4 below shows how the ratio of the peak asymmetrical current to the RMS
symmetrical current varies with the X/R ratio. (RMS symmetrical current equals

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 104
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
the peak symmetrical current divided by the square root of 2.) What Figure 4
shows is that the peak asymmetrical current increases with the X/R ratio.

Figure 4. Peak asymmetrical current as a function of symmetrical RMS current.


(Data taken from notes on the GE Electrical Distribution & Control Low-voltage
Protector Application Seminar.)

Role of X/R Ratio when Comparing Short Circuit Ratings:

Low voltage devices have one rating, as opposed to medium-voltage gear, which
have both a momentary and interrupting rating. This rating is reported in terms of
symmetrical current. Therefore, the rating must be compared to the calculated
symmetrical current.

But the story does not end here. All low voltage protective devices are tested at
an X/R ratio. The X/R ratio at which a device is tested depends upon the device
type. Table 1 below summarizes the device types and the X/R ratios at which
they are tested.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 105
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Table 1. X/R ratios at which low voltage protective devices are tested.

Although low voltage devices do not have asymmetrical ratings, if we know the
symmetrical current rating and the test X/R ratio, Figure 4 gives us the maximum
asymmetrical fault current. So, in a way, there is an asymmetrical fault current
rating, but it is not explicit. Therefore, in any short circuit study, both the X/R ratio
and the symmetrical fault current must be taken into account.

Remember that, for a calculated value of RMS symmetrical current, as X/R ratio
increase, the maximum asymmetrical current (peak or RMS) also increases.

If the calculated symmetrical fault current is larger than the device short circuit
rating, the device in underrated, regardless of X/R ratio. However, it is possible
for the device to be underrated even if the short circuit rating exceeds the
calculated symmetrical fault current. How is this possible? We will discuss this
next.

Consider some equipment whose calculated symmetrical fault current is less


than the short circuit rating of the equipment. Also, the calculated X/R ratio is less
than or equal to the test X/R ratio. The maximum calculated asymmetrical fault
current will be less than the maximum asymmetrical current that corresponds to
the short circuit rating and the test X/R ratio. The device will be properly rated.

Now consider another possibility. What if the symmetrical fault current is the
same as the equipment’s rated current, but the actual X/R ratio is larger than the
tested X/R ratio? Now, the maximum asymmetrical fault current will be larger
than the maximum asymmetrical current corresponding to the short circuit rating
and the test X/R ratio. Although the available symmetrical fault current is equal to
the rating, the asymmetrical fault current is higher than that when the device was
tested. The device is not rated properly.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 106
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
The above two paragraphs motivate a de-rating factor, or multiplying factor (MF),
that is defined by the following formula:

If the calculated X/R ratio at a device is larger than the test X/R ratio of the
device, then the calculated symmetrical fault current must be multiplied by the
multiplying factor. Or, equivalently, the short circuit rating must be divided by the
multiplying factor. The multiplying factor is equal to the ratio of the calculated
asymmetrical fault current to the asymmetrical fault current at the test X/R ratio
and the rated symmetrical current.

Here is an example of the process. After running a fault analysis, the symmetrical
fault current at some low voltage switchgear is found to be 62kA during the first
half-cycle. The switchgear contains power circuit breakers rated at 65kA. The
asymmetrical peak fault current was found to be 149kA. The X/R ratio was
calculated to be 11.1.

The test X/R ratio of low voltage power circuit breakers is 6.6. Although the
symmetrical fault current is lower than the rating of the circuit breakers, the fact
that the X/R ratio is higher than the test value means that we must use the
multiplying factor.

Therefore, the effective symmetrical fault current is 1.07 X 62kA = 66kA.


Because 66kA > 65kA, the switchgear is underrated. We can also de-rate the
switchgear. Then, the effective rating of the gear is 65kA / 1.07 = 61kA. Now,
because 62kA > 61kA, the switchgear is under-rated.

Summary of X/R Ratio:

When performing short circuit calculations, it is important to consider the X/R


ratio. The higher the X/R ratio, the higher the asymmetrical peak fault current.
Therefore, when verifying the ratings of electrical equipment, both the
symmetrical short circuit rating and the X/R ratio must be taken into
consideration.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 107
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

If the calculated X/R ratio is larger than the test X/R ratio, then the equipment
short circuit rating must be de-rated by a multiplying factor. This multiplying factor
equals the ratio of the calculated peak asymmetrical fault current divided by the
peak asymmetrical current corresponding to the rated symmetrical current and
the test X/R ratio.

3.3.7 Procedures and Methods:


Short-Circuit Current Calculations & Relay-Coordination:

To determine the fault current at any point in the system, first draw a one-line diagram
showing all of the sources of short-circuit current feeding into the fault, as well as the
impedances of the circuit components.

To begin the study, the system components, including those of the utility system, are
represented as impedances in the diagram.

It must be understood that short circuit calculations are performed without current
limiting devices in the system. Calculations are done as though these devices are
Replaced with copper bars, to determine the maximum “available” short circuit current.
This is necessary to project how the system and the current limiting devices will perform.

Also, current limiting devices do not operate in series to produce a “compounding”


current limiting effect. The downstream, or load side, fuse will operate alone under a
short circuit condition if properly coordinated.

3.3.7.1 Three-phase Short-Circuit Calculation by Per-Unit Method:


The Per-Unit method is generally used for calculating short-circuit currents when the
electrical system is more complex.

After establishing a one-line diagram of the system, proceed to the following


calculations:

Step-1:
Infinite Source (Power Grid) Impedance:
Source Impedance Zs = MVA Base / MVA Fault

Step-2:
Transmission Line Impedance:

Step-3:
Power/Distribution Transformer Impedance:

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 108
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
X PU = (%X)* (KVA Base) / (100)* (KVA X’mer)

R PU = (%R)* (KVA Base) / (100)* (KVA X’mer)


-----------------------------------------------------------------------

Z2 PU = √(X PU)2 + (R PU)2


Or
Z2 PU = (%Z)* (KVA Base) / (100)* (KVA X’mer)

Step-4:
Cable:

X PU = {(X in Ohms)* (KVA Base)} / {(1000)* (kV Base)2}

R PU = {(R in Ohms)* (KVA Base)} / {(1000)* (kV Base)2}


-----------------------------------------------------------------------

Z3 PU = √(X PU)2 + (R PU)2

Step-5:
Determine the total Single Circuit line Impedance of Power Grid:

Z’ Total PU = (Zs PU + Z1 PU + Z2 PU + Z3 PU)

Step-6:
Determine the total Short Circuit MVA from Power Grid:

MVA SC1 = (MVA Base) / (Z’ Total PU)

Step-7:
Determine Short Circuit Current Contribution from Power Grid:

I kA1 = (MVA SC1) / (1.7325* Rated KV)

Step-8:
Determine the Short Circuit Contribution from Generator:

Z gen PU = {(%X’d)* (MVA Base)} / {(100)* (MVA Rated)}

Step-9:
Determine the total Short Circuit MVA from Generator:

MVA SC2 = (MVA Base) / (Z gen PU)

Step-10:
Determine Short Circuit Current Contribution from Generator:

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 109
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
I kA2 = (MVA SC2) / (1.7325* Rated KV)

Step-11:
Determine the Short Circuit Contribution from Motors or Dynamic loads:

Z loads PU = {(%Z)* (MVA Base)} / {(100)* (MVA Rated)}

Generally, %Z = 25% consider for LT motors or loads and %Z = 15-20% for HT motors
or loads.

Step-12:
Determine the total Short Circuit MVA from Dynamic loads or Motors:

MVA SC3 = (MVA Base) / (Z loads PU)

Step-13:
Determine Short Circuit Current Contribution from Dynamic loads or Motors:

I kA3 = (MVA SC3) / (1.7325* Rated KV)

Step-14:
Determine Total Short Circuit Current at Fault:

I kA symm RMS = (I kA1 + I kA2 + I kA3)

Step-15:
Determine X/R ratio of the system to the point of fault:

X/Rratio = (X PU total) / (R PU total)

Step-16:
Determine the Asymmetrical RMS short-circuit current to the point of fault:

I kA asymm RMS = (I kA symm RMS)* (Asym Factor)

Step-17:
Determine the Asymmetrical Factor:

Asym Factor or Momentary multiplying factor (MFm) = Under root( 1 + (2e)-2*3.14/(X/R))

Step-16:
Determine the Peak value of short-circuit current to the point of fault:

I kA mom, peak = (I kA Asymm RMS)* (MFP)

Step-17:
Determine the Multiplying peak Factor:
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 110
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Peak Momentary multiplying factor (MFP) = 1.414*(Under root( 1 + (e)-3.14/(X/R)))

Example is shown in fig

All Sources and loads feed fault Current figure (3)

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 111
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

CASE STUDY-1:

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 112
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 113
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 114
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 115
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
CASE STUDY-2:

GR1 GR2 4-DGSETS

GR1-
TR1

F1
2MVA-TR

4X350KW 4X250KW

DY. LOAD

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 116
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

FAULT LEVEL CALCULATIONS

The calculation of fault level / short circuit current can be calculated using PU values
of impedances / reactances of different components of the system. For calculation of
PU values, let us select the base MVA = 15 MVA

¾ INFINITE SOURCE:
Fault level at infinite bus as given by GEB is 5481 MVA at Jambua Load Dispatch
Center, at 132 KV voltage level & 15.5 KM far from the plant site. Based on this,
source impedance can be found out as given below:

Source Impedance Zs = 15 / 5481 = 0.0027367269 PU

¾ TRANSMISSION LINE:
According to data available from GEB, the two 132 KV transmission lines, having
Panther 0.2 conductor & 15.5 KM length have following parameters

R = 9.31 X 10-4 PU / KM / circuit


X = 2.216 X 10-3 PU / KM / circuit

Zt = Under root of ( R2 + X2 )
= Under root of ( (0.000931)2 + (0.002216)2 )
Zt = 0.0024036258 PU / KM / circuit

Total impedance for 15.5 KM long line Zt = 0.00558837 PU / circuit

¾ POWER TRANSFORMER:
The rating of power transformer is 15 MVA / 20 MVA.
For calculation of transformer impedance, normal operating conditions are to be
considered. So the rating of the transformer = 15 MVA has to be considered.
Power transformer PU impedance can be calculated as follows.

9.2 X 15
Ztr = -----------------
100 X 15

Ztr = 0.092 PU

¾ CABLE:
The cable between power transformer & 6.6 KV HT panel is 8 X 3C X 300 sq.mm. &
the length of the cable = 100 mtrs

The impedance of the cable Zc = 0.0006780303 PU

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 117
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

¾ 2270 DESIEL GENERATOR:

According to Generator data, the sub-transient reactance (X”d) of the Generator =


16.3 %

The PU value of Generator impedance on 15 MVA base can be found out through
following formula:

16.3 X 15
PU impedance of Generator Zg = ---------------------
100 X 2.270

= 1.0770925 PU

¾ 350 KW, 6.6 KV CHILLER MOTOR:

As the actual motor transient reactance is not available, the motor transient
reactance is selected as 17 % for all HT motor, according to statistical analysis.

The PU value of 350 KW, 6.6 KV motor impedance on 15 MVA base can be found
out through following formula:

17 X 15
Motor impedance Zm = -------------------
100 X 0.4375

= 5.82857 PU

¾ 350 KW MOTOR CABLE:

The cable connecting 6.6 KV panel & 350 KW motor is 1 X 3C X 185 sq.mm. with
550 mtrs length.

The PU value of the cable connecting 350 KW motor & 6.6 KV panel Zcm

Zcm = 0.0436294 PU

¾ 250 KW, 6.6 KV COMPRESSOR MOTOR:

As the actual motor transient reactance is not available, the motor transient
reactance is selected as 17 % for all HT motor, according to statistical analysis.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 118
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

he PU value of 250 KW, 6.6 KV motor impedance on 15 MVA base can be found out
through following formula:

17 X 15
Motor impedance Zm = -------------------
100 X 0.3125

= 8.16 PU

¾ 2 MVA DISTRIBUTION TRANSFORMER( LT1, LT2, LT3 ):

Percentage Impedance of Transformer (%Z) = 6.43%

2 MVA distribution transformer PU impedance can be calculated as follows.

6.43 X 15
Ztr = -----------------
100 X 2

Ztr = 0.48225 PU

¾ CABLE:
The cable between distribution transformer & 6.6 KV HT panel is 8 X 3C X 300
sq.mm. & the length of the cable = 525 mtrs

The PU impedance of the cable Zc = 0.02847 PU

¾ LT DYNAMIC LOAD:

As the actual LT motor data of transient reactance is not available, according to


standard statistical analysis, it is taken as 25 %

The LT motors are not considered individually but are considered as a lumped load
on each LT transformer

According to the plant operating condition, 1. 2 MVA load is considered as a


Dynamic lumped load on each 2 MVA transformer

25 X 15
The PU impedance of the LT dynamic load Zm = ----------------
100 X 1.2

= 3.125 PU

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 119
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

FAULT LEVEL CALCULATION AT 132 KV SWITCHYARD BUS:

Total impedance of a Two grid from infinite source to 6.6 KV panel:

0.00558837
= 0.002736729 + -----------------
2

= 0.00553085 PU / circuit

Fault contribution of Both Grid running in parallel = 15 / 0.00553085 = 2712 MVA

CONDITION - A:

WHEN ALL 4 DG SETS ARE RUNNING IN PARALLEL WITH TWO GRID SUPPLY

¾ Fault contribution of both the Grid for a fault on 6.6 KV bus

Total impedance of two grid lines from infinite source to 6.6 KV panel:

0.00558837+ 0.092 + 0.0006780303


= 0.002736729 + -------------------------------------------------
2
= 0.518698 PU / circuit
Fault contribution of Both Grid running in parallel = 15 / 0.0518698 = 289 MVA

¾ Fault contribution of all the four DG SETS for a fault on 6.6 KV bus

The PU impedance of a single DG = 1.0770925 PU

Considering all four DG running in parallel, total PU impedance = 0.2692731 PU

Fault contribution of all DG running in parallel = 15 / 0.2692731 = 55.7 MVA


= 56 MVA (say)

¾ Fault contribution of all the HT motors for a fault on 6.6 KV bus

Considering normal working condition of the plant, total 4 no of 350 KW & 4 no of 250
KW motor are taken in to consideration for Fault contribution

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 120
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
Total PU impedance of a single 350 KW HT motor feeder = 5.8285714 + 0.0436294
= 5.872200814 PU

Total PU impedance of a single 250 KW HT motor feeder = 8.16 + 0.0436294


= 8.2036294 PU

Total PU impedance of all HT motors = 5.872200814 / 4 || 8.2036294 / 4


= 0.8556042 PU

Fault contribution of all HT motor running in parallel = 15 / 0.8556042


= 17.53 MVA
= 18 MVA (say)

Total fault level on 6.6 kv bus for 2 Grid & 4 DG-SET running in parallel = 363
MVA & This value exceeds the bus bar short circuit rating of 350 MVA.

CONDITION B:

WHEN ALL 4 DG ARE WORKING IN PARALLEL WITH ONE GRID

¾ Fault contribution of one Grid for a fault on 6.6 KV bus

This condition considers both the infinite sources & both the transmission lines
but only a single power transformer & a single 6.6 KV incoming grid, keeping 132
KV bus coupler closed.

Total impedance of a single grid from infinite source to 6.6 KV panel:


0.00558837
= 0.002736729 + ------------------+ 0.092 + 0.0006780303
2
= 0.0982088 PU

Fault contribution of one grid = 15 / 0.0968405 = 153 MVA

¾ Fault contribution of all the four DG for a fault on 6.6 KV bus

The PU impedance of a single DG = 1.0770925 PU

Considering all four DG running in parallel, total PU impedance = 0.2692731 PU

Fault contribution of all DG running in parallel = 15 / 0.2692731


= 55.7 MVA
= 56 MVA (say)
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 121
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

¾ Fault contribution of all the HT motors for a fault on 6.6 KV bus

Considering normal working condition of the plant, total 4 no of 350 KW & 4 no of 250
KW motor are taken in to consideration for Fault contribution

Total PU impedance of a single 350 KW HT motor feeder


= 5.8285714 + 0.0436294
= 5.872200814 PU

Total PU impedance of a single 250 KW HT motor feeder = 8.16 + 0.0436294


= 8.2036294 PU

Total PU impedance of all HT motors = 5.872200814 / 4 || 8.2036294 / 4


= 0.8556042 PU

Fault contribution of all HT motor running in parallel = 15 / 0.8556042

= 17.53 MVA

= 18 MVA (say)

Total fault level on 6.6 kv bus for 2 GRID & 4 DG running in parallel = 227 MVA
This value is well within the bus bar short circuit rating of 350 MVA.

CONDITION C:

WHEN 5 DG ARE WORKING IN PARALLEL WITH ONE GRID

¾ Fault contribution of one Grid for a fault on 6.6 KV bus

This condition considers both the infinite sources & both the transmission lines but only a
single power transformer & a single 6.6 KV incoming grid, keeping 132 KV bus coupler
closed.
Total impedance of a single grid from infinite source to 6.6 KV panel:

0.00558837
= 0.002736729 + ------------------+ 0.092 + 0.0006780303
2
= 0.0982088 PU

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 122
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
Fault contribution of one grid = 15 / 0.0968405 = 153 MVA

¾ Fault contribution of all the 5 DG for a fault on 6.6 KV bus

The PU impedance of a single DG = 1.0770925 PU

Considering all 5 DG running in parallel, total PU impedance = 0.2154185 PU

Fault contribution of all DG running in parallel = 15 / 0.2154185


= 69.63 MVA
= 70 MVA (say)

¾ Fault contribution of all the HT motors for a fault on 6.6 KV bus

Considering normal working condition of the plant, total 4 no of 350 KW & 4 no of 250
KW motor are taken in to consideration for Fault contribution

Total PU impedance of a single 350 KW HT motor feeder = 5.8285714 + 0.0436294


= 5.872200814 PU

Total PU impedance of a single 250 KW HT motor feeder = 8.16 + 0.0436294


= 8.2036294 PU

Total PU impedance of all HT motors = 5.872200814 / 4 || 8.2036294 / 4


= 0.8556042 PU

Fault contribution of all HT motor running in parallel = 15 / 0.8556042 = 17.53 MVA


= 18 MVA (say)

Total fault level on 6.6 kv bus for 2 GRID & 4 DG running in parallel = 241 MVA

This value is well within the bus bar short circuit rating of 350 MVA.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 123
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

SR. SOURCE 6.6kV Fault current


NO CONDITION BUSBAR at 6.6KV
(MVA) BUSBAR (KA)
1 2G+4D+M 363 32.45
2 1G + 4D + M 227 19.85
3 4D + M 74 6.47
4 2G + M 307 26.85
5 5D + M 88 7.69
6 1G + 5D + M 241 21.08
7 3D + 2G + M 349 30.53

SUMMARY OF THREE PHASE FAULT LEVEL CALCULATIONS


ON 6.6 kV VOLTAGE LEVEL

WHERE,
G = GRID OR GUJARAT ELECTRICITY BOARD SUPPLY.
D = DIESEL GENERATOR SETS.
M = MOTOR.

From above results, we can conclude that, running two grid in parallel with four DG
SETS will create a fault level greater than rated 350 MVA fault level. Hence, it is
recommended to run a single grid in parallel with four DG SETS considering future
scope of one more DG.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 124
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

3.3.7.2 Three-phase Short-Circuit Calculation by Ohmic Method:

Step-1:
Most circuit component impedances are given in ohms except utility and transformer
impedances, which are found by the following formulae, (Note that the transformer and
utility ohms are referred to the secondary KV by squaring the secondary voltage.)

tXutility in Ohms = 1000 (kVsecondary)2 / S.C. kVAutility.

Step-2:
Xtransformer in Ohms = (10)*(%X)*(kVsecondary)2 / kVAtransformer.

Step-3:
The impedance (in Ohms) given for current transformer, large switches and large C.B. is
essentially all X.

Step-4:
Xcable and bus in Ohms.
Rcable and bus in Ohms.

Step-5:
Total all X and R in system to point of fault.

Step-6:
Determine impedance (in Ohms) of the system by:

Step-7:
Calculate short-circuit symmetrical RMS amperes at point of fault.

Step-8:
Determine the motor load. Add up the full load motor currents. The full load motor
current in the system is generally a percentage of the transformer full load current,
depending upon the types of loads. The generally accepted procedure assumes 50%
motor load when both motor and lighting loads are considered.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 125
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
Step-9:
The symmetrical motor contribution can be approximated by using an average
multiplying factor associated with the motors in the system. This factor varies according
to motor design and in this text may be chosen as 4 times motor full load current for
approximate calculation purposes. To solve for the symmetrical motor contribution:

Step-10:
The total symmetrical short-circuit RMS current is calculated as:

Step-11:
Determine X/R ratio of the system to the point of fault.

Step-12:
Calculate the asymmetrical RMS short-circuit current.

Step-13:
The short-circuit current that the motor load can contribute is an asymmetrical current
usually approximated as being equal to the locked rotor current of the motor. As a close
approximation with a margin of safety use:

Step-14:
The total asymmetrical short-circuit RMS current is calculated as:

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 126
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 127
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 128
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 129
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 130
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Case Study-2:
Sc=175 MVA (min fault MVA )
Sc=220 MVA (max fault MVA )

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 131
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Determinate the equivalent impedance network related to the 22 kV level (figure 12) and
calculate the fault currents, on the 22 kV voltage level. In the example all impedances
are considered to be pure reactances.

The short-circuit currents are calculated for different fault points in the system. This is
done for both maximum and minimum short-circuit capacity.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 132
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Three-phase short-circuit current:

The phase to phase short-circuit current can be found by multiplying the three
phase short-circuit current by a factor:

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 133
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

3.3.7.3 Three-phase Short-Circuit Calculation by Point-to-Point Method:

The application of the point-to-point method permits the determination of available short-
circuit currents with a reasonable degree of accuracy at various points for either 3ø or 1ø
electrical distribution systems. This method can assume unlimited primary short-circuit
current (infinite bus).

Basic Point-to-Point Calculation Procedure:


Step-1:
Determine the transformer full load amperes from either the nameplate or the following
formulas:

Step-2:
Find the transformer multiplier.

Note:
Transformer impedance (Z) helps to determine what the short circuit current will be at
the transformer secondary. Transformer impedance is determined as follows:

The transformer secondary is short-circuited. Voltage is applied to the primary, which


causes full load current to flow in the secondary. This applied voltage divided by the
rated primary voltage is the impedance of the transformer.

Example: For a 440 volt rated primary, if 18.0 volts causes secondary full load current to
flow through the shorted secondary, the transformer impedance is 18/440 = 0.0409 =
4.09%Z.

In addition, UL listed transformer 25KVA and larger have a ± 10% impedance tolerance.
Short circuit amperes can be affected by this tolerance.

Step-3:
Determine the transformer short-circuit current;

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 134
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Note:
Motor short-circuit contribution, if significant, may be added to the transformer secondary
short-circuit current value as determined in Step 3. Proceed with this adjusted figure
through Steps 4, 5 and 6. A practical estimate of motor short-circuit contribution is to
multiply the total motor current in amperes by 4.

Step-4:
Calculate the "f" factor.

Where:
L = length (feet) of circuit to the fault.
C = constant from Table 6, page 27. For parallel runs, multiply C values by the number
of conductors per phase.
I = available short-circuit current in amperes at beginning of circuit.

Note:
The L-N fault current is higher than the L-L fault current at the secondary terminals of a
single-phase center-tapped transformer. The short-circuit current available (I) for this
case in Step 4 should be adjusted at the transformer terminals as follows:

At L-N center tapped transformer terminals,

I = 1.5 x L-L Short-Circuit Amperes at Transformer Terminals

At some distance from the terminals, depending upon wire size, the L-N fault current is
lower than the L-L fault current. The 1.5 multiplier is an approximation and will
theoretically vary from 1.33 to 1.67. These figures are based on change in turns ratio
between primary and secondary, infinite source available, zero feet from terminals of
transformer, and 1.2 x %X and 1.5 x %R for L-N vs. L-L resistance and reactance
values. Begin L-N calculations at transformer secondary terminals then proceed point-to-
point.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 135
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Step-5:
Calculate "M" (multiplier).

Step-6:
Calculate the available short-circuit symmetrical RMS current at the point of fault.

Calculation of Short-Circuit Currents at Second Transformer in System:

Use the following procedure to calculate the level of fault current at the secondary of a
second, downstream transformer in a system when the level of fault current at the
transformer primary is known.

Procedure for Second Transformer in System:

Step-1:
Calculate the "f" factor (IS.C. primary known)

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 136
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
Step-2:
Calculate "M" (multiplier).

Step-3:
Calculate the short-circuit current at the secondary of the transformer. (See Note under
Step 3 of "Basic Point-to- Point Calculation Procedure".)

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 137
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 138
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

3.3.7.4
1ø Short-Circuit Current Calculations – 1ø Transformer System:

Procedures and Methods:


Short-circuit calculations on a single-phase center tapped transformer system require a
slightly different procedure than 3Ø faults on 3Ø systems.

1.
It is necessary that the proper impedance be used to represent the primary system. For
3Ø fault calculations, single primary conductor impedance is only considered from the
source to the transformer connection. This is compensated for in the 3Ø short-circuit
formula by multiplying the single conductor or single-phase impedance by 1.73.

However, for single-phase faults, primary conductor impedance is considered from the
source to the transformer and back to the source. This is compensated in the
calculations by multiplying the 3Ø primary source impedance by two.

2.
The impedance of the center-tapped transformer must be adjusted for the half-winding
(generally line-to-neutral) fault condition.

The diagram at the right illustrates that during line-to-neutral faults, the full primary
winding is involved but, only the half-winding on the secondary is involved. Therefore,
the actual transformer reactance and resistance of the half winding condition is different
than the actual transformer reactance and resistance of the full winding condition.

Thus, adjustment to the %X and %R must be made when considering line-to-neutral


faults. The adjustment multipliers generally used for this condition are as follows:

1.5 times full winding %R on full winding basis.


1.2 times full winding %X on full winding basis.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 139
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

3.
The impedance of the cable and two-pole switches on the system must be considered
"both-ways" since the current flows to the fault and then returns to the source. For
instance, if a line-to-line fault occurs 50 feet from a transformer, then 100 feet of cable
impedance must be included in the calculation.

The calculations on the following pages illustrate 1ø fault calculations on a single-phase


transformer system. Both line-to-line and line-to-neutral faults are considered.

Note in these examples:


a).
The multiplier of 2 for some electrical components to account for the single-phase fault
current flow.

b).
The half-winding transformer %X and %R multipliers for the line-to-neutral fault situation.

c).
The KVA and voltage bases used in the per-unit calculations.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 140
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 141
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 142
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 143
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 144
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Comparison of Results:
Per-Unit Method vs. Point-to-Point Method
Per-Unit PTP
Method Method
X1
Line-Line 16,984A 18,453A
Line-Neutral 20,041A 20,555A

Impedance and Reactance Data–Transformers and Switches:

This table has been reprinted from IEEE Std 141-1986, IEEE Recommended Practice
for Electric Power Distribution for Industrial Plants, Copyright© 1986 by the Institute of
Electrical and Electronics Engineers, Inc with the permission of the IEEE Standards
Department.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 145
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Impedance Data for Three Phase Transformers:

Impedance Data for Single Phase Transformers:

National standards do not specify %Z for single-phase transformers. Consult


manufacturer for values to use in calculation.

Based on rated current of the winding (one–half nameplate kVA divided by secondary
line-to-neutral voltage).

Note:
UL Listed transformers 25 KVA and greater have a ± 10% tolerance on their impedance
nameplate.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 146
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
This table has been reprinted from IEEE-Std 242-1986 (R1991), IEEE Recommended
Practice for Protection and Coordination of Industrial and Commercial Power Systems,
Copyright© 1986 by the Institute of Electrical and Electronics Engineers, Inc. with the
permission of the IEEE Standards Department.

Impedance Data for Single Phase and Three Phase:

These represent actual transformer nameplate ratings taken from field installations.

Note:
UL Listed transformers 25KVA and greater have a ±10% tolerance on their impedance
nameplate.

Current Transformer Reactance Data:


Approximate Reactance of Current Transformers

Note:
Values given are in ohms per phase. For actual values, refer to manufacturers' data.
This table has been reprinted from IEEE Std 241-1990, IEEE Recommended Practice
for Commercial Building Power Systems, Copyright© 1990 by the Institute of Electrical
and Electronics Engineers, Inc. with the permission of the IEEE Standards Department.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 147
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Disconnecting Switch Reactance Data:


Disconnecting-Switch Approximate Reactance Data, in Ohms

Note:
The reactance of disconnecting switches for low-voltage circuits (600V and below) is in
the order of magnitude of 0.00008 - 0.00005 ohm/pole at 60 Hz for switches rated 400 -
4000 A, respectively.

For actual values, refer to manufacturers’ data.

This table has been reprinted from IEEE Std 241-1990, IEEE Recommended Practice
for Commercial Building Power Systems, Copyright© 1990 by the Institute of Electrical
and Electronics Engineers, Inc. with the permission of the IEEE Standards Department.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 148
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
3.3.7.5
INTRODUCTION: RELAY CO-ORDINATION STUDY

Relay co-ordination procedure is used for power system protection. Power system
protection engineering deals with precautionary measures to be taken to safeguard the
power system during abnormal operating conditions.

The practice of protection engineering involves periodic fault studies followed by relay
setting, checking and co-ordination studies.

The Protection philosophy is to adopt a mainly Primary Protection & Backup Protection.

PRIMARY PROTECTION & BACKUP PROTECTION:


-Æ Primary Protection: Device Closest to the Fault.
-Æ Backup Protection: Device next in the line.
-Æ Backup protection should be Operates, If the primary protection fails.
-Æ Reason for Providing Back up Protection;
• Failure of primary protection:
-Æ Mal-operation of the relay.
-Æ Incorrect system design.
-Æ Wrong selection of the relay.
-Æ Improper installation and maintenance.

• Circuit Breaker failure (Stuck breaker)

Ideal backup protection would be completely independent of the main protection. Current
transformers, Voltage transformers, auxiliary tripping relays, trip coils and dc supplies
would be duplicated.

The following compromises are typical;


-Æ Separate current transformers are used for each protective system as this involves
little extra cost.
-Æ Common voltage transformers are used.
-Æ Trip supplies to the two protections should be separately used.

Why do we need to coordinate protective relaying system?

It is evident that in spite of all precautions taken in the design & installation of electrical
power / distribution systems, there are bound to arise abnormal conditions or faults
some of which like short circuits may prove extremely damaging to not only the faulty
component but to the neighboring components & to the power system as a whole. It is of
vital importance to limit the damage to a minimum by speedy isolation of the faulty
section, without disturbing the working of the rest of the system.

It is obvious that faster the speed of operation of elements of protective system (relay &
breaker), less is the damage to the equipment. The time setting of the relays has to be
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 149
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
decided based on the short time rating of the equipments to be protected. More over if
the faults are not cleared within the time, the generator may go out of step and complete
shut down of all the generator may occur resulting in to total dark-out. On the same way
relay should not be made extremely fast, as otherwise the relays may operate
unnecessarily for transient conditions

Protective system should be able to discriminate between fault & load condition even
when the minimum fault current is less than the maximum load current. The relay should
be able to distinguish between over load & over current.

Only faulty element of the system should be isolated & healthy section should be left
intact. This selectivity can be obtained by grading of protections of several zones.

All the above can be achieved by proper coordination of protective relaying


system of different zones. The relay coordination is one of the ways through
which the system can become more stable & more reliable.

The following points may be considered while co-coordinating the operation of different
releases / relays in a radial system.

• Circuit Breaker Interrupting Time


• Release overshoot
• Release operating time error
• Final safety margin
The discrimination time between two electro-mechanical relays are as shown below;
T = ( 0.4t + 0.2 ) in second
The discrimination time between two numerical relays are as shown below;
T = ( 0.4t + 0.15 ) in second
Where “t” is the operating time of fuse and 0.4*t is the discrimination time between fuse
& breaker.

The discrimination time between two electro-mechanical relays are as shown below;
T = ( 0.25t + 0.2 ) in second
The discrimination time between two numerical relays are as shown below;
T = ( 0.25t + 0.15 ) in second
Where “t” is the operating time of fuse and 0.25*t is the discrimination time between
breaker & breaker.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 150
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
The time interval according to ANSI/ IEEE Std-242: 1986 is usually 0.3 to 0.4 seconds.
This interval is measured between relays in series either at the instantaneous setting of
the load side feeder circuit breaker relay or the maximum short circuit current which can
flow through both devices simultaneously, whichever is lowest. The recommended time
has the following components:
• Circuit breaker opening time (3 cycles): 0.06 seconds
• Relay over-travel or Overshoot: 0.10 seconds
• Safety factor for CT saturation, setting errors, etc.: 0.22 seconds

An over current Protections are used for the feeder protections because of economical
cost and more simplicity. An over current relay operates when the magnitude of the
current exceeds it’s preset value. Normally, various types over current protection with
various characteristics are used for feeder protection as mention below;

• Standard Normal inverse (3.0s at 10times of PS),


T in second = [0.14 / ((PSM)0.02 – 1)]* TMS
• Standard Very inverse (1.5s at 10times of PS),
T in second = [13.5 / ((PSM) – 1)]* TMS
• Standard extremely inverse(0.8s at 10times of PS),
T in second = [80 / ((PSM)2 – 1)]* TMS
• Standard long inverse(17s at 10times of PS),
T in second = [120 / ((PSM) – 1)]* TMS
• IEEE Normal inverse,
• IEEE Moderately inverse,
• IEEE very inverse,
• IEEE extremely inverse,
• IEEE short time inverse,
• IEEE long time inverse.

Earlier in electro-mechanical protection, one relay is used with only one characteristic
like CDG-11 has Normal inverse characteristic, CDG-12 has long inverse characteristic,
CDG-13 has Very inverse characteristic, CDG-14 has Extremely inverse characteristic.
But, now today modern numerical protection (like SPAJ-140C, 7SJ600, 7SJ61, IM30-AP,
P123, SEL-501 etc.) have more than one characteristics so, now, today we have better
selectivity and ranges which is given a better relay co-ordination.

Application of Extremely Inverse Time Over-current Relay:


It is sometimes difficult to find an inverse time relay having characteristics are not
suitable to grade with fuses because of characteristic curve is not close with defined fuse
characteristic.

Extremely inverse characteristic is very close with fuse operating characteristics as


shown in figure(1A).

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 151
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Figure (1A):- IEC CURVES

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 152
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Figure (1B):- IEEE CURVES at TD=7.0

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 153
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

3.3.7.6
Functional Characteristics:

Three essential characteristics of the protective relaying:


1) Sensitivity
2) Selectivity
3) Speed

1) Sensitivity:

-Æ Pickup Setting must be greater than maximum load current in circuit.


-Æ Lower the pickup of the relay more will be the sensitivity.
-Æ Relay should be able to detect minimum fault current.

Example:
----Æ Fault current magnitude = 35kA
----Æ CTR = 3000/1
----Æ Relay Pickup, set at 75%
Relay Operating current on Primary side = (75/100)*(3000) = 2250 Amp
Relay Operating current on Secondary side = (75/100)*(1) = 0.75 Amp
Sensitivity of relay during a fault = (2250/35000)*100 = 6.42%

----Æ Relay Pickup, set at 100%


Relay Operating current on Primary side = (100/100)*(3000) = 3000 Amp
Relay Operating current on Secondary side = (100/100)*(1) = 1.0 Amp
Sensitivity of relay during a fault = (3000/35000)*100 = 8.57%

Thus, lower the setting, higher will be the sensitivity for fault detection.

2) Selectivity:

Three methods to achieve the discrimination


5) Discrimination by Time
6) Discrimination by current
7) Discrimination by both Time & current
8) Direction of the fault current

5) Discrimination by Time:
• Basically used with definite time relays
• Time of operation is independent of current magnitude
• Discrimination time between successive relays say 0.3 sec

EXAMPLE:
• For fault on one outgoing feeder3
• Fuse Operates in 0.01s
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 154
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
• Next feeder2 relay operates in 0.25s
• Next feeder1 relay operates in 0.50s
• All upstream relays are graded accordingly

DISADVANTAGE:
• Operating time of the upstream relays will be very high
• The fault closest to the source takes longest time to clear

ADVANTAGE:
• Defined operating time for variable source operating condition.

6) Discrimination by Current:
• Applicable only when substantial difference between the fault current
magnitudes exist for the faults on the two ends of the equipment.
• The impedance of the equipment shall be substantial that will create the
above difference.

EXAMPLE:
• For the fault on the L.T. side of transformer TR
• Fault current = 40,000 A @ 415V
= 1509.09 A @ 11kV (Reflected fault on 11kV side)
• For the fault on the H.T. side of Transformer TR
• Fault current = 13.5 kA @ 11kV
• IDMTL unit of Transformer Primary side (11kV) relay should be operate
as a backup protection on L.T. fault
• HIGHSET unit of Transformer Primary side (11kV) relay should be
operate on H.T. fault

DISADVANTAGE:
• The discrimination is obtained but no backup ensured

7) Discrimination by both Time & Current:


• Obtained using Inverse time relays (IDMTL)
• IDMTL – Inverse definite minimum time lag
• Relay operating time varied by adjusting time dial & current setting
• Relay operating time depends on fault current. Higher fault, less operating
time. Operating time inversely proportional to current magnitude
• Discrimination achieved by both current & time

EXAMPLE:
• For a given fault current magnitude, discrimination time is 0.3s for all the
successive relays
• Pickup value for all the relays set below the fault current level
• For the fault on the outgoing feeder-1
• Fault current = 40,000 A @ 415V
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 155
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
= 1509.2 A @ 11kV (Reflected fault current on H.T. side)
• 250 A fuse operates in 0.01s
• Next feeder-2 relay operates in 0.25s on L.T. side fault
• Next feeder-3 relay operates in 0.5s on L.T. side fault
• Next feeder-4 relay operates in 0.75s on L.T. side fault
• For H.T. side of the Transformer TR
• Fault current = 13.5 kA @ 11kV
• Same Feeder-4 relay operates in 0.25s on H.T. faults

ADVANTAGE:
• With the same Pickup & Time dial settings, lower Tome of operating for
near end faults and higher operating times for near end faults inherently
achieved.
• In case of the difference in the fault current magnitude along system,
IDMTLL relays are superior to the DMT relays
• In case of same fault current magnitude along system, desired operating
time can be achieved by adjusting pickup & time dial

8) SPEED:
• Speed: the clearance time of the fault
• Fault clearing time < 100ms, high speed tripping
• Necessity of high speed tripping:
• Minimizing the damage of the equipment
• Increasing stability margin for synchronous machines
• Avoiding unwanted tripping of voltage sensitive loads

• Speed without sensitivity: Unsatisfactory co-ordination


• Methods to achieve high-speed tripping:
• Unit protection:
1) Protection provide to trip instantaneously for faults only within unit
under protection
2) No time co-ordination with external protections
• Example:
• Bus differential protection
• Feeder pilot wire protection
• Transformer or motor protection
• Directional protection
• Restricted earth fault protection

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 156
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

3.3.7.7
CRITERIAS FOR PICKUP SETTING & TIME DIAL:

Proper selection of Pickup & Time dial setting is essential.

DMT RELAYS:
• Primary Operating Current:
• Setting must be above maximum running load current and largest drive
starting current by safety margin.
• Setting must be below the lowest through fault current.
• Maximum load current includes motor full load current. Hence, it is
subtracted.
• Relevant for generally used DOL Starting.
• Formula;
o If > P.O.C > (IRL + ISTM – IFLM)

Where,
P.O.C. = Desired Primary Operating Current of relay
IRL = Maximum running load current
ISTM = Highest rating drive starting current
IFLM = Highest rating drive full load current
IF = Minimum fault current relay to sense

• Over Load Pickup setting:


o Pickup > (Primary operating current) / C.T. RATIO

IDMTL RELAYS:
• Generally the pickup setting is available in steps (not continuously) in
electromechanical relays & variable in numerical relays.
• Not possible to get the exact set point value.
• Select the next higher available step.
• PSM > 2 for IDMT Relays
• DMT Relays: Independent of fault current.

Step:-1
• Primary operating current:
o P.O.C. = (IRL + ISTM – IFLM)

Where,
P.O.C. = Desired primary operating current
IRL = Maximum running load current
ISTM = Highest drive starting current
IFLM = Highest drive full load current

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 157
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Step:-2
Plug setting (PS) = (P.O.C.) / (C.T.R) = [ (IRL + ISTM – IFLM) / C.T.R. ]

Selected Pickup setting: Select the next higher available step.

Step:-3
Actual Primary Operating current (P.O.C.) = Selected Pickup setting * C.T.R.

Step:-4
Plug setting Multiplier (PSM) = Fault current / Actual P.O.C.

Step:-5
Desired relay Operating time (t) = td + T

Where, td = Discrimination time & T = Downstream relay/fuse operating time

Step:-6
Based on formula or curves, Calculate the relay operating time at TMS1.0 on PSM

Step:-7
Desired Time Dial Set point (TMS) = { (Desired relay Operating time) / (Relay operating
time at TMS1.0) }

Select time dial setting: Nearest higher time dial setting selected

Example:
Relay type: CDG31 (3.0s at 10times) & CDG31 (1.3s at 10 times)

• Operating time at PSM = 10, & TMS = 1.0 is 3.0s / 1.3s


• For given change in time dial (Delta-TMS)-Æ Operating time of 3.0s relay
is more than 1.3s relay. So, the closer relay co-ordination will be achieved
by 1.3s relay.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 158
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

3.3.7.8
DATA REQUIRED TO PERFORM O/C & E/F RELAY CO-ORDINATION STUDY:

1. Power, voltage ratings, impedance, and connection configurations of all transformers


included in the system to be analyzed.

2. Normal and emergency switching/steady state conditions.

3. Nameplate data from all protective devices included in study; i.e., manufacturer’s
Catalog number, voltage/current, and IEC ratings.

4. Trip device type-range and current setting.

5. Conductor sizes, types, configurations, and temperature ratings.

6. Current transformer ratios.

7. Utility equipment rating and device settings.

8. Existing System one-line diagram.

REQUIRED DATA OF TRANSFORMER:

¾ MVA rating
¾ Primary and secondary voltage rating
¾ Percentage impedance [%Z] on the given MVA rating for
positive and zero sequence [%Z1 and %Z0]
¾ X/R Ratio for positive and zero sequence
¾ Winging connection and Neutral Grounding Reactance /
Resistance if any
¾ Tap data for both fixed taps and LTC taps, minimum and
maximum %tap position and steps size for LTC

REQUIRED DATA OF LINE / CABLE:

¾ Cable/Conductor type
¾ Cable length [ more than 100 Mt ] and cable size
¾ Resistance [ohm], Reactance [ohm] and Susceptance [mho]
per Km for both positive and zero sequence values.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 159
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

REQUIRED DATA OF MOTOR:

¾ KW rating
¾ MVA rating
¾ Rated RPM
¾ Rated current [ I ]
¾ Rated kV
¾ Starting current [ Ist ]
¾ No load current [ I0 ]
¾ Rotor resistance and reactance in ohm [ R2 & X2 ]
¾ Stator resistance and reactance in ohm [ R1 & X1 ]
¾ Magnetizing reactance in ohm
¾ Type of starting
¾ Motor performance characteristics

REQUIRED DATA OF GENERATOR:

¾ MW rating
¾ Voltage rating
¾ Direct axis reactance [ Xd ] in % or p.u.
¾ Quadrature axis reactance [ Xq ] in % or p.u.
¾ Direct axis transient reactance [ Xd’ ] in % or p.u.
¾ Quadrature axis transient reactance [ Xq’ ] in % or p.u.
¾ Direct axis sub-transient reactance [ Xd” ] in % or p.u.
¾ Quadrature axis sub-transient reactance [ Xq” ] in % or p.u.
¾ Synchronous reactance [ Xs ] in % or p.u.
¾ Negative phase sequence reactance [ X2 ] in % or p.u.
¾ Zero phase sequence reactance [ X0 ] in % or p.u.
¾ Transient time constant ( short circuit ) [ Td’ ] in seconds
¾ Sub-transient time constant ( short circuit ) [ Td” ] in
seconds
¾ Generator Reactive capacity curve, if available
¾ Generator negative phase sequence withstand capacity
curve
¾ Over-voltage and under-voltage withstand capacity
¾ Over-frequency and under-frequency withstand capacity

REQUIRED DATA OF RELAYS:

¾ Relay type, model and manufacturer’s name


¾ CT rating/ratio
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 160
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
¾ Plug setting range
¾ Time dial setting range
¾ Relay characteristic curve details
¾ Instantaneous setting data or Range.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 161
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

3.3.7.9
EXAMPLE FOR PHASE FAULT RELAY SETTING:-

Figure:- circuit diagram

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 162
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

IMPEDANCE CALCULATION:
Base MVA = 500
Base kV = 11

Step:-1
Source Impedance (Zs) = (500 / 500)*100 = 100%

Step:-2
Impedance of Cable (Z’c1 in Ohms) = ( (0.042)2 + (0.086)2 )0.5 = 0.096 Ohms

Length of cable = 2kM & number of parallel path = 5

Total Impedance of Cable (Zc1 in Ohms) = (0.096*2 / 5) = 0.038 Ohms

Value on Base MVA


(Zc1 in PU) = [ (0.038 * 500) / (11)2 ]* 100 = 15.7%

Step:-3
Impedance of reactor (Zr1 in PU) = (4 * 500) / (20) = 100%

Step:-4
Impedance of Cable (Z’c2 in Ohms) = ( (0.128)2 + (0.093)2 )0.5 = 0.1582 Ohms

Length of cable = 1kM & number of parallel path = 1

Value on Base MVA


(Zc2 in PU) = [ (0.1582 * 500) / (11)2 ]* 100 = 65.37%

Step:-5
Impedance of Cable (Z’c3 in Ohms) = ( (0.128)2 + (0.093)2 )0.5 = 0.1582 Ohms

Length of cable = 1kM & number of parallel path = 1

Value on Base MVA


(Zc3 in PU) = [ (0.1582 * 500) / (11)2 ]* 100 = 65.37%

Step:-6
Zc2 II Zc3, so total
(Zc4 in PU) = [ (0.1582 * 500) / (11)2 ]* 100 = 65.37/2 = 32.68%

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 163
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Fault Calculation:

1) Fault at Bus C:

CONDITION:-A
Both “C2” & “C3” cables are running in parallel

SC MVA at Bus C = (500) / (1 + 0.157 + 1 + 0.3268 ) = (500) / (2.4838 ) = 201.3MVA

SC current (IkA) = (201.3) / (1.73 * 11) = 10.56 kA

CONDITION:-A
Only “C2” cables are running

SC MVA at Bus C = (500) / (1 + 0.157 + 1 + 0.65 ) = (500) / (2.807 ) = 178MVA

SC current (IkA) = (178) / (1.73 * 11) = 9.33 kA

2) Fault at Bus B:

SC MVA at Bus B = (500) / (1 + 0.157 + 1 ) = (500) / (2.157) = 231.8MVA

SC current (IkA) = (231.8) / (1.73 * 11) = 12.16 kA

3) Fault at Bus A:

SC MVA at Bus A = (500) / (1 + 0.157 ) = (500) / (1.157) = 432.1MVA

SC current (IkA) = (432.1) / (1.73 * 11) = 22.68 kA

¾ Relay (F1/F2) –51–Extremely Inverse –0.8 sec

These relays perform overcurrent protection of the cable feeders, Busbar C and backup-
protection to relays F1, F2 and their associated fuses FS1 and FS2. The settings for
Relays 1 and 2 will be identical, so calculations will only be performed for Relay 1.
Consider first the current setting of the relay.

Relay 1 must be able to reset at a current of 400A – the rating of the feeder. The relay
has a drop-off/pick-up ratio of 0.95, so the relay current setting must not be less than
400/0.95, or 421A. A suitable setting that is greater than this value is 450A. The current
setting should be three times the largest fuse rating (i.e. 3 x 160A, the rating of the
largest fuse on the outgoing circuits from Bus bar C), leading to a current setting of 480A,
or 96% of relay rated primary current. Note that in this application of relays to a

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 164
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
distribution system, the question of maximum and minimum fault levels are probably not
relevant as the difference between maximum and minimum fault levels will be very small.
However in other applications where significant differences between maximum and
minimum fault levels exist, it is essential to ensure that the selection of a current setting
that is greater than full load current does not result in the relay failing to operate under
minimum fault current conditions. Such a situation may arise for example in a self-
contained power system with its own generation. Minimum generation may be
represented by the presence of a single generator and the difference between minimum
fault level and maximum load level may make the choice of relay current settings difficult.

The grading margin now has to be considered. For simplicity, a fixed grading margin of
0.3s between relays is used in the calculations. Between fuse and relay, Equation (0.4t +
0.15), and with fuse FS2 pre-arcing time of 0.01s (from Figure 1(C) & 1(D)), the grading
margin is 0.154s.

Consider first the IDMT overcurrent protection. Select the EI characteristic, as fuses
exist downstream, to ensure grading. The relay must discriminate with the longest
operating time between relays F1, F2 and fuse FS2 (being the largest fuse) at the
maximum fault level seen by relays 1 and 2. The maximum fault current seen by relay 1
for a fault at Busbar C occurs when only one of cables C2, C3 is in service. This is
because the whole of the fault current then flows through the feeder that is in service.
With two feeders in service, although the fault level at Busbar C is higher, each relay
only sees half of the total fault current, which is less than the fault current with a single
feeder in service. With EI characteristics used for relays F1 and F2, the operating time
for relay F1 is 0.02s at TMS=0.1 because the fault current is greater than 20 times relay
setting, at which point the EI characteristic becomes definite time and 0.05s for relay F2
(TMS=0.25).

¾ Relay (R1) & Relay (R2) –51–Extremely Inverse –0.8 sec


Relay (R1) must be co-ordinate with Fuse.

Plug settings

Phase fault setting:


CTR = 500/1A
Relay setting = 480 A
%Loading on CT = 480 / 500 = 0.96.
The full load current is 96 % of CT primary.
So selected setting is on secondary side = 0.96*5 = 4.8 Amp.

Time multiplier settings:

Phase fault setting:

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 165
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Condition:-1
The required time of operation of relay = 0.3 + 0.05 = 0.350 Seconds.
The 3- phase fault current at 11 V bus C is 9.33 kAmp.
Plug Setting Multiplier (PSM) = 9.33 *103 / 480 = 19.43
Time of operation at TMS1.0 = (80*1.0) / ((19.43)2 – 1)) = 0.212 Seconds

Require TMS = 0.35 / 0.21 = 1.64

This setting is outside the range of relay, so it is require to be changed by increasing


current setting value.

Now, new setting is 125% of CT primary = 500*1.25 = 625 A


New PSM = 9330 / 625 = 14.98
Time of Operation at new PSM on TMS1.0 = (80*1.0) / ((14.98)2 – 1)) = 0.358s
Require TMS = 0.35 / 0.358 = 0.98

Condition:-2
Fault current = 5.3 kA while two feeders (c2 & c3) are running in parallel
PSM at Fault current = 5.3*1000 / 625 = 8.48
Time of Operation at TMS1.0 = 1.12s
Actual Operating time at selected TMS = 1.12*0.98 = 1.09s

¾ Relay (R3) –51- Extremely Inverse –0.8 sec


Relay (R3) must be co-ordinate with Relay (R1 & R2)

Plug settings

Current Setting:
Full load current (Ifl) of feeder is = 1000A
CTR = 1000/5A
Plug setting Amp. Of Relay = (Ifl) / (CT primary *0.95) = 1052.0 Amp
Plug setting of Relay = 106% = 1000 * 1.06 = 1060 Amp
So the selected setting on CT secondary side = 1.06*5 = 5.3 Amp.

Two possibilities of faults are as below;


1. for a fault just beyond relays 1 and 2 where the fault current will be the
busbar fault current of 12.2kA
2. for a fault at Bus C where the fault current seen by either relay 1 or 2 will
be half the total Bus C fault current of 10.56kA, i.e. 5.28kA

Condition:-1
Set value = 1060 A
Fault Current = 12.2 kA
PSM = 12200 / 1060 = 11.50

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 166
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
Time of Operation at TMS1.0 = (80*1.0) / ((11.50)2 – 1)) = 0.609s
Require time of Operation = 0.35 + 0.21 = 0.51s
Require TMS = 0.51 / 0.609 = 0.8367 = Say (0.84)

Condition:-2
Set value = 1060 A
Fault Current = 10.56 kA
PSM = 10560 / 1060 = 9.96
Time of Operation at TMS1.0 = (80*1.0) / ((9.96)2 – 1)) = 0.8146s
Time of operation at TMS = 0.8146*0.84 = 0.6842s which is less than (R1 & R2 time)

So, It is require to be change;


set value = 1.06*1000 = 1060 Amp
New PSM = 5300 / 1060 = 5.0
Time of Operation at TMS1.0 = 3.36s
Require TMS = 1.12 / 3.36 = 0.33

Highset setting: 1.3*12.2 = 15.86 kA which is greater than L.T. fault current so, it
is not operate in through fault condition.

¾ Relay (R4) –51- Standard Inverse –3.0 sec


This must grade with relay 3 and relay 5. The supply authority requires that relay 5 use
an SI characteristic to ensure grading with relays further upstream, so the SI
characteristic will be used for relay 4 also. Relay 4 must grade with relay 3 at Bus A
maximum fault level of 22.7kA. However with the use of an instantaneous high set
element for relay 3, the actual grading point becomes the point at which the high set
setting of relay 3 operates, i.e. 15.86kA. At this current, the operation time of relay 3 is

[(80) / ((14.96)2 – 1)]*0.85s = 0.305s

Thus, relay 4 required operating time is 0.305 + 0.3 = 0.605s at a fault level of 15.86kA.
Relay 4 current setting must be at least (2800) / (3000 * 0.95) = 98%

For convenience, use a value of 100% (=3000A). Thus relay 4 must operate in 0.605s at
15860/3000 = 5.29 times setting. Thus select a time multiplier setting of 0.15, giving a
relay operating time of 0.62s for a normal inverse type characteristic.

At this stage, it is instructive to review the grading curves, which are shown in Figure
1(C). While it can be seen that there are no grading problems between the fuses and
relays 1/2, and between relays F1/2 and relays 1/2, it is clear that relay 3 and relay 4 do
not grade over the whole range of fault current. This is a consequence of the change
in characteristic for relay 4 to SI from the EI characteristic of relay 3 to ensure grading of
relay 4 with relay 5. The solution is to increase the TMS setting of relay 4 until correct
grading is achieved. The alternative is to increase the current setting, but this is
undesirable unless the limit of the TMS setting is reached, because the current setting

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 167
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
should always be as low as possible to help ensure positive operation of the relay and
provide overload protection. Trial and error is often used, but suitable software can
speed the task – for instance it is not difficult to construct a spreadsheet with the
fuse/relay operation times and grading margins calculated. Satisfactory grading can be
found for relay 4 setting values of:

Iset4 = 1.0 or 3000A


TMS = 0.275
At 22.7kA, the operation time of relay 4 is 0.93s. The revised grading curves are shown
in Figure 1(D).

¾ Relay (R5) –51- Standard Inverse –3.0 sec


Relay 5 must grade with relay 4 at a fault current of 22.7kA. At this fault current, relay 4
operates in 0.93s and thus relay 5 must operate in 0.3 + 0.93 = 1.23s at 22.7kA. A
current setting of 110% of relay 4 current setting (i.e. 110% or 3300A) is chosen to
ensure relay 4 picks up prior to relay 5. Thus 22.7kA represents 6.88 times the setting of
relay 5. Relay 5 must grade with relay 4 at a fault current of 22.7kA, where the required
operation time is 1.23s. At a TMS of 1.0, relay 5 operation time is

[(0.14*1.0) / ((6.88)0.02 – 1)] = 3.56s


Therefore, the required TMS is 1.23/3.56 = 0.345, use 0.35 nearest available value.

Figure:-1 (C) Initial grading curves

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 168
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Figure:-1 (D) revised initial grading curves

Figure:- 1 (E) Final curves

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 169
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

3.3.7.10
EXAMPLE CALCULATION FOR DMT (Definite Minimum time) RELAYS:

TRANSFORMER CAPACITY = 1000 KVA

PRIMARY VOLTAGE = 11KV

SECONDARY VOLTAGE = 0.415KV

PRIMARY CURRENT = 52.54 Ampere

SECONDARY CURRENT = 1392.8 Ampere

CTR = 1600 / 1A

HIGHEST DRIVE RATING = 100KW

FUL LOAD CURRENT OF HIGHEST DRIVE = 174 Ampere

RELAY TYPE = SPAJ140C

SPAJ140C relay having both characteristics DMT & IDMT, but here only DMT is used

Pickup range = (0.5 – 5.0)*In insteps of 0.1*In

Time delay = 0.05 – 300s insteps of 0.01s

Fault current = 40kA

Desired Pickup setting > (IRL + ISTM – IFLM) / CTR


> (600 + 870 – 174) / 1600
> 0.81

Allow 30% margin for minimum desired pickup setting because, 10% for safety & 20%
for impedance & voltage variation etc.

Pickup setting > 1.3 * 0.81 = 1.053

Set relay on 1.1*In

Desired time delay (t) = td + T = (0.4t1 + 0.15) + T


= (0.4*0.01 + 0.15) + 0.01
= 0.164s

Set time delay at 0.17s.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 170
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

3.3.8
Application:

Dynamic Testing of Relay by using DOBLE power system model & F6150 Power
system simulator:

FRONT-VIEW OF DOBLE F6150 SOFTWARE BASED PROTECTION TESTING SIMULATOR

POWER SYSTEM MODEL IN SOFTWARE:


It is used for automatic calculate a various fault conditions like 3-ph, ph-ph, ph-g, D-L-G
faults.

All Data are taken from generator data-sheet.

Make: Brush Electric Machine, USA


Rated MVA = 35
Rated V = 11kV
Fault Current = 1840A
Number of Machines = 2.0
Unsaturated direct axis Transient reactance of Machine(Xd') = 24.3%
Unsaturated Negative sequence reactance of machine(X2) = 21%
Zero sequence reactance of machine = 6.5%
Zero sequence resistance of machine = 0.914%
Consider only One NGR on circuit.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 171
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
Fault condition is considered as two machines are run in parallel on same bus and fault
is occurred on same bus. So, i have not considered any line data.

3.3.8.1
CASE:-1

---->PRIMARY OHMS TAB:

NEAR END FAR END

Res. in PU Reactance in PU Res. in PU React. in PU

Positive Sequence Imp.(Xd') 0.000 0.243 0.000 0.243


Negative Sequence Imp.(X2) 0.000 0.211 0.000 0.211
Zero Sequence Imp.(X0) 0.009 0.065 0.009 0.065

MVA = 35

kV = 11

CT Ratio : 2000 or 2000 / 1A

PT Ratio : 100 or 11000 / 110V

Method Used for Calculation = Per Unit.

Software calculated value of Base Impedance Value = 3.5 Ohms.

---->RESULT TAB:

Fault Type = 3-PH Fault.


Location = 100%

Grd. Resistance = 0.0


Arc Resistance = 0.0
Load Angle = 0.0

Source voltage consider as a PT secondary Volt:

Near End = 110/1.7325 = 63.5V


Far End = 110/1.7325 = 63.5V

Consider as a Radial Model OFF

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 172
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Output calculated DATA of Fault voltage and current are;

NEAR END FAR END

MAG. PH. MAG. PH.


VA 0.00 0.0 0.00 0.0
VB 0.00 0.0 0.00 0.0
VC 0.00 0.0 0.00 0.0
I1 3.779 270.0 3.779 270.0
I2 3.779 150.0 3.779 150.0
I3 3.779 30.0 3.779 30.0

CASE:-2

Now, changed Grd. Resistance fron 0.0 to 1.0 Ohm.


If you want to use your formulas with a Ground Resistance of 1.0 Ohm secondary, you may use
radial line model:

Fault Type = 3-PH Fault.


Location = 100%

Grd. Resistance = 1.0


Arc Resistance = 0.0
Load Angle = 0.0

Source voltage consider as a PT secondary Volt:

Near End = 110V / 1.732 = 63.51V

Consider as a Radial Model ON

Output calculated DATA of Fault voltage and current are;

NEAR END

MAG. PH.
VA 3.77 273.4
VB 3.77 153.4
VC 3.77 33.4
I1 3.773 273.4
I2 3.773 153.4
I3 3.773 33.4

Where the 3.773 A comes from:


63.51V / {16.802@90degrees(Xd' secondary) + 1(Grd. Res.)} = 63.51 / 16.832@86.6 = 3.773 @ -
86.6 = 3.773A @ 273.4 degrees

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 173
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

THEORETICAL CALCULATION FOR 3-PHASE FAULT:


Base MVA = 35
Base kV =11

(1)
BASE IMPEDANCE = (BASE KV)^2 / BASE MVA = (11)^2 / 35 = 3.4571 Ohms

(2)
Z in PU on new base = 0.243PU

(3)
Short Circuit or Fault MVA = Base MVA / Z in PU
= 35 / 0.243
= 144.03 MVA

(4)
Short Circuit Current in kA = ( (Fault MVA) / (1.7325 * Rated kV) )
= (144.03) / (1.7325* 11)
= 7.55kA on Primary side of CT.

(5)
Fault Current Flows in CT secondary is = ( Fault Current on Primary side / CT Ratio )
= (7.55 * 1000) / (2000)
= 3.77 Amp on Secondary side of CT during 3-ph fault
condition.

Above theoretical value of fault current is match with Power System Model software value.

Sample Calculation of L/R VALUE:


Consider a value of X/R of Transformer = 45.
==> X/R = 45
==> (2*3.14*Fn*L) / R = 45
==> L / R = 45 / (6.28*50)
==> L / R = 0.143 = 143.3ms

This value you have to put in "State Simulation" for differential Protection testing.

NOTE:
L/R values are depends on system Impedance (R + jX). So, it may be change to test for
generator, Line, Feeder (OC) protections. But, worst condition you will have to take like L/R =
300ms

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 174
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

VIEW OF POWER SYSTEM MODEL FOR DYNAMIC RELAY TESTING:

ENTER THE VALUES OF SEQ. IMPEDANCE

ENTER VALUES OF BASE MVA & KV

SELECT METHOD

THEORITICAL CALCULATION OF BASE IMPEDANCE = (11)2 / 35


= 3.45 OHMS
But, software shows only one decimal digit, so the value = 3.5 OHMS

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 175
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
3.3.8.2
PHASE TO GROUND FAULT SIMULATION:

---->RESULT TAB:

Fault Type = PH-G Fault.


Location = 100%

Grd. Resistance = 0.0


Arc Resistance = 0.0
Load Angle = 0.0

Source voltage consider as a PT secondary Volt:

Near End = 110/1.7325 = 63.5V


Far End = 110/1.7325 = 63.5V

Consider as a Radial Model OFF

Output calculated DATA of Fault voltage and current are;

NEAR END FAR END

MAG. PH. MAG. PH.


VA 0.00 0.0 0.00 0.0
VB 51.5 256.5 51.5 256.5
VC 54.3 102.6 54.3 102.6
I1 5.308 271.0 5.308 271.0
I2 0.000 00.0 0.000 00.0
I3 0.000 00.0 0.000 00.0

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 176
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

SOFTWARE SHOWS SIMULAION OF PHASE TO GROUND FAULT:

SELECT FAULT TYPE: “Ph-G”

MAGNITUDE OF GROUND FAULT CURRENT

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 177
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

THEORETICAL CALCULATION FOR PHASE TO GROUND FAULT:


Base MVA = 35
Base kV =11

(1)
BASE IMPEDANCE = (BASE KV)^2 / BASE MVA = (11)^2 / 35 = 3.4571 Ohms

(2)
Zpositive seq. in PU on new base = 0.243PU
Znegative seq. in PU on new base = 0.211PU
Zzero seq. in PU on new base = 0.065PU

(3)
Short Circuit or Fault MVA = Base MVA / Z in PU
= 35 / [(0.243 + 0.211 + 0.065) / 3]
= 202.31 MVA

(4)
Short Circuit Current in kA = ( (Fault MVA) / (1.7325 * Rated kV) )
= (202.31) / (1.7325* 11)
= 10.61kA on Primary side of CT.

(5)
Fault Current Flows in CT secondary is = ( Fault Current on Primary side / CT Ratio )
= (10.61 * 1000) / (2000)
= 5.305 Amp on Secondary side of CT during ph-g fault
condition.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 178
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
3.3.8.3
PHASE TO PHASE FAULT SIMULATION:

---->RESULT TAB:

Fault Type = PH-PH Fault.


Location = 100%

Grd. Resistance = 0.0


Arc Resistance = 0.0
Load Angle = 0.0

Source voltage consider as a PT secondary Volt:

Near End = 110/1.7325 = 63.5V


Far End = 110/1.7325 = 63.5V

Consider as a Radial Model OFF

Output calculated DATA of Fault voltage and current are;

NEAR END FAR END

MAG. PH. MAG. PH.


VA 59.0 360 59.0 360
VB 29.5 180.0 29.5 180.0
VC 29.5 180.0 29.5 180.0
I1 0.000 000.0 0.000 000.0
I2 3.504 180.0 3.504 000.0
I3 3.504 180.0 3.504 000.0

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 179
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

SOFTWARE SHOWS SIMULAION OF PHASE TO PHASE FAULT:

SELECT FAULT TYPE: “Ph-Ph”

Magnitude of Fault current

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 180
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

THEORETICAL CALCULATION FOR PHASE TO PHASE FAULT:


Base MVA = 35
Base kV =11

(1)
BASE IMPEDANCE = (BASE KV)^2 / BASE MVA = (11)^2 / 35 = 3.4571 Ohms

(2)
Zpositive seq. in PU on new base = 0.243PU
Znegative seq. in PU on new base = 0.211PU
Zzero seq. in PU on new base = 0.065PU

(3)
Short Circuit or Fault MVA = Base MVA / Z in PU
= 35 / [(0.243 + 0.211) / 1.73]
= 134.11 MVA

(4)
Short Circuit Current in kA = ( (Fault MVA) / (1.7325 * Rated kV) )
= (134.11) / (1.7325* 11)
= 7.039kA on Primary side of CT.

(5)
Fault Current Flows in CT secondary is = ( Fault Current on Primary side / CT Ratio )
= (7.039 * 1000) / (2000)
= 3.51 Amp on Secondary side of CT during ph-ph fault
condition.

Conclusion: Above all cases, theoretical values are similar to software simulated
values. same fault current apply to phase & earth fault over current relay to check for
relay co-ordination.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 181
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

“MULTIPLICATION OF THIS DOCUMENT IS STRICTLY PROHIBITED”

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 182
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

TEABLE OF CONTENTS:

TITLE Sr.No. PAGE NUMBER


Introduction 1.0 184
Nature & effects of 2.0 184
Transformer faults
Protection against 3.0 186
external faults
Protection against 4.0 190
internal faults
Magnetizing inrush 4.1 203
current
4-CTs REF scheme for 3- 4.2 207
phase 3-wire system
5-CTs REF scheme for 3- 4.2.1 210
phase 4-wire system
4-CTs REF scheme for 3- 4.2.2 211
phase 4-wire system
4-CTs REF scheme for 3- 4.2.2.1 213
phase 4-wire system by
using voltage operated
high impedance relay
Protection against 4.3 214
Incipient faults
Protection against 4.4 216
Overloading of
transformer
Overfluxing Protection 4.5 218

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 183
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

1.0 INTRODUCTION:

Power Transformer is one of the most important equipment in a power


transmission and distribution system. Being a static equipment, the design and
construction is relatively simple. Which makes the transformer a highly reliable
piece of equipment. The reliability can be further enhanced by providing
adequate protections, besides proper maintenance while in service.

The Choice of protection is influenced by several factors, the important ones


being.
1) Size and rating of the transformer
2) Vector configuration
3) Source and Neutral Earthing
4) Type of transformer (2 winding / 3 winding Auto Transformer, Rectifier
Transformer etc.)
5) Infeed condition (radial, parallel, interconnecting).
6) OLTC Range

2.0 NATURE AND EFECT OF TRANSFORMER FAULTS:

The nature of faults against which the transformer is to be protected, can be


broadly classified as:-

2.1 External Faults or Through Faults :

These are short circuits of earth faults on the supply net work outside the
transformer. The infeeds through the transformer may be high, if the faults are
electrically close and the leakage reactance of the transformer is low. The
excessive faults current may cause enormous Electromechanical forces causing
displacement / hot spot generation inside the transformer.

2.2 Internal Faults :

Primary protection of transformer is intended to protect the transformer against


internal faults associated with the windings and connections. Internal faults can
be classified as :

a. Short circuits, Inter turn faults due to insulation deterioration


b. Incipient faults
c. Regulation faults

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 184
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
a. Short Circuits , Inter turn faults, earth faults :

These faults are of serious nature causing immediate damage, but are generally
detectable due to unbalance / over shooting of current at the transformer
Terminals.

Faults are;
(ii) Phase-to-earth fault, or Phase-to-Phase fault on the H.V. & L.V.
bushing terminals.
(iii) Phase-to-earth fault, or Phase-to-Phase fault on H.V. & L.V.
windings.
(iv) Short circuit between turns of the H.V. & L.V. windings.
(v) Earth faults on a tertiary winding, or short-circuit between turns
of a tertiary winding.

b. Incipient Faults :
These are initially minor faults causing slowly developing damage. These are
not detectable at winding terminals in the absence of any unbalance in current or
voltage, incipient faults include :-

1) Limited arcing in the oil say due to failure of inter-lamination


or core bolt insulation or accident damage or poor electrical
connection causing hot spots in windings / connections .
2) Cooling system failure :- This may be due to low oil content
clogged oil flow due to sludge formation , failure of oil pumps
or fans or blocking of radiator.

c. Regulator Faults :

These include faults associated with the tap changer / tap change controls.
Operation on unequal taps parallel transformers may cause overheating due to
circulating currents.

2.3 Abnormal Operating Condition :

The abnormal operating condition include overloads and over excitation of


transformer.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 185
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

3.0 PROTECTION AGAINST EXTERNAL FAULTS:

Small distribution transformers with no control breakers are often protected by


fuses. The fuse ratings are chosen well above the maximum loads and should be
adequate to over ride any transient over current conditions such as magnetizing
in rush or DOL starting of a motor feeder.

While a fuse can provide adequate protection against short circuits, it cannot
provide effective protection against earth faults, in view of possible low infeeds.

For larger transformers , controlled by circuit breakers, IDMT over current relays
are more commonly used as phase and earth fault backups. The over-current
relay provides a two fold advantage.

1. it avoids delay at lower amplitudes of faults currents as would


happen in case of fuses.
2. It provides a sensitive earth fault protection largely independent of
the full load rating of the transformer as shown in figure().

The IDMT over-current relays are often supplemented by highest instantaneous


over-current elements on the primary side of the transformers. The highest
elements are set over and above the maximum through fault current and
primarily intended to ensure high speed clearance of terminal short circuits on
the primary side.

The choice of over current / earth fault backup greatly influenced by the vector
configuration, type of earthing and infeed conditions. Some of the typical
applications are discussed below.

3.1
Delta/ Star Transformers (Delta winding connected to Grounded Source):
The delta winding provides zero sequence isolation between the star winding and
the source, a residually connected earth-fault relay on the delta side will not
respond to earth-faults on the star side and hence its operation remains
restricted to earth faults in the delta windings. A sensitive instantaneous earth
fault relay(in high impedance mode ) can therefore, be provided on the delta-side
without requiring any time co-ordination with the star side backup protection .
This will be evident from the current distribution shown in below fig. 3.1(a)

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 186
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

In case of a delta/ star transformer, a phase to phase faults on the star side
produces 2:1:1 current distribution on the delta side. It is therefore,
advantageous to provide 3-0/c elements on delta side (as against 2 elements ) to
enable faster clearance, through the phase element sensing highest current, in
backup mode.

Below Fig. 3.1 (b) below shows the current distribution for phase fault on star
side to illustrate the above.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 187
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

3.2 Star/ Star Transformers:

Star/Star transformers with grounded neutrals exchange zero sequence current


between primary and secondary. The earth-fault backup is therefore usually
IDMT type , time co-ordinated with the down-stream protections.

Star/Star transformers with grounded neutrals have a comparatively low zero


sequence impedance, particularly, when these are provided with delta connected
tertiary. Even without a delta tertiary winding the zero sequence impedance of
the primary winding is significantly low due to the tank effect. Consequently, the
primary winding serves as a zero sequence shunt, by passing substantial zero
sequence current, in the events of an upstream earth faults, causing non-
selective tripping. It is therefore, preferable to provide a directional earth fault
protection looking into the transformer, on the primary side, to circumvent the
above problem. In case the transformer is having infeeds on both sides (say grid
supply on the primary and captive generation on the secondary), It would be
desirable to have directional earth-faults relays on both primary and secondary
side. Fig. 3.1 c) below shows the zero sequence shunting effect of a star/star
transformer.

Since an up stream earth faults cases a current outflow from the transformer, a
directional earth-fault relay (67 N)looking into the transformer would not respond
for such faults and enable better co-ordination. The over-current relays (phase
CT connected- not shown in the figure) will also face a similar situation. However,
since they have a comparatively high setting (above full load) and see only 1/3rd
current compared to earth fault relay, the problem is less pronounced . Over
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 188
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
current relays need not therefore, be directional. In case of interconnecting
transformers with infeeds on both sides, it is advantageous to go for directional
over-current and earth fault relays on either side, to minimize grading problems.

3.3 Highset Element:


The IDMT over current relays are often supplemented by highest instantaneous
over current elements on the primary side, mainly to provide high speed
clearance of severe terminals short circuits, overriding the IDMT elements. The
highest elements should be set over and above the through fault current on
secondary side and should preferably have low transient overreach to enable
closer setting, the presence of offset fault current.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 189
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

4.0 PROTECTIONS AGAINST INTERNAL FAULTS:

A high speed unit type of protection such as differential / restricted earth fault
protection is applied as a primary protection against internal faults.

4.1 Differential Protection :


• High Impedance differential protection scheme
o Too much popular in India for cable, generator, motor &
busbar differential protections.
o No more complexity, lower cost
o Stabilizing resistor is required to connect in series with
operating coil of relay for stability in external fault condition
o Metrosil require to connect in across of operating coil for
high voltage absorber

• Low Impedance differential protection scheme


o Too much popular in India for two winding or three winding
differential protections.
o More complexity, higher cost
o Inbuilt restraining coil & % slope characteristics which is
able to set at variable points. It maintain the stability at
external faults
o Inbuilt 2nd harmonic & 5th harmonic restraining feature

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 190
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Operation criteria:
Here as shown in below figure; this is a complete phase and earth fault
protection operating on Merz- price circulating current principle.

• Relay Operates while, Ix – Iy > Id (Means the difference between


CT1 & CT2 current is more than “Id” setting)

• Id > K(I1 + I2)/2, where K = %slope & (I1 + I2)/2 = Ibias

• Relay Restraint while, Ix – Iy = 0 (Means the CT1 current is equal


to CT2 current)

The differential relay compares the currents on the primary and secondary
side of the transformer using C.Ts of matched ratio, such that the secondary
currents are balanced in magnitude and phase for an external fault or load.

While magnitude balance is achieved by a proper selection of CT ratio on primary


and secondary side or by using interposing current transformers (ICTS), phase
balance is achieved by appropriate vector connections of the associated CT/ICTs
(for example star side CTs are connected in delta and vice versa). Though
theoretically it looks easier to achieve an amplitude and phasor balance, there are
certain practical problems. These are discussed below as also the measures
adopted to circumvent these problems, in a practical differential scheme.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 191
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Why Low impedance scheme is more reliable for Transformer differential


protection?

The reasons are;

• Unequal secondary currents or different voltage level at two


end, because of the different turns ratio of the transformer
windings & CTs (which is take care by % slope curve in relay)
• Phase shift between two windings (i.e. DYn11 – 330degree etc.)
(which is take care by ICTs selection)
• Tap changing under the load condition
• Magnetizing inrush current during transformer energize (which is
take care by 2nd harmonic feature of low impedance differential
relay)
• Unmeasured grounded neutral current (which is take care by zero
sequence elimination function in relay)

Normally above all the problems are not available in high impedance differential
scheme

Unequal current matching:


Normally, the unequal currents matching requires either auxiliary CTs (ICTs) or a
means of scaling within the relay. Fig. A shows the use of taps on the relay
windings to match a 2(10A)-to-1(5A) difference in the levels of the CT secondary
currents under normal load conditions. For this difference the 10A current flows
through just half the number of turns in restraint winding R1 as does the 5A
current in restraint winding R2, so that the ampere-turns of the two windings are
equal.

Fig. A-Schematic of electro-mechanical & static relay


DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 192
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Above figure normally applicable for electromechanical & static relays. But in
modern numerical relay “TAP” point is also adjustable as shown in Fig.B. So, that
the net differential current which is flows through operating coil is very-very close
to zero.

Fig. B-schematic of numerical relay

Phase Shift Compensation:


The phase shift developed in a star-delta power transformer can be handled by
connecting the CTs in star on one side and in delta on the other side, per Fig.
C. The relay current input from the delta CTs is the phasor difference of two
phase currents.

Fig.C- DY11 transformer with CT connection

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 193
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Note in Fig. C that the delta CTs are on the star-grounded side of the transformer.
The phase shift can be accommodated with the delta CTs on either side.
However, it is essential to put the delta CTs on the star side in order to prevent
incorrect tripping for an external ground fault, shown in Fig. D. Here, the delta
CTs are on the wrong side. The three units of current flow entering from the
grounded star are not measured, so they produce an unbalance. (The delta-CT
ratio is assumed to be 3/1 to provide balancing for phase faults.) In contrast, in
Fig. 10 delta CTs on the wye side produce a balance.

Fig. D

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 194
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Fig. E

Since the unbalance on the primary of the wye-side CTs is caused by zero-
sequence current, the delta CTs filter out this unbalance in Fig. E.

There are two ways to form the CT delta. The connections must mirror those of
the power transformer to provide the proper balance.

ICTs Connection for vector group matching:


A practical biased differential scheme showing C.T. connections is illustrated in
fig Fig. F below for a delta / star (Dy 11) transformer.

Transformer type : DY11


ICT type: YD1

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 195
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Vector Diagram before ICT

IRL Ir

Ir IRL

Ib Iy
Delta side vector
Star side vector

Vector IRL lead 30 degree to Ir

So, above diagram it is clear that the this 30 degree difference should be
compensated by adding the YD1 ICT on star winding of transformer otherwise it
may chance to mal-operate the relay on normal load condition or external fault
condition.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 196
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Fig. F Typical C.T. Connections for Biased Differential Protection

Following work out illustrates the choice of matching CTs/ICTs for a delta /star
transformer.
Transformers rating: 10 MVA, 66/33 KV, Dy11

Transformer F.L. current:

66KV side : IFL = (10 X 1000) / (1.73 X 66 ) = 87.5A

33KV side : IFL = (10 X 1000) / (1.73 X 33 ) = 175A

Equivalent secondary FL current, considering a matching CT ratio of 100/ 1A for


66 KV CTs and 200/1A for 33 kV CTs:-
IFL (Secondary side) = 87.5 / 100 = 0.875A (66kV side)

IFL (Secondary side) = 175 / 200 = 0.875A (33kV side)

Since the transformer is of Dy11 vector configuration the 33KV line current will be
leading the66KV side line currents by 30. To achieve phasor balance, the 33KV
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 197
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
side C.T. secondary current will have to be phase retarded by 30 by connecting
the interposing current transformers in star/ delta (Yd1 ) configuration as shown.
The ICT ratio can be worked out as follows.

ICT primary current (corresponding of F.L. condition )=0.875A


Line current on ICT secondary side to match in amplitude with the 66KV side CT
secondary current pf 0.875A.

The ICT secondary current corresponding to the above line current =0.875/

Hence, ICT ratio = {(0.875) / (0.875/1.7325)} = 1.0 / 0.577 A

Alternatively, a CT ratio of 200/0.58 Amps can be selected on 33 side and the


33KV CTs can be directly connected in delta to achieve both amplitude and
phase matching without necessitating ICTs.

Example:
Transformer Data:
Rated MVA = 150MVA
Rated Primary kV = 11kV
Rated Secondary kV = 132kV
Transformer type = DYn11

Step:-1
Rated full load current on primary (Delta) side (Ip) = (150*106)/(1.73*11*103)
= 7882.3 Amp
Now, CTR on primary side = 8000/5A

So, CT secondary current = (5*7882.3)/8000 = 4.92A

Step:-2
Rated full load current on secondary (Star) side (Is) = (7882.3)*(11/132)
= 656.85 Amp

Now, CTR on secondary side = 800/1A

So, CT secondary current = (1*656.85)/800 = 0.821 Amp

Step:-3
Selection of ICT of Star winging is YD1
Now, secondary current of each ICT = 4.92/1.73 = 2.84A
Thus, ICT RATIO = 0.821/2.84 = 1/3.45A

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 198
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Tap Changing under load:


• Current matching should occur for condition where the load tap
changer is in neutral position (Mid tap).
• Then, the unbalance current flows in relay with the taps at the
minimum or maximum tap positions.
• This unbalance current can causes operation of relay during normal
load condition.-

In practical differential protection for transformers, this problem is over come by


providing through current bias ( or restraint). The bias, modifies the differential
pick up and pegs it above the maximum expected differential current in the face
of ratio mismatch produced by the tap changer and C.T. errors, thereby ensuring
stability on through faults. A typical bias characteristic is shown in fig. G below;

Un restrain region = Id>>


3.0

Operate = Id>

Idiff
Restrain

0.15

1 2 10

Ibias
fig. G Typical Bias Characteristic

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 199
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Example for Relay setting:


Transformer Data:
Rated MVA : 250MVA
Rated Primary kV : 15.75kV
Rated Secondary kV : 240kV
Taps : -5% to +7.5%
Connection type : DY11
%Impedance : 14%

Current Transformer Data:


L.V. side : 10,000/5A - star connection
H.V. side : 1,000/1A - star connection

Step:-1
Transformer F.L. current:

15.75KV side : IFL = (10 X 250) / (1.73 X 15.75 ) = 9164A

240KV side : IFL = (10 X 106) / (1.73 X 240) = 601A


IFL (Secondary side) = 9164*5 / 10000 = 4.582A (15.75kV side)

IFL (Secondary side) = 601 / 1000 = 0.601A (240kV side)

Step:-2
ICT RATIO:

IFL secondary on delta side = 4.582A therefore, the current flows through
secondary on star side = 4.582/1.73 = 2.648A because of star-delta ICT.

Now, ICT ratio on star side should be = 0.601/2.648A = 1 / 4.4A

Step:-3
Now, Voltage at maximum TAP = {(7.5*240)/100} + 240 = 258kV

Voltage at minimum TAP = 240 - {(5*240)/100} = 228kV

So, at maximum TAP the turn ratio = 258/15.75 = 16.38

Step:-4
Now, assume the fault current on star side = 4.0kA

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 200
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
Reflected fault current on delta side = (4.0)*(16.38) = 65.52kA

Step:-5
CT secondary current:

Now, Secondary current on start side during a fault condition = (4000*1/1000)


= 4.0A

Secondary current on delta side during a fault condition = (65.52*1000*5)/10000


= 32.76A

Step:-6
ICT reflected current on delta side = (4.0*4.4) / 1.0 = 17.6A

Step:-7
ICT secondary (Delta side) current flows in relay restraining coil = 17.6*1.73 = 30.44A

Step:-8
Differential current flows in operating coil = (32.76 – 30.44) = 2.31A
Bias current = (32.76 + 30.44)/2 = 31.6A

Step:-9
%Slope = {(2.31) / (31.6)}*100 = 7.31%

Select the nearest slope setting

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 201
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 202
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
4.1
Magnetizing Inrush Current :

Inrush current:
It is define as the transient exciting current resulting from a sudden change in the
exciting voltage.

When the primary side of a transformer is switched on the supply with its
secondary unloaded, it acts as a simple inductive reactor. The value of the voltage
at the instant of switching can be any where between zero and the peak value.

a) Switching at peak voltage with core Initially demagnetized

At voltage maximum, the steady state value of the flux and hence the
magnetizing current it zero. Hence the flux wave immediately assumes the
normal shape for an inductive circuit with both the core flux and magnetizing
current rising from zero.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 203
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

b) Switching at Zero voltage with core initially demagnetized

Initial value of the flux in the core is zero as against the steady state value of
“flux” corresponding to voltage zero. Since the total steady state flux change
during voltage half cycle is 2times of flux (i.e.-flux to +flux ) the flux rises from
zero to 2times of flux. This is known as the doubling effect.

Modern transformers operate at very low saturation level (around 1.1times the
working flux level.) The flux doubling, therefore, causes extreme saturation of the
core and transformer consequently draws heavy magnetizing current from the
supply source. While the normal steady state magnetizing current may be less
than 5% of full load current, the transient core saturation may raise it to several
times the normal load current. The situation is even worse if there is remnant flux
in the core which happens to be in the direction in which the first peak occurs.

Since the Inrush current flows only in the primary winding it appears as an
operating current to the differential relay, producing instability. The immunity to
inrush current can be obtained either by delaying the protection or by providing a
harmonic restraint.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 204
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

a. Time delay :

Since the magnetizing inrush is a transient phenomena, a small time delay can
be provided in the differential relay to override the same and ensure stability

Induction disc relays with an adjustable delay provided by the disc movement, is
one of the earlier designs of biased differential protection.

b. Harmonic Restraint :

Time delay associated with the differential relay, as explained before, would
make the protection slower in operation and increase the fault damage. Modern
high speed differential relay, therefore, employ a different approach to this
problem. the inrush current is highly distorted and contains a fairly high
proportion of 2nd ammonic component. Typical analysis of an inrush current wave
shows following ammonic contents.

Harmonic Component %of Fundamental


Fundamental 100
DC 55
2nd 63
3rd 26.8
4th 5.1
5th 4.1
6th 3.7
7th 2.4

The proportion of 2nd harmonic generally varies between 30-65 % of the


fundamental and is unique to the inrush current. This component is filtered from
the filtering circuit and is used to restrain the protection the same way as through
current bias. The harmonic restraint is so proportioned that 15% of 2nd harmonic
current will just balance the operating current of 100% of fundamental frequency
elimination.

While through current bias and 2nd harmonic bias (restraint ) is an essential
feature of a modern high speed differential protection. Following additional
features are an incorporated to enhance stability and maintain operating speed.

i) 5th Harmonic bypass or restraint :

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 205
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
This feature is provided to immune the protection against over excited operation
of the transformer. The magnetizing current of an over excited transformer
contains substantial proportion of 5th harmonic restraint.

ii) Unrestrained Differential Highset (Id>>):

The harmonic restraint may slow down the protection , on severe internal fault, if
the associated CTs suffer transient saturation and produce a high degree of
harmonic distortion. To ensure high speed operation under the above condition
an unrestrained differential highest with pick up threshold (usually 8-10 times ) is
incorporated in the differential relay.

Typical circuit of a high speed, harmonic restraint biased differential relay


(DTH31) is shown fig below:

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 206
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
There are alternative designs which do not use harmonic bias (restraint) to
achieve immunity against magnetizing inrush or over excited operation of the
transformer. One such design, distinguishes between the above conditions and
an internal fault , by verifying the zero periods in the differential current waveform
over a cycle. The magnetizing current waveform during switching inrush or over
excited condition has substantial zero periods (in excess of ¼ cycle over one
cycle period), Unlike in the case of an internal fault. This methods enables high
speed of operation for internal fault in the absence of any harmonic restraint.

Numerical versions of differential protections are also now available which use
suitable algorithm for measurement. The ratio and phase angle correction is a
software function in these relays, which eliminate the need for matched CTs/
ICTs. The numerical versions are usually multifunction and provide additional
protection elements( such as REF / over-fluxing etc.). Besides, several diagnostic
non-continuous self monitoring are provided.

4.2
4- CTs Restricted Earth Fault (REF) Protection Scheme for 3-phase 3-wire system :

This is a circulating current earth fault differential system, usually applied to the
star winding of a transformer, by balancing the residual current of the three line
current transformers with the output current of a CT in the neutral earth
connection. The protection arrangement is shown in fig. 4.2.a ) below.

Fig. 4.2 a) Typical Ref C.T. Connections

For an external earth fault, the associated phase and neutral C.T. see same fault
current (lF) but of different polarity , while the phase C.T. sees an outflow of
current, the neutral C.T. sees an inflow with respect to the transformer. The
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 207
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
phase and neutral C.T. therefore, form a series connection between them with no
differential current through the relay, if the C.T. s are assumed to be ideal with no
errors. For an internal fault, either the neutral C.T. see an inflow because of
infeed reversal through the latter (in case of parallel transformers). This produces
a differential current through the relay corresponding to the summated infeeds at
the fault point, there by causing operation.

In practice, however, the associated C.T.s may experience unequal saturation


say due to the remnant flux in the core or dissimilarities in their magnetizing
characteristics, particularly when the through fault current has large D.C offsets
with slow decay rate. The worst condition would occur when one C.T. completely
saturates while the other remains fully active during a severe external fault as
shown in fig. 4.2 b)

Fig. 4.2 b) Equivalent C.T. Circuit for External Fault

The voltage that can be developed across the relay under the above condition is
given by;

Vs = (IF/n)*(RCT + 2RL) Volts

Where IF = Maximum through fault current limited by transformer leakage current


N = C.T. RATIO
RCT = C.T. secondary resistance
2RL = To & fro Lead resistance

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 208
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
The REF protection is invariably high impedance and is calibrated either in terms of
voltage or current. In case of voltage relay, a setting voltage above “Vs” can be set. In
case of current operated relay, a series stabilizing resistor is added to make the relay
branch high impedance such that current through the relay will not exceed its current
setting (Is). The external stabilizing resistor value can be worked out as follows:

Rst = (Vs/Is) – [( VAR ) / (Is)2]

Where, (VAR) = VA burden at relay setting (Is)


Rst = Stabilizing resistor
Is = relay setting

The minimum primary operating current (POC) is influenced by the magnetizing current
of the associated C.T.s and is given by:

POC = N [Is + N1*Im] Amps

Where, N = CT RATIO
N1 = Number of CTs are connected in parallel
Im = Magnetizing current of each CT at Vs

The relay branch being high impedance may force the CTs in to saturation for a severe
internal fault when summated current associated CTs seek its path through the relay.
This may cause peak over voltage across the CT secondary / Pilot as also the relay
threatening the insulation. The maximum peak voltage across the CT secondary is given
by the expression:-

Vpeak = (2*1.414)*[(Vk*(Vp – Vk))]1/2

Where, Vk = Knee point voltage


Vp = Prospective voltage assuming unsaturated operation
= (IF/N)*(Rst + Rr)
Where, Rr = Relay resistance or relay ohmic burden

If the peak voltage so worked out exceeds 3000 Volts a non-linear resistor (metrosil)
should be provided across the relay branch to limit this voltage within safe limits.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 209
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

4.2.1
5- CTs Restricted Earth Fault (REF) Protection Scheme for 3-phase 4-wire system :

CT1

Rph

CT2

Yph

CT3

Bph

External FAULT “F2”

mc

Stabilizing resistor

Relay

Internal Fault “F1”

Figure shows only secondary winding (Star) of DYn11 Transformer

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 210
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
Here as shown in above figure which shows 5-CTs connections scheme for 3-phase 4-
wire system.

Sensitivity:
If the internal fault (F1) occurred between “Bph-N” then it will not sensed by relay
because the fault current can not flows through Earth CT via earth but it sensed by
neutral CT via neutral wire.

Stability:
If the external fault (F2) occurred between “Bph-N” then it not sensed by relay through
Bph CT via neutral wire because the magnitude of fault current at relay terminal is near
by zero & it remains stable.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 211
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

4.2.2
4- CTs Restricted Earth Fault (REF) Protection Scheme for 3-phase 4-wire system :

CT1

CT2

CT3

K
External fault “F2”

mc

Stabilizing resistor

Relay

Internal Fault “F1”

Figure shows only secondary winding (Star) of DYn11 Transformer

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 212
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

4.2.2.1
4- CTs Restricted Earth Fault (REF) Protection Scheme for 3-phase 4-wire system
using voltage operated high impedance relay :

CT1

CT2

CT3

K
External fault “F2”

mc

Stabilizing resistor

Relay

Internal Fault “F1”

Figure shows only secondary winding (Star) of DYn11 Transformer

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 213
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

EXAMPLE:
CALCULATION OF RELAY SETTING FOR RELAY TYPE 7VH60:
The Minimum setting voltage for stability is;

Vs = (If/N)*(RCT + 2RL)------------------------------------(4.2.2.1)
Where,
If = fault current = 35,000 Amp(Say)
N = CT RATIO = 3000/1A
RCT = CT Secondary resistance = 2.0 OHMS
RL = Lead resistance = 0.5 OHMS

Now, above all values put in formula 4.2.2.1;

Vs = {(35000)/3000}* {2 + 1}
= {11.66}* {3}
= 34.99 Volts

Now, available next range = 48V

It means, the relay will operate while the operating current magnitude is more than relay
settings (20mA) with 48Volts across on relay terminals.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 214
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Here as shown in above figure which shows 4-CTs connections scheme for 3-phase 4-
wire system. Earth CT connection is below the point “K”. If the internal fault (F1)
occurred between “Bph-N” then it will sensed by relay through Earth CT via neutral wire
& during an external fault (F2) between “B-N”, it’s stable through Earth CT via neutral
wire.

4.3
Protection against Incipient Faults:

Most of the distribution plants (including chemical-petrochem & fertilizers etc.) commonly
used protection against incipient (developing) faults is Buchholz relay. The relay has two
floats actuating mercury switches & is placed in the pipe connecting the transformer tank
to the conservator.

A slow generation of gas due to a minor fault causes a stream of bubbles which pass
towards the conservator and in the process get trapped into the Buchholz chamber,
lowering its oil level. Consequently the alarm float lower (trip) floats, tilting the mercury
switch and closing the trip contact.

While mounting the relay care should be taken to ensure that the arrow on its case
should point to the conservator and the connecting pipe should have an upward slope of
about 8o.

Besides, Buchholz relay, temperature monitoring devices such as oil and winding
temperature indicators are provided for transformers. These can also give fairly good
indication of an incipient failure such as generation of hot spot, failure of cooling system
etc.

The winding temperature is measured by thermal image technique. In this technique a


temperature sensing device (usually a silistor-silicon resistor) is placed in the
transformer oil at the top of the transformer tank. The silistor is encapsulated with a
heater element in a thermal moulded material, the latter being fed from the load current,
through a bushing CT. The combination thus forms a thermal replica of the transformer
winding. The silistor is used as an arm of a resistance bridge supplied from stabilized
d.c. supply. An indicating instrument calibrated in terms of temperature is energized from
the out of balance voltage of the bridge.

4.4
Protection against overloading of transformer:

The winding temperature indicator is primary protection to effectively detect overloading.

Thermal image overcurrent relays with exponential or I2*t time/current characteristics


(like CDG12 etc.)are also used for protection against overload. This protection detects

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 215
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
overload but does not detect failure of cooling system unlike the temperature indicating
devices.

Definite time over current relays (like CTU-31 etc.) are also used to provide pre-trip
alarm, if the overload exceeds permissible limit. Such relays are required to have high
reset ratio continuously adjustable current setting to match permissible overload rating of
the transformer.

4.5
Overfluxing Protections:

Increase in input voltage causes increase in working flux levels, thereby increasing the
iron losses and magnetizing current. The core bolt get heated and the interlamination
insulation and core bolt insulation is weakened. The reduction in supply frequency also
increases the core flux and has similar effect as that due to over voltage.

The generator transformers are more prone for overfluxing as these may be subjected to
an uncomfortable combination of over voltage and under frequency during start up or
coasting down, due to AVR/Governor malfunctioning.

The expression for induced voltage in a transformer is given by

V = pHi*f*T

Where, pHi = Core flux


F = Frequency
T = No. of turns (Constant)

Thus “pHi” is inversely proportional to (V/F).

The ration of V/F is therefore, an index of overfluxing in a transformer. Typical seting


range for the relay is (1.05-1.2) on 110V/50Hz basis. The overfluxing condition does not
warrant immediate isolation of transformer and hence the relay is provided with
adjustable time delays which also helps to prevent transient operation due to momentary
disturbances. The practical overfluxing relays are either definite time of inverse time
versions with a pre-trip alarm.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 216
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

4.6
Application Diagram of Complete OC & EF scheme for 2.5MVA DYn11 TR:

F1
I=0

O/C & E/F SCHEME FOR “F1” FAULT ON DELTA SIDE

STAND BY EARTH FAULT SCHEME FOR EXTERNAL “E/F” ON STAR SIDE

“REF” SCHEME FOR INTERNAL FAULT “E/F” ON STAR SIDE

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 217
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

4.7
Application Diagram of Differential scheme for Y-Y TR with one sets of ICTs:

The D-connected equalizing windings of the interposing CTs are used to eliminate
possible zero sequence currents in case of external earth faults and could always
be arranged for rated current 1 A.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 218
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

4.8
Application Diagram of Differential scheme for Y-Y TR with two sets of ICTs:

When interposing CTs are used on both windings of the power transformer they
should be Yd-connected. In that case there is no need for any D-connected equalizing
winding.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 219
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

4.9
Application Diagram of Differential scheme for D-Y TR with one set of ICTs:

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 220
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

4.10
Application Diagram of Combined Differential & REF scheme for D-Y TR with one set
of ICTs:

Fig. DY11 TR with YD1 ICTs

• Separate relays are require while using electromechanical or static relays


for differential & REF Protections as shown in figure below (MBCH-12 +
CAG14).
• It is very is to use with modern numerical relays (i.e. SPAD346C) by
using proper vector group selection in differential element.
• Separate “PS” class CTs are not require for both schemes on star
side.
• Complex scheme.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 221
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

4.10.1
Application diagram of combined differential & REF scheme by using MBCH-12 &
CAG14 relay on DY1 TR.

Here as shown in above figure;


• 3-units of MBCH-12 Relays are used for low impedance differential
protection
• single pole unit of CAG-14 Relay is used for High impedance REF
protection on star winding of TR
• ICT connections are YD11

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 222
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Example of Application Relays for Low impedance differential Protection:

Sr.No. Make Type


1 ALSTOM DTH31/32
2 ALSTOM MBCH12
3 ALSTOM KBCH12
4 ALSTOM MICOMP632
5 ABB RADSB-4
6 ABB SPAD-346C
7 ABB RET521
8 EASUN REYROLLE DUOBIAS-M/420
9 SIEMENS 7UT62

Example of Application Relays for High impedance REF Protection:

Sr.No. Make Type


1 ALSTOM CAG14
2 ALSTOM FAC14
3 ABB SPAE010
4 EASUN-REYROLLE 4B3/5B3
5 SIEMENS 7VH60

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 223
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

“MULTIPLICATION OF DOCUMENT IS STRICTLY PROHIBITED”

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 224
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

TABLE OF CONTENTS:

TITLE Sr.No. PAGE NUMBER


Shunt capacitor bank prot 1.0 222
Capacitor unbalance prot 1.1 222
Unbalance prot. Methods 1.2 226
for ungrounded Wye
connected bank
Unbalance prot. Methods 1.3 233
for grounded Wye
connected bank
Prot. of the SCB against 1.4 237
system disturbances &
faults
Example Relay application 1.5 239

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 225
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
1.0

SHUNT CAPACITOR BANK PROTECTION:


The protection of Shunt Capacitor Bank’s involves:

a) Protection of the bank against faults occurring within the bank including
those inside the capacitor unit; and,

b) Protection of the bank against system disturbances and faults.

The protection selected for a capacitor bank depends on bank configuration, whether or
not the capacitor bank is grounded and the system grounding.

1.1
Capacitor Unbalance Protection:
The protection of shunt capacitor banks against internal faults involves several protective
devices/elements in a coordinated scheme. Typically, the protective elements found in a
SCB for internal faults are: individual fuses (not discuss in this paper), unbalance
protection to provide alarm/ trip and over-current elements for bank fault protection.

Removal of a failed capacitor element or unit by its fuse results in an increase in voltage
across the remaining elements/ units causing an unbalance within the bank. A
continuous over-voltage (above 1.1pu) on any unit shall be prevented by means of
protective relays that trip the bank. Unbalance protection normally senses changes
associated with the failure of a capacitor element or unit and removes the bank from
service when the resulting over-voltage becomes excessive on the remaining healthy
capacitor units.

Unbalance protection normally provides the primary protection for arcing faults within a
capacitor bank and other abnormalities that may damage capacitor elements/ units.
Arcing faults may cause substantial damage in a small fraction of a second. The
unbalance protection should have minimum intentional delay in order to minimize the
amount of damage to the bank in the event of external arcing.

In most capacitor banks an external arc within the capacitor bank does not result in
enough change in the phase current to operate the primary fault protection (usually an
over-current relay) The sensitivity requirements for adequate capacitor bank protection
for this condition may be very demanding, particularly for SBC with many series groups.
The need for sensitive resulted in the development of unbalance protection where
certain voltages or currents parameters of the capacitor bank are monitored and
compared to the bank balance conditions.

Capacitor unbalance protection is provided in many different ways, depending on the


capacitor bank arrangement and grounding. A variety of unbalance protection schemes
are used for internally fused, externally fused, fuse-less, or un-fused shunt capacitor.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 226
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
a) Capacitor Element Failure Mode
For an efficient unbalance protection it is important to understand the failure mode of the
capacitor element. In externally fused, fuseless or unfused capacitor banks, the failed
element within the can is short-circuited by the weld that naturally occurs at the point of
failure (the element fails short-circuited). This short circuit puts out of service the whole
group of elements, increasing the voltage on the remaining groups. Several capacitor
elements breakdowns may occur before the external fuse (if exists) removes the entire
unit. The external fuse will operate when a capacitor unit becomes essentially short
circuited, isolating the faulted unit.

Internally fused capacitors have individual fused capacitor elements that are
disconnected when an element breakdown occurs (the element fails opened). The risk of
successive faults is minimized because the fuse will isolate the faulty element within a
few cycles. The degree of unbalance introduced by an element failure is less than that
which occurs with externally fused units (since the amount of capacitance removed by
blown fuse is less) and hence a more sensitive unbalance protection scheme is required
when internally fused units are used.

b) Schemes with Ambiguous Indication


A combination of capacitor elements/ units failures may provide ambiguous indications
on the conditions of the bank. For instance, during steady state operation, negligible
current flows through the current transformer between the neutrals of an ungrounded
wye-wye capacitor bank for a balanced bank, and this condition is correct. However, the
same negligible current may flow through this current transformer if an equal number of
units or elements are removed from the same phase on both sides of the bank (Fig.1 ).
This condition is undesirable, and the indication is obviously ambiguous.

Where ambiguous indication is a possibility, it is desirable to have a sensitive alarm


(preferably one fuse operation for fused banks or one faulted element for fuseless or
unfused banks) to minimize the probability of continuing operation with canceling failures
that result in continuing, undetected over-voltages on the remaining units.

It may also be desirable to set the trip level based on an estimated number of canceling
failures in order to reduce the risk of subjecting capacitor units to damaging voltages and
requiring fuses to operate above their voltage capability when canceling failures occur.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 227
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Figure-1: Compensating failures in the same phase result in no unbalance signal

Alstom make electromechanical Over current relay type “CDG-11” is used for
above application which is mention in figure-1.

c) Undetectable Faults
For certain capacitor bank configurations some faults within the bank will not cause an
unbalance signal and will go undetected. For example:

a) Rack-to-rack faults for banks with two series groups connected phase-over-
phase and using neutral voltage or current for unbalance protection;

b) Rack-to-rack faults for certain H-bridge connections.

d) Inherent Unbalance and System Unbalance


In practice, the unbalance seen by the unbalance relay is the result of the loss of
individual capacitor units or elements and the inherent system and bank unbalances.
The primary unbalance, which exists on all capacitor bank installations (with or without
fuses), is due to system voltage unbalance and capacitor manufacturing tolerance.
Secondary unbalance errors are introduced by sensing device tolerances and variation
and by relative changes in capacitance due to difference in capacitor unit temperatures
in the bank.

The inherent unbalance error may be in the direction to prevent unbalance relay
operation, or to cause a false operation. The amount of inherent unbalance for
various configurations may be estimated using the equations provided in reference.

If the inherent unbalance error approaches 50% of the alarm setting, compensation
should be provided in order to correctly alarm for the failure of one unit or element as
specified. In some cases, a different bank connection can improve the sensitivity without
adding compensation. For example, a wye bank can be split into a wye-wye bank,
thereby doubling the sensitivity of the protection and eliminating the system voltage
unbalance effect.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 228
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

A neutral unbalance protection method with compensation for inherent unbalance is


normally required for very large banks. The neutral unbalance signal produced by the
loss of one or two individual capacitor units is small compared to the inherent unbalance
and the latter can no longer be considered negligible. Unbalance compensation should
be used if the inherent unbalance exceeds one half of the desired setting.

Harmonic voltages and currents can influence the operation of the unbalance relay
unless power frequency band-pass or other appropriate filtering is provided.

e) Unbalance Trip Relay Considerations


The time delay of the unbalance relay trip should be minimized to reduce damage from
an arcing fault within the bank structure and prevent exposure of the remaining capacitor
units to over-voltage conditions beyond their permissible limits.

The unbalance trip relay should have enough time delay to avoid false operations due to
inrush, system ground faults, switching of nearby equipment, and non-simultaneous pole
operation of the energizing switch. For most applications, 0.1s should be adequate. For
unbalance relaying systems that would operate on a system voltage unbalance, a delay
slightly longer than the upstream protection fault clearing time is required to avoid
tripping due to a system fault. Longer delays increase the probability of catastrophic
bank failures.

With grounded capacitor banks, the failure of one pole of the SCB switching device or a
single phasing from a blown bank fuse will allow zero sequence currents to flow in
system ground relays. Capacitor bank relaying, including the operating time of the
switching device, should be coordinated with the operation of the system ground relays
to avoid tripping system load.

The unbalance trip relay scheme should have a lockout feature to prevent inadvertent
closing of the capacitor bank switching device if an unbalance trip has occurred.

The unbalance trip time delay should be long enough to avoid false tripping due to
following conditions;
• Inrush.
• System ground faults.
• Switching of near by equipment.

The unbalance trip time delay should be minimized to reduce damage from arcing faults
with in the bank structure & reduce damage to CTs, VTs & relay system for single phase
or open phase conditions.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 229
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

f) Unbalance Alarm Relay Considerations


To allow for the effects of inherent unbalance within the bank, the unbalance relay alarm
should be set to operate at about one-half the level of the unbalance signal determined
by the calculated alarm condition based on an idealized bank. The alarm should have
sufficient time delay to override external disturbances.

1.2

Unbalance Protection Methods for Ungrounded Wye connected Banks:


Shunt capacitor banks are not grounded in industrial or commercial power systems for a
various reasons. The some reasons are as below;

• Grounded bank provide a low impedance path to ground for zero-sequence


(ground or unbalanced) harmonic currents. These harmonic currents have the
potential of exciting resonances and may also cause communication interference
and nuisance ground fault relay tripping.
• Grounded bank may cause ground fault relay operation when unbalanced due
to a blown capacitor fuse or fuses, capacitor tolerances and system voltage
unbalances.
• Grounded bank have high discharge currents during system ground faults.
These discharge currents can cause nuisance fuse operation surge arrestor
damage.
• Grounded banks on resistive grounded systems can be damaged during system
ground faults.
Due to these disadvantages, most of the capacitor banks are left ungrounded for
industrial and commercial power systems up to 33kV.

Disadvantage:
• The disadvantage of ungrounded bank is the over voltage that occurs when the
bank is unbalanced due to a capacitor fuse blowing as shown in figure below.
The over voltage appears across the remaining capacitors on the phase in which
the fuse has opened. The over voltage can be as high as 50%, depending
upon the bank configuration, and can reduce the life and permanently damage
the remaining capacitors.
• Above reason, the kVAR out is reduced

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 230
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Considerations for Neutral Voltage Unbalance Protection:

There are so many technical considerations when setting and applying a neutral voltage
unbalance protection system. The following are the some considerations as below;

• The unbalance protection system should be sensitive enough to alarm for the
loss of one or more capacitors, but trip out for a loss of sufficient or additional
capacitor units that will cause an over voltage in excess of 110% on the
remaining capacitors.
• The unbalance protection system should have a time delay of at least 0.5s to
overcome false operations due to inrush, ground faults on the line, lightning,
switching of nearby equipment, and other transient unbalance conditions.
• The unbalance protection system should have a lockout feature to prevent
automatic reclosing of the capacitor bank switching device.

a) Unbalance Protection for Ungrounded Single Wye Banks


The simplest method to detect unbalance in single ungrounded Wye banks is to
measure the bank neutral or zero sequence voltage. If the capacitor bank is balanced
and the system voltage is balance the neutral voltage will be zero. A change in any
phase of the bank will result in a neutral or zero sequence voltage.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 231
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Figure-(a) Figure-(b)
Fig. (a) shows a method that measures the voltage between capacitor neutral and
ground using a VT and an over-voltage relay with 3rd harmonic filter. It is simple but
suffers in presence of system voltage unbalances and inherent unbalances. The voltage-
sensing device is generally a voltage transformer but it could be a capacitive potential
device or resistive potential device. The voltage-sensing device should be selected for
the lowest voltage ratio attainable, while still being able to withstand transient and
continuous over-voltage conditions to obtain the maximum unbalance detection
sensitivity. However, a voltage transformer used in this application should be rated for
full system voltage because the neutral voltage can under some conditions rise to as
high as 2.5 per unit during switching.

An equivalent zero sequence component that eliminate the system unbalances can be
derived utilizing three voltage-sensing devices with their high side voltage wye-
connected from line to ground, and the secondaries connected in a broken delta. The
voltage source VTs can be either at a tap in the capacitor bank or used the VTs of the
bank bus.

Figs. (b) shows a neutral unbalance relay protection scheme for an ungrounded wye
capacitor bank, using three phase-to-neutral voltage transformers with their secondaries
connected in broken delta to an over-voltage relay. Compared to the scheme in Fig. (a),
this scheme has the advantage of not being sensitive to system voltage unbalance. Also,
the unbalance voltage going to the over-voltage relay is three times the neutral voltage
as obtained from Fig (a). For the same voltage transformer ratio, there is a gain of three
in sensitivity over the single neutral-to-ground voltage transformer scheme. The voltage
transformers should be rated for line-to-line voltage.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 232
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Figure-1(a) Figure-1(b)
Modern digital relays can calculate the zero sequence voltage from the phase voltages
as shown in Fig (a), eliminating the need of additional auxiliary VTs to obtain the zero
sequence voltage. Fig (b) shows the same principle but using the VTs on the capacitor
bank bus. Although schemes shown in Fig (b), 1(a) and 1(b) eliminate system
unbalances, they do not eliminate the inherent capacitor unbalance.

Alstom make electromechanical residual IDMTL over voltage relay type “VDG-14”
is used for above application.
Range: (5.4V – 20V) & TMS = (0.1 – 1.0)

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 233
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

IDMTL Characteristic of VDG-14

Fig. 2 shows a protection scheme that removes the system unbalance and compensate
for the inherent capacitor unbalance. It is a variation of the voltage differential scheme
for grounded banks described below). The best method to eliminate the system
unbalance is to split the bank in two Wyes; however, it may not be always possible or
desirable. The system unbalance appears as a zero sequence voltage both at the bank
terminal and at the bank neutral. The bank terminal zero sequence component is derived
from 3 line VTs with their high side Wye connected and their secondaries connected in
broken delta. The difference voltage between the neutral unbalance signal due to
system unbalance and the calculated zero sequence from the terminal VTs will be
compensated for all conditions of system unbalance. The remaining error appearing at
the neutral due to manufacturers capacitor tolerance is then compensated for by means
of a phase shifter.

b) Unbalance Protection for Ungrounded Double Wye Banks


Ungrounded banks can be split into two equal banks. This bank configuration inherently
compensates for system voltage unbalances; however, the effects of manufacturers

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 234
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
capacitor tolerance will affect relay operation unless steps are taken to compensate for
this error.

Figure-2: Compensated Neutral Voltage unbalance method

Three methods of providing unbalance protection for double wye ungrounded banks are
presented. Fig. 3(a) uses a current transformer on the connection of the two neutrals
and an over-current relay (or a shunt and a voltage relay). Fig. 3(b) uses a voltage
transformer connected between the two neutrals and an over-voltage relay. The effect of
system voltage unbalances are avoided by both schemes, and both are unaffected by
third harmonic currents or voltages when balanced. The current transformer or voltage
transformer should be rated for system voltage.

The neutral current is one-half of that of a single grounded bank of the same size.
However, the current transformer ratio and relay rating may be selected for the desired
sensitivity because they are not subjected to switching surge currents or single-phase
currents as they are in the grounded neutral scheme.

Although a low-ratio voltage transformer would be desirable, a voltage transformer rated


for system voltage is required for the ungrounded neutral. Therefore, a high turns ratio
should be accepted.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 235
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Figure-3(a) Figure-3(b)
Fig. 4 shows a scheme where the neutrals of the two capacitor sections are ungrounded
but tied together. A voltage transformer, or potential device, is used to measure the
voltage between the capacitor bank neutral and ground. The relay should have a
harmonic filter.

Figure-4

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 236
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

1.3
Unbalance Protection Methods for Grounded Wye connected Banks:

a) Unbalance Protection for Grounded Single Wye Banks


An unbalance in the capacitor bank will cause current to flow in the neutral. Fig. 5 (a)
shows a protection based on a current transformer installed on the connection between
the capacitor bank neutral and ground. This current transformer has unusual high over-
voltage and current requirements. The ratio is selected to give both adequate over-
current capability and appropriate signal for the protection.

The current transformer output has a burden resistor and a sensitive voltage relay.
Because of the presence of harmonic currents (particularly the third, a zero sequence
harmonic that flows in the neutral-to-ground connection), the relay should be tuned to
reduce its sensitivity to frequencies other than the power frequency.

The voltage across the burden resistor is in phase with the neutral-to-ground current.
This neutral-to-ground current is the vector sum of the three-phase currents, which are
90° out of the phase with the system phase-to-ground voltages. This scheme may be
compensated for power system voltage unbalances, by accounting for the 90° phase
shift, and is not unusually appropriate for very large capacitor banks requiring very
sensitive settings.

Each time the capacitor bank is energized, momentary unbalanced capacitor charging
currents will circulate in the phases and in the capacitor neutral. Where a parallel bank is
already in service these current can be on the order of thousands Amps causing the
relay to mal-operate and CT to fail.

Figure-5(a) Figure-5(b)

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 237
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
Fig.5 (b) presents an unbalance voltage protection scheme for single grounded wye
connected SCB’s using capacitor tap point voltages. An unbalance in the capacitor bank
will cause an unbalance in the voltages at the tap point of the three phases. The
protection scheme consists of a voltage sensing device connected between the
capacitor intermediate point and ground on each phase. A time delay voltage relay with
third harmonic filter is connected to the broken delta secondaries. Modern digital relays
use the calculated zero sequence voltage instead as shown in Fig. 5(b).

b) Unbalance Protection for Grounded Double Wye Banks


Fig. 6 shows a scheme where a current transformer is installed on each neutral of the
two sections of a double Why SCB. The neutrals are connected to a common ground.
The current transformer secondaries are cross-connected to an over-current relay so
that the relay is insensitive to any outside condition that affects both sections of the
capacitor bank in the same direction or manner. The current transformers can be
subjected to switching transient currents and, therefore, surge protection is required.
They should be sized for single-phase load currents if possible. (Alternatively, the
connections from neutral to ground from the two wyes may be in opposite directions
through a single-window current transformer).

Figure-6
c) Voltage differential protection method for grounded wye banks
On large SCBs with large number of capacitor units, it is very difficult to detect the loss
of 1 or 2 capacitor units as the signal produced by the unbalance is buried in the
inherent bank unbalance. The voltage differential provides a very sensitive and efficient
method to compensate for both system and inherent capacitor bank unbalances in
grounded wye capacitor banks. Fig. 8 shows the voltage differential scheme for a single
wye-connected bank and Fig. 8 for a double wye-connected bank.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 238
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

The scheme uses two voltage transformers per phase: one connected to a tap on the
capacitor bank; the other, at the bank bus for single Wye banks; or, for double Wye
banks, at a similar tap on the second bank. By comparing the voltages of both VTs, a
signal responsive to the loss of individual capacitor elements or units is derived.

The capacitor bank tap voltage is obtained by connecting a voltage-sensing device


across the ground end parallel group (or groups) of capacitors. This may be a midpoint
tap, where the voltage is measured between the midpoint of the phase and ground.
Alternatively, the tap voltage may be measured across low-voltage capacitors (that is, a
capacitive shunt) at the neutral end of the phase.

Figure-7 Voltage differential scheme for grounded single wye SCB


For commissioning, after checking that all capacitors are good and no fuses have
operated, the voltage levels are initially adjusted to be equal. The initial difference signal
between the capacitor bank tap voltage and the bus voltage (for single Wye banks)
signals is zero, and the capacitor tolerance and initial system voltage unbalance is
compensated. If the system voltage unbalance should vary, the relay system is still
compensated because a given percent change in bus voltage results in the same
percent change on the capacitor bank tap. Any subsequent voltage difference between
capacitor tap voltage and bus voltage will be due to unbalances caused by loss of
capacitor units within that particular phase. For double Wye banks, the tap voltage is
compared the other Wye tap voltage.

Modern digital relay dynamically compensate secondary errors introduced by sensing


device variation and temperature differences between capacitor units within the bank.

If the bank is tapped at the midpoint the sensitivity is the same for failures within and
outside the tapped portion. If the bank is tapped below (above) the midpoint, the
sensitivity for failures within the tapped portion will be greater (less) than for failures
outside the tap portion. This difference may cause difficulty in achieving an appropriate
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 239
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
relay setting. The sensitivity for a midpoint tap and a tap across low-voltage capacitors at
the neutral end of the phase is the same.

Tapping across the bottom series groups or a midpoint tap is not appropriate for fuseless
banks with multiple strings because the strings are not connected to each other at the
tap point. Tapping across the low-voltage capacitors is suitable for fuseless capacitor
banks.

Figure-8 Voltage differential scheme for grounded double wye SCB


Protection against Other Internal Bank Faults:
The are certain faults within the bank that the unbalance protection will not detect or
other means are required for its clearance.

a) Mid-Rack Phase to Phase Faults


Usually individual phases of a SCB are built on separate structures where phase to
phase faults are unlikely. However, consider an ungrounded single Wye capacitor bank
with two series groups per phase where all three phases are installed upon a single steel
structure. A mid-rack fault between 2 phases as shown in Fig. 9 is possible and will go
undetected. This fault does not cause an unbalance of the neutral voltage (or neutral
current if grounded) as the healthy voltage is counter balance by the 2 other faulty phase
voltages.

The most efficient protection for mid-rack phase to phase faults is the negative sequence
current. Tripping shall be delayed to coordinate with other relays in the system.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 240
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Figure-9 Mid-rack Fault


b) Faults on the Capacitor Bank Bus
Time over-current relays for phase and ground are required to provide protection for
phase and ground faults on the connecting feeder (or bus-work) between the bank bus
and the first capacitor unit. Directional over-current relays looking into the bank are
preferred to avoid mal-operation of the TOC 51N for unbalance system faults.
1.4
Protection of the SCB Against System Disturbances and Faults:

System Over-voltage Protection


The capacitor bank may be subjected to over-voltages resulting from abnormal system
operating conditions. If the system voltage exceeds the capacitor capability the bank
should be removed from service. The removal of the capacitor bank lowers the voltage
in the vicinity of the bank reducing the over-voltage on other system equipment. Time
delayed or inverse time delayed phase over-voltage relays are used.

Relays for Bank Closing Control


Once disconnected from the system a shunt capacitor bank cannot be re-inserted
immediately due to the electrical charge trapped within the capacitor units, otherwise
catastrophic damage to the circuit breaker or switch can occur. To accelerate the
discharge of the bank, each individual capacitor unit has a resistor to discharge the
trapped charges within 5min.

Under-voltage or undercurrent relays with timers are used to detect the bank
going out of service and prevent closing the breaker until the set time has
elapsed.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 241
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
Alstom make electromechanical relay type “VDG-13”, “CTIG-12” & “VTT-11”
Relays are used for above applications. VTT-11 relay setting should be around
5.0s

CONCLUSIONS:
The protection of shunt capacitor banks uses simple, well known relaying principles such
as over-voltage, over-currents. However, it requires the protection engineer to have a
good understanding of the capacitor unit, its arrangement and bank design issues before
embarking in its protection.

Unbalance is the most important protection in a shunt capacitor bank, as it provides fast
and effective protection to assure a long and reliable life for the bank. To accomplish its
goal, unbalance protection requires high degree of sensitivity that might be difficult to
achieve.

The latest IEEE Guide for the Protection of Shunt Capacitors Banks shall be the guiding
document when implementing a protection scheme to a shunt capacitor bank.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 242
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
1.5
RELAY APPLICATION:
-Æ Application diagram of ABB make Numerical capacitor bank protection relay type
SPAJ-160 is shown below;

Schematic connection diagram of “SPAJ-160”

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 243
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Application Example of SPAJ-160:

Fig. Protection of a capacitor bank connected as a double-star in a distribution


network with three-phase current measurement.

Fig. Protection of a capacitor bank connected as a double-star in a distribution


network with two-phase current measurement.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 244
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Fig. Protection of a capacitor bank connected as a double-star in an industrial


network with two- or three-phase current measurement. In this case a non-
directional earth-fault protection is used.

Fig. Protection of a one-phase bridge connected capacitor filter bank.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 245
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

References:
(1) IEEE Std C37.99-2000, IEEE Guide for the Protection of Shunt Capacitors
Banks.
(2) ABB & ALSTOM Relay Manuals.

Thank You
DOBLE ENGINEERING PVT LTD,
305-SAKAR BUILDING,
OLD PADRA ROAD,
VADODARA
PH: (+91) (265) 555 77 15
Email: kdave@doble.com

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 246
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

“MULTIPLICATION OF DOCUMENT IS STRICTLY PROHIBITED”

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 247
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Question #1: What is Power Factor?


Question #2: What Causes Low Power Factor?
Question #3: Why Should I Improve My Power Factor?
Question #4: How Do I Correct (Improve) My Power Factor?
Question #5: How Long Will It Take My Investment in Power Factor
Correction to Pay for Itself?
Question #6: Testing of Application Relay by using DOBLE F6150
INSTRUMENT?

Question #1:
What is Power Factor?

KW is Working Power (also called Actual Power or Active Power or Real Power).
It is the power that actually powers the equipment and performs useful work.

KVAR is Reactive Power.


It is the power that magnetic equipment (transformer, motor and relay) needs to
produce the magnetizing flux.

KVA is Apparent Power.


It is the “vectorial summation” of KVAR and KW.

Let’s look at a simple analogy in order to better understand these terms….

Let’s say you are at the ballpark and it is a really hot day. You order up a mug of
your favorite brew sky. The thirst-quenching portion of your Tea is represented
by KW (Figure 1).

Unfortunately, life isn’t perfect. Along with your ale comes a little bit of foam. (And
let’s face it…that foam just doesn’t quench your thirst.) This foam is represented
by KVAR.

The total contents of mug, KVA, are this summation of KW (the Coffee) and
KVAR (the foam).

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 248
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Figure-1

Power Factor (P.F.) is the ratio of Working Power to Apparent Power.

Looking at our Coffee mug analogy above, power factor would be the ratio of
Coffee (KW) to Coffee plus foam (KVA).

Total Coffee
P.F. = ---------------------
Coffee + FOAM

Thus, for a given KVA:


• The more foam you have (the higher the percentage of KVAR), the lower
your ratio of KW (Coffee) to KVA (Coffee plus foam). Thus, the lower your
power factor.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 249
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

• The less foam you have (the lower the percentage of KVAR), the higher your
ratio of KW (Coffee) to KVA (Coffee plus foam). In fact, as your foam (or KVAR)
approaches zero, your power factor approaches 1.0.

Our Coffee mug analogy is a bit simplistic. In reality, when we calculate KVA, we must
determine the “vectorial summation” of KVAR and KW. Therefore, we must go one
step further and look at the angle between these vectors.

Let’s look at another analogy ……

Kamin here is dragging a heavy load (Figure 2). Kamin’s Working Power (or
Actual Power) in the forward direction, where he most wants his load to travel, is
KW.

Unfortunately, Kamin can’t drag his load on a perfect horizontal (he would get a
tremendous backache), so his shoulder height adds a little Reactive Power, or
KVAR.

The Apparent Power Kamin is dragging, KVA, is this “vectorial summation” of


KVAR and KW.

Figure:-2

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 250
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

The “Power Triangle” (Figure 3) illustrates this relationship between KW, KVA,
KVAR, and Power Factor:

POWER TRIANGLE:

Note that…in an ideal world…looking at the Coffee mug analogy:

• KVAR would be very small (foam would be approaching zero)


• KW and KVA would be almost equal (more Coffee; less foam)

Similarly…in an ideal world…looking at Kamin’s heavy load analogy:


• KVAR would be very small (approaching zero)

• KW and KVA would be almost equal (Kamin wouldn’t have to waste any
power along his body height)
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 251
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

• The angle theta (formed between KW and KVA) would approach zero

• Cosine(Theta) would then approach one

• Power Factor would approach one

So….
In order to have an “efficient” system (whether it is the Coffee mug or Kamin
dragging a heavy load), we want power factor to be as close to 1.0 as possible.

Sometimes, however, our electrical distribution has a power factor much less
than 1.0. Next, we’ll see what causes this.

Question #2:
What Causes Low Power Factor?

Since power factor is defined as the ratio of KW to KVA, we see that low power
factor results when KW is small in relation to KVA. Remembering our beer mug
analogy, this would occur when KVAR (foam, or Kamin’s shoulder height) is
large.

What causes a large KVAR in a system? The answer is…inductive loads.


Inductive loads (which are sources of Reactive Power) include:

• Transformers
• Induction motors
• Induction generators (wind mill generators)
• High intensity discharge (HID) lighting

These inductive loads constitute a major portion of the power consumed in


industrial complexes.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 252
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

So, inductive loads (with large KVAR) result in low power factor.

Question #3:
Why Should I Improve My Power Factor?

You want to improve your power factor for several different reasons. Some of the
benefits of improving your power factor include:

1) Lower utility fees by:

a. Reducing peak KW billing demand

Recall that inductive loads, which require reactive power, caused your low power
factor. This increase in required reactive power (KVAR) causes an increase in
required apparent power (KVA), which is what the utility is supplying.

So, a facility’s low power factor causes the utility to have to increase its
generation and transmission capacity in order to handle this extra demand.

By lowering your power factor, you use less KVAR. This results in less KW,
which equates to a dollar savings from the utility.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 253
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

b. Eliminating the power factor penalty

Utilities usually charge customers an additional fee when their power factor is
less than 0.95. (In fact, some utilities are not obligated to deliver electricity to
their customer at any time the customer’s power factor falls below 0.85.) Thus,
you can avoid this additional fee by increasing your power factor.

2) Increased system capacity and reduced system losses in your electrical


system:

By adding capacitors (KVAR generators) to the system, the power factor is


improved and the KW capacity of the system is increased.

For example, a 1,000 KVA transformer with an 80% power factor provides 800
KW (600 KVAR) of power to the main bus.

By increasing the power factor to 90%, more KW can be supplied for the same amount
of KVA.

The KW capacity of the system increases to 900 KW and the utility supplies only
436 KVAR.

Uncorrected power factor causes power system losses in your distribution


system. By improving your power factor, these losses can be reduced. With the
current rise in the cost of energy, increased facility efficiency is very desirable.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 254
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
And with lower system losses, you are also able to add additional load to your
system.

3) Increased voltage level in your electrical system and cooler, more efficient
motors

As mentioned above, uncorrected power factor causes power system losses in


your distribution system. As power losses increase, you may experience voltage
drops. Excessive voltage drops can cause overheating and premature failure of
motors and other inductive equipment.

So, by raising your power factor, you will minimize these voltage drops along
feeder cables and avoid related problems. Your motors will run cooler and be
more efficient, with a slight increase in capacity and starting torque.

Question #4
How Do I Correct (Improve) My Power Factor?
We have seen that sources of Reactive Power (inductive loads) decrease
power factor:

• Transformers
• Induction motors
• Induction generators (wind mill generators)
• High intensity discharge (HID) lighting

Similarly, consumers of Reactive Power increase power factor:

• Capacitors
• Synchronous generators (utility and emergency)
• Synchronous motors

Thus, it comes as no surprise that one way to increase power factor is to add
capacitors to the system. These--and other ways of increasing power factor--are
listed below:

1) Installing capacitors (KVAR Generators)

Installing capacitors decreases the magnitude of reactive power (KVAR or


foam), thus increasing your power factor.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 255
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
Here is how it works (Figure 5 below)…

Inductance and capacitance react 180 degrees to each other.


Capacitors store KVARS and release energy opposing the reactive energy
caused by the inductor.

The presence of both a capacitor and inductor in the same circuit results in the
continuous alternating transfer of energy between the two.

Thus, when the circuit is balanced, all the energy released by the inductor is
absorbed by the capacitor.

Following is an example of how a capacitor cancels out the effect of an inductive


load….

2) Minimizing operation of idling or lightly loaded motors.

We already talked about the fact that low power factor is caused by the presence of
induction motors. But, more specifically, low power factor is caused by running induction
motors lightly loaded.

3) Avoiding operation of equipment above its rated voltage.

4) Replacing standard motors as they burn out with energy-efficient


motors.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 256
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
Even with energy-efficient motors, power factor is significantly affected by
variations in load. A motor must be operated near its rated load in order to realize
the benefits of a high power factor design.

Question #5
How Long Will It Take my Investment in Power Factor
Correction to Pay for Itself?

A calculation can be run to determine when this payoff will be. As an example,
assume that a portion of your facility can be modeled as in Figure 6 below. Your
current power factor is 0.65.

Following are the parameters for your original system:

• 163 KW load
• 730 hours per month
• 480 Volt, 3 phase service
• 5% system losses
• Load PF = 65%

We’ll calculate the total amount the utility charges you every month as follows:

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 257
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

First, we’ll calculate your energy usage:

163 KW X 730 Hours/Month X Rs4.08/KWH = Rs4,854.79/Month

Next, we’ll calculate your demand charge:

163 KW X Rs2.16/KW = Rs352.08/Month

Finally, we’ll calculate your Power Factor Penalty:

190 KVAR X 730 Hours/Month X Rs0.15/KVARH = Rs208/Month

Now, let’s say that you decide to install a capacitor bank (Figure 7). The 190
KVAR from the capacitor cancels out the 190 KVAR from the inductive motor.
Your power factor is now 1.0.

Following are your parameters for your system with capacitors:

• Corrected PF = 1.0

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 258
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

You can calculate your loss reduction:

Loss Reduction = 1-(0.652 / 1.002) = 0.58

Therefore, your system loss reduction will be as follows:

0.58 X 0.05 (losses) = 0.029 System Loss Reduction


Your total KW load will be reduced as follows:

163 KW X 0.029 = 4.7 KW

Now we can calculate your savings in energy usage:

4.7 KW X 730 Hours/Month X Rs4.08/KWH = Rs141.00/Month

Next, we’ll calculate your savings in demand charge:

4.7 KW X Rs2.16/KW = Rs10.15/Month

Finally, remember that your Power Factor Penalty is zero.

Let’s calculate how long it will take for this capacitor bank to pay for itself.

• Capacitor Cost = Rs30.00/KVAR

Suppose your savings per month are as follows:

• Rs141.00 Energy Usage


• Rs10.15 Demand Charge
• Rs208.00 PF Penalty Charge
Rs359.15 Total

Your payback will be at the following time:

Rs15.00/KVAR X 190 KVAR/Rs359/Month = 16 Months

Installation of your capacitors will pay for themselves in 16 months.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 259
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Question #6:
Testing of Application Relay (LoVAR) by using DOBLE F6150
INSTRUMENT?

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 260
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Vector Diagram

• Select Phase Rotate “I” (PHROTI) macro in “ProTesT software.


• Click on the “Test Tab”.
• Select Source “VA” in SRC column.
• Select Source “I1” in SRC column.
• Put the terminal numbers (i.e. 27-28, 25-26) in high and low column.
• Put the Amplitude of Voltages (i.e. VA=110V & I1=1A).
• Put the Action Tab of phase angles in phs column.
• Put the value of Frequency (i.e. FA=50.000Hz, FB=50.000Hz) in Freq
column.
• Put the value of Expected angle at which the relay will operate (
P.F.=0.85lag, so angle is 31.78deg.)
• Select “Action” menu.
• Put the value of Offset phase, Offset duration.
• Put the value of “+/- Delta phase” (Say 1deg.), Delta time.
• Put the value of “Phase limit” (Say –90deg)
• Give run command.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 261
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

“MULTIPLICATION OF DOCUMENT IS STRICTLY PROHIBITED”

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 262
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Introduction:

The objective of the electric utility is to deliver sinusoidal voltage at fairly constant
magnitude throughout their system. This objective is complicated by the fact that there
are loads on the system that produce harmonic currents. These currents result in
distorted voltages and currents that can adversely impact the system performance in
different ways.
As the number of harmonic producing loads has increased over the years, it has become
increasingly necessary to address their influence when making any additions or changes
to an Installation.
To fully appreciate the impact of this phenomenon, there are two important concepts to
bear in mind with regard to power system harmonics. The first is the nature of harmonic-
current producing loads (non-linear loads) and the second is the way in which harmonic
currents flow and how the resulting harmonic voltages develop.

Linear and non-linear loads:

A linear element in a power system is a component in which the current is proportional to


the voltage. In general, this means that the current wave shape will be the same as the
voltage. Typical examples of linear loads include motors, heaters and incandescent
lamps.

On the other hand, the current wave shape on a non-linear load is not the same as the
voltage. Typical examples of non-linear loads include rectifiers (power supplies, UPS
units, discharge lighting), adjustable speed motor drives, ferromagnetic devices, DC
motor drives and arcing equipment.

The current drawn by non-linear loads is not sinusoidal but it is periodic, meaning that
the current wave looks the same from cycle to cycle. Periodic waveforms can be
described mathematically as a series of sinusoidal waveforms that have been summed
together.

Harmonics are created by electronic circuits such as adjustable frequency speed


drives (VFD), rectifiers, rectiformer etc. They can cause problems to other loads in
power system. The bas frequency of the power supply is the fundamental, or first
harmonic, which in the standard Indian power system, is 50Hz. Additional harmonics,
which in frequency are multiples of the first or fundamental, can appear on the power
supply. For example, the second harmonic of a 50Hz supply is 100Hz, which is twice
50Hz. The third becomes 150Hz.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 263
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

Fundamental Frequency 50Hz

Third Harmonic Frequency 150Hz

Symmetrical & Un-symmetrical waves:

Symmetrical waves contain only odd harmonics and un-symmetrical waves contain
even and odd harmonics.
A symmetrical wave is one in which the positive portion of the wave is identical to the
negative portion of the wave. An un-symmetrical wave contains a DC component (or
offset) or the load is such that the positive portion of the wave is different than the
negative portion. An example of un-symmetrical wave would be a half wave rectifier.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 264
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
Phase Rotation:

Phase rotation describes the order in which waveforms in each phase of a three-phase
system cross zero. This can be shown with a waveform diagram, as illustrated below, or
with a phasor diagram of lines and arrows, also shown below. Phasors are used for
simplification purposes. The length of the arrows represents voltage or current
magnitudes, while the angles between them show phase relationship.

Odd-numbered harmonic, such as the 3rd, 5th, etc, are more prevalent than even-
numbered harmonics, such as the 2nd and 4th. Higher-numbered harmonics are generally
smaller in amplitude, reducing their effect on the power distribution system.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 265
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
All harmonics cause heat in conductors and other system components. This is in
addition to the heat generated by normal operating currents. Negative sequence
harmonics, in addition to this heating effect, also cause another problem in induction
motors. The reverse phase rotation of these harmonics generates a reversal rotating
magnetic field, which not only reduces forward motor torque, but also increases the
motor current demand.

Harmonic current flow:


When a non-linear load draws current, that current passes through all of the impedance
that is between the load and the system source. As a result of the current flow, harmonic
voltages are produced by impedance in the system for each harmonic. Distorted-current
induced voltage distortion. These voltages sum and when added to the nominal voltage
produce voltage distortion. The magnitude of the voltage distortion depends on the
source impedance and the harmonic voltages produced. If the source impedance is low
then the voltage distortion will be low. If a significant portion of the load becomes non-
linear (harmonic currents increase) and/or when a resonant condition prevails (system
impedance increases), the voltage can increase dramatically.

These voltages sum and when added to the nominal voltage produce voltage distortion.
The magnitude of the voltage distortion depends on the source impedance and the
harmonic voltages produced.

If the source impedance is low then the voltage distortion will be low. If a significant
portion of the load becomes non-linear (harmonic currents increase) and/or when a
resonant condition prevails (system impedance increases), the voltage can increase
dramatically.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 266
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
Harmonic Effects:

Zero sequence harmonics add together, creating a single-phase signal that does not
produce a rotating magnetic field. This harmonics, however, can cause additional
heating in the neutral conductor of a three-phase, four-wire system. This can be a
significant problem since the neutral conductor is usually not protected by a fuse or
circuit breaker.

Harmonic currents can produce a number of problems, namely:


• Equipment heating
• Equipment malfunction
• Equipment failure
• Communications interference
• Fuse and breaker mis-operation
• Process problems
• Conductor heating

K- Factor for Transformer:

K-Factor is a numerical rating that indicates a transformer’s ability to handle the extra
heating caused by harmonics. A standard transformer has a K-1 rating. A transformer
with a K-5 rating would be able to handle five times the harmonic heating effects of a
standard transformer.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 267
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
It is essentially a transformer survival rating. As long as the load k-factor is lower than
the ‘k’rating of the transformer, the full kVA rating of the transformer can be used. The
transformer survives the harmonic losses without overheating but voltage distortion
remains essentially unaffected.

Harmonics analysis & Testing of Relays:

Harmonic analysis is required for power system & protection engineers to reduce
or avoid nuisance trips under healthy power system. DOBLE “DATC” and
“TransWin” Application software are used for harmonic, Swing, Various transient
phenomenon like C.T. saturations, magnetizing inrush phenomenon, Locked
rotor characteristic of motor etc.

Capability:

• User friendly and easy to use.


• No programming skilled is required.
• Easy for analysis.
• Graphical representation.
• Graphical display output.
• Export “COMTRADE” file for Testing of Relays.
• Automatic Fault calculations like “S-L-G”, “D-L-G”, “Three-phase fault” etc.

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 268
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery
Problem, Effect, & Solution:

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 269
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

The design & application of relays is always a challenge for power system
protection engineers because it’s job like as a detective to detect a power system
faults & isolate the faulty circuit from the power system.

It offers all the satisfying life, security, interest & number of varieties
(technological)

Security: Means the profession is not over crowded, in fact the manufacturers of
relays have the greatest difficulty in finding a good protection engineers.

Interest: Means it’s require wide range of knowledge of Power system &
machines while the engineers want to design the relays. It means the relay
engineers constantly adds to mathematical, electrical & general knowledge.

Varieties: Means it comes from the wide range of characteristics required of


protective relays and activities which is connected with making & selling them,
such as power system study, automation study, computer applications, customer
applications etc.

References:
2. Protective Relaying, Wan.C.Warrington.
3. Art & Science of Relay, Russell Masson.
4. Power System & Protection, Bhuvnesh Ojha & Date.
5. Engineering Dependable Protection Part-I.
6. IEEE/ANSI Committee Reports.
7. ALSTOM, ABB, SIEMENS, REYROLLY Relay Manuals
8. Protective relay Application guide – GEC ALSHOM, UK
9. ProTesT user guide – Doble Engineering Company, USA

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 270
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India

DATE 1/10/2005
Knowledge Is Power SM

Apparatus Maintenance and Power


Management For Energy Delivery

DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 271
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com

Das könnte Ihnen auch gefallen