Beruflich Dokumente
Kultur Dokumente
DATE 1/10/2005
Knowledge Is Power SM
DATE 1/10/2005
Knowledge Is Power SM
DATE 1/10/2005
Knowledge Is Power SM
Types of protection
A - Fuses
For LV Systems, Distribution Feeders and Transformers, VT’s, Auxiliary Supplies
C - DIFFERENTIAL
For feeders, Bus-bars, Transformers, Generators etc
1. High Impedance
2. Low Impedance
3. Restricted E/F
4. Biased
5. Pilot Wire
D - Distance
For transmission and sub-transmission lines and distribution feeders, also used as back-
up protection for transformers and generators without signaling with signaling to provide
unit protection e.g.:
DATE 1/10/2005
Knowledge Is Power SM
E - Miscellaneous:
1. Under and over voltage
2. Under and over frequency
3. A special relay for generators, transformers, motors etc.
4. Control relays: auto-reclose, tap change control, etc.
5. tripping and auxiliary relays
Speed
Fast operation: minimizes damage and danger
Very fast operation: minimizes system instability discrimination and security can be
costly to achieve.
Examples:
1. differential protection
2. differential protection with digital signaling
3. distance protection with signaling
4. directional comparison with signaling
Dependability / reliability
Protection must operate when required to Failure to operate can be extremely damaging
and disruptive Faults are rare. Protection must operate even after years of inactivity
Improved by use of:
1. Back-up Protection and
2. duplicate Protection
Security / Stability
Protection must not operate when not required to e.g. due to:
1. Load Switching
2. Faults on other parts of the system
3. Recoverable Power Swings
Overlap of protections
1. No blind spots
2. Where possible use overlapping CTs
DATE 1/10/2005
Knowledge Is Power SM
Auxiliary supplies
Required for:
1. Tripping circuit breakers
2. Closing circuit breakers
3. Protection and trip relays
• AC. auxiliary supplies are only used on LV and MV systems.
• DC. auxiliary supplies are more secure than ac supplies.
• Separately fused supplies used for each protection.
• Duplicate batteries are occasionally provided for extra security.
• Modern protection relays need a continuous auxiliary supply.
• During operation, they draw a large current which increases due to
operation of output elements.
Relays are given a rated auxiliary voltage and an operative auxiliary voltage range. The
rated value is marked on the relay. Refer to relay documentation for details of operative
range. it is important to make sure that the range of voltages which can appear at the
relay auxiliary supply terminals is within the operative range.
IEC recommended values (IEC 255-6):
Rated battery voltages:
12, 24, 48, 60, 11 0, 125, 220, 250, 440
Preferred operative range of relays:
80 to 10% of voltage rated
AC. component ripple in the dc supply:
<10% of voltage rated
COST
The cost of protection is equivalent to insurance policy against damage to plant, and loss
of supply and customer goodwill.
Acceptable cost is based on a balance of economics and technical factors. Cost of
protection should be balanced against the cost of potential hazards there is an economic
limit on what can be spent.
Minimum cost:
Must ensure that all faulty equipment is isolated by protection
Other factors:
1. Speed
2. Security/Stability
3. Sensitivity:
Degree of risk in allowing a low level fault to develop into a more severe fault
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 5
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
DATE 1/10/2005
Knowledge Is Power SM
Check list
1) Is the correct rated voltage applied?
2) Is the applied coil voltage within the allowable continuous
voltage limit?
3) Is the ripple in the coil voltage within the allowable level?
4) For voltage applied to a polarized coil, is polarity observed?
5) When hot start is required, is the increase in coil resistance
resulting from coil temperature rise taken into account in setting
Coil Drive Input coil voltage?
6) Is the coil voltage free from momentary drop caused by load
current?
(Special attention for self-holding relays.)
7) Is supply voltage fluctuation taken into account when setting
the rated coil voltage?
8) The relay status may become unstable if the coil voltage (current)
is gradually increased or decreased. Was the relay tested in a
real circuit or with a real load?
DATE 1/10/2005
Knowledge Is Power SM
DATE 1/10/2005
Knowledge Is Power SM
DATE 1/10/2005
Knowledge Is Power SM
DATE 1/10/2005
Knowledge Is Power SM
TABLE OF CONTENTS:
DATE 1/10/2005
Knowledge Is Power SM
1.1 INTRODUCTION:
Industrial power distribution systems make extensive use of cable feeder for
example, between “captive generation bus” or “grid supply bus” to load center /
power control center. These feeders are too often radial or sometimes form part
of ring main system. While IDMTL OC / E/F protection is mostly used for radial
distribution feeders particularly in the tail end, unit type protection such as a pilot
wire protection, are also sometimes used on critical feeders.
The unit protections are highly selective, sensitive & fast in operation but don’t
have any backup capabilities. The IDMTL protections on the contrary, are simple
& economical but slower in operation to necessities time co-ordination between
adjacent sections for selective tripping. IDMTL relays, however provide excellent
backup protection to the downstream system.
DATE 1/10/2005
Knowledge Is Power SM
While at the lower end of the distribution system (particularly at low voltage
levels), fuses or series connected trip coils operating on switching devices, are
used for short circuit protection, IDMT over phase/earth current relays find wide
application at medium voltage levels.
As the name implies, IDMTL relays have an inverse time OC characteristic (i.e.
the operating time is inversely proportional to the current) and a definite minimum
time (DMT) for high multiples of setting current. The time /current curve is usually
represented on a logarithmic scale and gives the operating time at different
multiples of setting current, for the maximum “Time Multiple Setting” (TMS). The
TMS is continuously adjustable giving a range of time/current characteristic.
DATE 1/10/2005
Knowledge Is Power SM
Where,
PSM = Plug setting multiplier = If/Is
TMS = Time multiplier setting
TD = Time dial setting
DATE 1/10/2005
Knowledge Is Power SM
DATE 1/10/2005
Knowledge Is Power SM
DATE 1/10/2005
Knowledge Is Power SM
G1 TR
F1 F2 F3
R1 R2
1.0s
0.75s
0.5s
0.2s
Disadvantage: Relay “R1” will operate after 1.0s on “F1”, “F2” & “F3”
Where there are many section in series the tripping time for a fault near the
power source may be dangerously high. This is obviously un-desirable because
such faults involve large currents and are destructive if not removed quickly. In
fact, the disadvantage of time-graded over current relays is the heaviest faults
are cleared slowest.
Standard Inverse Definite Minimum Time lag (IDMTL) over current relays:
It’s a combination curve of Inverse time + Definite minimum time. This relay
covers majority of the application in power system
DATE 1/10/2005
Knowledge Is Power SM
The IDMTL relays provide both time & current grading to achieve discrimination
between successive stage in the distribution system.
DATE 1/10/2005
Knowledge Is Power SM
1) Sensitivity:
Example:
----Æ Fault current magnitude = 35kA
----Æ CTR = 3000/1
----Æ Relay Pickup, set at 75%
Relay Operating current on Primary side = (75/100)*(3000) = 2250 Amp
Relay Operating current on Secondary side = (75/100)*(1) = 0.75 Amp
Sensitivity of relay during a fault = (2250/35000)*100 = 6.42%
Thus, lower the setting, higher will be the sensitivity for fault detection.
2) Selectivity:
1) Discrimination by Time:
• Basically used with definite time relays
• Time of operation is independent of current magnitude
• Discrimination time between successive relays say 0.3 sec
DATE 1/10/2005
Knowledge Is Power SM
DISADVANTAGE:
• Operating time of the upstream relays will be very high
• The fault closest to the source takes longest time to clear
ADVANTAGE:
• Defined operating time for variable source operating condition.
2) Discrimination by Current:
• Applicable only when substantial difference between the fault
current magnitudes exist for the faults on the two ends of the
equipment.
• The impedance of the equipment shall be substantial that will
create the above difference.
EXAMPLE:
• For the fault on the L.T. side of transformer TR
• Fault current = 40,000 A @ 415V
= 1509.09 A @ 11kV (Reflected fault on 11kV side)
• For the fault on the H.T. side of Transformer TR
• Fault current = 13.5 kA @ 11kV
• IDMTL unit of Transformer Primary side (11kV) relay should be
operate as a backup protection on L.T. fault
• HIGHSET unit of Transformer Primary side (11kV) relay should be
operate on H.T. fault
DISADVANTAGE:
• The discrimination is obtained but no backup ensured
DATE 1/10/2005
Knowledge Is Power SM
EXAMPLE:
• For a given fault current magnitude, discrimination time is 0.3s for
all the successive relays
• Pickup value for all the relays set below the fault current level
• For the fault on the outgoing feeder-1
• Fault current = 40,000 A @ 415V
= 1509.2 A @ 11kV (Reflected fault current on H.T.
side)
• 250 A fuse operates in 0.01s
• Next feeder-2 relay operates in 0.25s on L.T. side fault
• Next feeder-3 relay operates in 0.5s on L.T. side fault
• Next feeder-4 relay operates in 0.75s on L.T. side fault
• For H.T. side of the Transformer TR
• Fault current = 13.5 kA @ 11kV
• Same Feeder-4 relay operates in 0.25s on H.T. faults
ADVANTAGE:
• With the same Pickup & Time dial settings, lower Tome of
operating for near end faults and higher operating times for near
end faults inherently achieved.
• In case of the difference in the fault current magnitude along
system, IDMTLL relays are superior to the DMT relays
• In case of same fault current magnitude along system, desired
operating time can be achieved by adjusting pickup & time dial
4) SPEED:
• Speed: the clearance time of the fault
• Fault clearing time < 100ms, high speed tripping
• Necessity of high speed tripping:
• Minimizing the damage of the equipment
• Increasing stability margin for synchronous machines
• Avoiding unwanted tripping of voltage sensitive loads
DATE 1/10/2005
Knowledge Is Power SM
1.4 Mainly Two types of Phase & Earth fault Over current relays:
Non-directional means when the fault current can flows on both direction
through relay & fault current magnitude is more than threshold level of relay, it
gives trip command to Circuit breaker.
F1 F2
G1
F1
F2
R1
Where,
R1 = Non-directional OC relay
F1 = In zone fault
F2 = Out zone fault
DATE 1/10/2005
Knowledge Is Power SM
1.4.1 Non-directional Three Over current and One Earth Fault Scheme of
Protection of a “DY1” & “DY11” Transformer’s feeder
If the relays are protecting a transformer feeder, two over current and one earth fault
Why two over current & one earth fault scheme of Protection is inadequate?
For the “Y-B” fault as shown in figure-2, the directions and magnitudes of fault currents
are shown. If “Y-B” fault occurs on the secondary side of a transformer having vector
group “DY1”, the magnitude of the current will be Iy, 2Iy & Iy in the R, Y & B lines of
primary side respectively. The magnitude of the fault current is maximum in “Y-ph” &
in “Y-ph” there is no over current element in this scheme as shown in figure-3.
The tripping of the circuit breaker will be delayed because of low current (Iy) flows in “R-
ph” & “B-ph”. Thus two over current and one earth fault scheme is inadequate protection
for this particular case.
DATE 1/10/2005
Knowledge Is Power SM
FIGURE:-2
DATE 1/10/2005
Knowledge Is Power SM
Figure-3
RECOMMENDATION:
IT IS BETTER TO PUT 3-OC & 1-E/F SCHEME INSTEAD OF 2-OC & 1-E/F SCHEME
FOR CRITICAL TRANSFORMER WHICH HAVE “DY-1” OR “DY-11” VECTOR GROUP.
DATE 1/10/2005
Knowledge Is Power SM
Particularly on any Transformer primary feeder required Two Over current elements;
[A] Inverse definite Minimum time lag (IDMTL) Over current Unit
Application of IDMTL Unit is for Backup Protection of any down stream faults
on Secondary side & primary faults on primary side. It is always co-ordinate with
(take more time) for fault on primary side & it may chance to damage the
transformer to sustain the fault current for longer time (Say 400ms or more). That
is why the highest unit is required to operate instantaneously (Say 50ms) for
primary feeder.
on fault (F1).
The setting of an instantaneous over current unit on the primary side of transformer
should be little above asymmetrical value of the fault current for three phase fault on
the secondary of the transformer & it should be lesser than minimum value of the
fault current on the primary side.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 26
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
CTR = 150 / 1A
RELAY TYPE = CDG-61
PLUG SETTING RANGE OF IDMETL UNIT = 0.5 – 2.0A
PLUG SETTING OF IDMTL UNIT = 1.0A
PLUG SETTING RANGE OF HIGHSET UNIT = 2.0 – 20A
FAULT CURRENT (F2) = 40Ka on 415V BUS
“F2” FAULT CURRENT REFLECTED ON 11Kv = 1.509kA
[A]
PLUG SETTING MULTIPLIER DURING “F2” FAULT = 1.509 *1000 / 150
PSM = 10.06
[B]
PLUG SETTING MULTIPLIER DURING “F1” FAULT = 4.000 *1000 / 150
PSM = 26.66
[C]
HIGHSET UNIT SHOULD NOT BE OPERATED ON FAULT “F2”. THEREFORE,
HIGHSET SETTING is > PSM “10.06” other wise it will immediately tripped on
through fault (F2) & isolate whole system.
DATE 1/10/2005
Knowledge Is Power SM
DATE 1/10/2005
Knowledge Is Power SM
When fault current can flow in both directions through the relay location, it may
be necessary to make the response of the relay directional by the introduction of
a directional control facility. The facility is provided by use of additional voltage
inputs or Polarizing voltage inputs to the relay.
Relays that must respond to power are generally used for protecting against
conditions other than short circuits. Such relays are connected to be polarized by
a voltage of a circuit, and the current connections and the relay characteristics
are chosen so that maximum torque in the relay occurs when unity-power-factor
load is carried by the circuit. The relay will then pick up for power flowing in one
direction through the circuit and will reset for the opposite direction of power flow.
Directional Element of OC relay checks the phase angle between current &
voltage and threshold magnitude of current. If the phase angle is reverse & fault
magnitude crosses it’s threshold then it allows to operation of relay.
Application:
• Generally the Protection is applied for parallel feeders, cables, lines
& transformers in ring main system.
• Sometimes it is more helpful while relay co-ordination is not
possible through non-directional IDMTL OC relays.
• Protection should be able to offered with higher sensitivity while
using the directional control. This is not possible with non-
directional OC relays.
• Selective tripping
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 29
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
G1
F1
R1 CB
G2
F2
“F2” FAULT FEED BY
“SOURCE – G1
R2
Where,
R1 = Directional OC relay on Line-1
R2 = Directional OC relay on Line-2
F1 = In zone fault of Line-1
F2 = In zone fault of Line-2
DATE 1/10/2005
Knowledge Is Power SM
RELAY CONNECTIONS:
There are mainly three possibilities for a connectional connections of voltage and
current inputs & these connections are dependent on the phase angle, at unity
system power factor, by which the current and voltage applied to the relay are
displaced.
DATE 1/10/2005
Knowledge Is Power SM
Circuit diagram of most commonly method for phase over current element is 90o
quadrature connection as shown below;
DATE 1/10/2005
Knowledge Is Power SM
Fig.5 Connections and vector diagram for a directional relay where phase-to-
neutral voltage is not available.
DATE 1/10/2005
Knowledge Is Power SM
1) 30o MTA LEAD (Maximum torque angle) or 30o RCA LEAD (Relay
characteristic angle)
The A phase relay element is supplied with Ia current and Vbc voltage displaced
by 30° in an anti-clockwise direction. In this case, the relay maximum sensitivity
is produced when the current lags the system phase to neutral voltage by 60°.
This connection gives a correct directional tripping zone over the current range of
30° leading to 150° lagging; see Figure 6. The relay sensitivity at unity power
factor is 50% of the relay maximum sensitivity and 86.6% at zero power factor
lagging. This characteristic is recommended when the relay is used for the
protection of plain feeders with the zero sequence source behind the relaying
point.
DATE 1/10/2005
Knowledge Is Power SM
2) 45o MTA LEAD (Maximum torque angle) or 30o RCA LEAD (Relay
characteristic angle)
The A phase relay element is supplied with current Ia and voltage Vbc displaced
by 45° in an anti-clockwise direction. The relay maximum sensitivity is produced
when the current lags the system phase to neutral voltage by 45°. This
connection gives a correct directional tripping zone over the current range of 45°
leading to 135° lagging. The relay sensitivity at unity power factor is 70.7% of the
maximum torque and the same at zero power factor lagging; see Figure 7.
DATE 1/10/2005
Knowledge Is Power SM
PRINCILAL:
The directional earth-fault unit measures the neutral current “I0”, the residual
voltage “U0” from open delta PT and the phase angle(pHi) between residual
voltage(U0) and neutral current(I0). An earth-fault stage starts if all of the three
criteria below are fulfilled at the same time:
RELAY CONNECTIONS:
The residual current is extracted as shown in Figure 8. Since this current may be
derived from any phase, in order to obtain a directional response it is necessary
to obtain an appropriate quantity to polarize the relay.
Residual voltage:
A suitable quantity is the residual voltage of the system. This is the vector sum of
the individual phase voltages. If the secondary windings of a three-phase, five
limb voltage transformer or three single-phase units are connected in broken
delta, the voltage developed across its terminals will be the vector sum of the
phase to ground voltages and hence the residual voltage of the system, as
illustrated in Figure 8. The primary star point of the VT must be earthed.
However, a three-phase, three limb VT is not suitable, as there is no path for the
residual magnetic flux.
DATE 1/10/2005
Knowledge Is Power SM
Figure 8. Residual voltage connection for Earth fault element by using open delta PT
DATE 1/10/2005
Knowledge Is Power SM
DATE 1/10/2005
Knowledge Is Power SM
The characteristic angles are varies from relay to relay but, most commonly are
as shown below;
1) 30o MTA LAG or 30o RCA LAG FOR SOLIDLY EARTHED SYSTEM
2) 45o MTA LAG or 45o RCA LAG FOR SOLIDLY EARTHED SYSTEM
3) 12.5o MTA or 14o MTA FOR RESISTIVE EARTHED SYSTEM
DATE 1/10/2005
Knowledge Is Power SM
where:
Vres = residual voltage
Ires = residual current
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 40
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
where:
Vres = residual voltage
Ires = residual current
Vo = zero sequence voltage
Io = zero sequence current
φ = angle between Vres and Ires
φc = relay characteristic angle setting
DATE 1/10/2005
Knowledge Is Power SM
R-ph
Y-ph
B-ph
IDMT /
DMT E/F
3Iao
DATE 1/10/2005
Knowledge Is Power SM
1.7 Sensitive Earth fault protection using Core Balance C.T. (CBCTs):
The CBCT surrounds all 3-phases (and neutral also in case of 4-core cables) and
is excited by the primary residual current. Better sensitivities are achieved due to
reduced number of secondary turns since the turns ratio is independent of the
load current. Usually static relays with sensitive setting and low ohmic burdens
should be used with CBCTs to limit the output voltage requirement in view of low
turns ratio.
The CBCTs are used on cables which are usually armoured. The earthing of the
cable sheath/armour should be such that the earth return current carried by the
armour should not offset the earth fault current in the phase conductor as it would
adversely affect the sensitivity. Typical earthing arrangement of the
sheath/armour at load and source end is shown in figure ANNEXURE:-1
DATE 1/10/2005
Knowledge Is Power SM
E/F O/C
DATE 1/10/2005
Knowledge Is Power SM
1.9 Non-operation of two O/C and one E/F scheme for Parallel Feeder:
Here as shown in figure below; two O/C and E/F scheme of protection as applied
to a parallel feeder where the phase relays are provided in “R” & “B” phases. Let
us consider “R-Y” phase fault as shown in figure below. The instantaneous
directions of currents are as shown. For the case of the “R-Y” fault as shown in
figure(), the relay in “R-phase” gets practically zero current (if fault current is of
the order of the normal load current of feeder) while “Y-phase” carries practically
double the fault current. The relay “R” will not operate because of insignificance
current flow through its element and since there is no relay element in “Y-phase”
this fault is not cleared.
Solution:
Three O/C & one E/F relay protection scheme take care of this.
IF2
IF2
IF1 IF2
2IF2
IF2 = IF1
DATE 1/10/2005
Knowledge Is Power SM
DATE 1/10/2005
Knowledge Is Power SM
DATE 1/10/2005
Knowledge Is Power SM
In this arrangement current transformers of identical ratio & ratings are provided
at each end of the protected zone & are interconnected by secondary pilot as
shown in figure:2.1 below;
DATE 1/10/2005
Knowledge Is Power SM
CABLE
CT1 CT2
PILOT CHANNEL
87 R1 87 R2
Figure:2.1
For external faults, the two end CT’s see equal inflow & out flow producing a
circulating current between the CT secondary & Pilots, with no differential current
through the relay. For an in zone fault, however, the secondary current have an
additive polarity & hence the summated current flows through the relay, causing
operation.
In practice, unequal saturation of the CTs can cause increased spill current
through the relay on external faults, producing instability. The problem is normally
overcome by making the relay branch “high impedance” by adding series
stabilizing resistor.
In balanced voltage system, CT secondary outputs are opposed for through fault
so that no current flows in series connected relays. An in zone fault however,
produce a circulating current, causing operation. The arrangement is shown in
figure 2.2
DATE 1/10/2005
Knowledge Is Power SM
CABLE
CT1 CT2
PILOT CHANNEL
87 R1 87 R2
Figure: 2.2
DATE 1/10/2005
Knowledge Is Power SM
In three phase system, independent protection can be provided for each phase
using phase by phase comparison of the two end currents. This would however a
require a minimum for core pilot adding up to the cost. An alternative is to
combine the separate phase current in to a single quantity for comparison over a
pair of Pilots. This achieved by using summation current transformer. A typical
summation CT is shown in figure 2.3
R-ph
Y-ph
B-ph
The interface section of the summation winding (i.e. A-B & B-C) usually have
equal number of turns & the neutral end winding (C-N) having greater number of
turns. The above summation arrangement would produce output for balanced as
well as un balanced faults. However, the relay offers a different sensitive for
different types of faults depending upon the phases involved. In the summation
arrangement illustrated, the associated relay will have highest sensitive for A-C &
A-N faults.
DATE 1/10/2005
Knowledge Is Power SM
The pilot circuits are subjected to various hazards, which can cause open circuit
or short circuit of the pilot cores. While overhead pilots are vulnerable to storms,
buried pilots may be damaged during excavation. The pilot failure may lead to
either mal operation or non-operation of the protection and hence continuous
supervision of the healthiness of the pilots becomes necessary.
This is achieved by injecting a small d.c. current through the pilot from one end
and monitoring its presence at the other end by energizing an auxiliary relay. The
auxiliary relay resets in the event of any discrepancy in the pilots and sounds an
alarm. A small time delay is introduced to prevent transient operation due to
primary system faults causing momentary dip in the auxiliary supply.
Over current check feature may also be incorporated to prevent tripping on load
in the event of a pilot open circuit condition as it may lead to instability. A typical
pilot supervision arrangement is shown in figure-ANAXURE-2.
The supervision arrangement detects any discrepancy in the pilot including open
circuit, short circuit & cross pilot conditions.
DATE 1/10/2005
Knowledge Is Power SM
DATE 1/10/2005
Knowledge Is Power SM
TABLE OF CONTENTS:
DATE 1/10/2005
Knowledge Is Power SM
DATE 1/10/2005
Knowledge Is Power SM
3.1 INTRODUCTION:
Successful Operation of a power system depends largely on the engineer’s
ability to provide reliable and uninterrupted service to loads. The reliability of the
power supply implies much more than merely being available. Ideally, the loads
must be fed at constant voltage and frequency at all times. In practical terms this
means that consumer’s equipment may operate satisfactorily. For example, a
drop in voltage of 10-15% or a reduction of the system frequency of only a few
hertz may lead to stalling of the motor loads on the system.
As electrical utilities have grown in size, and the number of interconnections has
increased, planning for future expansion has become increasingly complex. The
increasing cost of additions and modifications has made it imperative that utilities
consider a range of design options, and perform detailed studies of the effects on
the system of each option, based on the number of assumptions: like normal and
abnormal operating conditions, peak and off-peak loadings, and present and
future years of handled.
Future transmission and distribution systems will be far more complex than those
of today. This means that the power system planner’s task will be more complex.
If the systems being planned are to be optional with respect to construction cost,
performance, and operating efficiency, better planning tools are required.
The per unit method has an advantage over the percent method because the
product of two quantities expressed in per unit is expressed in per unit itself, but
the product of two quantities expressed in percent must be divided by 100 to
obtain the result in percent.
The per unit value of a line to neutral voltage on the line to neutral voltage base
is equal to the per unit value of the line to line voltage at the same point on the
line to line voltage base if the system is balanced. Similarly, the three-phase kVA
is three times the kVA/phase and the three-phase kVA base is three times the
DATE 1/10/2005
Knowledge Is Power SM
Base impedance and base current value can be computed directly from three-
phase values of base kilovolts and base kilo-amperes.
Which shows that per unit impedance is directly proportional to “base MVA” and
inversely proportional to the square of the base voltage. Therefore, to change
from per unit impedance on a given base to per unit impedance on a new base,
the following equation is used,
Per unit Znew = ( Per unit Zgiven )*( Base kVgiven / Base kVnew )2*( Base MVAnew / Base MKVAgiven )
DATE 1/10/2005
Knowledge Is Power SM
• The way in which transformers are connected in three phase circuits does not
affect the “PU” impedances of the equivalent circuit, although the transformer
connection does determine the relation between the voltage bases on the two
sides of the transformer.
If the transformer parameters are given in actual units (ohms). Then the values
are converted to common base as;
Base kV is the voltage referred to the side at which measurements are made.
The transformer R/X ratio is used to separate the transformer resistance and
reactance values from the impedance. If number of units are in parallel then the
effective equivalent impedance is computed by dividing the impedance by units.
X = [ {√Z2 / { 1 + ( R / X )2 }} / Units ]
R = (X)*(R / X)
DATE 1/10/2005
Knowledge Is Power SM
Tapmin(pu) = [ { VTap min kV / Base kVpri }*{ Base kVsec / Rated kVsec } ]
Tapmax(pu) = [ { VTap max kV / Base kVpri }*{ Base kVsec / Rated kVsec } ]
Tap step(pu) = [ { VTap max kV – VTap min kV } / { NTap max – NTap min } ]
Tap nom = [ { VTap min kV + { ( NTap nom – NTap min )*Tap step kV } } ]*[ Base kV sec / Rated kV sec ]
• Vector Group Dy5 – High voltage in Delta and low voltage in star connection.
• Vector Group Yz11 – High voltage in Star and low voltage in zigzag connection.
The transformer vector group information is required for 3-phase load flow and
unbalanced fault studies. The different vector groups used are;
DATE 1/10/2005
Knowledge Is Power SM
EXAMPLE:
Rated MVA = 315
Primary Voltage = 420 kV
Secondary Voltage = 240 kV
Positive sequence impedance = 0.125PU or 12.5%
Zero sequence impedance = 0.100PU or 10%
TAPmin = 1.0
TAPmax = 17.0
TAPnormal = 12.0
Minimum TAP Voltage = 360 kV
Maximum TAP Voltage = 440 kV
Neutral Rpri = Rsec = 2.0 Ohm.
Connection = YnYn0
The transformer is connected to a bus on HT side with voltage 400 kV and on LT side is
connected to a bus with voltage 220 kV. Hence primary base voltage = 400 kV and the
secondary base voltage is 220 kV.
The common base MVA = 100
DATE 1/10/2005
Knowledge Is Power SM
Tapmin(pu) = [ { VTap min kV / Base kVpri }*{ Base kVsec / Rated kVsec } ]
= [ { 360 / 400 }*{ 220 / 240 } ]
= 0.82500 PU
Tapmax(pu) = [ { VTap max kV / Base kVpri }*{ Base kVsec / Rated kVsec } ]
= [ { 440 / 400 }*{ 220 / 240 } ]
= 1.00833 PU
Tap step(pu) = [ { VTap max kV – VTap min kV } / { NTap max – NTap min } ]
= [ { 440 – 360 } / { (17 – 1)*400 } ]
= 0.0125 PU
Tap nom = [ { VTap min kV + { ( NTap nom – NTap min )*Tap step kV } } ]*[ Base kV sec / Rated kV sec ]
= [ { 360 + { (12 – 1)*5 } } / 400 ]*[ 220 / 240 ]
= 0.95104 PU
The neutral impedance values are computed as;
DATE 1/10/2005
Knowledge Is Power SM
• Impedance measured in primary with secondary short circuited and tertiary open
(Z ps).
• Impedance measured in primary with tertiary short circuited and secondary open
(Z pt).
• Impedance measured in secondary with tertiary short circuited and primary open
(Z st).
If the three impedances measured in Ohms are referred to the voltage of one of
the windings, the impedance of each separate winding referred to that same
winding are related to the measured impedances as;
Z ps = Zp + Zs
Z pt = Zp + Zt
Zst = Zs + Zt
Where Zp, Zs, and Zt are the impedance of primary, secondary and tertiary windings
referred to primary circuit. If Zps, Zpt, Zst are the measured impedances refer to
primary circuit, the real and reactive parts are separated as;
X ps = [ { √Z ps2 } / {( R / X ps )2 + 1} ] / Units
X pt = [ { √Z pt2 } / {( R / X pt )2 + 1} ] / Units
X st = [ { √Z st2 } / {( R / X st )2 + 1} ] / Units
Solving the above impedance simultaneous equations for Rp, Rs, & Rt, Xp, Xs & Xt
yields,
Rp = [ R ps + R pt – R st ] / 2
Rs = [ R ps + R st – R pt ] / 2
Rt = [ R pt + R st – R ps ] / 2
Xp = [ X ps + X pt – X st ] / 2
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 62
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Xs = [ X ps + X st – X pt ] / 2
Xt = [ X pt + X st – X ps ] / 2
The impedance of the three windings are connected in star (Y) to represent the single
phase equivalent circuit of the three winding transformer. Since the ohmic values of the
impedances must be referred to the same voltage, it follows that conversion to PU
requires the same MVA base for all the three circuits and requires voltage bases in three
circuits of the transformer.
The neutral impedances, if present is converted to per unit values on common base as;
EXAMPLE:
Rated Primary MVA = 15
Primary Voltage = 66 kV
Rated Secondary MVA = 10
Secondary Voltage = 13.2 kV
Rated tertiary MVA = 5.0
Tertiary Voltage = 2.3 kV
Zps = 7% on 15 MVA, 66 kV
RX-Ratio-ps = 0.05
Zpt = 9% on 15 MVA, 66 kV
RX-Ratio-pt = 0.05
Zst = 8% on 15 MVA, 66 kV
RX-Ratio-st = 0.05
TAPmin = 1.0
TAPmax = 17.0
TAPnormal = 12.0
Minimum TAP Voltage = 59.4 kV
Maximum TAP Voltage = 72.6 kV
Rpri = Rsec = Rtertiary = 2.0 Ohm.
Connection = YYnYn0
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 63
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Assuming the common base values as 15MVA and 66 kV. First step is to convert
all the impedance to common base on primary side. Zps & Zpt are measured at
primary ratings, need no conversion while the Zst measured at different ratings it
is converted to common base values as;
X ps = [ { √Z ps2 } / {( R / X ps )2 + 1} ] / Units
= [ { √(0.07)2 } / {( 0.05 )2 + 1} ] / Units
= 0.06991 PU
X pt = [ { √Z pt2 } / {( R / X pt )2 + 1} ] / Units
= [ { √(0.09)2 } / {(0.05)2 + 1} ] / Units
= 0.0898877 PU
X st = [ { √Z st2 } / {( R / X st )2 + 1} ] / Units
= [ { √(0.12)2 } / {(0.05)2 + 1} ] / Units
= 0.1198503 PU
Rp = [ R ps + R pt – R st ] / 2
DATE 1/10/2005
Knowledge Is Power SM
Rs = [ R ps + R st – R pt ] / 2
= [ 0.0034955 + 0.0059925 – 0.00449438 ] / 2
= 0.00249685 PU
Rt = [ R pt + R st – R ps ] / 2
= [ 0.00449438 + 0.0059925 – 0.0034955 ] / 2
= 0.00349565 PU
Xp = [ X ps + X pt – X st ] / 2
= [ 0.06991 + 0.0898877 – 0.1198503 ] / 2
= 0.0199737 PU
Xs = [ X ps + X st – X pt ] / 2
= [ 0.06991 + 0.1198503 – 0.0898877 ] / 2
= 0.0499363 PU
Xt = [ X pt + X st – X ps ] / 2
= [ 0.0898877 + 0.1198503 – 0.06991 ] / 2
= 0.069914 PU
Tapmin(pu) = [ { VTap min kV / Base kVpri }*{ Base kVsec / Rated kVsec } ]
= [ { 59.4 / 66 }*{ 13.2 / 13.2 } ]
= 0.9 PU
Tapmax(pu) = [ { VTap max kV / Base kVpri }*{ Base kVsec / Rated kVsec } ]
= [ { 72.6 / 66 }*{ 13.2 / 13.2 } ]
= 1.10 PU
Tap step(pu) = [ { VTap max kV – VTap min kV } / { NTap max – NTap min } ]
= [ { 72.6 – 59.4 } / { (17 – 1)*66 } ]
= 0.0125 PU
Tap nom = [ { VTap min kV + { ( NTap nom – NTap min )*Tap step kV } } ]*[ Base kV sec / Rated kV sec ]
= [ { 59.4 + { (12 – 1)*0.825 } } / 66 ]*[ 13.2 / 13.2 ]
= 1.0375 PU
DATE 1/10/2005
Knowledge Is Power SM
DATE 1/10/2005
Knowledge Is Power SM
EXAMPLE:
Number of Circuits = 1.0
Length of Line = 181km.
Positive sequence R = 0.0288864 Ohm/km.
Zero sequence R = 0.072216 Ohm/km.
Positive sequence X = 0.32704 Ohm/km.
Zero sequence X = 0.8176 Ohm/km.
Positive sequence B = 1.78087E-06 mho/km.
Zero sequence B = 1.52374E-06 mho/km.
Common base MVA = 100 and Base voltage = 400.0 kV.
DATE 1/10/2005
Knowledge Is Power SM
Rmotor = Rold ( Base kV old / Base kV new )2*( MVA new / MVA old )
Xmotor = Xold ( Base kV old / Base kV new )2*(MVA new / MVA old )
Type of motor winding connection is used for zero sequence network calculations
only. The motor neutral impedance, value is converted to common base and 3-
times of it is added to the zero sequence impedance value of the motor to get the
effective zero sequence impedance.
EXAMPLE:
Number of Units = 1.0
Voltage Rating = 2.3 kV
Rating = 1.6785 MW, 0.8 P.F.
Stator resistance = 0.029 Ohm.
Stator reactance = 0.226 Ohm.
Rotor resistance = 0.022 Ohm.
Rotor reactance = 0.226 Ohm.
Magnetizing reactance = 13.04 Ohm.
Winding type = Delta.
Common base = 100 MVA and base volt = 2.3 kV.
Motor Zbase = (Base kV)2 / (Base MVA)
= (2.3)2 / (2.098125)
= 2.5213 Ohm.
DATE 1/10/2005
Knowledge Is Power SM
= 0.5482 PU.
Xstator = Xold ( Base kV old / Base kV new )2*(MVA new / MVA old )
= 4.2722 PU.
Rrotor = Rold ( Base kV old / Base kV new )2*( MVA new / MVA old )
= 0.41588 PU.
Xrotor = Xold ( Base kV old / Base kV new )2*(MVA new / MVA old )
= 4.2722 PU.
Xmagnetizing = Xold ( Base kV old / Base kV new )2*(MVA new / MVA old )
= 246.504 PU.
Rmotorq = Rstator + [ { ( Slip * Rrotor * ( Xmag )2 ) } / { Rrotor2 + ( Slip2 ( Xrotor + Xmag )2 } ]
= 0.5482 + [{ (0.0077*0.41588*(246.504)2 )} / {(0.41588)2 + ( (0.0077)2 ( 4.2722 + 246.504)2 }]
= 50.010 PU.
Xmotorq = Xstator + [ ( Rrotor2*Xmag ) + ( Slip2*Xrotor*Xmag ( Xrotor + Xmag ) ) ] / [ Rrotor2 + ( Slip2 ( Xrotor + Xmag )2 ) ]
= 19.215899 PU.
DATE 1/10/2005
Knowledge Is Power SM
R new = (R old)* (Base kV old / Base kV new)2* (MVA new / MVA old)
X new = (X old)* (Base kV old / Base kV new)2* (MVA new / MVA old)
EXAMPLE:
Rated Voltage = 11 kV.
Rated Current = 262 Amp.
kVar = 256.
Xreactor = (0.514)*(100/5)*(11/11)2
= 1.028 PU
G new = (G old)* (Base kV new / Base kV old)2 * (MVA old / MVA new)
B new = (B old)* (Base kV new / Base kV old)2 * (MVA old / MVA new)
DATE 1/10/2005
Knowledge Is Power SM
G new = (G old)* (Base kV new / Base kV old)2 * (MVA old / MVA new)
All series elements are molded in impedance form, hence the parameters are
converted to impedance form by inverting the admittance.
R new = (R old)* (Base kV old / Base kV new)2* (MVA new / MVA old)
X new = (X old)* (Base kV old / Base kV new)2* (MVA new / MVA old)
All shunt elements are molded in admittance form; its data is converted to
admittance form by using the formula-
R gen = (R old)* (Base kV old / Base kV new)2* (MVA new / MVA old)
X gen = (X old)* (Base kV old / Base kV new)2* (MVA new / MVA old)
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 71
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
X 2(Neg.) = (X d” + X q”) / 2
T q’ = T d’ / 2
By using the above formula, the Sub-transient, Transient, & Steady-state direct
axis reactance, negative sequence reactance and the zero sequence reactance
values are converted to PU on common base.
Tdo’ = No load time constant determines the excitation and de-magnetisation with Open
stator circuit.
Td” = Sub-transient time constant determines the excitation and de-magnetization with
three phase short circuit.
Td’ = Transient time constant determines the excitation and de-magnetization with three
phase short circuit.
EXAMPLE:
Number of units = 1.0
Voltage Rating = 11.0 kV
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 72
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
R gen = (R old)* (Base kV old / Base kV new)2* (MVA new / MVA old)
= (0.00154)*(11 / 11)2* (100 / 260)
= 0.00059 PU.
X gen pos. = (X old)* (Base kV old / Base kV new)2* (MVA new / MVA old)
= (2.22)*(11 / 11)2* (100 / 260)
= 0.8538 PU.
X gen Neg. = (X old)* (Base kV old / Base kV new)2* (MVA new / MVA old)
= (0.225)*(11 / 11)2* (100 / 260)
= 0.08654 PU
Rated MVA = 35
Terminal Voltage = 11.0kV
Frequency = 50Hz
Speed = 3000RPM
Power Factor = 0.85
Applicable national standard = IEC 34-3
Rated Air inlet temperature = 15 deg.
Unsaturated Direct axis Synchronous Reactance (Xd) = 243.9%
Saturated Direct axis Synchronous Reactance (Xd) = 243.9%
Saturated Direct axis Transient Reactance (Xd’) = 25.1%
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 73
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Rated MVA = 60
Terminal Voltage = 11.0kV
Frequency = 50Hz
Speed = 3000RPM
Power Factor = 0.85
Applicable national standard = IEC 34-3
Rated Air inlet temperature = 15 deg.
Unsaturated Direct axis Synchronous Reactance (Xd) = 257%
Saturated Direct axis Transient Reactance (Xd’) = 22.7%
Saturated Direct axis Sub-transient Reactance (Xd”) = 15.9%
Unsaturated Zero Sequence Reactance (X0) = 10.4%
Unsaturated Negative sequence Reactance (X2) = 19.4%
Short Circuit Ratio = 0.41
DATE 1/10/2005
Knowledge Is Power SM
Generator:
• Transient (Xd’) or sub-transient (Xd”) reactance is considered for positive
sequence.
• Negative sequence reactance which is approximately equal to (Xd”).
• Zero sequence reactance, which is comparatively small around 0.1 to 0.7 times
of (Xd”).
• Assume Short Circuit Ratio = 1 / Xd while value of Xd is not given in data-sheet
Transformer:
• Positive sequence, Negative sequence, & Zero sequence impedances are equal.
DATE 1/10/2005
Knowledge Is Power SM
Choosing Base:
DATE 1/10/2005
Knowledge Is Power SM
• In Ohms, on 11 kV side:
Z base = (Base Voltage)2 / Base MVA = (11)2 / 50 = 2.42 Ohms
Z 11 = (Z base * Z pu) = (2.42)* (0.1) = 0.242 Ohms.
On 33 kV side:
• Per Unit Impedance lie within a Narrow Band while Ohmic values can be
widely different.
• Transformer 415 V to 400 kV and 500 kVA to 500 MVA.
Z lies between 5% (0.05PU) to 15% (0.15PU)
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 77
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
The protection for an electrical system should not only be safe under all service
conditions but, to insure continuity of service, it should be selectively coordinated
as well. A coordinated system is one where only the faulted circuit is isolated
without disturbing any other part of the system. Over-current protection devices
should also provide short-circuit as well as overload protection for system
components, such as bus, wire, motor controllers, etc.
To obtain reliable, coordinated operation and assure that system components are
protected from damage, it is necessary to first calculate the available fault current
at various critical points in the electrical system.
Once the short-circuit levels are determined, the engineer can specify proper
interrupting rating requirements, selectively coordinate the system and provide
component protection.
DATE 1/10/2005
Knowledge Is Power SM
Sources of short circuit current that are normally taken under consideration
include:
- Utility Generation
- Local Generation
- Synchronous Motors and
- Induction Motors
Capacitor discharge currents can normally be neglected due to their short time
duration. Certain IEEE (Institute of Electrical and Electronic Engineers)
publications detail how to calculate these currents if they are substantial.
Figure 1.
In Figure 2, note that the total short-circuit current Ia is the summation of two
components - the symmetrical RMS current IS, and the DC component, IDC. The
DC component is a function of the stored energy within the system at the
initiation of the short circuit. It decays to zero after a few cycles due to I2R losses
in the system, at which point the short circuit current is symmetrical about the
zero axis. The RMS value of the symmetrical component may be determined
using Ohm’s Law. To determine the asymmetrical component, it is necessary to
know the X/R ratio of the system. To obtain the X/R ratio, the total resistance and
total reactance of the circuit to the point of fault must be determined. Maximum
thermal and mechanical stress on the equipment occurs during these first few
cycles. It is important to concentrate on what happens during the first half cycle
after the initiation of the fault.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 79
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Figure 2.
Where,
Ia = Asymmetrical RMS Fault Current in kA.
IDC = DC component depend on X/R in kA
Is = Asymmetrical RMS Fault Current in kA.
Ip = Instantaneous Peak Current in kA.
Figure 2 illustrates a worst case waveform that 1 phase of the 3 phase system
will assume during the first few cycles after the fault initiation.
Interrupting Rating:
Equipment intended to break current at fault levels shall have an interrupting
rating sufficient for the system voltage and the current, which is available at the
line terminals of the equipment.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 80
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Low voltage fuses have their interrupting rating expressed in terms of the
symmetrical component of short-circuit current, IS. They are given an RMS
symmetrical interrupting rating at a specific power factor. This means that the
fuse can interrupt any asymmetrical current associated with this rating. Thus only
the symmetrical component of short-circuit current need be considered to
determine the necessary interrupting rating of a low voltage fuse. For U.L. listed
low voltage fuses, interrupting rating equals its interrupting capacity.
Low voltage molded case circuit breakers also have their interrupting rating
expressed in terms of RMS symmetrical amperes at a specific power factor.
However, it is necessary to determine a molded case circuit breaker’s
interrupting capacity in order to safely apply it. The reader is directed to Buss
bulletin PMCB II for an understanding of this concept.
Example: (Z1 + Zf) = 0.2 PU., Base MVA = 15, Rated kV = 11, Base kV = 11.
PU method:
Step:-1
Fault MVA = 15 / 0.2 = 75 MVA
Step:-2
Ia1 = 75 / 1.7325*(11) = 3.93kA.
Ohm method:
Step:-1
Find Base Impedance value in Ohm
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 81
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Step:-2
Find Z value in Ohm
Z in Ohm = (Z base * Z pu) = (8.066)* (0.2) = 1.613 Ohms.
Step:-3
Find Fault current
Ia1 = Rated kV / 1.7325*(Z in Ohm) = 3.93kA.
Example: Z1 = 1.35 PU., Z2 = 1.35 PU, Z0 = 1.0 PU, Base MVA = 100, Rated kV = 6.6,
Base kV = 6.6.
PU method:
Step:-1
(Z1’ + Z2’ + Z0’) = (Z1 + Z2 + Z0) / 3 = (1.35 + 1.35 + 1.0) / 3 = 1.23 PU
Step:-1
Fault MVA = 100 / 1.23 = 81.30 MVA
Step:-2
Ia0 = 81.30 / 1.7325*(6.6) = 7.11kA.
Ohm method:
Step:-1
Find Base Impedance value in Ohm
Z base = (Base Voltage)2 / Base MVA = (6.6)2 / 100 = 0.4356 Ohms
Step:-2
Find Z value in Ohm
Z in Ohm = (Z base * Z pu) = (0.4356)* (1.23) = 0.5357 Ohms.
DATE 1/10/2005
Knowledge Is Power SM
Figure 2.1.1 shows plots that resemble actual short-circuit currents in the three
armature phases. The phase a current is completely offset in the negative
direction, while the b and c phase currents are offset half as much in the positive
direction. The exact offsets will depend on the instant at which the fault occurs
relative to the pre-fault voltage waveform.
DC offsets:
The physical reason for the existence of the DC offsets is that the current and
flux waveforms of an inductive circuit cannot change instantly. Since the pre-fault
current is zero, the DC offset in any given phase must take on a value equal in
magnitude and opposite in sign to the value of the AC waveform just after the
fault. Since the AC currents are shifted by 120o from each other, the DC
components of the three phases will always add to zero.
The maximum DC offset in a phase current is the peak value of the AC initial
component. This occurs in one phase at most, since the three DC offsets must
add to zero as discussed above. That means that the maximum DC offset is
1.414 times the initial RMS AC waveform.
DATE 1/10/2005
Knowledge Is Power SM
DATE 1/10/2005
Knowledge Is Power SM
Figure 2.1.1 Synchronous machine armature short-circuit currents for sudden 3-ph Fault
DATE 1/10/2005
Knowledge Is Power SM
Figure 2.1.2(below) shows the rms ac (or symmetrical) short-circuit current for
the same case that is illustrated in the previous figure.
If the short circuit is left on until the transients die out, the steady-state short-
circuit current may be determined. We subtract the steady-state current from the
ac component, and plot the result on semi-log paper, as shown in Figure 2.1.3
(below), to determine transient and sub-transient time constants and reactances.
DATE 1/10/2005
Knowledge Is Power SM
Figure 2.1.3 The transient time constant Td' is the slope of the line fitted by
ignoring the initial part of this curve. The excess current for the first few cycles
may be plotted on a similar graph to obtain the sub-transient time constant Td".
Calculation:
According to ANSI/IEEE Std. 242-1996, the total AC component of armature
current consists of the steady-state (Id) value and two components that decaying
at a rate according to their respective time constant.
Iac = (Id” – Id’)*(e(2*3.14*f*t)/(Td”) ) + (Id’ – Id)*(e(2*3.14*f*t)/(Td’) ) + Id-----------(1)
Id = (et/Xd)* (If/Ifg)----------------------------------------------------------(3)
(4) The DC component of the armature current is controlled by the sub-transient
reactance and the armature time constant:
DATE 1/10/2005
Knowledge Is Power SM
Short circuit calculations during the design phase require some assumptions and
generalizations, which are validated or corrected when a detailed study is
completed. The detailed study is usually completed prior to the review of
equipment submittals. Underrated equipment identified in the study can be
changed before orders are released or factories prepare the equipment for
shipment.
In the case study mentioned in the introduction, the detailed short circuit study
was not completed until after the equipment had been installed. Since the
engineer had used the positive sequence impedance of the generator for his
calculations (or used generator decrement curve data, which is based on the
positive sequence impedance), some of the equipment was underrated. As will
be discussed below, the lower zero sequence impedance of a generator can
result in line-to-ground fault currents that can be as high as one and a half times
the phase fault currents.
ANALYSIS
To graphically illustrate the variation in magnitude between line-to-ground faults
and phase faults, we will begin by looking at the one-line diagram for a typical
installation. This is shown in Figure below. The service transformers are 2500
kVA and the generators are 1500 kW.
DATE 1/10/2005
Knowledge Is Power SM
Table 1 summarizes the impedance values for the transformers and generators
shown. All values are shown in per unit for each phase. The kVA base is 10,000
and the kV base for the primary is 13.8 and 0.48 for the secondary. Note that the
values for the generator reactance are sub-transient values.
DATE 1/10/2005
Knowledge Is Power SM
Using the impedance values for the conductors shown in Table 2, for a fault at
the ATS, the positive sequence network, with the generator as the source, would
be as shown in Figure. (Since the line-to-ground fault current magnitudes for the
transformer source are the same as the phase fault current magnitudes, we will
confine our analysis to the generator source.)
DATE 1/10/2005
Knowledge Is Power SM
The equivalent impedance of the positive sequence network would then be the
parallel combination of the series combination of generators and their conductors
in series with the conductor to the ATS.
We now turn our attention to the available line-to-ground fault currents. For this
calculation, the pre-fault voltage would be divided by the equivalent zero
sequence impedance of the network, as seen from the faulted bus. Looking at
the impedance seen at the ATS for a line-to-ground fault, the following sequence
network is generated.
DATE 1/10/2005
Knowledge Is Power SM
DATE 1/10/2005
Knowledge Is Power SM
As before, we will neglect the impedance of the conductors and the resistance of
the generators. This would yield the following results:
As can be seen from this calculation, the line-to-ground fault current is almost
125% of the three-phase fault current. If the model were expanded to include five
generators, the three-phase fault current would be approximately 27.75 kA and
the line-to-ground fault current would be 34.5 kA. If the AIC rating of the
equipment to be used were based on the three phase currents, the equipment
would be underrated. Of course, in a case with fewer and/or smaller machines,
the disparity between the phase fault currents and the ground fault currents may
not be a problem, that is, 125% of the phase fault currents may still be well below
the minimum IEC rating of equipment in a given voltage rating. However, it is
always important to check before the equipment is approved for manufacture and
shipment.
CONCLUSIONS
This simple, two machine model demonstrates the higher magnitudes that can be
anticipated for line-to-ground faults when a facility is fed from a generator source.
When specifying the IEC rating of equipment, it is important to consider the
source of the fault and the nature of that source.
Although simple installations with small machines may not be affected, good
design practice would dictate that consideration be given to the calculation of
line-to-ground fault currents. Failure to compare the equipment short circuit
ratings to the calculated line-to-ground fault currents can cause construction
delays and expensive equipment replacement.
DATE 1/10/2005
Knowledge Is Power SM
All machines are represented by their internal impedances. Line capacitances and static
loads are neglected. Transformer taps can be set at either the nominal position or at the
tapped position, and different schemes are available to correct transformer impedance
and system voltages if off-nominal tap setting exists. It is assumed the fault is bolted,
therefore, arc resistances are not considered. System impedances are assumed to be
balanced three-phase, and the method of symmetrical components is used for
unbalanced fault calculations.
ANSI/IEEE standards recommend the use of separate “R” and “X” networks to calculate
X/R values. An X/R ratio is obtained for each individual faulted bus and short-circuit
current. This X/R ratio is then used to determine the multiplying factor to account for the
system DC OFFSET.
½ Cycle Fault:
½ cycle fault is also consider as a sub-transient period fault, primarily because all
rotating machines are represented by their sub-transient reactances, as shown in table:
DATE 1/10/2005
Knowledge Is Power SM
Utility X”
Condenser Xd”
Induction machine >1000hp @ 1800rpm or Xd” = 1/LRC (LRC = Locked rotor current)
less
It is used to calculate the interrupting short-circuit and protective device duties 1.5 – 4.0
Cycle after the fault. The following table shows the type of device and its associated
duties using the 1.5 – 4.0 cycle fault.
Fuse N/A
1.5 – 4.0 cycle fault is also consider as a transient period fault, because all rotating
machines are represented by their transient reactances, as shown in table:
DATE 1/10/2005
Knowledge Is Power SM
Utility X”
Condenser Xd”
30 Cycle Fault:
It is used to calculate the steady state short-circuit current and duties for some of the
protective devices 30 Cycle after the fault. The following table shows the type of device
and its associated duties using the 1.5 – 4.0 cycle fault.
Fuse N/A
The type of rotating machine and its representation in the 30-cycle fault is shown in
following table. Note that induction machines, synchronous motors, and condensers are
not considered in the 30-cycle fault calculation.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 96
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Utility X”
Condenser Infinite
The ANSI (American National Standards & Institute) multiplying factor is determined by
the equivalent system X/R ratio at a particular fault location. The X/R ratio is calculated
by the separate “R” and “X” networks.
The momentary short-circuit current at the ½ cycle represents the highest or maximum
value of the short-circuit current (before its AC & DC components decay toward the
steady state value). Although, in reality, the highest or maximum short-circuit current
actually occurs slightly before the ½ cycle, the ½ cycle network is used for this
calculation.
Step:-1
Calculate the symmetrical rms value of momentary short-circuit current using the
following formula:
DATE 1/10/2005
Knowledge Is Power SM
Where Zeq is the equivalent impedance at the faulted bus from the ½ cycle fault.
Step:-2
Calculate the Asymmetrical rms value of momentary short-circuit current using the
following formula:
Step:-3
Calculate the Peak value of momentary short-circuit current using the following formula:
Step:-5
The interrupting fault currents for high voltage circuit breakers correspond to the 1.5 –
4.0 cycle short-circuit for high voltage circuit breakers:
DATE 1/10/2005
Knowledge Is Power SM
Step:-1
Calculate the symmetrical rms value of the interrupting short-circuit current using the
following formula:
Where Zeq is the equivalent impedance at the faulted bus from the 1.5 – 4.0 cycle fault.
Step:-2
Calculate the short-circuit current contributions to the fault location from the surrounding
buses.
Step:-3
If contribution is from a Remote bus, the symmetrical value is corrected by the factor of
MFr, calculated from
Where t is the circuit breaker contact parting time in cycles, as given in the following
table:
Circuit breaker rating in Cycles Contact Parting time in Cycles
8 4.0
5 3.0
3 2.0
2 1.5
Due to the instantaneous action of low voltage circuit breakers at maximum short-circuit
values, the ½ cycle network is used for calculating the interrupting short-circuit current.
Step:-1
Calculate the symmetrical rms value of the interrupting short-circuit current using the
following formula:
DATE 1/10/2005
Knowledge Is Power SM
Step:-2
Calculate the adjusted asymmetrical rms value of the interrupting short-circuit current
duty using the following formula:
Iint,rms,adj = MF * Iint,rms,symm
Step:-3
(MF) = {1.414*(Under root( 1 + (e)-3.14/(X/R)))} / {1.414*(Under root( 1 + (e)-3.14/(X/R)TEST))} for
unfused power breakers.
Where (X/R)test is calculated based on the test power factor. The manufacturer
maximum testing power factors given in the following table are used as the default
values:
Circuit breaker type Max Design %PF (X/R)test
Power breaker (Unfused) 15 6.59
Power breaker (fused) 20 4.90
Molded case (>20000A) 20 4.90
Molded case (10001-20000A) 30 3.18
Molded case (<10000A) 50 1.73
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 100
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
According to IEC Standard 909, the synchronous motor impedance used in IEC short-
circuit calculations is calculated in the same way as the synchronous generator.
Zk = KG(R+Xd”)
Where kVn and kVr are the nominal voltage of the terminal bus and the motor rated
voltage respectively, Cmax is determine based on machine rated voltage, Xd” is
machine sub-transient reactance (Per unit in motor base), and “pHi” is the machine rated
power factor angle.
Voltage factor C:
This is the factor used to adjust the value of the equivalent voltage source for minimum
and maximum current calculation according to the following table:
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 101
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
3.3.6 The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies:
Introduction:
In some short circuit studies, the X/R ratio is ignored when comparing the short
circuit rating of the equipment to the available fault current at the equipment.
What is not always realized is that when low-voltage gear is tested, it is tested at
a certain X/R ratio. The X/R ratio is important because it determines the peak
asymmetrical fault current. The asymmetrical fault current can be much larger
than the symmetrical fault current. The purpose of this article is to introduce such
terms as the X/R ratio and asymmetrical fault current and to relate the
importance of the X/R ratio to the rating of low-voltage equipment.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 102
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
The resistance and reactance of a circuit establishes a power factor. The power
factor (p.f.) is given by the following equation:
p.f. = cos(tan-1(X/R))
If the power factor is unity (1), then the impedance only has resistance. If the
power factor is zero, then the impedance only has reactance.
The power factor also determines how much the voltage and current waveforms (sine
waves) are out of phase. Remember that both voltage and current are sine waves in
linear AC electrical systems. For purely resistive systems, the voltage and current are in
phase. For purely reactive systems, the voltage and current are 90-degress (one-quarter
of a cycle) out of phase, with the voltage leading the current. Figure 2 below illustrates
this.
The above equation means that the power factor and X/R ratio are related.
Therefore, power factor and X/R ratio are different ways of saying the same
thing. Please note that as power factor decreases, the X/R ratio increases.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 103
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Please note that the decaying exponential added to the sine wave causes the
current to reach a much larger value than that of the sine wave alone. The
waveform that equals the sum of the sine wave and the decaying exponential is
called the asymmetrical current because the waveform does not have symmetry
above and below the time axis. The sine wave alone is called the symmetrical
current because it does have symmetry above and below the time axis.
The actual waveform of the asymmetrical fault current is hard to predict because
it depends on what time in the voltage cycle waveform the fault occurs. However,
the largest asymmetrical fault current occurs when a fault happens at a point
when the voltage is zero. Then, the asymmetrical fault current depends only on
the X/R ratio, or power factor, and the magnitude of the symmetrical fault current.
Figure 4 below shows how the ratio of the peak asymmetrical current to the RMS
symmetrical current varies with the X/R ratio. (RMS symmetrical current equals
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 104
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Low voltage devices have one rating, as opposed to medium-voltage gear, which
have both a momentary and interrupting rating. This rating is reported in terms of
symmetrical current. Therefore, the rating must be compared to the calculated
symmetrical current.
But the story does not end here. All low voltage protective devices are tested at
an X/R ratio. The X/R ratio at which a device is tested depends upon the device
type. Table 1 below summarizes the device types and the X/R ratios at which
they are tested.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 105
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Table 1. X/R ratios at which low voltage protective devices are tested.
Although low voltage devices do not have asymmetrical ratings, if we know the
symmetrical current rating and the test X/R ratio, Figure 4 gives us the maximum
asymmetrical fault current. So, in a way, there is an asymmetrical fault current
rating, but it is not explicit. Therefore, in any short circuit study, both the X/R ratio
and the symmetrical fault current must be taken into account.
Remember that, for a calculated value of RMS symmetrical current, as X/R ratio
increase, the maximum asymmetrical current (peak or RMS) also increases.
If the calculated symmetrical fault current is larger than the device short circuit
rating, the device in underrated, regardless of X/R ratio. However, it is possible
for the device to be underrated even if the short circuit rating exceeds the
calculated symmetrical fault current. How is this possible? We will discuss this
next.
Now consider another possibility. What if the symmetrical fault current is the
same as the equipment’s rated current, but the actual X/R ratio is larger than the
tested X/R ratio? Now, the maximum asymmetrical fault current will be larger
than the maximum asymmetrical current corresponding to the short circuit rating
and the test X/R ratio. Although the available symmetrical fault current is equal to
the rating, the asymmetrical fault current is higher than that when the device was
tested. The device is not rated properly.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 106
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
If the calculated X/R ratio at a device is larger than the test X/R ratio of the
device, then the calculated symmetrical fault current must be multiplied by the
multiplying factor. Or, equivalently, the short circuit rating must be divided by the
multiplying factor. The multiplying factor is equal to the ratio of the calculated
asymmetrical fault current to the asymmetrical fault current at the test X/R ratio
and the rated symmetrical current.
Here is an example of the process. After running a fault analysis, the symmetrical
fault current at some low voltage switchgear is found to be 62kA during the first
half-cycle. The switchgear contains power circuit breakers rated at 65kA. The
asymmetrical peak fault current was found to be 149kA. The X/R ratio was
calculated to be 11.1.
The test X/R ratio of low voltage power circuit breakers is 6.6. Although the
symmetrical fault current is lower than the rating of the circuit breakers, the fact
that the X/R ratio is higher than the test value means that we must use the
multiplying factor.
DATE 1/10/2005
Knowledge Is Power SM
If the calculated X/R ratio is larger than the test X/R ratio, then the equipment
short circuit rating must be de-rated by a multiplying factor. This multiplying factor
equals the ratio of the calculated peak asymmetrical fault current divided by the
peak asymmetrical current corresponding to the rated symmetrical current and
the test X/R ratio.
To determine the fault current at any point in the system, first draw a one-line diagram
showing all of the sources of short-circuit current feeding into the fault, as well as the
impedances of the circuit components.
To begin the study, the system components, including those of the utility system, are
represented as impedances in the diagram.
It must be understood that short circuit calculations are performed without current
limiting devices in the system. Calculations are done as though these devices are
Replaced with copper bars, to determine the maximum “available” short circuit current.
This is necessary to project how the system and the current limiting devices will perform.
Step-1:
Infinite Source (Power Grid) Impedance:
Source Impedance Zs = MVA Base / MVA Fault
Step-2:
Transmission Line Impedance:
Step-3:
Power/Distribution Transformer Impedance:
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 108
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Step-4:
Cable:
Step-5:
Determine the total Single Circuit line Impedance of Power Grid:
Step-6:
Determine the total Short Circuit MVA from Power Grid:
Step-7:
Determine Short Circuit Current Contribution from Power Grid:
Step-8:
Determine the Short Circuit Contribution from Generator:
Step-9:
Determine the total Short Circuit MVA from Generator:
Step-10:
Determine Short Circuit Current Contribution from Generator:
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 109
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Step-11:
Determine the Short Circuit Contribution from Motors or Dynamic loads:
Generally, %Z = 25% consider for LT motors or loads and %Z = 15-20% for HT motors
or loads.
Step-12:
Determine the total Short Circuit MVA from Dynamic loads or Motors:
Step-13:
Determine Short Circuit Current Contribution from Dynamic loads or Motors:
Step-14:
Determine Total Short Circuit Current at Fault:
Step-15:
Determine X/R ratio of the system to the point of fault:
Step-16:
Determine the Asymmetrical RMS short-circuit current to the point of fault:
Step-17:
Determine the Asymmetrical Factor:
Step-16:
Determine the Peak value of short-circuit current to the point of fault:
Step-17:
Determine the Multiplying peak Factor:
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 110
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 111
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
CASE STUDY-1:
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 112
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 113
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 114
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 115
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
GR1-
TR1
F1
2MVA-TR
4X350KW 4X250KW
DY. LOAD
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 116
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
The calculation of fault level / short circuit current can be calculated using PU values
of impedances / reactances of different components of the system. For calculation of
PU values, let us select the base MVA = 15 MVA
¾ INFINITE SOURCE:
Fault level at infinite bus as given by GEB is 5481 MVA at Jambua Load Dispatch
Center, at 132 KV voltage level & 15.5 KM far from the plant site. Based on this,
source impedance can be found out as given below:
¾ TRANSMISSION LINE:
According to data available from GEB, the two 132 KV transmission lines, having
Panther 0.2 conductor & 15.5 KM length have following parameters
Zt = Under root of ( R2 + X2 )
= Under root of ( (0.000931)2 + (0.002216)2 )
Zt = 0.0024036258 PU / KM / circuit
¾ POWER TRANSFORMER:
The rating of power transformer is 15 MVA / 20 MVA.
For calculation of transformer impedance, normal operating conditions are to be
considered. So the rating of the transformer = 15 MVA has to be considered.
Power transformer PU impedance can be calculated as follows.
9.2 X 15
Ztr = -----------------
100 X 15
Ztr = 0.092 PU
¾ CABLE:
The cable between power transformer & 6.6 KV HT panel is 8 X 3C X 300 sq.mm. &
the length of the cable = 100 mtrs
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 117
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
The PU value of Generator impedance on 15 MVA base can be found out through
following formula:
16.3 X 15
PU impedance of Generator Zg = ---------------------
100 X 2.270
= 1.0770925 PU
As the actual motor transient reactance is not available, the motor transient
reactance is selected as 17 % for all HT motor, according to statistical analysis.
The PU value of 350 KW, 6.6 KV motor impedance on 15 MVA base can be found
out through following formula:
17 X 15
Motor impedance Zm = -------------------
100 X 0.4375
= 5.82857 PU
The cable connecting 6.6 KV panel & 350 KW motor is 1 X 3C X 185 sq.mm. with
550 mtrs length.
The PU value of the cable connecting 350 KW motor & 6.6 KV panel Zcm
Zcm = 0.0436294 PU
As the actual motor transient reactance is not available, the motor transient
reactance is selected as 17 % for all HT motor, according to statistical analysis.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 118
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
he PU value of 250 KW, 6.6 KV motor impedance on 15 MVA base can be found out
through following formula:
17 X 15
Motor impedance Zm = -------------------
100 X 0.3125
= 8.16 PU
6.43 X 15
Ztr = -----------------
100 X 2
Ztr = 0.48225 PU
¾ CABLE:
The cable between distribution transformer & 6.6 KV HT panel is 8 X 3C X 300
sq.mm. & the length of the cable = 525 mtrs
¾ LT DYNAMIC LOAD:
The LT motors are not considered individually but are considered as a lumped load
on each LT transformer
25 X 15
The PU impedance of the LT dynamic load Zm = ----------------
100 X 1.2
= 3.125 PU
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 119
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
0.00558837
= 0.002736729 + -----------------
2
= 0.00553085 PU / circuit
CONDITION - A:
WHEN ALL 4 DG SETS ARE RUNNING IN PARALLEL WITH TWO GRID SUPPLY
Total impedance of two grid lines from infinite source to 6.6 KV panel:
¾ Fault contribution of all the four DG SETS for a fault on 6.6 KV bus
Considering normal working condition of the plant, total 4 no of 350 KW & 4 no of 250
KW motor are taken in to consideration for Fault contribution
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 120
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Total fault level on 6.6 kv bus for 2 Grid & 4 DG-SET running in parallel = 363
MVA & This value exceeds the bus bar short circuit rating of 350 MVA.
CONDITION B:
This condition considers both the infinite sources & both the transmission lines
but only a single power transformer & a single 6.6 KV incoming grid, keeping 132
KV bus coupler closed.
DATE 1/10/2005
Knowledge Is Power SM
Considering normal working condition of the plant, total 4 no of 350 KW & 4 no of 250
KW motor are taken in to consideration for Fault contribution
= 17.53 MVA
= 18 MVA (say)
Total fault level on 6.6 kv bus for 2 GRID & 4 DG running in parallel = 227 MVA
This value is well within the bus bar short circuit rating of 350 MVA.
CONDITION C:
This condition considers both the infinite sources & both the transmission lines but only a
single power transformer & a single 6.6 KV incoming grid, keeping 132 KV bus coupler
closed.
Total impedance of a single grid from infinite source to 6.6 KV panel:
0.00558837
= 0.002736729 + ------------------+ 0.092 + 0.0006780303
2
= 0.0982088 PU
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 122
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Considering normal working condition of the plant, total 4 no of 350 KW & 4 no of 250
KW motor are taken in to consideration for Fault contribution
Total fault level on 6.6 kv bus for 2 GRID & 4 DG running in parallel = 241 MVA
This value is well within the bus bar short circuit rating of 350 MVA.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 123
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
WHERE,
G = GRID OR GUJARAT ELECTRICITY BOARD SUPPLY.
D = DIESEL GENERATOR SETS.
M = MOTOR.
From above results, we can conclude that, running two grid in parallel with four DG
SETS will create a fault level greater than rated 350 MVA fault level. Hence, it is
recommended to run a single grid in parallel with four DG SETS considering future
scope of one more DG.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 124
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Step-1:
Most circuit component impedances are given in ohms except utility and transformer
impedances, which are found by the following formulae, (Note that the transformer and
utility ohms are referred to the secondary KV by squaring the secondary voltage.)
Step-2:
Xtransformer in Ohms = (10)*(%X)*(kVsecondary)2 / kVAtransformer.
Step-3:
The impedance (in Ohms) given for current transformer, large switches and large C.B. is
essentially all X.
Step-4:
Xcable and bus in Ohms.
Rcable and bus in Ohms.
Step-5:
Total all X and R in system to point of fault.
Step-6:
Determine impedance (in Ohms) of the system by:
Step-7:
Calculate short-circuit symmetrical RMS amperes at point of fault.
Step-8:
Determine the motor load. Add up the full load motor currents. The full load motor
current in the system is generally a percentage of the transformer full load current,
depending upon the types of loads. The generally accepted procedure assumes 50%
motor load when both motor and lighting loads are considered.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 125
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Step-10:
The total symmetrical short-circuit RMS current is calculated as:
Step-11:
Determine X/R ratio of the system to the point of fault.
Step-12:
Calculate the asymmetrical RMS short-circuit current.
Step-13:
The short-circuit current that the motor load can contribute is an asymmetrical current
usually approximated as being equal to the locked rotor current of the motor. As a close
approximation with a margin of safety use:
Step-14:
The total asymmetrical short-circuit RMS current is calculated as:
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 126
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 127
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 128
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 129
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 130
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Case Study-2:
Sc=175 MVA (min fault MVA )
Sc=220 MVA (max fault MVA )
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 131
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Determinate the equivalent impedance network related to the 22 kV level (figure 12) and
calculate the fault currents, on the 22 kV voltage level. In the example all impedances
are considered to be pure reactances.
The short-circuit currents are calculated for different fault points in the system. This is
done for both maximum and minimum short-circuit capacity.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 132
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
The phase to phase short-circuit current can be found by multiplying the three
phase short-circuit current by a factor:
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 133
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
The application of the point-to-point method permits the determination of available short-
circuit currents with a reasonable degree of accuracy at various points for either 3ø or 1ø
electrical distribution systems. This method can assume unlimited primary short-circuit
current (infinite bus).
Step-2:
Find the transformer multiplier.
Note:
Transformer impedance (Z) helps to determine what the short circuit current will be at
the transformer secondary. Transformer impedance is determined as follows:
Example: For a 440 volt rated primary, if 18.0 volts causes secondary full load current to
flow through the shorted secondary, the transformer impedance is 18/440 = 0.0409 =
4.09%Z.
In addition, UL listed transformer 25KVA and larger have a ± 10% impedance tolerance.
Short circuit amperes can be affected by this tolerance.
Step-3:
Determine the transformer short-circuit current;
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 134
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Note:
Motor short-circuit contribution, if significant, may be added to the transformer secondary
short-circuit current value as determined in Step 3. Proceed with this adjusted figure
through Steps 4, 5 and 6. A practical estimate of motor short-circuit contribution is to
multiply the total motor current in amperes by 4.
Step-4:
Calculate the "f" factor.
Where:
L = length (feet) of circuit to the fault.
C = constant from Table 6, page 27. For parallel runs, multiply C values by the number
of conductors per phase.
I = available short-circuit current in amperes at beginning of circuit.
Note:
The L-N fault current is higher than the L-L fault current at the secondary terminals of a
single-phase center-tapped transformer. The short-circuit current available (I) for this
case in Step 4 should be adjusted at the transformer terminals as follows:
At some distance from the terminals, depending upon wire size, the L-N fault current is
lower than the L-L fault current. The 1.5 multiplier is an approximation and will
theoretically vary from 1.33 to 1.67. These figures are based on change in turns ratio
between primary and secondary, infinite source available, zero feet from terminals of
transformer, and 1.2 x %X and 1.5 x %R for L-N vs. L-L resistance and reactance
values. Begin L-N calculations at transformer secondary terminals then proceed point-to-
point.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 135
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Step-5:
Calculate "M" (multiplier).
Step-6:
Calculate the available short-circuit symmetrical RMS current at the point of fault.
Use the following procedure to calculate the level of fault current at the secondary of a
second, downstream transformer in a system when the level of fault current at the
transformer primary is known.
Step-1:
Calculate the "f" factor (IS.C. primary known)
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 136
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Step-3:
Calculate the short-circuit current at the secondary of the transformer. (See Note under
Step 3 of "Basic Point-to- Point Calculation Procedure".)
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 137
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 138
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
3.3.7.4
1ø Short-Circuit Current Calculations – 1ø Transformer System:
1.
It is necessary that the proper impedance be used to represent the primary system. For
3Ø fault calculations, single primary conductor impedance is only considered from the
source to the transformer connection. This is compensated for in the 3Ø short-circuit
formula by multiplying the single conductor or single-phase impedance by 1.73.
However, for single-phase faults, primary conductor impedance is considered from the
source to the transformer and back to the source. This is compensated in the
calculations by multiplying the 3Ø primary source impedance by two.
2.
The impedance of the center-tapped transformer must be adjusted for the half-winding
(generally line-to-neutral) fault condition.
The diagram at the right illustrates that during line-to-neutral faults, the full primary
winding is involved but, only the half-winding on the secondary is involved. Therefore,
the actual transformer reactance and resistance of the half winding condition is different
than the actual transformer reactance and resistance of the full winding condition.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 139
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
3.
The impedance of the cable and two-pole switches on the system must be considered
"both-ways" since the current flows to the fault and then returns to the source. For
instance, if a line-to-line fault occurs 50 feet from a transformer, then 100 feet of cable
impedance must be included in the calculation.
b).
The half-winding transformer %X and %R multipliers for the line-to-neutral fault situation.
c).
The KVA and voltage bases used in the per-unit calculations.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 140
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 141
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 142
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 143
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 144
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Comparison of Results:
Per-Unit Method vs. Point-to-Point Method
Per-Unit PTP
Method Method
X1
Line-Line 16,984A 18,453A
Line-Neutral 20,041A 20,555A
This table has been reprinted from IEEE Std 141-1986, IEEE Recommended Practice
for Electric Power Distribution for Industrial Plants, Copyright© 1986 by the Institute of
Electrical and Electronics Engineers, Inc with the permission of the IEEE Standards
Department.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 145
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Based on rated current of the winding (one–half nameplate kVA divided by secondary
line-to-neutral voltage).
Note:
UL Listed transformers 25 KVA and greater have a ± 10% tolerance on their impedance
nameplate.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 146
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
These represent actual transformer nameplate ratings taken from field installations.
Note:
UL Listed transformers 25KVA and greater have a ±10% tolerance on their impedance
nameplate.
Note:
Values given are in ohms per phase. For actual values, refer to manufacturers' data.
This table has been reprinted from IEEE Std 241-1990, IEEE Recommended Practice
for Commercial Building Power Systems, Copyright© 1990 by the Institute of Electrical
and Electronics Engineers, Inc. with the permission of the IEEE Standards Department.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 147
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Note:
The reactance of disconnecting switches for low-voltage circuits (600V and below) is in
the order of magnitude of 0.00008 - 0.00005 ohm/pole at 60 Hz for switches rated 400 -
4000 A, respectively.
This table has been reprinted from IEEE Std 241-1990, IEEE Recommended Practice
for Commercial Building Power Systems, Copyright© 1990 by the Institute of Electrical
and Electronics Engineers, Inc. with the permission of the IEEE Standards Department.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 148
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Relay co-ordination procedure is used for power system protection. Power system
protection engineering deals with precautionary measures to be taken to safeguard the
power system during abnormal operating conditions.
The practice of protection engineering involves periodic fault studies followed by relay
setting, checking and co-ordination studies.
The Protection philosophy is to adopt a mainly Primary Protection & Backup Protection.
Ideal backup protection would be completely independent of the main protection. Current
transformers, Voltage transformers, auxiliary tripping relays, trip coils and dc supplies
would be duplicated.
It is evident that in spite of all precautions taken in the design & installation of electrical
power / distribution systems, there are bound to arise abnormal conditions or faults
some of which like short circuits may prove extremely damaging to not only the faulty
component but to the neighboring components & to the power system as a whole. It is of
vital importance to limit the damage to a minimum by speedy isolation of the faulty
section, without disturbing the working of the rest of the system.
It is obvious that faster the speed of operation of elements of protective system (relay &
breaker), less is the damage to the equipment. The time setting of the relays has to be
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 149
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Protective system should be able to discriminate between fault & load condition even
when the minimum fault current is less than the maximum load current. The relay should
be able to distinguish between over load & over current.
Only faulty element of the system should be isolated & healthy section should be left
intact. This selectivity can be obtained by grading of protections of several zones.
The following points may be considered while co-coordinating the operation of different
releases / relays in a radial system.
The discrimination time between two electro-mechanical relays are as shown below;
T = ( 0.25t + 0.2 ) in second
The discrimination time between two numerical relays are as shown below;
T = ( 0.25t + 0.15 ) in second
Where “t” is the operating time of fuse and 0.25*t is the discrimination time between
breaker & breaker.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 150
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
An over current Protections are used for the feeder protections because of economical
cost and more simplicity. An over current relay operates when the magnitude of the
current exceeds it’s preset value. Normally, various types over current protection with
various characteristics are used for feeder protection as mention below;
Earlier in electro-mechanical protection, one relay is used with only one characteristic
like CDG-11 has Normal inverse characteristic, CDG-12 has long inverse characteristic,
CDG-13 has Very inverse characteristic, CDG-14 has Extremely inverse characteristic.
But, now today modern numerical protection (like SPAJ-140C, 7SJ600, 7SJ61, IM30-AP,
P123, SEL-501 etc.) have more than one characteristics so, now, today we have better
selectivity and ranges which is given a better relay co-ordination.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 151
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 152
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 153
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
3.3.7.6
Functional Characteristics:
1) Sensitivity:
Example:
----Æ Fault current magnitude = 35kA
----Æ CTR = 3000/1
----Æ Relay Pickup, set at 75%
Relay Operating current on Primary side = (75/100)*(3000) = 2250 Amp
Relay Operating current on Secondary side = (75/100)*(1) = 0.75 Amp
Sensitivity of relay during a fault = (2250/35000)*100 = 6.42%
Thus, lower the setting, higher will be the sensitivity for fault detection.
2) Selectivity:
5) Discrimination by Time:
• Basically used with definite time relays
• Time of operation is independent of current magnitude
• Discrimination time between successive relays say 0.3 sec
EXAMPLE:
• For fault on one outgoing feeder3
• Fuse Operates in 0.01s
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 154
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
DISADVANTAGE:
• Operating time of the upstream relays will be very high
• The fault closest to the source takes longest time to clear
ADVANTAGE:
• Defined operating time for variable source operating condition.
6) Discrimination by Current:
• Applicable only when substantial difference between the fault current
magnitudes exist for the faults on the two ends of the equipment.
• The impedance of the equipment shall be substantial that will create the
above difference.
EXAMPLE:
• For the fault on the L.T. side of transformer TR
• Fault current = 40,000 A @ 415V
= 1509.09 A @ 11kV (Reflected fault on 11kV side)
• For the fault on the H.T. side of Transformer TR
• Fault current = 13.5 kA @ 11kV
• IDMTL unit of Transformer Primary side (11kV) relay should be operate
as a backup protection on L.T. fault
• HIGHSET unit of Transformer Primary side (11kV) relay should be
operate on H.T. fault
DISADVANTAGE:
• The discrimination is obtained but no backup ensured
EXAMPLE:
• For a given fault current magnitude, discrimination time is 0.3s for all the
successive relays
• Pickup value for all the relays set below the fault current level
• For the fault on the outgoing feeder-1
• Fault current = 40,000 A @ 415V
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 155
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
ADVANTAGE:
• With the same Pickup & Time dial settings, lower Tome of operating for
near end faults and higher operating times for near end faults inherently
achieved.
• In case of the difference in the fault current magnitude along system,
IDMTLL relays are superior to the DMT relays
• In case of same fault current magnitude along system, desired operating
time can be achieved by adjusting pickup & time dial
8) SPEED:
• Speed: the clearance time of the fault
• Fault clearing time < 100ms, high speed tripping
• Necessity of high speed tripping:
• Minimizing the damage of the equipment
• Increasing stability margin for synchronous machines
• Avoiding unwanted tripping of voltage sensitive loads
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 156
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
3.3.7.7
CRITERIAS FOR PICKUP SETTING & TIME DIAL:
DMT RELAYS:
• Primary Operating Current:
• Setting must be above maximum running load current and largest drive
starting current by safety margin.
• Setting must be below the lowest through fault current.
• Maximum load current includes motor full load current. Hence, it is
subtracted.
• Relevant for generally used DOL Starting.
• Formula;
o If > P.O.C > (IRL + ISTM – IFLM)
Where,
P.O.C. = Desired Primary Operating Current of relay
IRL = Maximum running load current
ISTM = Highest rating drive starting current
IFLM = Highest rating drive full load current
IF = Minimum fault current relay to sense
IDMTL RELAYS:
• Generally the pickup setting is available in steps (not continuously) in
electromechanical relays & variable in numerical relays.
• Not possible to get the exact set point value.
• Select the next higher available step.
• PSM > 2 for IDMT Relays
• DMT Relays: Independent of fault current.
Step:-1
• Primary operating current:
o P.O.C. = (IRL + ISTM – IFLM)
Where,
P.O.C. = Desired primary operating current
IRL = Maximum running load current
ISTM = Highest drive starting current
IFLM = Highest drive full load current
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 157
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Step:-2
Plug setting (PS) = (P.O.C.) / (C.T.R) = [ (IRL + ISTM – IFLM) / C.T.R. ]
Step:-3
Actual Primary Operating current (P.O.C.) = Selected Pickup setting * C.T.R.
Step:-4
Plug setting Multiplier (PSM) = Fault current / Actual P.O.C.
Step:-5
Desired relay Operating time (t) = td + T
Step:-6
Based on formula or curves, Calculate the relay operating time at TMS1.0 on PSM
Step:-7
Desired Time Dial Set point (TMS) = { (Desired relay Operating time) / (Relay operating
time at TMS1.0) }
Select time dial setting: Nearest higher time dial setting selected
Example:
Relay type: CDG31 (3.0s at 10times) & CDG31 (1.3s at 10 times)
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 158
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
3.3.7.8
DATA REQUIRED TO PERFORM O/C & E/F RELAY CO-ORDINATION STUDY:
3. Nameplate data from all protective devices included in study; i.e., manufacturer’s
Catalog number, voltage/current, and IEC ratings.
¾ MVA rating
¾ Primary and secondary voltage rating
¾ Percentage impedance [%Z] on the given MVA rating for
positive and zero sequence [%Z1 and %Z0]
¾ X/R Ratio for positive and zero sequence
¾ Winging connection and Neutral Grounding Reactance /
Resistance if any
¾ Tap data for both fixed taps and LTC taps, minimum and
maximum %tap position and steps size for LTC
¾ Cable/Conductor type
¾ Cable length [ more than 100 Mt ] and cable size
¾ Resistance [ohm], Reactance [ohm] and Susceptance [mho]
per Km for both positive and zero sequence values.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 159
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
¾ KW rating
¾ MVA rating
¾ Rated RPM
¾ Rated current [ I ]
¾ Rated kV
¾ Starting current [ Ist ]
¾ No load current [ I0 ]
¾ Rotor resistance and reactance in ohm [ R2 & X2 ]
¾ Stator resistance and reactance in ohm [ R1 & X1 ]
¾ Magnetizing reactance in ohm
¾ Type of starting
¾ Motor performance characteristics
¾ MW rating
¾ Voltage rating
¾ Direct axis reactance [ Xd ] in % or p.u.
¾ Quadrature axis reactance [ Xq ] in % or p.u.
¾ Direct axis transient reactance [ Xd’ ] in % or p.u.
¾ Quadrature axis transient reactance [ Xq’ ] in % or p.u.
¾ Direct axis sub-transient reactance [ Xd” ] in % or p.u.
¾ Quadrature axis sub-transient reactance [ Xq” ] in % or p.u.
¾ Synchronous reactance [ Xs ] in % or p.u.
¾ Negative phase sequence reactance [ X2 ] in % or p.u.
¾ Zero phase sequence reactance [ X0 ] in % or p.u.
¾ Transient time constant ( short circuit ) [ Td’ ] in seconds
¾ Sub-transient time constant ( short circuit ) [ Td” ] in
seconds
¾ Generator Reactive capacity curve, if available
¾ Generator negative phase sequence withstand capacity
curve
¾ Over-voltage and under-voltage withstand capacity
¾ Over-frequency and under-frequency withstand capacity
DATE 1/10/2005
Knowledge Is Power SM
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 161
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
3.3.7.9
EXAMPLE FOR PHASE FAULT RELAY SETTING:-
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 162
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
IMPEDANCE CALCULATION:
Base MVA = 500
Base kV = 11
Step:-1
Source Impedance (Zs) = (500 / 500)*100 = 100%
Step:-2
Impedance of Cable (Z’c1 in Ohms) = ( (0.042)2 + (0.086)2 )0.5 = 0.096 Ohms
Step:-3
Impedance of reactor (Zr1 in PU) = (4 * 500) / (20) = 100%
Step:-4
Impedance of Cable (Z’c2 in Ohms) = ( (0.128)2 + (0.093)2 )0.5 = 0.1582 Ohms
Step:-5
Impedance of Cable (Z’c3 in Ohms) = ( (0.128)2 + (0.093)2 )0.5 = 0.1582 Ohms
Step:-6
Zc2 II Zc3, so total
(Zc4 in PU) = [ (0.1582 * 500) / (11)2 ]* 100 = 65.37/2 = 32.68%
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 163
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Fault Calculation:
1) Fault at Bus C:
CONDITION:-A
Both “C2” & “C3” cables are running in parallel
CONDITION:-A
Only “C2” cables are running
2) Fault at Bus B:
3) Fault at Bus A:
These relays perform overcurrent protection of the cable feeders, Busbar C and backup-
protection to relays F1, F2 and their associated fuses FS1 and FS2. The settings for
Relays 1 and 2 will be identical, so calculations will only be performed for Relay 1.
Consider first the current setting of the relay.
Relay 1 must be able to reset at a current of 400A – the rating of the feeder. The relay
has a drop-off/pick-up ratio of 0.95, so the relay current setting must not be less than
400/0.95, or 421A. A suitable setting that is greater than this value is 450A. The current
setting should be three times the largest fuse rating (i.e. 3 x 160A, the rating of the
largest fuse on the outgoing circuits from Bus bar C), leading to a current setting of 480A,
or 96% of relay rated primary current. Note that in this application of relays to a
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 164
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
The grading margin now has to be considered. For simplicity, a fixed grading margin of
0.3s between relays is used in the calculations. Between fuse and relay, Equation (0.4t +
0.15), and with fuse FS2 pre-arcing time of 0.01s (from Figure 1(C) & 1(D)), the grading
margin is 0.154s.
Consider first the IDMT overcurrent protection. Select the EI characteristic, as fuses
exist downstream, to ensure grading. The relay must discriminate with the longest
operating time between relays F1, F2 and fuse FS2 (being the largest fuse) at the
maximum fault level seen by relays 1 and 2. The maximum fault current seen by relay 1
for a fault at Busbar C occurs when only one of cables C2, C3 is in service. This is
because the whole of the fault current then flows through the feeder that is in service.
With two feeders in service, although the fault level at Busbar C is higher, each relay
only sees half of the total fault current, which is less than the fault current with a single
feeder in service. With EI characteristics used for relays F1 and F2, the operating time
for relay F1 is 0.02s at TMS=0.1 because the fault current is greater than 20 times relay
setting, at which point the EI characteristic becomes definite time and 0.05s for relay F2
(TMS=0.25).
Plug settings
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 165
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Condition:-1
The required time of operation of relay = 0.3 + 0.05 = 0.350 Seconds.
The 3- phase fault current at 11 V bus C is 9.33 kAmp.
Plug Setting Multiplier (PSM) = 9.33 *103 / 480 = 19.43
Time of operation at TMS1.0 = (80*1.0) / ((19.43)2 – 1)) = 0.212 Seconds
Condition:-2
Fault current = 5.3 kA while two feeders (c2 & c3) are running in parallel
PSM at Fault current = 5.3*1000 / 625 = 8.48
Time of Operation at TMS1.0 = 1.12s
Actual Operating time at selected TMS = 1.12*0.98 = 1.09s
Plug settings
Current Setting:
Full load current (Ifl) of feeder is = 1000A
CTR = 1000/5A
Plug setting Amp. Of Relay = (Ifl) / (CT primary *0.95) = 1052.0 Amp
Plug setting of Relay = 106% = 1000 * 1.06 = 1060 Amp
So the selected setting on CT secondary side = 1.06*5 = 5.3 Amp.
Condition:-1
Set value = 1060 A
Fault Current = 12.2 kA
PSM = 12200 / 1060 = 11.50
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 166
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Condition:-2
Set value = 1060 A
Fault Current = 10.56 kA
PSM = 10560 / 1060 = 9.96
Time of Operation at TMS1.0 = (80*1.0) / ((9.96)2 – 1)) = 0.8146s
Time of operation at TMS = 0.8146*0.84 = 0.6842s which is less than (R1 & R2 time)
Highset setting: 1.3*12.2 = 15.86 kA which is greater than L.T. fault current so, it
is not operate in through fault condition.
Thus, relay 4 required operating time is 0.305 + 0.3 = 0.605s at a fault level of 15.86kA.
Relay 4 current setting must be at least (2800) / (3000 * 0.95) = 98%
For convenience, use a value of 100% (=3000A). Thus relay 4 must operate in 0.605s at
15860/3000 = 5.29 times setting. Thus select a time multiplier setting of 0.15, giving a
relay operating time of 0.62s for a normal inverse type characteristic.
At this stage, it is instructive to review the grading curves, which are shown in Figure
1(C). While it can be seen that there are no grading problems between the fuses and
relays 1/2, and between relays F1/2 and relays 1/2, it is clear that relay 3 and relay 4 do
not grade over the whole range of fault current. This is a consequence of the change
in characteristic for relay 4 to SI from the EI characteristic of relay 3 to ensure grading of
relay 4 with relay 5. The solution is to increase the TMS setting of relay 4 until correct
grading is achieved. The alternative is to increase the current setting, but this is
undesirable unless the limit of the TMS setting is reached, because the current setting
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 167
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 168
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 169
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
3.3.7.10
EXAMPLE CALCULATION FOR DMT (Definite Minimum time) RELAYS:
CTR = 1600 / 1A
SPAJ140C relay having both characteristics DMT & IDMT, but here only DMT is used
Allow 30% margin for minimum desired pickup setting because, 10% for safety & 20%
for impedance & voltage variation etc.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 170
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
3.3.8
Application:
Dynamic Testing of Relay by using DOBLE power system model & F6150 Power
system simulator:
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 171
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
3.3.8.1
CASE:-1
MVA = 35
kV = 11
---->RESULT TAB:
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 172
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
CASE:-2
NEAR END
MAG. PH.
VA 3.77 273.4
VB 3.77 153.4
VC 3.77 33.4
I1 3.773 273.4
I2 3.773 153.4
I3 3.773 33.4
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 173
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
(1)
BASE IMPEDANCE = (BASE KV)^2 / BASE MVA = (11)^2 / 35 = 3.4571 Ohms
(2)
Z in PU on new base = 0.243PU
(3)
Short Circuit or Fault MVA = Base MVA / Z in PU
= 35 / 0.243
= 144.03 MVA
(4)
Short Circuit Current in kA = ( (Fault MVA) / (1.7325 * Rated kV) )
= (144.03) / (1.7325* 11)
= 7.55kA on Primary side of CT.
(5)
Fault Current Flows in CT secondary is = ( Fault Current on Primary side / CT Ratio )
= (7.55 * 1000) / (2000)
= 3.77 Amp on Secondary side of CT during 3-ph fault
condition.
Above theoretical value of fault current is match with Power System Model software value.
This value you have to put in "State Simulation" for differential Protection testing.
NOTE:
L/R values are depends on system Impedance (R + jX). So, it may be change to test for
generator, Line, Feeder (OC) protections. But, worst condition you will have to take like L/R =
300ms
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 174
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
SELECT METHOD
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 175
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
---->RESULT TAB:
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 176
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 177
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
(1)
BASE IMPEDANCE = (BASE KV)^2 / BASE MVA = (11)^2 / 35 = 3.4571 Ohms
(2)
Zpositive seq. in PU on new base = 0.243PU
Znegative seq. in PU on new base = 0.211PU
Zzero seq. in PU on new base = 0.065PU
(3)
Short Circuit or Fault MVA = Base MVA / Z in PU
= 35 / [(0.243 + 0.211 + 0.065) / 3]
= 202.31 MVA
(4)
Short Circuit Current in kA = ( (Fault MVA) / (1.7325 * Rated kV) )
= (202.31) / (1.7325* 11)
= 10.61kA on Primary side of CT.
(5)
Fault Current Flows in CT secondary is = ( Fault Current on Primary side / CT Ratio )
= (10.61 * 1000) / (2000)
= 5.305 Amp on Secondary side of CT during ph-g fault
condition.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 178
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
---->RESULT TAB:
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 179
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 180
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
(1)
BASE IMPEDANCE = (BASE KV)^2 / BASE MVA = (11)^2 / 35 = 3.4571 Ohms
(2)
Zpositive seq. in PU on new base = 0.243PU
Znegative seq. in PU on new base = 0.211PU
Zzero seq. in PU on new base = 0.065PU
(3)
Short Circuit or Fault MVA = Base MVA / Z in PU
= 35 / [(0.243 + 0.211) / 1.73]
= 134.11 MVA
(4)
Short Circuit Current in kA = ( (Fault MVA) / (1.7325 * Rated kV) )
= (134.11) / (1.7325* 11)
= 7.039kA on Primary side of CT.
(5)
Fault Current Flows in CT secondary is = ( Fault Current on Primary side / CT Ratio )
= (7.039 * 1000) / (2000)
= 3.51 Amp on Secondary side of CT during ph-ph fault
condition.
Conclusion: Above all cases, theoretical values are similar to software simulated
values. same fault current apply to phase & earth fault over current relay to check for
relay co-ordination.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 181
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 182
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
TEABLE OF CONTENTS:
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 183
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
1.0 INTRODUCTION:
These are short circuits of earth faults on the supply net work outside the
transformer. The infeeds through the transformer may be high, if the faults are
electrically close and the leakage reactance of the transformer is low. The
excessive faults current may cause enormous Electromechanical forces causing
displacement / hot spot generation inside the transformer.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 184
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
These faults are of serious nature causing immediate damage, but are generally
detectable due to unbalance / over shooting of current at the transformer
Terminals.
Faults are;
(ii) Phase-to-earth fault, or Phase-to-Phase fault on the H.V. & L.V.
bushing terminals.
(iii) Phase-to-earth fault, or Phase-to-Phase fault on H.V. & L.V.
windings.
(iv) Short circuit between turns of the H.V. & L.V. windings.
(v) Earth faults on a tertiary winding, or short-circuit between turns
of a tertiary winding.
b. Incipient Faults :
These are initially minor faults causing slowly developing damage. These are
not detectable at winding terminals in the absence of any unbalance in current or
voltage, incipient faults include :-
c. Regulator Faults :
These include faults associated with the tap changer / tap change controls.
Operation on unequal taps parallel transformers may cause overheating due to
circulating currents.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 185
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
While a fuse can provide adequate protection against short circuits, it cannot
provide effective protection against earth faults, in view of possible low infeeds.
For larger transformers , controlled by circuit breakers, IDMT over current relays
are more commonly used as phase and earth fault backups. The over-current
relay provides a two fold advantage.
The choice of over current / earth fault backup greatly influenced by the vector
configuration, type of earthing and infeed conditions. Some of the typical
applications are discussed below.
3.1
Delta/ Star Transformers (Delta winding connected to Grounded Source):
The delta winding provides zero sequence isolation between the star winding and
the source, a residually connected earth-fault relay on the delta side will not
respond to earth-faults on the star side and hence its operation remains
restricted to earth faults in the delta windings. A sensitive instantaneous earth
fault relay(in high impedance mode ) can therefore, be provided on the delta-side
without requiring any time co-ordination with the star side backup protection .
This will be evident from the current distribution shown in below fig. 3.1(a)
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 186
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
In case of a delta/ star transformer, a phase to phase faults on the star side
produces 2:1:1 current distribution on the delta side. It is therefore,
advantageous to provide 3-0/c elements on delta side (as against 2 elements ) to
enable faster clearance, through the phase element sensing highest current, in
backup mode.
Below Fig. 3.1 (b) below shows the current distribution for phase fault on star
side to illustrate the above.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 187
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Since an up stream earth faults cases a current outflow from the transformer, a
directional earth-fault relay (67 N)looking into the transformer would not respond
for such faults and enable better co-ordination. The over-current relays (phase
CT connected- not shown in the figure) will also face a similar situation. However,
since they have a comparatively high setting (above full load) and see only 1/3rd
current compared to earth fault relay, the problem is less pronounced . Over
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 188
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 189
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
A high speed unit type of protection such as differential / restricted earth fault
protection is applied as a primary protection against internal faults.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 190
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Operation criteria:
Here as shown in below figure; this is a complete phase and earth fault
protection operating on Merz- price circulating current principle.
The differential relay compares the currents on the primary and secondary
side of the transformer using C.Ts of matched ratio, such that the secondary
currents are balanced in magnitude and phase for an external fault or load.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 191
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Normally above all the problems are not available in high impedance differential
scheme
DATE 1/10/2005
Knowledge Is Power SM
Above figure normally applicable for electromechanical & static relays. But in
modern numerical relay “TAP” point is also adjustable as shown in Fig.B. So, that
the net differential current which is flows through operating coil is very-very close
to zero.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 193
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Note in Fig. C that the delta CTs are on the star-grounded side of the transformer.
The phase shift can be accommodated with the delta CTs on either side.
However, it is essential to put the delta CTs on the star side in order to prevent
incorrect tripping for an external ground fault, shown in Fig. D. Here, the delta
CTs are on the wrong side. The three units of current flow entering from the
grounded star are not measured, so they produce an unbalance. (The delta-CT
ratio is assumed to be 3/1 to provide balancing for phase faults.) In contrast, in
Fig. 10 delta CTs on the wye side produce a balance.
Fig. D
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 194
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Fig. E
Since the unbalance on the primary of the wye-side CTs is caused by zero-
sequence current, the delta CTs filter out this unbalance in Fig. E.
There are two ways to form the CT delta. The connections must mirror those of
the power transformer to provide the proper balance.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 195
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
IRL Ir
Ir IRL
Ib Iy
Delta side vector
Star side vector
So, above diagram it is clear that the this 30 degree difference should be
compensated by adding the YD1 ICT on star winding of transformer otherwise it
may chance to mal-operate the relay on normal load condition or external fault
condition.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 196
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Following work out illustrates the choice of matching CTs/ICTs for a delta /star
transformer.
Transformers rating: 10 MVA, 66/33 KV, Dy11
Since the transformer is of Dy11 vector configuration the 33KV line current will be
leading the66KV side line currents by 30. To achieve phasor balance, the 33KV
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 197
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
The ICT secondary current corresponding to the above line current =0.875/
Example:
Transformer Data:
Rated MVA = 150MVA
Rated Primary kV = 11kV
Rated Secondary kV = 132kV
Transformer type = DYn11
Step:-1
Rated full load current on primary (Delta) side (Ip) = (150*106)/(1.73*11*103)
= 7882.3 Amp
Now, CTR on primary side = 8000/5A
Step:-2
Rated full load current on secondary (Star) side (Is) = (7882.3)*(11/132)
= 656.85 Amp
Step:-3
Selection of ICT of Star winging is YD1
Now, secondary current of each ICT = 4.92/1.73 = 2.84A
Thus, ICT RATIO = 0.821/2.84 = 1/3.45A
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 198
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Operate = Id>
Idiff
Restrain
0.15
1 2 10
Ibias
fig. G Typical Bias Characteristic
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 199
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Step:-1
Transformer F.L. current:
Step:-2
ICT RATIO:
IFL secondary on delta side = 4.582A therefore, the current flows through
secondary on star side = 4.582/1.73 = 2.648A because of star-delta ICT.
Step:-3
Now, Voltage at maximum TAP = {(7.5*240)/100} + 240 = 258kV
Step:-4
Now, assume the fault current on star side = 4.0kA
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 200
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Step:-5
CT secondary current:
Step:-6
ICT reflected current on delta side = (4.0*4.4) / 1.0 = 17.6A
Step:-7
ICT secondary (Delta side) current flows in relay restraining coil = 17.6*1.73 = 30.44A
Step:-8
Differential current flows in operating coil = (32.76 – 30.44) = 2.31A
Bias current = (32.76 + 30.44)/2 = 31.6A
Step:-9
%Slope = {(2.31) / (31.6)}*100 = 7.31%
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 201
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 202
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Inrush current:
It is define as the transient exciting current resulting from a sudden change in the
exciting voltage.
When the primary side of a transformer is switched on the supply with its
secondary unloaded, it acts as a simple inductive reactor. The value of the voltage
at the instant of switching can be any where between zero and the peak value.
At voltage maximum, the steady state value of the flux and hence the
magnetizing current it zero. Hence the flux wave immediately assumes the
normal shape for an inductive circuit with both the core flux and magnetizing
current rising from zero.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 203
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Initial value of the flux in the core is zero as against the steady state value of
“flux” corresponding to voltage zero. Since the total steady state flux change
during voltage half cycle is 2times of flux (i.e.-flux to +flux ) the flux rises from
zero to 2times of flux. This is known as the doubling effect.
Modern transformers operate at very low saturation level (around 1.1times the
working flux level.) The flux doubling, therefore, causes extreme saturation of the
core and transformer consequently draws heavy magnetizing current from the
supply source. While the normal steady state magnetizing current may be less
than 5% of full load current, the transient core saturation may raise it to several
times the normal load current. The situation is even worse if there is remnant flux
in the core which happens to be in the direction in which the first peak occurs.
Since the Inrush current flows only in the primary winding it appears as an
operating current to the differential relay, producing instability. The immunity to
inrush current can be obtained either by delaying the protection or by providing a
harmonic restraint.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 204
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
a. Time delay :
Since the magnetizing inrush is a transient phenomena, a small time delay can
be provided in the differential relay to override the same and ensure stability
Induction disc relays with an adjustable delay provided by the disc movement, is
one of the earlier designs of biased differential protection.
b. Harmonic Restraint :
Time delay associated with the differential relay, as explained before, would
make the protection slower in operation and increase the fault damage. Modern
high speed differential relay, therefore, employ a different approach to this
problem. the inrush current is highly distorted and contains a fairly high
proportion of 2nd ammonic component. Typical analysis of an inrush current wave
shows following ammonic contents.
While through current bias and 2nd harmonic bias (restraint ) is an essential
feature of a modern high speed differential protection. Following additional
features are an incorporated to enhance stability and maintain operating speed.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 205
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
The harmonic restraint may slow down the protection , on severe internal fault, if
the associated CTs suffer transient saturation and produce a high degree of
harmonic distortion. To ensure high speed operation under the above condition
an unrestrained differential highest with pick up threshold (usually 8-10 times ) is
incorporated in the differential relay.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 206
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Numerical versions of differential protections are also now available which use
suitable algorithm for measurement. The ratio and phase angle correction is a
software function in these relays, which eliminate the need for matched CTs/
ICTs. The numerical versions are usually multifunction and provide additional
protection elements( such as REF / over-fluxing etc.). Besides, several diagnostic
non-continuous self monitoring are provided.
4.2
4- CTs Restricted Earth Fault (REF) Protection Scheme for 3-phase 3-wire system :
This is a circulating current earth fault differential system, usually applied to the
star winding of a transformer, by balancing the residual current of the three line
current transformers with the output current of a CT in the neutral earth
connection. The protection arrangement is shown in fig. 4.2.a ) below.
For an external earth fault, the associated phase and neutral C.T. see same fault
current (lF) but of different polarity , while the phase C.T. sees an outflow of
current, the neutral C.T. sees an inflow with respect to the transformer. The
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 207
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
The voltage that can be developed across the relay under the above condition is
given by;
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 208
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
The minimum primary operating current (POC) is influenced by the magnetizing current
of the associated C.T.s and is given by:
Where, N = CT RATIO
N1 = Number of CTs are connected in parallel
Im = Magnetizing current of each CT at Vs
The relay branch being high impedance may force the CTs in to saturation for a severe
internal fault when summated current associated CTs seek its path through the relay.
This may cause peak over voltage across the CT secondary / Pilot as also the relay
threatening the insulation. The maximum peak voltage across the CT secondary is given
by the expression:-
If the peak voltage so worked out exceeds 3000 Volts a non-linear resistor (metrosil)
should be provided across the relay branch to limit this voltage within safe limits.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 209
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
4.2.1
5- CTs Restricted Earth Fault (REF) Protection Scheme for 3-phase 4-wire system :
CT1
Rph
CT2
Yph
CT3
Bph
mc
Stabilizing resistor
Relay
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 210
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Sensitivity:
If the internal fault (F1) occurred between “Bph-N” then it will not sensed by relay
because the fault current can not flows through Earth CT via earth but it sensed by
neutral CT via neutral wire.
Stability:
If the external fault (F2) occurred between “Bph-N” then it not sensed by relay through
Bph CT via neutral wire because the magnitude of fault current at relay terminal is near
by zero & it remains stable.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 211
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
4.2.2
4- CTs Restricted Earth Fault (REF) Protection Scheme for 3-phase 4-wire system :
CT1
CT2
CT3
K
External fault “F2”
mc
Stabilizing resistor
Relay
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 212
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
4.2.2.1
4- CTs Restricted Earth Fault (REF) Protection Scheme for 3-phase 4-wire system
using voltage operated high impedance relay :
CT1
CT2
CT3
K
External fault “F2”
mc
Stabilizing resistor
Relay
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 213
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
EXAMPLE:
CALCULATION OF RELAY SETTING FOR RELAY TYPE 7VH60:
The Minimum setting voltage for stability is;
Vs = (If/N)*(RCT + 2RL)------------------------------------(4.2.2.1)
Where,
If = fault current = 35,000 Amp(Say)
N = CT RATIO = 3000/1A
RCT = CT Secondary resistance = 2.0 OHMS
RL = Lead resistance = 0.5 OHMS
Vs = {(35000)/3000}* {2 + 1}
= {11.66}* {3}
= 34.99 Volts
It means, the relay will operate while the operating current magnitude is more than relay
settings (20mA) with 48Volts across on relay terminals.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 214
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Here as shown in above figure which shows 4-CTs connections scheme for 3-phase 4-
wire system. Earth CT connection is below the point “K”. If the internal fault (F1)
occurred between “Bph-N” then it will sensed by relay through Earth CT via neutral wire
& during an external fault (F2) between “B-N”, it’s stable through Earth CT via neutral
wire.
4.3
Protection against Incipient Faults:
Most of the distribution plants (including chemical-petrochem & fertilizers etc.) commonly
used protection against incipient (developing) faults is Buchholz relay. The relay has two
floats actuating mercury switches & is placed in the pipe connecting the transformer tank
to the conservator.
A slow generation of gas due to a minor fault causes a stream of bubbles which pass
towards the conservator and in the process get trapped into the Buchholz chamber,
lowering its oil level. Consequently the alarm float lower (trip) floats, tilting the mercury
switch and closing the trip contact.
While mounting the relay care should be taken to ensure that the arrow on its case
should point to the conservator and the connecting pipe should have an upward slope of
about 8o.
Besides, Buchholz relay, temperature monitoring devices such as oil and winding
temperature indicators are provided for transformers. These can also give fairly good
indication of an incipient failure such as generation of hot spot, failure of cooling system
etc.
4.4
Protection against overloading of transformer:
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 215
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Definite time over current relays (like CTU-31 etc.) are also used to provide pre-trip
alarm, if the overload exceeds permissible limit. Such relays are required to have high
reset ratio continuously adjustable current setting to match permissible overload rating of
the transformer.
4.5
Overfluxing Protections:
Increase in input voltage causes increase in working flux levels, thereby increasing the
iron losses and magnetizing current. The core bolt get heated and the interlamination
insulation and core bolt insulation is weakened. The reduction in supply frequency also
increases the core flux and has similar effect as that due to over voltage.
The generator transformers are more prone for overfluxing as these may be subjected to
an uncomfortable combination of over voltage and under frequency during start up or
coasting down, due to AVR/Governor malfunctioning.
V = pHi*f*T
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 216
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
4.6
Application Diagram of Complete OC & EF scheme for 2.5MVA DYn11 TR:
F1
I=0
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 217
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
4.7
Application Diagram of Differential scheme for Y-Y TR with one sets of ICTs:
The D-connected equalizing windings of the interposing CTs are used to eliminate
possible zero sequence currents in case of external earth faults and could always
be arranged for rated current 1 A.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 218
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
4.8
Application Diagram of Differential scheme for Y-Y TR with two sets of ICTs:
When interposing CTs are used on both windings of the power transformer they
should be Yd-connected. In that case there is no need for any D-connected equalizing
winding.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 219
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
4.9
Application Diagram of Differential scheme for D-Y TR with one set of ICTs:
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 220
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
4.10
Application Diagram of Combined Differential & REF scheme for D-Y TR with one set
of ICTs:
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 221
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
4.10.1
Application diagram of combined differential & REF scheme by using MBCH-12 &
CAG14 relay on DY1 TR.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 222
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 223
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 224
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
TABLE OF CONTENTS:
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 225
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
a) Protection of the bank against faults occurring within the bank including
those inside the capacitor unit; and,
The protection selected for a capacitor bank depends on bank configuration, whether or
not the capacitor bank is grounded and the system grounding.
1.1
Capacitor Unbalance Protection:
The protection of shunt capacitor banks against internal faults involves several protective
devices/elements in a coordinated scheme. Typically, the protective elements found in a
SCB for internal faults are: individual fuses (not discuss in this paper), unbalance
protection to provide alarm/ trip and over-current elements for bank fault protection.
Removal of a failed capacitor element or unit by its fuse results in an increase in voltage
across the remaining elements/ units causing an unbalance within the bank. A
continuous over-voltage (above 1.1pu) on any unit shall be prevented by means of
protective relays that trip the bank. Unbalance protection normally senses changes
associated with the failure of a capacitor element or unit and removes the bank from
service when the resulting over-voltage becomes excessive on the remaining healthy
capacitor units.
Unbalance protection normally provides the primary protection for arcing faults within a
capacitor bank and other abnormalities that may damage capacitor elements/ units.
Arcing faults may cause substantial damage in a small fraction of a second. The
unbalance protection should have minimum intentional delay in order to minimize the
amount of damage to the bank in the event of external arcing.
In most capacitor banks an external arc within the capacitor bank does not result in
enough change in the phase current to operate the primary fault protection (usually an
over-current relay) The sensitivity requirements for adequate capacitor bank protection
for this condition may be very demanding, particularly for SBC with many series groups.
The need for sensitive resulted in the development of unbalance protection where
certain voltages or currents parameters of the capacitor bank are monitored and
compared to the bank balance conditions.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 226
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Internally fused capacitors have individual fused capacitor elements that are
disconnected when an element breakdown occurs (the element fails opened). The risk of
successive faults is minimized because the fuse will isolate the faulty element within a
few cycles. The degree of unbalance introduced by an element failure is less than that
which occurs with externally fused units (since the amount of capacitance removed by
blown fuse is less) and hence a more sensitive unbalance protection scheme is required
when internally fused units are used.
It may also be desirable to set the trip level based on an estimated number of canceling
failures in order to reduce the risk of subjecting capacitor units to damaging voltages and
requiring fuses to operate above their voltage capability when canceling failures occur.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 227
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Alstom make electromechanical Over current relay type “CDG-11” is used for
above application which is mention in figure-1.
c) Undetectable Faults
For certain capacitor bank configurations some faults within the bank will not cause an
unbalance signal and will go undetected. For example:
a) Rack-to-rack faults for banks with two series groups connected phase-over-
phase and using neutral voltage or current for unbalance protection;
The inherent unbalance error may be in the direction to prevent unbalance relay
operation, or to cause a false operation. The amount of inherent unbalance for
various configurations may be estimated using the equations provided in reference.
If the inherent unbalance error approaches 50% of the alarm setting, compensation
should be provided in order to correctly alarm for the failure of one unit or element as
specified. In some cases, a different bank connection can improve the sensitivity without
adding compensation. For example, a wye bank can be split into a wye-wye bank,
thereby doubling the sensitivity of the protection and eliminating the system voltage
unbalance effect.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 228
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Harmonic voltages and currents can influence the operation of the unbalance relay
unless power frequency band-pass or other appropriate filtering is provided.
The unbalance trip relay should have enough time delay to avoid false operations due to
inrush, system ground faults, switching of nearby equipment, and non-simultaneous pole
operation of the energizing switch. For most applications, 0.1s should be adequate. For
unbalance relaying systems that would operate on a system voltage unbalance, a delay
slightly longer than the upstream protection fault clearing time is required to avoid
tripping due to a system fault. Longer delays increase the probability of catastrophic
bank failures.
With grounded capacitor banks, the failure of one pole of the SCB switching device or a
single phasing from a blown bank fuse will allow zero sequence currents to flow in
system ground relays. Capacitor bank relaying, including the operating time of the
switching device, should be coordinated with the operation of the system ground relays
to avoid tripping system load.
The unbalance trip relay scheme should have a lockout feature to prevent inadvertent
closing of the capacitor bank switching device if an unbalance trip has occurred.
The unbalance trip time delay should be long enough to avoid false tripping due to
following conditions;
• Inrush.
• System ground faults.
• Switching of near by equipment.
The unbalance trip time delay should be minimized to reduce damage from arcing faults
with in the bank structure & reduce damage to CTs, VTs & relay system for single phase
or open phase conditions.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 229
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
1.2
Disadvantage:
• The disadvantage of ungrounded bank is the over voltage that occurs when the
bank is unbalanced due to a capacitor fuse blowing as shown in figure below.
The over voltage appears across the remaining capacitors on the phase in which
the fuse has opened. The over voltage can be as high as 50%, depending
upon the bank configuration, and can reduce the life and permanently damage
the remaining capacitors.
• Above reason, the kVAR out is reduced
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 230
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
There are so many technical considerations when setting and applying a neutral voltage
unbalance protection system. The following are the some considerations as below;
• The unbalance protection system should be sensitive enough to alarm for the
loss of one or more capacitors, but trip out for a loss of sufficient or additional
capacitor units that will cause an over voltage in excess of 110% on the
remaining capacitors.
• The unbalance protection system should have a time delay of at least 0.5s to
overcome false operations due to inrush, ground faults on the line, lightning,
switching of nearby equipment, and other transient unbalance conditions.
• The unbalance protection system should have a lockout feature to prevent
automatic reclosing of the capacitor bank switching device.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 231
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Figure-(a) Figure-(b)
Fig. (a) shows a method that measures the voltage between capacitor neutral and
ground using a VT and an over-voltage relay with 3rd harmonic filter. It is simple but
suffers in presence of system voltage unbalances and inherent unbalances. The voltage-
sensing device is generally a voltage transformer but it could be a capacitive potential
device or resistive potential device. The voltage-sensing device should be selected for
the lowest voltage ratio attainable, while still being able to withstand transient and
continuous over-voltage conditions to obtain the maximum unbalance detection
sensitivity. However, a voltage transformer used in this application should be rated for
full system voltage because the neutral voltage can under some conditions rise to as
high as 2.5 per unit during switching.
An equivalent zero sequence component that eliminate the system unbalances can be
derived utilizing three voltage-sensing devices with their high side voltage wye-
connected from line to ground, and the secondaries connected in a broken delta. The
voltage source VTs can be either at a tap in the capacitor bank or used the VTs of the
bank bus.
Figs. (b) shows a neutral unbalance relay protection scheme for an ungrounded wye
capacitor bank, using three phase-to-neutral voltage transformers with their secondaries
connected in broken delta to an over-voltage relay. Compared to the scheme in Fig. (a),
this scheme has the advantage of not being sensitive to system voltage unbalance. Also,
the unbalance voltage going to the over-voltage relay is three times the neutral voltage
as obtained from Fig (a). For the same voltage transformer ratio, there is a gain of three
in sensitivity over the single neutral-to-ground voltage transformer scheme. The voltage
transformers should be rated for line-to-line voltage.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 232
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Figure-1(a) Figure-1(b)
Modern digital relays can calculate the zero sequence voltage from the phase voltages
as shown in Fig (a), eliminating the need of additional auxiliary VTs to obtain the zero
sequence voltage. Fig (b) shows the same principle but using the VTs on the capacitor
bank bus. Although schemes shown in Fig (b), 1(a) and 1(b) eliminate system
unbalances, they do not eliminate the inherent capacitor unbalance.
Alstom make electromechanical residual IDMTL over voltage relay type “VDG-14”
is used for above application.
Range: (5.4V – 20V) & TMS = (0.1 – 1.0)
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 233
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Fig. 2 shows a protection scheme that removes the system unbalance and compensate
for the inherent capacitor unbalance. It is a variation of the voltage differential scheme
for grounded banks described below). The best method to eliminate the system
unbalance is to split the bank in two Wyes; however, it may not be always possible or
desirable. The system unbalance appears as a zero sequence voltage both at the bank
terminal and at the bank neutral. The bank terminal zero sequence component is derived
from 3 line VTs with their high side Wye connected and their secondaries connected in
broken delta. The difference voltage between the neutral unbalance signal due to
system unbalance and the calculated zero sequence from the terminal VTs will be
compensated for all conditions of system unbalance. The remaining error appearing at
the neutral due to manufacturers capacitor tolerance is then compensated for by means
of a phase shifter.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 234
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Three methods of providing unbalance protection for double wye ungrounded banks are
presented. Fig. 3(a) uses a current transformer on the connection of the two neutrals
and an over-current relay (or a shunt and a voltage relay). Fig. 3(b) uses a voltage
transformer connected between the two neutrals and an over-voltage relay. The effect of
system voltage unbalances are avoided by both schemes, and both are unaffected by
third harmonic currents or voltages when balanced. The current transformer or voltage
transformer should be rated for system voltage.
The neutral current is one-half of that of a single grounded bank of the same size.
However, the current transformer ratio and relay rating may be selected for the desired
sensitivity because they are not subjected to switching surge currents or single-phase
currents as they are in the grounded neutral scheme.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 235
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Figure-3(a) Figure-3(b)
Fig. 4 shows a scheme where the neutrals of the two capacitor sections are ungrounded
but tied together. A voltage transformer, or potential device, is used to measure the
voltage between the capacitor bank neutral and ground. The relay should have a
harmonic filter.
Figure-4
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 236
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
1.3
Unbalance Protection Methods for Grounded Wye connected Banks:
The current transformer output has a burden resistor and a sensitive voltage relay.
Because of the presence of harmonic currents (particularly the third, a zero sequence
harmonic that flows in the neutral-to-ground connection), the relay should be tuned to
reduce its sensitivity to frequencies other than the power frequency.
The voltage across the burden resistor is in phase with the neutral-to-ground current.
This neutral-to-ground current is the vector sum of the three-phase currents, which are
90° out of the phase with the system phase-to-ground voltages. This scheme may be
compensated for power system voltage unbalances, by accounting for the 90° phase
shift, and is not unusually appropriate for very large capacitor banks requiring very
sensitive settings.
Each time the capacitor bank is energized, momentary unbalanced capacitor charging
currents will circulate in the phases and in the capacitor neutral. Where a parallel bank is
already in service these current can be on the order of thousands Amps causing the
relay to mal-operate and CT to fail.
Figure-5(a) Figure-5(b)
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 237
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Figure-6
c) Voltage differential protection method for grounded wye banks
On large SCBs with large number of capacitor units, it is very difficult to detect the loss
of 1 or 2 capacitor units as the signal produced by the unbalance is buried in the
inherent bank unbalance. The voltage differential provides a very sensitive and efficient
method to compensate for both system and inherent capacitor bank unbalances in
grounded wye capacitor banks. Fig. 8 shows the voltage differential scheme for a single
wye-connected bank and Fig. 8 for a double wye-connected bank.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 238
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
The scheme uses two voltage transformers per phase: one connected to a tap on the
capacitor bank; the other, at the bank bus for single Wye banks; or, for double Wye
banks, at a similar tap on the second bank. By comparing the voltages of both VTs, a
signal responsive to the loss of individual capacitor elements or units is derived.
If the bank is tapped at the midpoint the sensitivity is the same for failures within and
outside the tapped portion. If the bank is tapped below (above) the midpoint, the
sensitivity for failures within the tapped portion will be greater (less) than for failures
outside the tap portion. This difference may cause difficulty in achieving an appropriate
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 239
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Tapping across the bottom series groups or a midpoint tap is not appropriate for fuseless
banks with multiple strings because the strings are not connected to each other at the
tap point. Tapping across the low-voltage capacitors is suitable for fuseless capacitor
banks.
The most efficient protection for mid-rack phase to phase faults is the negative sequence
current. Tripping shall be delayed to coordinate with other relays in the system.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 240
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Under-voltage or undercurrent relays with timers are used to detect the bank
going out of service and prevent closing the breaker until the set time has
elapsed.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 241
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
CONCLUSIONS:
The protection of shunt capacitor banks uses simple, well known relaying principles such
as over-voltage, over-currents. However, it requires the protection engineer to have a
good understanding of the capacitor unit, its arrangement and bank design issues before
embarking in its protection.
Unbalance is the most important protection in a shunt capacitor bank, as it provides fast
and effective protection to assure a long and reliable life for the bank. To accomplish its
goal, unbalance protection requires high degree of sensitivity that might be difficult to
achieve.
The latest IEEE Guide for the Protection of Shunt Capacitors Banks shall be the guiding
document when implementing a protection scheme to a shunt capacitor bank.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 242
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 243
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 244
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 245
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
References:
(1) IEEE Std C37.99-2000, IEEE Guide for the Protection of Shunt Capacitors
Banks.
(2) ABB & ALSTOM Relay Manuals.
Thank You
DOBLE ENGINEERING PVT LTD,
305-SAKAR BUILDING,
OLD PADRA ROAD,
VADODARA
PH: (+91) (265) 555 77 15
Email: kdave@doble.com
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 246
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 247
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Question #1:
What is Power Factor?
KW is Working Power (also called Actual Power or Active Power or Real Power).
It is the power that actually powers the equipment and performs useful work.
Let’s say you are at the ballpark and it is a really hot day. You order up a mug of
your favorite brew sky. The thirst-quenching portion of your Tea is represented
by KW (Figure 1).
Unfortunately, life isn’t perfect. Along with your ale comes a little bit of foam. (And
let’s face it…that foam just doesn’t quench your thirst.) This foam is represented
by KVAR.
The total contents of mug, KVA, are this summation of KW (the Coffee) and
KVAR (the foam).
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 248
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Figure-1
Looking at our Coffee mug analogy above, power factor would be the ratio of
Coffee (KW) to Coffee plus foam (KVA).
Total Coffee
P.F. = ---------------------
Coffee + FOAM
DATE 1/10/2005
Knowledge Is Power SM
• The less foam you have (the lower the percentage of KVAR), the higher your
ratio of KW (Coffee) to KVA (Coffee plus foam). In fact, as your foam (or KVAR)
approaches zero, your power factor approaches 1.0.
Our Coffee mug analogy is a bit simplistic. In reality, when we calculate KVA, we must
determine the “vectorial summation” of KVAR and KW. Therefore, we must go one
step further and look at the angle between these vectors.
Kamin here is dragging a heavy load (Figure 2). Kamin’s Working Power (or
Actual Power) in the forward direction, where he most wants his load to travel, is
KW.
Unfortunately, Kamin can’t drag his load on a perfect horizontal (he would get a
tremendous backache), so his shoulder height adds a little Reactive Power, or
KVAR.
Figure:-2
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 250
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
The “Power Triangle” (Figure 3) illustrates this relationship between KW, KVA,
KVAR, and Power Factor:
POWER TRIANGLE:
• KW and KVA would be almost equal (Kamin wouldn’t have to waste any
power along his body height)
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 251
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
• The angle theta (formed between KW and KVA) would approach zero
So….
In order to have an “efficient” system (whether it is the Coffee mug or Kamin
dragging a heavy load), we want power factor to be as close to 1.0 as possible.
Sometimes, however, our electrical distribution has a power factor much less
than 1.0. Next, we’ll see what causes this.
Question #2:
What Causes Low Power Factor?
Since power factor is defined as the ratio of KW to KVA, we see that low power
factor results when KW is small in relation to KVA. Remembering our beer mug
analogy, this would occur when KVAR (foam, or Kamin’s shoulder height) is
large.
• Transformers
• Induction motors
• Induction generators (wind mill generators)
• High intensity discharge (HID) lighting
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 252
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
So, inductive loads (with large KVAR) result in low power factor.
Question #3:
Why Should I Improve My Power Factor?
You want to improve your power factor for several different reasons. Some of the
benefits of improving your power factor include:
Recall that inductive loads, which require reactive power, caused your low power
factor. This increase in required reactive power (KVAR) causes an increase in
required apparent power (KVA), which is what the utility is supplying.
So, a facility’s low power factor causes the utility to have to increase its
generation and transmission capacity in order to handle this extra demand.
By lowering your power factor, you use less KVAR. This results in less KW,
which equates to a dollar savings from the utility.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 253
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Utilities usually charge customers an additional fee when their power factor is
less than 0.95. (In fact, some utilities are not obligated to deliver electricity to
their customer at any time the customer’s power factor falls below 0.85.) Thus,
you can avoid this additional fee by increasing your power factor.
For example, a 1,000 KVA transformer with an 80% power factor provides 800
KW (600 KVAR) of power to the main bus.
By increasing the power factor to 90%, more KW can be supplied for the same amount
of KVA.
The KW capacity of the system increases to 900 KW and the utility supplies only
436 KVAR.
DATE 1/10/2005
Knowledge Is Power SM
3) Increased voltage level in your electrical system and cooler, more efficient
motors
So, by raising your power factor, you will minimize these voltage drops along
feeder cables and avoid related problems. Your motors will run cooler and be
more efficient, with a slight increase in capacity and starting torque.
Question #4
How Do I Correct (Improve) My Power Factor?
We have seen that sources of Reactive Power (inductive loads) decrease
power factor:
• Transformers
• Induction motors
• Induction generators (wind mill generators)
• High intensity discharge (HID) lighting
• Capacitors
• Synchronous generators (utility and emergency)
• Synchronous motors
Thus, it comes as no surprise that one way to increase power factor is to add
capacitors to the system. These--and other ways of increasing power factor--are
listed below:
DATE 1/10/2005
Knowledge Is Power SM
The presence of both a capacitor and inductor in the same circuit results in the
continuous alternating transfer of energy between the two.
Thus, when the circuit is balanced, all the energy released by the inductor is
absorbed by the capacitor.
We already talked about the fact that low power factor is caused by the presence of
induction motors. But, more specifically, low power factor is caused by running induction
motors lightly loaded.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 256
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Question #5
How Long Will It Take my Investment in Power Factor
Correction to Pay for Itself?
A calculation can be run to determine when this payoff will be. As an example,
assume that a portion of your facility can be modeled as in Figure 6 below. Your
current power factor is 0.65.
• 163 KW load
• 730 hours per month
• 480 Volt, 3 phase service
• 5% system losses
• Load PF = 65%
We’ll calculate the total amount the utility charges you every month as follows:
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 257
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Now, let’s say that you decide to install a capacitor bank (Figure 7). The 190
KVAR from the capacitor cancels out the 190 KVAR from the inductive motor.
Your power factor is now 1.0.
• Corrected PF = 1.0
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 258
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Let’s calculate how long it will take for this capacitor bank to pay for itself.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 259
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Question #6:
Testing of Application Relay (LoVAR) by using DOBLE F6150
INSTRUMENT?
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 260
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Vector Diagram
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 261
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 262
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Introduction:
The objective of the electric utility is to deliver sinusoidal voltage at fairly constant
magnitude throughout their system. This objective is complicated by the fact that there
are loads on the system that produce harmonic currents. These currents result in
distorted voltages and currents that can adversely impact the system performance in
different ways.
As the number of harmonic producing loads has increased over the years, it has become
increasingly necessary to address their influence when making any additions or changes
to an Installation.
To fully appreciate the impact of this phenomenon, there are two important concepts to
bear in mind with regard to power system harmonics. The first is the nature of harmonic-
current producing loads (non-linear loads) and the second is the way in which harmonic
currents flow and how the resulting harmonic voltages develop.
On the other hand, the current wave shape on a non-linear load is not the same as the
voltage. Typical examples of non-linear loads include rectifiers (power supplies, UPS
units, discharge lighting), adjustable speed motor drives, ferromagnetic devices, DC
motor drives and arcing equipment.
The current drawn by non-linear loads is not sinusoidal but it is periodic, meaning that
the current wave looks the same from cycle to cycle. Periodic waveforms can be
described mathematically as a series of sinusoidal waveforms that have been summed
together.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 263
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Symmetrical waves contain only odd harmonics and un-symmetrical waves contain
even and odd harmonics.
A symmetrical wave is one in which the positive portion of the wave is identical to the
negative portion of the wave. An un-symmetrical wave contains a DC component (or
offset) or the load is such that the positive portion of the wave is different than the
negative portion. An example of un-symmetrical wave would be a half wave rectifier.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 264
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Phase rotation describes the order in which waveforms in each phase of a three-phase
system cross zero. This can be shown with a waveform diagram, as illustrated below, or
with a phasor diagram of lines and arrows, also shown below. Phasors are used for
simplification purposes. The length of the arrows represents voltage or current
magnitudes, while the angles between them show phase relationship.
Odd-numbered harmonic, such as the 3rd, 5th, etc, are more prevalent than even-
numbered harmonics, such as the 2nd and 4th. Higher-numbered harmonics are generally
smaller in amplitude, reducing their effect on the power distribution system.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 265
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
These voltages sum and when added to the nominal voltage produce voltage distortion.
The magnitude of the voltage distortion depends on the source impedance and the
harmonic voltages produced.
If the source impedance is low then the voltage distortion will be low. If a significant
portion of the load becomes non-linear (harmonic currents increase) and/or when a
resonant condition prevails (system impedance increases), the voltage can increase
dramatically.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 266
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Zero sequence harmonics add together, creating a single-phase signal that does not
produce a rotating magnetic field. This harmonics, however, can cause additional
heating in the neutral conductor of a three-phase, four-wire system. This can be a
significant problem since the neutral conductor is usually not protected by a fuse or
circuit breaker.
K-Factor is a numerical rating that indicates a transformer’s ability to handle the extra
heating caused by harmonics. A standard transformer has a K-1 rating. A transformer
with a K-5 rating would be able to handle five times the harmonic heating effects of a
standard transformer.
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 267
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
Harmonic analysis is required for power system & protection engineers to reduce
or avoid nuisance trips under healthy power system. DOBLE “DATC” and
“TransWin” Application software are used for harmonic, Swing, Various transient
phenomenon like C.T. saturations, magnetizing inrush phenomenon, Locked
rotor characteristic of motor etc.
Capability:
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 268
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 269
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
The design & application of relays is always a challenge for power system
protection engineers because it’s job like as a detective to detect a power system
faults & isolate the faulty circuit from the power system.
It offers all the satisfying life, security, interest & number of varieties
(technological)
Security: Means the profession is not over crowded, in fact the manufacturers of
relays have the greatest difficulty in finding a good protection engineers.
Interest: Means it’s require wide range of knowledge of Power system &
machines while the engineers want to design the relays. It means the relay
engineers constantly adds to mathematical, electrical & general knowledge.
References:
2. Protective Relaying, Wan.C.Warrington.
3. Art & Science of Relay, Russell Masson.
4. Power System & Protection, Bhuvnesh Ojha & Date.
5. Engineering Dependable Protection Part-I.
6. IEEE/ANSI Committee Reports.
7. ALSTOM, ABB, SIEMENS, REYROLLY Relay Manuals
8. Protective relay Application guide – GEC ALSHOM, UK
9. ProTesT user guide – Doble Engineering Company, USA
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 270
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com
India
DATE 1/10/2005
Knowledge Is Power SM
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA 271
PH: (+91) (265) 555 77 15, FAX: (+91) (265) 235 62 85
DOBLE ENGINEERING COMPANY, WATER TOWN, MA, USA
www.doble.com