Installation and service instructions
7.2/12 kV - 400 A
Index
I. Introduction 3
V. Qualified personnel 5
1. Description 6
2. Checking on receipt 9
3. Handling 10
4. Storage 12
5. Installation 13
7. Maintenance 34
1
Index
I. Introduction 3
II. Programme for environmental protection 4
III. Application of the standards for X-ray emission 4
IV. Safety information 4
V. Qualified personnel 5
VI. Interventions in the field 5
1. Description 6
1.1. “MAC” magnetic drive 6
1.2. Versions available 7
1.3. Characteristics 7
1.4. Weights and dimensions 8
1.5. Performances 8
1.6. Contactor auxiliary contacts 8
1.7. Compliance with Standards 8
1.8. Protection against short-circuit 8
2. Checking on receipt 9
3. Handling 10
3.1. Handling using a lifting or fork-lift truck 10
3.2. Handling and lifting using a crane 11
4. Storage 12
5. Installation 13
5.1. General 13
5.2. Installation and operating conditions 13
5.3. Normal conditions 13
5.4. Special conditions 13
5.5. Overall dimensions 14
5.6. Assembly and making the connections 18
5.7. Description of the closing and opening operations 25
5.8. Manual emergency opening operation 27
6. Putting into service 28
6.1. General procedures 28
6.2. Racking the contactor in and out 29
6.3. Accessories and tools for the operations 32
6.4. Contactors with motorised withdrawable truck 33
7. Maintenance 34
7.1. General 34
7.2. Inspection 34
7.3. Servicing 37
7.4. Servicing following a short-circuit or overload 37
7.5. Repairs 38
7.6. Instructions for dismantling or replacing fuses 38
7.7. Replacement of the contactor fuses 40
7.8. Mounting and dismantling the short-circuit busbar 43
7.9. Putting the contactor back into service 43
8. Spare parts and accessories 44
8.1. List of spare parts 44
2
I. Introduction
The instructions in this manual refer to the fixed and withdrawable versions of the VSC series of
contactors. For correct use of the product, please read it carefully.
For the electrical and construction characteristics and the overall dimensions of the V-Contact
VSC contactors, please also see technical catalogue 1VCP000165.
Like all the apparatus we manufacture, the V-Contact vacuum contactors are designed for dif-
ferent installation configurations. Furthermore, this apparatus allows further technical and con-
struction modifications (at the customer’s request) to adapt to special installation requirements.
Consequently, this manual may not provide information concerning special configurations of the
apparatus.
Apart from this manual, it is therefore always necessary to consult the latest technical documen-
tation (circuit and wiring diagrams, assembly and installation drawings, any protection coordina-
tion studies, etc.), especially regarding any variants requested in relation to the standardised
configurations.
Only use original spare parts for maintenance operations. The use of non-original spare parts
can cause hazardous malfunctions and the apparatus warranty will no longer be valid.
Please refer to the technical sheets of the Kits for correct assembly of the accessories and/or
spare parts. For further information, also see the 1VCP000165 technical catalogue of the contac-
tor and the spare parts catalogue.
This manual and all the enclosed drawings must be considered an integral part of the apparatus.
They must be easily to hand at all times for revision and reference.
These instructions do not intend to cover all the details, configurations or variants of the appa-
ratus, storage or installation. For this reason, the information given below may sometimes not
contain the instructions regarding special configurations. This does not relieve the user from
their responsibility for using good technical working practices in application, installation, service
and maintenance of the apparatus purchased. Should further information be required, please
contact ABB.
WARNING
3
II. Environmental protection programme
The V-Contact vacuum contactors are manufactured in accordance with the ISO 14000 Standards
(Guidelines for environmental management). The production processes are carried out in compli-
ance with the Standards for environmental protection in terms of reduction in energy consumption
as well as in raw materials and production of waste materials. All this is thanks to the medium
voltage apparatus manufacturing facility environmental management system.
4
V. Qualified personnel
For the purposes of this manual and the product rating plates, a qualified person is intended as
a person who:
1) carefully reads the instruction manual all the way through.
2) has in-depth knowledge of the installation, construction and service of the apparatus and knows
about the risks connected with any interventions.
3) is qualified and authorised to energise, de-energise, earth and identify the circuits according
to the safety procedures and the local regulations in force.
4) is qualified and authorised to put this apparatus into service, and to carry out maintenance
and repair operations on it.
5) is trained in correct use of protective equipment, such as rubber gloves, hard hats, protective
goggles, face shields, flameproof clothing, etc. according to the safety procedures and the local
regulations in force.
6) is trained in first-aid procedures.
5
1. Description The drive is operated by means of an electronic
feeder which, with just three versions, can cover
The medium voltage V-Contact VSC contactors
all the power supply voltage values required by
are pieces of apparatus suitable for operating
the major international Standards.
in alternating current and are normally used to
control users requiring a high number of hourly
1.1. “MAC” magnetic drive
operations.
The basic contactors consist of: Based on the experience gained in the field
• moulded polyester resin monobloc containing of circuit-breakers with magnetic drive, ABB
the vacuum interrupters has implemented this technology in the field of
• bistable electromagnet drive contactors.
• multi-voltage feeder The magnetic drive adapts perfectly to this type
• auxiliary contacts of apparatus thanks to its precise and linear
• mechanical status indicator (open/closed). travel.
Apart from what is specified for the fixed contac- This means that a simple and direct axial trans-
tors, the withdrawable contactors also consist mission of the movement to the moving contacts
of: of the vacuum interrupter can be realised, with
• fuseholders preset for DIN or BS fuses (ac- both electrical and mechanical benefits.
cording to the customer’s requirements) The drive, which is of bistable type, is fitted with
• automatic opening device for intervention of an opening and a closing coil.
even a single fuse The two coils - individually energised - allow
• truck the drive core to be moved from one of the two
• lock which prevents closing during the racking- stable positions to the other.
in/out operation. The drive shaft is solid with an iron core which is
The V-Contact VSC contactor introduces the immersed and held in position in a field gener-
drive with permanent magnets - already widely ated by two permanent magnets (fig. A).
used, experimented and appreciated in medium Energising the coil opposite to the magnetic
voltage circuit-breakers - into the worldwide latching position (fig. A) of the core, the mag-
panorama of medium voltage contactors. netic field (fig. B) is generated, which attracts
The experience acquired by ABB in the field and moves the core into the opposite position
of medium voltage circuit-breakers fitted with (fig. C).
drives with “MABS” permanent magnets, has Every opening and closing operation creates a
made it possible to develop an optimised version magnetic field concordant with the one gener-
of the actuator (Bistable MAC drive) for medium ated by the permanent magnets, with the advan-
voltage contactors. tage, during service, of keeping the intensity of
the field itself constant as the number of opera-
tions carried out increases.
6
The energy needed for operation is not sup- voltage feeder extremely reliable, unaffected by
plied directly by the auxiliary power supply, but electromagnetic interference generated by the
is always “stored” in the capacitor which acts as surrounding environment and free of any emis-
an energy accumulator, and therefore operation sions which may affect other apparatus placed
always takes place with constant speeds and in the vicinity.
times, regardless of the divergence of the power These characteristics have made it possible
supply voltage from the rated value. for the V-Contact VSC contactors to pass the
The auxiliary power supply only has the aim of electromagnetic compatibility tests (EMC) and
keeping the capacitor charged. Consumption is obtain the CE mark.
therefore minimal. The power required is less
than 5 W. In order to re-instate the rated energy 1.2. Versions available
value in the capacitor following an operation, The V-Contact VSC are available in the fixed
there is an inrush of 15 W for a duration of a few and the fixed with fuse versions, as well as the
tens of milliseconds. plug-in version with manual or motorised truck
Careful selection of the components and a with rated voltage of 7.2 kV and 12 kV. The
precise design make the electronic multi- main characteristics are listed below.
7
1.4. Weights and dimensions
Contactor VSC7 VSC12 VSC7/F VSC12/F VSC7/P VSC12/P
Weight [Kg] 23 23 35(**) 35(**) 52(**) 52(**)
Overall dimensions [mm] H 371 391 494 532 636 636
[mm] L 350 350 466 466 531 531
[mm] P 215 215 622 702 657 657
(**) Without fuses
1.5. Performances
Contactor VSC7-VSC7/F-VSC7/P VSC12-VSC12/F-VSC12/P
Rated voltage [kV] 2.2/2.5 3.6 3.6/7.2 6.2/7.2 12
Ultimate performances for:
(1) Overvoltage surge ar-
Motors [kW] 1.000 1.500 1.500 3.000 5.000
resters are compulsory
between phases and be- Transformers [kVA] 1.100 1.600 2.000 4.000 5.000
tween phase and earth. Capacitors [kVAR] 1.000 1.500 1.500 3.000 4.800 (1)
8
2. Checking on receipt through the agent or supplier) as soon as possible
and in any case within five days of receipt.
During handling, take great care not The apparatus is only supplied with the acces-
to stress the insulating parts of the sories specified at the time of ordering and vali-
apparatus and the terminals of the
dated in the order confirmation sent by ABB.
contactor.
The accompanying documents inserted in the
Any operation carried out on the
shipping packing are:
contactor must be done without the
– instruction manual (this document)
presence of voltage and with the main
– test certification
protection device open: danger of
electrocution and/or severe burns. – identification label
Make sure that operations are car- – fiscal copy of the shipping advice note
ried out with the main and auxiliary – electric wiring diagram.
power off. Other documents which are sent prior to ship-
ment of the apparatus are:
On receipt, immediately check integrity of the – order confirmation
packing and the colour of the “SHOCKWATCH” – original shipping advice note
indicator (Fig. 1) placed on it. – any drawings or documents referring to special
If the “SHOCKWATCH” impact indicator is configurations/conditions.
WHITE, it means that the packing has not
received any notable shocks during transport.
Open the packing, remove the contactor as
indicated below, and check the state of the
apparatus and its correspondence with the
Shock indicator
nameplate data (see fig. 2) with what is speci-
fied in the accompanying shipping note and in
the order confirmation sent by ABB.
If the “SHOCKWATCH” impact indicator is RED,
follow the instructions indicated on the plate.
Opening the packing does not damage its com-
ponents and it can therefore be re-instated using Fig. 1
the original material.
The contactor is shipped in special packing, in A
the open position.
Each piece of apparatus is protected by a plastic VACUUM CONTACTOR
B F
cover to prevent any infiltration of water during VSC/P . . . IEC 60470
the loading and unloading stages and to keep C SN 1VC1 AL ................ PR. YEAR ......
the dust off during storage. Ur VOLTAGE ... kV
To remove the contactor from the packing, pro- Up LIGHTING IMPULSE WITHSTAND VOLTAGE ... kV
Ud POWER FREQUENCY WITHSTAND VOLTAGE ... kV
ceed as follows: fr FREQUENCY ... Hz
Ie RATED OPERATONAL CURRENT ... A
– open the plastic bag M MASS ... kg
D
– remove the contactor, avoiding any stress to ALTITUDE CLASS < 1000 m
9
3. Handling 5. Avoid excessive speed, sudden starts and
stops or sharp changes in direction during
The contactor can be lifted using a lifting truck contactor handling.
or a fork-lift truck. 6. Only lift the contactor enough to avoid any
The following precautions must be taken during obstacles on the floor.
contactor handling: 7. Take care to avoid any impacts with struc-
1. Keep the contactor in the upright position. tures, other apparatus or with personnel
2. Make sure that the load is balanced on the when handling the contactor.
truck or on the transport plate/pallet. 8. Never lift a contactor over an area where
3. Interpose protective material between the there are people.
contactor and the truck to avoid any damage 9. During handling of the apparatus, do not
or scratches. stress the insulating parts and the contactor
4. Fix the contactor onto the truck or onto the terminals.
transport plate/pallet to prevent it moving or
tilting over.
Fig. 3a
10
3.2. Handling and lifting using a crane
– Insert the lifting plates
– Lift
– After the unpacking and lifting operations, remove the lifting accessories.
Removal of the contactor from the packing and dismantling the lifting tools.
Fig. 3b
11
4. Storage
When a period of storage is foreseen, the origi- Should the original packing no longer be avail-
nal packing must be put back. Store the contac- able and immediate installation is not possible,
tor in a dry dust-free area. It must not be left store in a covered, well-ventilated, dry, dust-free,
outside or in adverse micro-climatic conditions: non-corrosive ambient, with a dry atmosphere,
if it is left without protection, rust and deteriora- away from any flammable materials and at a
tion of the insulation can occur. temperature between – 5 °C and + 40 °C.
Insert special hygroscopic packets inside the In any case, avoid any accidental impacts or
packing, with at least one standard packet per positioning which stresses the structure of the
piece of apparatus. Replace the packets ap- apparatus.
proximately every 6 months.
12
5. Installation 5.3. Normal conditions
Follow the recommendations in the IEC 60694
5.1. General
and 60470 Standards. In more detail:
Correct installation is of primary importance.
The manufacturer’s instructions must be care-
Ambient temperature
fully studied and followed. It is good practice
Maximum + 40 °C
to use gloves for handling the pieces during Average maximum over 24 hours + 35 °C
installation. Minimum (according to class – 5), – 5 °C
apparatus for indoor installation
13
5.5. Overall dimensions
5.5.1. VSC fixed contactor
For the overall dimensions and distances between fixing holes, refer to figure 4a.
In any case, avoid stressing the supporting structure of the contactor: if necessary, arrange slots
in the fixing area to facilitate correct positioning of the apparatus.
The assembly positions can be selected between the two shown in figure 4b.
VSC7
VSC12
Fig. 4a
14
Installation of fixed contactors
The contactor keeps its performances in the installation positions indicated:
A) floor-mounted with moving contacts at the bottom
B) wall-mounted with horizontal moving contacts and terminals at the bottom.
A B
Fig. 4b
VSC7/F
Fig. 5a
15
VSC12/F
Fig. 5b
Fig. 5c
16
5.5.3. VSC/P withdrawable contactors
VSC7/P - VSC12/P
Fig. 6
17
5.6. Assembly and making the connections
5.6.1. Fixed contactors
WARNING
!
Dangerous voltages. Risk of death, serious injury to people, damage to
the apparatus or other objects.
Remove the power supply, ground and put all the power and control voltage
sources under safe conditions before starting the work on this or any other
electrical apparauts.
Installation must only be carried out by qualified personnel.
18
– The use of bolts according to DIN class 8.8 Furthermore, earthing must always be carried
Standards is recommended, also referring to out between the VSC frame and the main
what is indicated in the table. earthing system of the plant.
– In the case of cable connections, strictly follow Use cables with a suitable cross-section and of
the manufacturer’s instructions for making the the minimum length needed.
terminals.
Earthing and cabling procedures The length of the earthing cables must be as
short as possible. Connection to earth of the
VSC conforms to level 3 of the IEC 61000-4-x
parts must guarantee the same electric potential
EMC Standards. With regard to medium voltage
and low impedance.
switchgear, the plants where the VSC contac-
tors are to be installed must conform to the
IEC 60694:2002-01 and IEC 62271-1 ed. 1.0
Standards, to ensure adequate electromagnetic
immunity.
Pay great attention during earthing and cabling
operations of the auxiliary circuits. Follow the
procedures indicated. For further advice, please
contact the ABB Service office.
Earthing
A good connection to earth guarantees correct
operation of all the apparatus installed. However,
even earthing carried out correctly is not a
sufficient measure to ensure a good connection
between the VSC control module and earth. In
fact, since the control module of the contactor
is connected to the metallic base of the VSC
by means of a copper connection (Fig. 7), it is
always necessary to check that the connection
is intact.
Grounding
Fig. 7
19
Figs. 8a - 8b show an earthing operation carried out correctly.
Fig. 8a Fig. 8b
Figs. 8c - 8d show an earthing operation not carried out correctly and which, apart from being
dangerous, does not guarantee correct operation of the VSC.
Fig. 8c Fig. 8d
Cabling
Make short connections (maximum 1 metre) inside the medium voltage units and avoid positioning
them close to the medium voltage busbars.
All long connections must follow paths as close as possible to the metallic frame. The connections
must also be fitted with ferrite rings to suppress high frequency interference.
It is good practice to run the cables inside metallic pipes or ducts (earthed at several points) when
they are subject to or may be a cause of interference.
Where possible, the power supply and auxiliary circuit cables must be braided. Their length must
be calculated appropriately to prevent any surplus. In any case, any surplus parts of cables must
be wound separately and taken into the low voltage apparatus compartment. Always avoid placing
them in the vicinity of the medium voltage cables or close to cables which may generate interference
or disturbances, such as current or voltage transformer cables or power supply cables.
20
Figs. 8e - 8f show examples of cabling carried out correctly.
Fig. 8e Fig. 8f
The cross-section of the connection cables must not be less than 1.5 mm2.
Connection of the contactor auxiliary circuits must be made by means of the socket with terminal
box mounted on the front of the electronic card.
Outside, the wires must run through metallic pipes or ducts suitably earthed.
21
KM1-1 KM1-12
KM1-2 KM1-11
KM1-3 KM1-10
KM1-4 KM1-9
KM1-5 KM1-8
KM1-6 KM1-7
Fig. 9
Checks
After the above-mentioned operations, carry out the following checks:
– check that the connections do not exert any force on the terminals
– check tightness of the connections.
Fig. 10
22
5.6.2. Withdrawable contactors and Heating
enclosures
Refer to technical catalogue 1VCP000165 for
The withdrawable contactors are used in the rated capacity of the contactors, bearing in
the UniGear ZS1 type switchgear and in the mind that apparatus heating is affected by the
PowerCube modules. following variables:
Appropriately fixed together in the configura- • layout of the enclosures in the switchgear
tions defined by the customer, the enclosures designed by the customer;
build up medium voltage switchgear consisting • degree of protection (ventilation slats);
of various units. • current density of the power supply busbars
(busbar duct - branches);
Rules for designing the switchgear
• ambient temperature.
Arc proof For any needs, please contact ABB Service.
The ABB enclosures are supplied with a re-
inforced door, suitable for making arc proof Reference Standards
switchgear. The enclosures and contactors comply with the
following Standards:
• The reinforced enclosure alone
! – CEI 17/6 (1993) (where applicable)
cannot guarantee arc proofing of – IEC 62271-200 (2003) (where applicable)
the switchgear designed by the cus- – CEI EN 60694 (1997) (where applicable)
tomer. To guarantee this, some repre- – IEC 60694 (2002) (where applicable)
sentative configurations, selected by – IEC 60470 (2000) (where applicable)
the customer, must be subjected to
the tests according to the prescrip- Withdrawable VSC/P contactors
tions indicated in the IEC 62271-200
The contactors are used for rated voltages from
Standards.
7.2 to 12 kV, rated normal currents up to 400 A
• For UniGear ZS1 type switchgear, all
and fault levels up to 1000 MVA (with suitable
the door knurls must be tightened to
protection fuses in series with the contactor).
guarantee arc proofing.
The VSC/P contactor is made up of:
– a three-pole contactor with SCO or DCO func-
tion
Degree of protection
– mechanical signalling of open/closed
Limited to the front part, the ABB enclosures – two pairs of auxiliary contacts signalling open/
guarantee the following degree of protection: closed
• IP30 on the external housing; – multi-voltage feeder:
• IP20 inside the switchgear with the door • type 1: from 24 to 60 Vdc
open. • type 2: from 100 to 135 Vdc/Vac- 50-60 Hz
Special versions up to IP41. • type 3: from 220 to 250 Vdc/Vac- 50-60 Hz
– a truck on which the supporting structure of
The reinforced enclosure alone sup- the contactor is fixed, consisting of two sup-
!
plied by ABB cannot guarantee the ports, closed at the front by the protection with
degree of protection of the switchgear characteristics nameplate.
designed by the customer. It must In the top part of the protection there are
undergo the tests according to the strikers 30a and 30b (fig.20b - page 39) for
prescription indicated in the IEC62271- actuating the enclosure contacts to signal
200 Standards. protection connected/isolated.
The pin (34) for locking contactor racking-in
with the earthing switch closed on the en-
closure, comes out on the right side of the
truck.
23
The crosspiece for hooking up the contactor – input and output tulip isolating contacts;
to the enclosure for operation of the truck is – locks as per par. 5.6.2.1.;
mounted on the front of the truck; – three current-limiting fuses (supplied on re-
– two supports house the slide for actuation of quest) with high breaking capacity connected
the segregation shutters of the fixed medium in series to the contactor, with dimensions
voltage contacts of the enclosure and the according to:
locking slide of operation of the switch itself • DIN 43625 Standard with maximum cartridge
with the contactor in the connected position length e = 442 mm;
or during the isolation stage; • BS 2692 Standard with maximum centre
– when it is not inserted in the socket located fixing distance L = 553 mm;
on the enclosure, the plug connector for the – an impulse counter (supplied on request)
auxiliary circuits of the contactor must be which indicates the number of operations
hooked up to the stake; carried out by the contactor;
– mechanical signalling of open/closed; – manual emergency opening device and device
– fuseholder complete with connections for for opening when a fuse blows.
fuses;
Fig. 11a
80
35
43
39
44
50
42
34
24
5.6.2.1. Description of the locks for with- – Electric lock on racking-in and racking-out with
drawable contactors the door open (microswitch on the door) of the
– Electric lock which prevents the contactor be- enclosure connected in series with the locking
ing closed when the truck is not in the racked- electromagnet on the contactor truck.
in and isolated positions. – Key lock on earthing truck racking-in - with
– Mechanical lock which prevents the contactor the lock activated all the operations with the
being racked-in and out when it is closed and contactor are possible, but positioning the
closing of the contactor when the truck is not earthing truck in the isolated position starting
in the racked-in and isolated positions. from the racked-out position is not allowed.
– Electric lock which prevents closing of the – Mechanical lock which prevents racking-out
contactor when a fuse is missing or blown. of the connector of the auxiliaries when the
– Lock which prevents putting a contactor into contactor is racked-in and during racking-in
service in an enclosure preset for a circuit- and racking-out.
breaker (*). – Electro-mechanical lock on de-energisation
– Locking electromagnet on the contactor truck for the earthing switch, which when there is
which when there is no voltage, prevents no voltage prevents the earthing switch opera-
racking-in or racking-out. tions.
– Mechanical lock which prevents contactor – Electro-mechanical lock on the compartment
racking-in if the enclosure door is not closed door.
(requires the same interlock in the fixed
part).
– Mechanical interlock with earthing switch
placed on the enclosure - with earthing switch
5.7. Description of the closing and
closed the contactor cannot be racked-in and
opening operations
with the contactor racked-in or in intermediate
The contactor drive operates in two different
positions between racked-in and isolated, it is
ways as shown in Table 1.
not possible to close the earthing switch.
For the DCO version, further personalisation of
– Mechanical lock of the shutters when the
the apparatus can be made. In fact – the first of
contactor is racked-out. its kind – the V-Contact VSC contactor is fitted
– Key lock on contactor racking-in - it is only (on request) with an undervoltage function (UV)
possible to activate the lock and free the key with delays which can be set according to the
preventing contactor racking-in with the con- requirements of the installation.
tactor in the isolated position. For a more detailed description of the behaviour
– Key lock with earthing switch open - this can of the apparatus according to the version, see
only be activated with the earthing switch table 2.
open. The key can only be removed with the Supply the contactor with auxiliary voltage and
electric lock activated. operate it several times electrically. The con-
– Key lock with earthing switch closed - this tactor must carry out the opening and closing
operations correctly at between 85% and 110%
can only be activated with the contactor in the
of the rated auxiliary control voltage.
isolated position and with the earthing switch
closed. The key can only be removed with the
(*) This lock consists of
lock activated. some pins assembled in
– Preset for independent padlock locks of the the plugs of the auxiliary
circuits which, with a
shutters and in the closed and/or open posi- suitable code, prevent
tion. connection of the plug
in the enclosure socket.
The lock also foresees
compulsory application
of the locking magnet in
the truck.
25
TABLE 1
SCO (Single Command With this version the closing operation takes place by
Operated) supplying auxiliary energy to the UV (undervoltage) input
of the apparatus. On the other hand, the opening operation
takes place when the auxiliary energy is either voluntarily Not used Not used Used
cut off (by means of an auxiliary command) or involuntarily
(due to no auxiliary energy in the installation) at the UV
(undervoltage) input of the contactor.
DCO (Double Command With this version, the closing operation takes place by
Operated) supplying the input of the closing command of the apparatus Used if the
in an impulsive way. On the other hand, the opening Used Used undervoltage
operation takes place when the input of the opening function is
command of the contactor is supplied in an impulsive requested
way.
TABLE 2a
Automatic opening operation. • Drop in the auxiliary voltage supplied at the UV input (1) below the trip threshold pre-
scribed by the Standards
TABLE 2b
Closing operation. • Power supply, in an impulsive way, of the closing input (30 ms minimum impulse time).
Voluntary opening operation. • Power supply, in an impulsive way, of the opening input (30 ms minimum impulse time).
If the closing command persists at the same time, the contactor opens since the open-
ing command has priority. In this situation the contactor remains in the open position
due to the integrated anti-pumping function (until the opening command ceases).
(1) The opening operation can be instantaneous or delayed (adjusting the delay by means of the special selectors) by 0.5 - 1 - 2 - 3 - 4 - 5 s. It is adjusted to 0 s as the
default.
It is possible to preset the opening delay with Selector Delay Selector Delay
the group of selectors S1... S3 both in the SCO
SCO = 0 s S1-on
version and, when the undervoltage accessory S1-off S2-off S3-off DCO = (*) S2-off S3-off
2s
Fig. 12
26
5.8. Emergency opening operation a transmission made of insulating material of
suitable length which allows safe operation.
The contactor is provided with manual The transmission device is to be provided by
the customer.
emergency operation which must
For the withdrawable VSC/P contactors placed
be carried out by suitably qualified
in UniGear ZS1 type switchgear or PowerCube
personnel with in-depth knowledge of
modules, carry out the emergency operation
the apparatus and with voltage to the
with the compartment door closed. To carry out
apparatus compulsorily turned off on
the operation, work towards the opening on the
the power supply side.
compartment door using the special tool pro-
The following Standards must be taken
vided, fitted on the end with an 8 mm hexagonal
into particular consideration during
spanner. Apply a torque of 5 N with an operating
installation and service:
angle of about 30° clockwise. The point to oper-
– IEC60694/DIN VDE 0101 ate in is shown by the special plate located on
– VDE 0105: Operation of electrical the contactor shield (see fig. 13b).
plants
– DIN VDE 0141: Earthing systems for
electrical installations with rated For fixed contactors, if the operations
voltage higher than 1 kV are carried out with the medium volt-
– All the accident prevention regula- age protection “B” removed, pay great
tions, in force in the relative coun- attention to the moving parts.
tries. For withdrawable contactors, do not
To manually open the contactor, it is necessary remove the front shield to carry out the
to work on operating part A, consisting of a 17 emergency opening operation.
mm hexagonal-head bolt, working clockwise In any case, if auxiliary voltage is
with a torque of about 5 Nm and at an angle of present, take special care not to
about 30° (see fig. 13a). remove the protective shield of the
If the contactor (in the fixed version) is placed stored energy capacitor and not to
inside the switchgear, it is necessary to provide touch the capacitor itself in any way.
A
B
Fig. 13 a Fig. 13 b
27
6. Putting into service – check that no foreign bodies, such as bits of
packing, have got into the moving parts
6.1. General procedures
– check that the value of the power supply voltage
All the operations regarding putting of the circuits is between 85% and 110% of the
into service must be carried out by rated auxiliary voltage of the apparatus
ABB personnel or by suitably quali- – check that the contactor vacuum interrupter
fied customer personnel with in-depth has not been damaged due to accidental im-
knowledge of the apparatus and of the pacts. In case of doubt, carry out the check
installation. indicated in paragraph 7.2 Table 4.
– make sure that all the barriers and protective
Before putting the apparatus into service, carry shields are correctly installed
out the following operations as well as those – carry out the inspections indicated in table 3.
indicated in the table: On completion of the operations indicated,
– check that the voltage and current applied are check that everything is put back in its original
within the specified rated values position.
– check tightness of the power connections of
the fixed contactors and integrity of the isolat- The check can only be considered as
ing contacts of the withdrawable contactors passed if all the tests indicated have
– carefully clean the sheets and insulating parts had a positive outcome.
with brushes and clean dry cloths. Avoid using In the case of a negative check, do not
jets of compressed air put the apparatus into service and, if
– check the earthing connection of the fixed necessary, contact ABB Service.
contactors
TABLE 3
1mm
28
6.2. Racking the contactor in and out – open the compartment door;
– move the truck close to the switchgear (fig.
• Should operations be carried out
! 14a)
with the contactor racked-out of the – insert the hooking bracket (4) (fig. 14b - c),
switchgear, pay great attention to the and lock the wheels (3) (fig. 14a);
moving parts. – release the contactor from the truck by mov-
• The contactor must only be racked ing the two handles (5) (fig. 14d) at the same
into the unit in the open position. time towards the median axis of the contac-
Racking-in and racking-out must be tor and simultaneously progressively push
gradual to avoid shocks which might towards the back of the module by means of
deform the mechanical interlocks. the contactor, until the contactor locks with
the handles (5) (fig. 14e) which click sideways
Operations in ABB enclosure inserting themselves into the slots (6) (fig.
14b);
In the instructions given below, an ABB circuit-
– unlock the wheels (3) (fig. 14a), lift the hooking
breaker is shown.
bracket (4) (fig. 14f) and move the truck away
The instructions are, in any case, also valid for
from the switchgear.
V-Contact VSC/P contactors.
Make sure that the handles have clicked
a) Racking-in operation !
sideways (horizontal locks of the truck
(1) Passing from contactor racked-out to the racked into the enclosure).
“isolated” position
– lift the apparatus (2) (fig. 14a) and rest it on
the handling truck (1) (fig. 14a) following the
instructions given in par. 3.2. “Handling the
contactor with a crane”;
4 6
1
4
29
5 5 5
5 4
(2) Passing from the “isolated” to the “isolated Make sure that the lever (3) (fig. 16) is
!
for test” position (connection of the auxilia- fully pressed against the connector
ries). (1) (fig. 16).
– Insert and hook up the mobile connector (1)
(fig. 16) in the fixed socket of the enclosure
(2) (fig. 15).
2 1 3
Fig. 15 Fig. 16
(3) Passing from the “isolated for test” to the • the key locks (7-8-9), if foreseen, are de-
“racked-in” position (with earthing switch activated;
closed) (fig. 17). – insert the operating lever (13) in the seat of
– close the compartment door (1) by pushing the earthing switch, making the protrusion (12)
the handle downwards; coincide with one of the two slots (11);
– close the feeder compartment door (2) by – open the earthing switch by turning the operat-
pushing the handle downwards; ing lever anti-clockwise (13);
– check that: – remove the operating lever (13) from the earth-
• the locking magnet of the earthing switch (if ing switch seat;
provided) is supplied;
30
Check that the feeder compartment – through the inspection window (4) check that
! door (2) is locked. the contactor is open (indicator in position
“O”);
– close the shutter of the operating seat of the
– fully insert the racking-in/out lever of the truck
ST turning the actuator (10) clockwise. This
(2) fig. 18 in the corresponding coupling (5)
operation releases the contactor and a pre-
and turn it anti-clockwise until the contactor
vention lock against insertion of the operating
stops;
lever into the earthing switch is activated;
– open the shutter of the ST operating seat by
– check that the locking magnet on the contac-
turning the actuator (10) anti-clockwise;
tor truck (if provided) is supplied with power
– insert the operating lever (13) in the seat of
and check that the key lock on racking-in (if
the earthing switch, making the protrusion (12)
provided) is de-activated;
coincide with one of the two slots (11);
– fully insert the truck racking-in lever (2) (fig.
– close the earthing switch by turning the operat-
18) in the corresponding coupling (5) and turn
ing lever clockwise;
it clockwise until the contactor is completely
– remove the operating lever (13) from the earth-
racked-in;
ing switch seat;
– through the inspection window (4) check that
– check that the position indicator of the earth-
the contactor is racked-in.
ing switch indicates that it is closed “I” on the
operating seat (14 - fig. 17b) and through the
b) Racking-out operation (only with contac-
inspection window (6);
tor open)
– open the contactor compartment door (1) by
(1) Passing from the “racked-in” position to the
pulling the handle upwards.
“isolated for test” position (with contactor
open) (fig. 17a)
13
9 7 10 11
12
5
14
6
2
8 11
Fig. 17a
Fig. 17b
31
(2) Passing from the “isolated for test” to the – move the two handles (5) (fig. 14d) at the same
“isolated” position (disconnection of the time towards the median axis of the contactor,
auxiliaries) and simultaneously pull the contactor progres-
– release the mobile connector (1) (fig. 16) and sively towards the outside on the truck by
remove it from the fixed socket of the enclo- means of the handles;
sure (2) (fig. 15); – let go of the handles and continue extraction
until the contactor locks with the handles (fig.
(3) Passing from the “isolated” to the “racked-out” 14a) which click sideways locking the contac-
position tor on the truck.
– bring the truck close to the switchgear; – release the wheels (3) (fig. 14a);
– insert the hooking bracket (4) (fig. 14b - c) and – lift the hooking bracket (4) (fig. 14f) and move
lock the wheels (3) (fig. 14a); the truck away from the switchgear.
1 2 3
Caption
1 Operating lever of the earthing switches
2 Contactor racking-in/out lever
3 Tool for manual emergency opening operation
Fig. 18
32
6.4. Contactors with motorised – Insert the manual racking-in lever (2 - Fig. 18)
withdrawable truck in the special coupling (B - Fig. 13b).
Carry out the racking-in/out test of the motorised The torque needed to carry out truck handling
truck in the same was as for a manual truck, is < 25 Nm.
following the instructions below: Checks:
– Rack the contactor into the switchgear in the a) clockwise rotation of the motor during
open and isolated position, with the motor circuit-breaker racking-in.
power supply circuit de-energised and the b) anti-clockwise rotation of the motor during
enclosure door closed. circuit-breaker racking-out.
– Supply the truck motor with power supply. – Remove the manual lever (2 - Fig. 18) from
– Activate the command for the electrical the coupling (B - Fig. 13b)
racking-in operation. When racking-in has
Note
been done, check correct changeover of the
By means of the chain transmission, truck handling carried
relative auxiliary contact. out with the manual lever causes the rotation of the motor
rotor which, behaving like a generator, can cause reversal
– Afterwards, activate the command for the elec- of voltage at the connection terminals. This can damage
trical racking-out operation. When racking-in the permanent magnet of the motor, therefore all the truck
racking-in and racking-out operations carried out with the
has been done, check correct changeover of manual lever must be done with the voltage on the motor
the relative auxiliary contact. circuit turned off.
33
7. Maintenance It is good practice to keep a maintenance card
and a service book where all the operations car-
Maintenance operations are aimed at ensuring ried out can be noted down in detail, together
trouble-free operation of the apparatus for the with the date, description of the anomaly and
longest possible time. The following operations the references of data needed to identify the
must be carried out in accordance with the IEC apparatus, etc. (see chapter 2).
61208/DIN 31051 Standards: Experience gained in use of the apparatus will
Inspection: Assessment of the actual condi- allow the optimal time intervals for interventions
tions to be established. In any case, inspection of the
Servicing: Measures to be taken to maintain apparatus not more than one year after it has
the specified conditions been put into service is recommended.
Repairs: Measures to be taken to restore In case of need and for further details, please
the specified conditions. refer to what is prescribed in article 10.4.2 of
the Standard (CEI EN 60694).
7.1. General
In any case, for any problems, please do not
• Maintenance must be carried out
! hesitate to contact us.
by ABB personnel or by suitably
qualified customer personnel with
in-depth knowledge of the apparatus 7.2. Inspection
and of the installation (IEC 60694, – Carry out regular inspections to check that the
CEI EN 60694 par. 10.4.2.). interruption devices are in good condition.
Should maintenance be carried – The checks must include a visual inspection
out by the customer’s personnel, to find any contamination, traces of corrosion
responsibility for the interventions or electrical discharge phenomena (accord-
lies with the customer. ing to what is prescribed in table 4 (see next
• Before carrying out any maintenance page).
operation, always check that the ap- – When there are unusual service conditions
paratus is in the open position. (including adverse climatic conditions) and/
• Check that the medium voltage and or in the case of environmental pollution (e.g.
auxiliary power supply are turned heavy contamination or an atmosphere with
off. Maintenance of the apparatus aggressive agents), the frequency of inspec-
must only be carried out with the tions must be increased.
contactor without power supply and – Visual examination of the main contacts. The
racked out of the enclosure compart- contact areas must be cleaned if there are
ment and with the capacitor suitably signs of overheating (discoloured surface)
discharged. (also see the paragraph on “Repairs”).
Notes
If any anomalous conditions are found, appropri-
The following rules must be respected for all maintenance
operations: ate maintenance measures must be taken (see
– the relative specifications indicated in the “Standards the “Servicing” paragraph).
and specifications” chapter;
– the regulations for safety in the workplace indicated in
the “Putting into service and running” chapter;
– the regulations and specifications in the country of instal-
lation.
34
TABLE 4
1 Insulating parts. 1 year or Visual inspection of the insulating parts. The insulating parts must be
50,000 operations. free of any accumulation of dust, humidity, dirt (clean), cracks, traces
of surface discharges or damage.
2 Structure. 1 year or Visual inspection of the structure and mechanisms. The components
50,000 operations. must be free of any deformation, accumulation of dust, dirt or dam-
age. The screws, nuts and bolts must be correctly tightened. Avoid
touching the ceramic surface.
3 Interrupter. 1 year or Check that the interrupter is free of accumulation of dust, dirt (clean),
50,000 operations. cracks (replace), traces of surface discharges or damage.
In case of accidental Carry out a voltage test with the contacts open at 15 kV - 50 Hz for one
impacts. minute. If there is a discharge during the test, the interrupter must be
replaced because this type of phenomenon corresponds to deteriora-
tion in the degree of vacuum. In case of need, contact ABB Service.
Refer to fig. 19. The contact material vaporises from the surfaces
4 Interrupter contacts. 1 year or during each interruption and condenses elsewhere inside the vacuum
50,000 interruptions at interrupter. This is a normal process, and is foreseen by the overrun,
the rated current. or by the wear tolerance.
As the contacts wear, the overrun distance “M” decreases. When dis-
tance “M”, of any pole, goes below 0.5 mm with the contactor in the
closed position, all the sub-assemblies must be replaced.
Use a fork-shaped gauge 0.5 mm thick to carry out this measure-
ment.
Caution! Never attempt to adjust the nuts of the vacuum inter-
rupters for any reason whatsoever.
The overrun distance must be checked, but not adjusted.
5 Auxiliary contacts. 1 year or Check correct operation and the signals.Check that there are no burnt
50,000 operations. or worn contacts (replace).
6 Auxiliary circuit conduc- 1 year or Check whether any cabling straps are loose or broken and check con-
tors. 50,000 operations. nection tightness.Examine all the wire or cable connections to make
sure that none of them are loose and that there is no overheating.
7 Visual inspection of the 5 years or The isolating contacts must be free of any deformation or erosion.
isolating contacts (with- 5.000 operations. Lubricate the contact elements with 5RX Moly type grease.
drawable contactors)
35
M
VSC 7 VSC 12
Fig. 19
36
7.3. Servicing
Carry out the checks described below.
Item to be Interval Operation to be carried out
serviced
1 Contactor. 2 years or Carry out five mechanical closing and opening operations. The
100,000 operations. contactor must operate regularly without stopping in intermediate
positions.
3 Power connections. 2 years or Check tightness: M8 bolt = 19 Nm; M10 bolt = 33 Nm.
100,000 operations. Check there are no traces of overheating or oxidation.
37
Enclosures 7.6. Instructions for dismantling and
External evidence of deformation of the en-
replacing fuses
closure is usually indicative of damage inside 7.6.1. General
it. Extensive damage will require replacement All the operations described below
!
of the enclosure parts and of the apparatus must be carried out by suitably
contained in it. qualified personnel with in-depth
knowledge of the apparatus.
Terminals and internal conductors Do not rack the contactor out unless
Replace the damaged parts which show discol- the enclosure is securely fixed in the
ouration, melting or damage caused by electric switchgear or to a stable base.
arcs. Pay special attention to the moving parts. Check that the contactor is open
Carry out the “Checking” procedures indicated before proceeding with isolation and
in par. 6. of this manual before putting the ap- its racking-out from the enclosure.
paratus back into service. Check that the contactor is open
before proceeding with replacement
of the fuses.
7.5. Repairs The withdrawable contactor is not
Replacement with spare parts and accessories preset for housing fuses of CMF/BS
must only be carried out by ABB personnel or and CEF/BS type.
by suitably qualified personnel with appropriate
training. The fuseholder is preset for installation of fuses
All the power supply sources must be turned off with the dimensions and average type of striker
and the capacitor must be discharged. according to DIN 43625 (1983) and BS 2692
Always work with the contactor open, with the (1975) Standards and with electrical characteris-
work area insulated and made safe. tics according to IEC 282-1 (1974) Standards.
70-71
Fig. 20a
38
The fuseholder is always fitted with an automatic
2
opening device for a fuse blowing. This device
prevents contactor closing when even a single
fuse is missing.
69
Fig. 20d
30a 30b
1
14
Fig. 20b Fig. 20e
39
7.7. Replacement of the contactor fuses
40
50
50
49
49
41
a) Mounting the adapters (fig. 22a) b) Mounting the fuses (fig. 22b)
The fuseholder (32) (fig. 22b) is preset to take Mount the fuses or the adapter (preassembled
fuses with fixing centre distance of 553 mm. For as indicated in par. a) with the striker, (indicated
smaller sizes, three adapters are needed, as by the arrow) facing the opposite side to the one
indicated below: of the contactor tulips and fix them by means of
– adapter (51) for fuses with fixing centre dis- the screws (56) and the spring washers (57).
tance l = 235 mm
– adapter (52) for fuses with fixing centre dis- c) Dismantling the fuses
tance l = 305 mm To dismantle the fuses and relative adapters,
– adapter (53) for fuses with fixing centre dis- proceed in reverse order to par. b) and a).
tance l = 454 mm.
54 61
51
52
53 32
55
Striker side
58
42
7.8. Mounting and dismantling the 7.9. Putting the contactor back into
short-circuit busbar (fig. 23) service
a) Mounting 7.9.1. Mounting the shield and insulating
Mount the busbar with the feeler pin (60) on the guard (fig. 17)
opposite side to that of the tulips and fix it with Reposition the protection (1) (fig. 20b), repeat-
the screws (61). ing the operations indicated in par. 7.6.2. in
reverse order.
b) Dismantling Remount the shield. Check that the impulse
To dismantle, proceed in reverse order. counter (14) (fig. 20c) inserts itself into the spe-
cial seat (69) (fig. 20d) and fix the shield with
The same instructions are given in the Kit sheet the screws (70) and DIN washers (71) (fig.20a).
put in the short-circuit busbar packing.
7.9.2. Checking apparatus functions
Rack the contactor into the enclosure, working
as indicated in par. 6.
In the “isolated for test” position, check the
correctness and functionality of the contactor
“open/closed” signalling by carrying out a few
operations.
61
61
60
Fig. 23
43
8. Spare parts and accessories 8.1. List of spare parts
– Vacuum interrupter assembly (replacement to
To order contactor spare parts/accessories,
be carried out by ABB)
refer to technical catalogue 1VCP000165 and
– Electronic feeder
always state the following:
– Auxiliary contacts (5 normally open and/or 5
– type of contactor
normally closed)
– rated voltage of the contactor
– Capacitor
– rated normal current of the contactor
– Interfacing shaft (only fixed contactors)
– serial number of the contactor
– 12 kV insulation shields (only fixed contac-
– rated voltage and frequency of any electrical
tors)
spare parts.
– Drive assembly (replacement to be carried out
For availability and to order spare parts, please
by ABB).
contact ABB Service.
– Operation counter
– Fuses
– Adapters for fuses
– Fuseholder (replacement to be carried out by
ABB)
– Isolating contacts
– Locking magnet in the truck
– Microswitches.
44
For more information please contact:
ABB AG
Calor Emag Medium Voltage Products
Oberhausener Strasse 33 Petzower Strasse 8
D-40472 Ratingen D-14542 Glindow
Phone: +49(0)2102/12-1230, Fax: +49(0)2102/12-1916
E-mail: calor.info@de.abb.com
www.abb.com
The data and illustrations are not binding. We reserve the right to make
changes without notice in the course of technical development of the
product.