I. POWER TURBINE
Note: PT speed = 5900 RPM to 6100 RPM (6.1KHZ) and Ref Speed = 6159 RPM
Beyond or excess that P.T Speed the 1X Amplitude will not read.
Note: G.G speed = 6300 RPM to 6700 RPM (6.7KHZ) and Ref Speed = 6800 RPM
Note: G.G Speed should be kept approximately closes to Ref speed but not over.
III. GG Casing
Range:
Note: G.G speed = 6300 RPM to 6700 RPM (6.7KHZ) and Ref Speed = 6800 RPM
Note: G.G Speed should be kept approximately closes to Ref speed but not over.
Important:
It will not trigger the Relay Module Rack (i.e. Alarm and trip) to MarkVie once the bypass LED
RED is always on.
Bypass LED permanent RED ON on this following condition.
GG speed is lower than reference.
Zero speed for PT
To remove the Bypass LED RED ON need to provide temporary speed.
GG Speed is less 8.1% from Reference GG Speed.
Actual PT Speed = Reference PT speed