Sie sind auf Seite 1von 2

Protection Automation Control

MUX-2M/64
Communication Interface

7KH 08;0. LV D JURXS RI FRPPXQLFDWLRQ LQWHUIDFHV $ UHOD\ LV FRQQHFWHG WR WKH 08;0. ZLWK RSWLFDO ILEHU
connecting relays with pilot protection and digital communication based on C37.94 protocol. The MUX-2M interface is connected
multiplexers. For NR Electric PCS series products, the relays to the SDH multiplexer with twisted-wire based on G.703
with pilot protection are PCS-902 line distance relay and PCS- SURWRFRO (VSHFLDOO\ WKH 08;. LQWHUIDFH DGRSWV D SXOVH
931 line differential relay. code modulation (PCM) digital communication device with
twisted-wire based on G.703 protocol between itself and the
SDH multiplexer to convert 64kbit/s signal to 2Mbit/s.

Type Optical interface Electrical interface Rate Codec Power

1B/1B
Single-mode, FC, 1B/2B
MUX-2MA Balanced twisted-wire .ESV
9/125um 1B/4B
C37.94

1B/1B
Multimode, ST, 1B/2B
MUX-2MB Balanced twisted-wire .ESV DC: 18V~373V
62.5/125um 1B/4B
AC: 88V~264V
C37.94

Single-mode, FC,
08;.$ Balanced twisted-wire .ESV 1B/4B
9/125um

Multimode, ST,
08;.% Balanced twisted-wire .ESV 1B/4B
62.5/125um

144
www.nrec.com/en

M N

~ 52 52 ~

Substation A Substation B

Co-directional Co-direct ional


Interface Interface
Optical Twisted SDH SDH Twist ed Optical
Relay MUX-2M Optical-fiber MUX-2M Relay
fiber Wire Multiplexer Multiplexer Wire fiber

Other signals Other signals


Relay cubicle Comm. Room Comm. Room Relay cubicle

Figure 1 MUX-2M application

M N

~ 52 52 ~

Substation A Substation B

Co-directional Co-directional Co-directional Co-directional


Interface Interface Interface Interface
Optical Twist ed PCM Twist ed SDH SDH Twisted PCM Twisted Optical
Relay MUX-64K Optical-fiber MUX-64K Relay
fiber Wire Multiplexer Wire Multiplexer Multiplexer Wire Multiplexer Wire fiber

Other signals Other signals Other signals Other signals


Relay cubicle Comm. Room Comm. Room Relay cubicle

Figure 2 MUX-64K application

Automation System

145

Das könnte Ihnen auch gefallen