Beruflich Dokumente
Kultur Dokumente
Room
Recirculated air
Exhaust air Return air
section.
For information onbalanced ventilationseeVENTILATION
Cooling Coil
Pre-filter Supply fan
Heater Battery
Bag filter(s)
Pre-heater
Dampers
Humidifier Room
Recirculated
air
Exhaust air Return air
The photograph below shows a typical air handling unit with handles on
the doors for access to equipment.
2.0 Room Air Conditioning Units
These units use refrigerant to transfer cooling effect into rooms.
Room air conditioning units fall into two main categories:
1. Split type
2. Window/wall units.
Dust filter
Cabinet
T Room Air
Thermostat
Fan coil units may be looked upon as beingsmall air handling units
located in rooms and they can be piped with chilled water for cooling
and low temperature hot water (LTHW) for heating if necessary.
Each system has its own advantages and the following is a summary of
some of the main advantages and disadvantages.
1. Cheaperto install.
2. Individualroom control.
3. Works well where rooms have individual requirements.
4. No long runs of ductwork.
5. Can be used toheat as well as cool if a reversing valve is fitted.
Fan coil units are similar is some respects to Room Air Conditioners.
Where;
Volume flow rate (m 3/s) = mass flow rate (kg/s) / density of air (kg/m 3
)
Supply Air Rate (AC/h) = Volume Flow Rate (m3/h) / Room Volume (m3)
6. Check out the recommended air flow rate from CIBSE Guide B2
(Ventilation and Air Conditioning) Section 3 - Requirements.
Use the higher value of air change rate for design purposes.
Example 1
Determine the supply, fresh air and recirculation air flow rates for the Sports Centre
(Fitness Suite No.1) shown below.
See Assignments section – Drawings.
The room is to be fully air conditioned.
Air Handling Unit
(AHU) in roof space
above.
44 m
DATA
Occupancy = 80 people
Room volume = 3740 m 3.
Room temperature = 18oC from table 3.19 CIBSE guide.
Sensible heat gain = 70 kW from calculations (not shown)
See Heat Gains section of these notes for further details.
Supply air temp. = 13oC from psychrometric chart (not shown)
See Psychrometrics section of these notes for further details.
Supply air density = 1.225 kg/m 3.
See Science section – Properties of air – density at 13 oC and 50%
Volume flow rate (m 3/s) = mass flow rate (kg/s) / density of air (kg/m 3)
= 13.93 / 1.225 = 11.37 m 3/s
Volume flow rate (m 3/h) = 3
Volume flow rate (m /s) x 3600
= 11.37 m 3/s x 3600 = 40,932 m 3/h
Supply Air Rate (AC/h) = Volume Flow Rate (m 3/h) / Room Volume (m 3)
= 40,932 m 3/h / 3740
= 10.9 AC/h
Section 3.2.1.3 Body odour (CIBSE guide B2) gives the following information;
Since the level of activity is higher than sedentary in the Fitness Room, we will
adopt a fresh air rate of 24 l/s per person.
Dampers
Recirc.10.1 AC/h Room
air 10.55 m3/s
Return
1.9 AC/h Exhaust
air 12.0 AC/h
1.92 m3/s air
12.47 m3/s
Schematic Diagram Of
Central Plant Air Conditioning System
The heat gain through the glass windows is divided two into parts since
there is a heat gain due to
temperature differencebetween outside and
inside and another gain due to
solar radiationshining through windows.
Heat gains through solid ground floors are minimal and can be
neglected.
This is the Solar Gain due to differences between inside and outside
temperatures. In very warm countries this can be quite significant.
This gain only applies to materials of negligible thermal capacity i.e.
glass.
Qg = Ag . Ug (to- tr)
eqn. 1
Where;
Qg = Sensible heat gain through glass (W)
Ag = 2)
Surface area of glass (m
Ug = 'U' value for glass (W/m2 oC)
(see CIBSE guide A (2006) Table 3.23 to 3.32).
to = outside air temperature o( C). Can be obtained from
CIBSE Guide J (2002) - Tables 5.36 to 5.38 for various months and times in the day.
tr = room air temperature (oC)
Qsg = Fc . Fs . qsg . Ag
eqn. 2
Shading factors (F
s)
Internal gains can account for most heat gain in buildings in the U.K.
These gains are from occupants, lights, equipment and machinery, as
detailed below.
OCCUPANTS - Sensible and latent heat gains can be obtained CIBSE
from
Guide A (2006) - Table 6.3.
Typical gains are shown below.
Sensible Latent
Heat Heat
Conditions Typical building
Gain Gain
(Watts) (Watts)
Seated very light work Offices, hotels, apartments 70 45
Moderate office work Offices, hotels, apartments 75 55
Standing, light work;
Department store, retail store 75 55
walking
Walking standing Bank 75 70
Sedentary work Restaurant 80 80
Light bench work Factory 80 140
Athletics Gymnasium 210 315
This is the unsteady-state heat flow through a wall due to the varying
intensity of solar radiation on the outer surface.
the value of the outside air temperature which would, in the absence of
all radiation exchanges, give the same rate of heat flow into the outer
surface of the wall as the actual combination of temperature difference
and radiation exchanges.
SOL-AIR TEMP,
t eo = t a + ( . I . cos a . cos n + I s )
hso
eqn. 4.1
where
t eo = sol-air temperature o
( C)
ta = outside air temperature o( C)
= absorption coefficient of surface
I = intensity of direct solar radiation on a surface at right
2
angles to the rays of the sun. (W/m)
a = solar altitude (degrees)
n = wall-solar azimuth angle (degrees)
Is = intensity of scattered radiation normal to a surface
2
(W/m )
2
hso = external surface heat transfer coefficient (W/moC)
The thermal capacity will not affect the daily mean solar gainbut will
affect the solar gain at a particular time.
The particular time of a solar gain is normally the time of the
maximum gain.
The heat gain arrives at the inside of a thick wall some time after the sun
hits the outside surface of the wall.
This time lag is.
Q = A . U ( et m - tr)
eqn. 4.2
eqn. 4.3
eqn. 4.4
The heat gain through a roof uses the same equation as for a wall as
shown below.
Q +Roof = A U [( t em - t r ) + f ( t eo - t em )]
eqn. 5
eqn. 6
or
Ventilation or fresh air supply loads can be added to either the room
central plant loads but should only be accounted for once.
+ Qint. 3. Internal
eqn. 7
Qli = 0.8 . n . V ( m
so –msr )
Where;
DATA:
Occupants = 100
Infiltration = 0.5 air changes per hour
Building classification = lightweight,
Building response = fast.
External wall 'U' value = 0.45 W/m2oC, internal insulation,
neglect time lag through wall.
External wall colour = light.
External wall decrement factor f = 0.65
Glass type & 'U' value = clear 6mm, double glazing, U
= 2.80 W/m2oC
Window blinds = internal blind..
Lighting = 30 Watts / m2 floor area
Heat gain from machinery and equipment = 4000 Watts
NOTE: It should be noted that this total heat gain is used to size central
plant items such as Chillers, Condensers and Cooling Towers.
Cooling coils are sized usually with a pschrometric chart.
Answer
Areas:
where:
where,
Q = heat gain through wall at time q+f (Watts)
2
A = area of wall facing South (m )
U = overall thermal transmittance given in question as 0.45
2o
W/m C.
tem = 24 hour mean sol-air temperature (oC) CIBSE Guide J
(2002) - Table 5.36 at 12.30 hrs, light wall facing South –
22.6oC
tr = constant dry resultant temperature (oC). Room dry bulb
of 21oC is given.
f = decrement factor for wall is given as 0.65.
teo = sol-air temperature when Tabulated cooling load (qsg) is
at 13.00 hrs. CIBSE Guide J (2002) - Table 5.36, light wall, South facing gives 38.8oC.
DATA:
Occupants = 80
Lighting = 35 Watts / m2 floor area
Infiltration = 0.4 air changes per hour
Building classification = lightweight with fast response.
External wall surface texture= dark.
External wall thickness = 300mm, internal insulation, decrement
factor is 0.27, neglect time lag through wall.
Blinds = Internal Heat gain from machinery and
equipment = 3000 Watts
External Walls - ‘U’ value = 0.35 W/m2oC.
Answer
Areas:
Gains:
1. Sensible transmission through glass Qg = Ag Ug (to - tr)
Qg = 20.4 x 2.6 (25.4 – 21)
Qg = 233.4 Watts
2. Solar Gain through glass Qsg = Fc Fs qsg Ag
where:
where,
Q = heat gain through wall at time (Watts)
2
A = area of wall facing South West (m )
2o
U = overall thermal transmittance given in question as 0.35 W/m C.
tem = 24 hour mean sol-air temperature (oC) CIBSE Guide J (2002) –
Table 5.36 at 13.00 hrs, dark wall facing South West– 26.7oC
tr = constant dry resultant temperature (oC). Room dry bulb of 21oC
is given.
f = decrement factor for wall is given as 0.27.
teo = sol-air temperature when Tabulated cooling load (qsg) is at
13.00 hrs. CIBSE Guide J (2002) - Table 5.36, dark wall, South Westfacing gives 47.1oC.
(dark façade) Q Wall = 43.8 x 0.35 [( 26.7 – 21) + 0.27 ( 47.1 – 26.7)]
Q Wall = 15.33 [ 5.7 + 5.51 ]
Q Wall = 171.9 Watts
The heat gain in the previous example was 88.8 W/m2 floor area and the
total was 27,377 Watts .
The heat gain in this example is 86.4 W/m2 floor area and the total is
24,884.5 Watts.
The value of sensible heat gain can be used in a psychrometic chart to
determine the cooling coil size in an Air Handling Unit (AHU).
Example 3
The Restaurant shown below is to be maintained at a constant environmental temperature of 22oC for a plant operation
of 12 hours per day.
The Restaurant area is on the ground floor of an Single storey building located at 51.7oN.
The internal construction is lightweight partitions, concrete hollow slab floors and suspended ceilings.
Calculate the maximum sensible cooling load in the Restaurant area in July.
DATA:
Occupants = 70
Lighting = 22 Watts / m2 floor area
Infiltration = 1.0 air changes per hour
Outside air temperature (to) = 28oC.
Building classification = lightweight, fast response building.
External wall surface texture = dark.
External wall - use information from CIBSE guide A (2006) section 8(e) in Table 3.49, 105mm Brick,
internal 50mm EPS insulation, 100mm lightweight aggregate concrete block, 13mm
dense plaster, cavity wall.
Windows - Double glazed internal shade, clear 6mm glass, light slatted blinds, intermittent
shading.
Roof - use information from CIBSE guide A (2006) section 2(d) in Table 3.50.
Heat gain from equipment = 2000 Watts
7.7 m
Male Female
Toilet Toilet Cold
Store
9.5 m
Kitchen
Lobby
Restaurant
Reception
Prep.
Room
Entrance
PLAN
Scale: 1:100
All Restaurant Windows Height of ceiling at Height of wall to eaves
1.4 m wide x 2.0 m high, ridge = 5.9 metres. = 3.0 metres.
South
double glazed.
South
Answer
Areas:
Area of wall facing South = 14.0 m x 3.0 m high = 42 m2 less glass = 42 - 14 = 28.0 m2.
Gains:
4. External wall
Find information from CIBSE Guide A (2006) Table A3.49.
Wall is type 8(e) and the decrement factor is 0.42, time lag is 8.8 hours, ‘U’ value 0.52 W/m2oC.
If the maximum solar heat gain is at 12.30 pm and the time lag is 8.8 hours then the time of the relevant sol air temperature is;
12.50 - 8.8 = 3.7 say is at 4.00 am.
teo = sol-air temperature when Tabulated cooling load (qsg) is at 04.00 hrs. CIBSE Guide J (2002) - Table 5.36, dark wall, South
facing gives 10.4 oC.
A correction can be applied to this since we are using outside air temperature (to) of 28oC.
The tabulated maximum outside air temperature (to) from CIBSE Guide J (2002) - Table 5.36 page A6-127 (July 4th) ocurrs at 16.00
hrs. and is 25.40C.
The difference in outside temperatures is; 28 – 25.4 = 2.6 oC.
The actual sol air temperature (teo) to use in this example is; 2.6 oC + 10.4 oC = 12.8 oC
The heating elements are normally manufactured with copper tubes, with the
extended surfaces, or fins, being of aluminium or sometimes copper. The most
common type of finning arrangements are the spirally wound and the rectangular
fin.
Heating coils may be used with hot water or steam as the heat transfer media
whilst frost pre-heaters usually have electric heating elements. Cooling coils are
classified as being either of the water or the direct expansion type depending on
the media flowing through the tubes.
A heating coil is shown below.
In water coils, hot or chilled water or brine circulates through the tubes of the
coil either emitting or absorbing sensible heat as the air flows over the fins
attached to the outside surfaces. Usually the flow of water and air are in
opposite directions to each other, this being known as counter-flow heat
exchanger. This configuration gives maximum heat transfer.
Refrigeration
pipework
Evaporator
DX coil as
Air On evaporator
Latent heat is absorbed by the air stream from the refrigerant as the refrigerant
evaporates. With this type of coil, as with steam, there is no distinction made
between parallel and counter-flow since the surface temperature is more uniform
owing to the refrigerant in the tubes boiling at a constant temperature.
When direct expansion coils are used they become the evaporator of the
refrigeration cycle, and may be termed either ‘dry’ or ‘flooded’. In the ‘dry’
DX coil only a sufficient quantity of refrigerant is introduced to operate in the
predominantly vapour state. In the ‘flooded’ DX coil most of the coil is filled
with liquid refrigerant and although this is more efficient, it is not used so much
in air-conditioning since the additional refrigerant is expensive.
Evaporator coils come in a variety of shapes and sizes, depending on the type of
installation, the amount of cooling capacity needed, and the manufacturer. They
are constructed of aluminium finned copper tubing. The copper tubing runs
perpendicular to the aluminium fins, making U-turns back and forth until the
desired coil size is achieved. Added cooling capacity without an increase in
length and width is accomplished by adding more rows of copper tubing.
All evaporator coils must have a drain pan to collect the water that condenses as
the air flowing across the coil cools. The water can drain away by gravity or be
pumped away.
The cooling effect that takes place inside the coil requires a pressure drop in the
refrigerant. This drop can be accomplished in a number of ways: capillary tube,
piston or orifice, or thermostatic expansion valve.
A capillary tube is a thin copper tube of predetermined length into which the
compressed liquid refrigerant is pumped. The length of the tubing causes the
pressure drop and subsequent cooling effect of the refrigerant.
A piston or orifice blocks the flow of refrigerant and forces it through a tiny
hole, creating the needed pressure drop.
Water Removal
Moisture in air can condense in the air stream or when the air impinges upon a
solid cool surface. This can happen at sharp bends where water collects in a
puddle at the lower surface on the ductwork. A drain can be fitted on vertical
sections of ductwork to remove water that has collected. Ducts can also be
insulated in areas where condensing moisture is likely to occur.
Q = U × A × LMTD
Where,
Where;
One way to increase LMTD is to supply the coil with colder water.
System designers can do little to affect thermal conductance, but they can alter
the film coefficients. Increasing the rate of airflow reduces heat-transfer
resistance on the air side of the cooling coil. Likewise, increasing the water
velocity reduces the waterside resistance to heat transfer.
Fin geometry can improve the overall heat-transfer coefficient, too, by lessening
the airside film coefficient. Like velocity, fin geometry can be specified as part of
the design of the HVAC system. For comfort-cooling applications, coil fins are
usually stamped into waveforms resembling corrugated cardboard. These
waveforms create turbulence in the passing air stream, which lessens the
resistance to heat transfer. More exaggerated waveforms produce more
turbulence.
Turbulent water flow, like turbulent airflow, also reduces resistance to heat
transfer. And, like fin geometry, it can become an important criterion for coil
selection. Waterside turbulence can be created by metal ribbons or helical wires
inside the tubes. Called turbulators, these devices create eddies as the water
flows across them.
The third determinant of heat transfer is the coil’s surface area. Typically, fin
spacing for comfort heating or cooling ranges from 24 to 50 fins per metre.
Spacing the fins closer together multiplies the surface area by permitting more
fins per linear unit. Although the airside pressure drop may increase, adding fins
extends the available surface area without affecting the overall size of the coil.
Adding rows of tubes also increases the heat-transfer surface area. Most coils are
constructed with same-end connections, so rows are usually added in pairs. The
weight and cost of the coil increase accordingly, but the airside pressure drop
may not. (Wider fin spacing often accompanies the decision to add rows.)
The best way to extend the surface area for heat transfer is to decrease the face
velocity of the coil, that is, face area relative to airflow:
Face velocity can be reduced in one of two ways: by increasing the size of the
coil or (paradoxically) by reducing the required airflow. Selecting a physically
larger coil increases the initial investment in the coil and the air handler, and may
also enlarge the air-handler footprint ... seldom desirable outcomes. So, how can
we reduce the required airflow without sacrificing coil capacity?
To compensate for the negative effects on coil performance that accompany less
airflow, we must find a way to increase U (heat-transfer coefficient) and/or A
(surface area). In other words, we must select a cooling coil with better-than-
average heat-transfer characteristics.
Increase U
Recall that turbulent flow reduces the film resistance to heat transfer. Choosing a
fin configuration with a more pronounced waveform and/or adding turbulators
inside the coil tubes will improve the heat-transfer coefficient.
Increase A
Any additional increase in heat-transfer capacity must be achieved by physically
increasing the available surface area; that is, by:
Adding rows
Adding fins
Increasing the physical size of the coil (which will increase the
initial costs of the coil, air handler, and airside accessories).
Psychrometry for Air Conditioning
Introduction
The aim of this section of the notes is to allow students to size air
conditioning plant such as; Cooling coil, heater battery and
humidifier.
The notes are divided into several sections as follows:
1. PSYCHROMETRY FOR AIR CONDITIONING
2. THE PSYCHROMETRIC CHART
3. EXAMPLES OF PSYCHROMETRIC PROPERTIES
4. AIR CONDITIONING PLANT FOR SUMMER & WINTER
5. BASIC PROCESSES
6. TYPICAL AIR CONDITIONING PROCESSES
7. ANNOTATION AND ROOM RATIO
8. SUMMER AND WINTER CYCLES
9. EXAMPLES
The first section deals with Psychrometry for air conditioning and
discusses some properties of moist air.
A simplified psychrometric chart is shown for familiarisation, and
some examples of how to find air properties are provided.
A diagram of an air conditioning system is shown in schematic form
in the section entitled AIR CONDITIONING PLANT FOR SUMMER &
WINTER.
Before sizing takes place the student should also understand the
processes that take place in air conditioning systems.
There are four basic processes for summer and winter air
conditioning systems.
The following basic processes are explained:
1. Mixing
2. Sensible Cooling and Heating
3. Cooling with Dehumidification
4. Humidification
The section on Typical Air Conditioning Processes shows winter and
summer schematic diagrams and psychrometric charts.
There are some more details that may be useful to the designer of air
conditioning systems.
Further information is as follows: Annotation, Room ratio
When the processes have been superimposed onto a psychrometric
chart then calculations may commence.
These are as detailed in the following sections of the notes.
Summer and Winter Cycles
1. Summer cycle psychrometrics
2. Summer cycle calculations
3. Winter cycle psychrometrics
4. Winter cycle calculations
5. Duct and Fan gains.
The final section is seven examples of plant sizing using
psychrometric charts.
Psychrometry for Air Conditioning
Psychrometry is the study of air and water vapour mixtures.
Air is made up of five main gases i.e.
Nitrogen 78.03%, Oxygen 20.99%, Argon 0.94%, Carbon Dioxide
0.03%, and Hydrogen 0.01% by volume.
The Ideal Gas Laws are used to determine psychrometric data for air
so that the engineer can carry out calculations.
To make life easier a chart has been compiled with all the relevant
psychrometric data indicated.
This is called the Psychrometric Chart.
A typical chart is shown below.
This gives an indication of how ‘dry’ or how ‘moist’ the air is, since in
‘dry’ air the water will evaporate quickly from the gauze, which
depresses the thermometer reading.
3. Moisture content
4. Percentage saturation
This is the ratio of the moisture content of moist air to the moisture
content of saturated air at the same temperature.
5. Specific enthalpy
6. Specific volume
This is the volume of moist air (dry air + water vapour) per unit mass.
If any two properties of air are known then the other four can be
found from the psychrometric chart.
Examples of Psychrometric
Properties
EXAMPLE 1
EXAMPLE 2
Find the specific volume and wet-bulb temperature of air at 20oC dry-
bulb temperature and 50% saturation.
Referring to the chart below, a vertical line is drawn upwards from
20oC dry-bulb temperature until it intersects with the 50% saturation
curve.
EXAMPLE 3
Where:
When air is fully saturated it cannot hold any more moisture in the
form of water vapour.
If the air is cooled to the dew point air and is still further cooled then
moisture will drop out of the air in the form of condensate.
In reality the ADP of the cooling coil is close to the cooling liquid
temperature inside the coil.
Where:
H = Cooling energy (kW)
m = mass flow rate of air (kg/s)
h = specific enthalpy of air (kJ/kg) found from psychrometric chart.
Where:
H = Cooling energy (kW)
m = mass flow rate of air (kg/s)
Cp = Specific heat capacity of air, may be taken as 1.01 kJ/kg degC.
t = Dry bulb temperature of air (oC)
hfg = latent heat of evaporisation, may be taken as 2454 kJ/kg @20oC.
g = moisture content of air from psychrometric chart (kg/kg dry air)
Basic Air Conditioning Processes
3.1 Cooling Coil Contact Factor
Some of the air going through a cooling coil does not come into
contact with the tubes or fins of the cooling coil and is therefore not
cooled to the ADP temperature.
One air stream is cooled down to the ADP and the other air stream
by-passes the coil surfaces to give an off-coil air temperature (mixed
air stream) a little higher than the ADP.
The steam package unit is situated close to the air duct and is sized
to meet the maximum requirements; this is usually in winter in the
U.K.
A steam pipe (sometimes hoses are used) passes from the packaged
unit to the air duct and steam at 100oC is injected into the air stream
via. a sparge pipe. The un-used steam is drained from the system via
a condensate tundish and drain. It is important to layout the steam
pipework so that any condensate will drain back to the unit.
Room Ratio
This is the ratio of sensible to total heat in the room for summer or
winter.
(SUMMER)
(WINTER)
The supply air state point must also be somewhere on this room ratio
line to meet the room heat gain requirements i.e. the room ratio line
always passes through points R and S.
Examples of Psychrometric Calculations for
Summer and Winter
Example 1. Summer Cycle
DATA:
The cooling coil output of 38.2 kW is a much higher value than the sensible
heat gain of 10.8 kW. It should be remembered that the difference is these
two values is mostly from the fresh air cooling load.
It takes quite a lot of energy in summer to cool fresh air coming into air
handling units. This can be minimised by bringing in minimum fresh air but
not too little otherwise the building will suffer from lack of oxygen and feel
stuffy. Sometimes mistakes are made when sizing cooling apparatus.
If a cooling coil or indoor cooling unit is sized on the sensible heat gain only
without allowing for fresh air load then it will be grossly undersized.
That is why psychrometric charts are required to calculate cooling coil output
including fresh air loads. So, don’t size cooling coil and indoor cooling units
on sensible heat gain only if there is fresh air coming into the plant? Size
these items of plant using a psychrometric chart.
Example 2. Winter Cycle
A room has an 18.0 kW sensible heat loss in winter and a 4.5 kW
latent heat gain from the occupants.
DATA:
Indoor condition : 21oC dry-bulb temperature, 50% saturation.
Outdoor condition : -2oC d.b., 80% saturation.
The outdoor air and recirculated air ratio is 20%/80%.
No preheating or humidification takes place in this simplified example.
If there is more recirculated air than outside air at the mix point,
then point M will be closer to point R than point O.
Neglect signs i.e. the total heat for the room will be Sensible loss
plus Latent gain.
Hs = ma x Cp (ts - tr)
Where:
Hs = Sensible heat loss (kW)
ma = mass flow rate of air (kg/s)
Cp = Specific heat capacity of humid air (approx.1.01 kJ/kg degC)
tr = room temperature (oC)
ts = supply air temperature (oC)
..............therefore:
ma = Hs / Cp ( ts - tr )
ma = 18 / 1.01 (32.5 - 21)
ma = 18 / 11.615
ma = 1.55 kg/s
Heater Battery Output
The heater battery output is as follows:
Where:
H reheater battery = Reheater battery output (kW)
ma = mass flow rate of air (kg/s)
hS = specific enthalpy at condition S (kJ/kg)
hM = specific enthalpy at condition M (kJ/kg)
ma = Hs / ( Cp ( tr - ts ) )
Where:
Hs = Sensible heat gain to room (kW)
ma = mass flow rate of air (kg/s)
Cp = Specific heat capacity of humid air (approx.1.01 kJ/kg degC)
tr = room temperature (oC)
ts = supply air temperature (oC)
ma = 8 / ( 1.01 ( 22 - 17 ) )
ma = 1.584 kg/s
Cooling Coil Output
The cooling coil output is as follows:
Where:
H cooling coil = Cooling coil output (kW)
ma = mass flow rate of air (kg/s)
hM = specific enthalpy at condition M (kJ/kg) determined from
psychrometric chart.
hADP = specific enthalpy at condition ADP (kJ/kg) determined from
psychrometric chart
Where:
H heater battery = Heater battery output (kW)
ma = mass flow rate of air (kg/s)
hS = specific enthalpy at condition S (kJ/kg) determined from
psychrometric chart.
hW = specific enthalpy at condition W (kJ/kg) determined from
psychrometric chart.
The latent heat gain is 40 Watts per person (see Air Conditioning
section).
DATA:
Supply air mass flow rate (kg/s) = Supply air quantity (m3/s) / Specific
Volume (m3/kg)
Supply air mass flow rate (kg/s) = 2.13 (m3/s) / 0.87 (m3/kg)
The fresh air flow rate (kg/s) = 2.45 kg/s x 50% = 1.23 kg/s
( ts - tr ) = Hs / ma x Cp
( ts - tr ) = 17 / 2.45 x 1.01
( ts - tr ) = 6.87 deg.C
( ts - 21) = 6.87 deg.C
ts = 21 + 6.87 deg.C
ts = 27.87 oC say 28 oC.
Humidifier Output
The amount of moisture added to the air may be calculated from
the following formula:
DATA:
Outdoor condition is 28oC, 80% saturation.
The Apparatus Dew Point ADP is 7.5oC.
The latent heat gain is 10.0 kW.
The sensible heat gain is 12.0 kW.
Maximum occupancy is 200 people.
Use CIBSE guide B2 (2001) to determine air flow rates and calculate the
mass flow rate of fresh air and supply air to the room.
The lecture room may be taken as an Assembly hall.
The room is a non-smoking area.
Mass Flow Rates
Information from CIBSE Guide B2 (2001) Table 3.3 is as follows
(see Ventilation – Ventilation rates section); The recommended
outdoor air rate is 8 l/s/person for non-smoking.
= 1.82 kg/s .
If the maximum ventilation supply air rate is taken from Table 3.6
to be 10.0 air changes per hour, then the mass flow rate can be
calculated.
Volume flow rate (m3/h) = Volume of room (m3) x air change rate (ac/h)
Volume of room (m3) = 15 x 10 x 6 = 900 m3
3 3
Volume flow rate (m /h) = 900 (m ) x 10 (ac/h)
Volume flow rate (m3/h) = 9000 m3/h
3
Volume flow rate (m /s) = 9000 / 3600 = 2.5 m3/s.
Hs = ma x Cp ( tr - ts )
Where:
Hs = Sensible heat gain to room (kW)
ma = mass flow rate of air (kg/s)
Cp = Specific heat capacity of humid air (approx.1.01 kJ/kg degC)
tr = room temperature (oC)
ts = supply air temperature (oC)
( tr - ts ) = Hs / ( ma x Cp )
( tr - ts ) = 12 / ( 3.00 x 1.01 )
( tr - ts ) = 3.96 deg.C
since tr = 22oC
ts = 22 - 3.96 = 18.04 oC
ts = 18 oC approx.
o
From the psychrometric chart point W is at approximately 9 C
dry bulb.
DATA:
10. Sensible heat gain in 100 W/person + 20.5 kW fabrics, lights, solar &
summer ventilation gains.
Fresh air rate = 12 l/s/p x 1000 people = 12,000 l/s = 12.0 m3/s
The specific volume at the outside condition may be determined from a
psychrometric chart. It is approximately 0.88 m3/kg
Mass flow rate = Volume flow rate / specific volume
Mass flow rate (Fresh Air) = 12.0 / 0.88 = 13.64 kg/s.
The ventilation supply air rate is taken from table B2.3 and is given as 8 air changes
per hour; the mass flow rate can be calculated.
Volume flow rate (m3/h) = Volume of room (m3) x air change rate (ac/h)
Volume of room (m3) = 40 x 20 x 8 = 6400 m3
Volume flow rate (m3/h) = 6400 (m3) x 8 (ac/h)
Volume flow rate (m3/h) = 51,200 m3/h
Volume flow rate (m3/s) = 51,200 / 3600 = 14.22 m3/s.
Mass flow rate = Volume flow rate / specific volume
The specific volume at the supply condition may be approximated at this stage from
a psychrometric chart. It can be taken as 0.834 m3/kg.
Mass flow rate (Supply Air) = 14.22 / 0.834 = 17.05 kg/s.
Heat Gains
Heat Loss
In this example the supply air temperature will be found by rearranging the
following formula:
Hs = ma x Cp ( tr - ts )
Where:
Hs = Sensible heat gain to room (kW)
ma = mass flow rate of air (kg/s)
Cp = Specific heat capacity of humid air (approx.1.01 kJ/kg degC)
tr = room temperature (oC)
ts = supply air temperature (oC)
ts = 22 - 7.0 = 15.0 oC
ts = 15 oC
On a full size psychrometric chart the length of the line from point M to point
ADP is 116mm.
Where:
H cooling coil = Cooling coil output (kW)
ma = mass flow rate of air (kg/s)
hM = specific enthalpy at condition M (kJ/kg) determined from
psychrometric chart.
hADP = specific enthalpy at condition ADP (kJ/kg) determined from
psychrometric chart
The cooling coil output is very high and a lot of energy would be required
to provide this amount of cooling.
The cooling coil load would probably be spread over several air handling
units but it could be examined with a view to some reduction.
The coil output is high because the mass flow rate of supply air is high
(17.05 kg/s ) and the proportion of fresh air is also high ( 80%).
If 6 air changes per hour are used as the ventilation rate then this would
reduce the mass flow rate of supply air.
Also the engineer may consider other methods of air-conditioning a hall
with a large volume such as using partial radiant cooling where surfaces
are cooled rather than air.
Reheater Battery Output in Summer
Hs = ma x Cp ( ts - tr )
Where:
Hs = Sensible heat loss from room (kW)
ma = mass flow rate of air (kg/s) same as summer rate for constant volume
Systems.
Cp = Specific heat capacity of humid air (approx.1.01 kJ/kg degC)
tr = room temperature (oC)
ts = supply air temperature(oC)
( ts - tr ) = Hs / ma x Cp
( ts - tr ) = 128 / 17.05 x 1.01
( ts - tr ) = 7.43 deg.C
ts = 22 + 7.43 deg.C
ts = 29.43 oC say 29.5 oC.
6. Plot the condition H at 29.5oC dB. on a horizontal line from M.
7. Plot condition S on a vertical line from H on the RRL.
Assume the humidity process is vertical.
Where:
H preheater battery = Preheater battery output (kW)
maf = mass flow rate of fresh air (kg/s)
hP = specific enthalpy at condition P (kJ/kg)
hO = specific enthalpy at condition O (kJ/kg)
Where:
NOTE:
The heater battery load may be reduced by using other forms of heating
for some of the load, e.g. perimeter convectors or radiators.
The amount of moisture added to the air may be calculated from the following
formula:
Where:
m moisture added = The amount of moisture or added or steam flow rate (kg/s)
ma = mass flow rate of air (kg/s)
msS = moisture content at condition S (kg/kg d.a.)
msH = moisture content at condition H (kg/kg d.a.)
DATA:
HEAT GAINS
Sensible
(200 x 80) + (100 x 80) + (15 x 24 x 10)
= 27,600 Watts = 27.6 kW + solar gain 5.0 kW = 32.6 kW
Latent
(40 x 80) = 3200 Watts = 3.2 kW + other 5kW = 8.2 kW
ma = Hs / ( Cp ( tr - ts ) )
Where:
o
The supply air temperature is 14.5 C.
Where:
Where: