MÄGA ENGINEERING (PVT) LTD.

Design of Halaba Bridge at 8+380 Sheet No


200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
6.0 DESIGN OF PIER

450 855
V1 V2

W1
A

1900
W2

400 900 B HFL 542.866

400
2500
W3

200 1700

200
C

2500
W4

200 2100 D
200
300-2000
VARIES

W5

500 2500 E
800

W6
534.300 F
3500

Fig. 4.6 Section of Pier

The stability of the Pier is checked for the following conditions


under Serviceability Limit State & Ultimate Limit State

1 - Dry condition
2 - Wet condition
3 - Construction Stage

General Data

Pier bottom level = 536.830 m


High Flood level = 542.866 m

Weight of dry mass concrete (γ) = 23.60 KN/m2


Weight of wet mass concrete (γ) = 23.60-9.81 KN/m3
13.79 KN/m3
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
3
Weight of dry concrete (γ) = 24.00 KN/m
Weight of wet concrete (γ) = 24.00-9.81 KN/m3
14.19 KN/m3

Weight of dry soil (γ) = 17.28 KN/m3


3
Weight of wet soil (γ) = 17.28-9.81 KN/m
7.47 KN/m3

Weight of dry Porous fill material (γ) = 18.00 KN/m3


3
Weight of wet Porous fill material (γ) = 18.00-9.81 KN/m
8.19 KN/m3

2
Active earth Load Fb = 1/2 Ka γh

Surcharge Load Fb = K a ns h

2
Reynolds Passive earth Load Fb" = 1/2 (1/Ka) γs h"
Hand book
Table 16 ϕ = 35 deg
Ka = 0.271
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
6.1 DESIGN OF CAPPING BEAM
6.1.1 Calculation of Loads
6.1.1.1 Dead Load

450 855
V1 V2

W1
A

1900
W2

400 900 B HFL 542.866

400
2500
W3

200 1700

200
C

2500

W4

200 2100 D
200
300-2000
VARIES

W5

500 2500 E
600

W6
534.300 F
3500

Fig. 6.1 Section of Pier

No of beams = 20
Length of span = 13.500 m
Length of the capping beam = 10.650 m
Top width of the Section = 0.900 m
Height of the curtain wall = 0.855 m
Length of the curtain wall = 0.900 m
Width of curtain wall = 0.200 m

Cross sectional area of the deck


2
= 7.698 m

Volume of concrete in deck


= 7.698 x 13.5
3
= 103.93 m
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
Volume of displacers in deck
2
= 19 x π x 0.5 x (16.500 - 2 x 0.75)
3
= 2.01 m

Net volume of concrete in deck


= 103.93 - 2.01
3
= 101.92 m

Load due to weight of concrete in deck


= 101.92 x 24.0
= 2446.05 kN

Load due to weight of concrete in deck per m (one side)


= 2446.05 / 10.65 /2
= 114.84 kN/m

Weight of the curtain wall


= 0.2x0.9x0.855x24
= 3.69 kN

Load for unit length of curtain wall


= 3.69x2/10.65
= 0.69 kN/m

Total dead load per meter length


= 114.84 + 0.69 Dead load
= 115.53 kN/m = 115.53
kN/m
6.1.1.2 Superimposed Dead Load
Load due to weight of hand rails
= 2 x 13.500 x 0.58
= 15.795 kN

Load due to weight of wearing surface


= 7.14 x 13.500 x 0.05 x 22.6
= 108.9207 kN

Total super imposed dead load


= 15.795 + 108.92
= 124.72 kN Super
Imposed
Load due to weight of concrete in deck per m (one side) Dead load
= 124.72 / 13.5 /2 = 5.86
= 5.86 kN/m kN/m
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
BS 5400-Part 2 6.1.1.3 Live Loads
Cl 3.2.9.3.1
Carriageway width = 3.700 x 2
= 7.4 m
No of notional lanes = 2 ( 4.6m <7.4m < 7.6m)

HA Loading
BS 5400-Part 2 Loaded length = 13.5 m (< 30.0m)
Cl 6.2.1
Type HA Uniformly Distributed Load (UDL)
= 30 kN/m/lane

HA -loading
= 13.5 x 2 x 30
= 810.0 kN

BS 5400-Part 2 Nominal knife edge load = 120 kN/lane


Cl 6.2.2
Total knife edge load
= 2 x 120 kN
= 240.0 kN

BS 5400-Part 2 6.1.1.4 Nominal Live Load on Footways


Cl 7.1.1 loaded length <30m
uniformly distributed load = 5 kN/m2

Width of foot walk = 1.60 m

Total pedestrian live load


= 13.5 x 1.6 x 5 x 2
= 216.0 kN

Total HA live load acting on a capping beam


= (810 + 216)/2 + 240.00
= 753.00 kN
HA Live
Total HA live load acting on unit length of capping beam Load
= 753 / 10.65 = 70.70
= 70.7 kN/m kN/m
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
6.1.1.5 Tractive Force
BS 5400-Part 2 Nominal load for type HA loading
Cl 6.6.1 = 8kN/m of loaded length + 200kN <700kN
= 13.50 x 8 + 200
= 308.00 kN/m

RDA Bridge Tractive force for Pier


Design Manual = 0.8 x Tractive force
Cl 2.2.4 = 246.40 kN

Total tractive force per unit length of capping beam HA Tractive


= 246.4 / 10.65 force
= 23.14 kN/m = 23.14
kN/m
Table 6.1
Loads Applying on Unit Length of the Capping Beam(SLS)
BS 5400 Part 2 Load type Nominal γFL γf3 Design
Table 1 Load (kn/m) Load (kn/m)
Vertical Forces
BS 5400 Dead load 115.53 1.00 1.00 115.53
Part 4 : 1990 Superimposed dead load 5.86 1.20 1.00 7.03
Cl. 4.2.2 W1 10.04 1.00 1.00 10.04
Live load 70.70 1.20 1.00 84.84
Sub Total 217.44 VSLS
Longitudinal Forces = 217.44
Tractive force 23.14 1.00 1.00 23.14 kN/m
Sub Total 23.14 HSLS
= 23.14
kN/m
Table 6.2
Loads Applying on Unit Length of the Capping Beam(ULS)
BS 5400 Part 2 Load type Nominal γFL γf3 Design
Table 1 Load (kn/m) Load (kn/m)
Vertical Forces
BS 5400 Dead load 115.53 1.15 1.10 146.14
Part 4 : 1990 Superimposed dead load 5.86 1.75 1.10 11.27
Cl. 4.2.2 W1 11.12 1.15 1.10 14.07
Live load 70.70 1.25 1.10 97.21
Sub Total 268.69 VULS
Longitudinal Forces = 268.69
Tractive force 23.14 1.25 1.10 31.82 kN/m
Sub Total 31.82 HULS
= 31.82
kN/m
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
6.1.2 Analysis of Capping Beam
For Ultimate Limit State

6.2.1.2 Check for Stability


695
205

V2 V1
H
450

W1
A
900

Essentials of Bridge Fig. 6.2 Section of Capping Beam


Eng. By D.J. Victor
4th Edition, 1991 V1 = Dead load + Superimposed dead load + Live load
Cl 12.4 V1 = 146.14 + 11.27 + 97.21
V1 = 254.6 kN/m V1 =

254.62
V2 = Dead load + Superimposed dead load kN/m
V2 = 146.14 + 11.27
V2 = 157.4 kN/m V2 =

157.41
H = 31.82 kN/m kN/m

H =
Table 6.3 - Analysis of Capping Beam For Stability 31.82
(Moments are taken around A) kN/m
Load type Design load Length Moment (kNm/m)
(kN/m) from Stability Over turning
A (m) Ms Mo
V1 254.62 0.205 52.20
V2 157.41 0.695 109.40
W1 14.07 0.450 6.33
Longitudinal Forces
H 31.82 0.500 15.91
Total 167.93 15.91

Bridge Design Factor of safety against overturning


Manual Cl.2.1 F.O.S = Stability moment / Over turning F.O.S
= 167.93/15.91 = 10.6
= 10.6 >1.3
Therefore section is safe in stability.
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
6.1.3 DESIGN OF REINFORCEMENT FOR CAPPING BEAM

The stuctural design is made for ultimate loads.


MU
Ultimate bending moment = Ms - Mo = 167.9
= 167.9 - 15.91 kNm/m
= 152.0

BS 5400 Cover thickness should not be less than the maximum size of the
Part 4 : 1990 coarse aggregete + 5mm
Cl. 5.8.2
Maximum size of the coarse aggregate = 19 mm
= 19 + 5 mm
= 24 mm

BS 5400 Minimum cover is 45 mm for grade 25 concrete


Part 4 : 1990 Therefore provide 50mm cover
Table 13
Assume 16 mm bar for main bars & 10 mm bar for shear links
are provided.
Width of the Section (b) = 900 mm
Effective depth (d) = 450-50-16/2-10
= 382 mm

BS 8110 K' = 0.156


Part 1 : 1997
M
Cl. 3.4.4.4 K  2
bd f cu
fcu = 25 N/mm2

K = (167.93 x10^6)
(900Х 382^2 Х 25)
= 0.0511
K < K'
Therefore, compression reinforcement is not required.


  K  
Lever arm, z  d  0 .5   0 . 25  

  0 .9  


  .051
z  d0.5 0.25 

  0.9 

z = 359 mm
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
But z should not exceed 0.95d
0.95 d = 0.95 x 382
= 363 mm
Therefore get, z = 359 mm

Required tension reinforcement , As = M


0.95  f y  z

AS 6
= 167.9 x 10
0.95 x 460 x 358.89

AS = 1071 mm2

100AS = 100 x 1071


bd 900 x 382

= 0.3114 > 0.15


Hence OK

6.1.3.1 Main Reinforcement

BS 5400 Minimum main reinforcement requirement


Part 4 : 1990 AS = 1071 mm2
Cl. 5.8.4.1 No. of bars = 1071 /(π x 16^2/4) No. of bars
= 5.33 7 T16@
Provide 7 Nos of 16 mm bars 114 mm

Therefore Provide16mm Φ tor steel bars at 114mm intervals


center to center for both bottom and top layers.

provided As = (π x 16^2/4) Х 7 mm2 As,prov


= 1408 mm2 = 1408
mm2
BS 5400 6.1.3.2 Shear reinforcement
Part 4 : 1990
Cl. 5.3.3.1 Max. Shear force, V = 268.69 kN/m

Shear stress,v = V/bd


= 268.69 x 1000 v =
900 x 382 0.780
2
= 0.78 N/mm N/mm2

0.75√(fcu) = 0.75√(25)
= 3.75 N/mm2 > v
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT

Depth factor, ξs = (500/d)^(1/4)


= 500 ^(1/4)
382
= 1.0696

BS 5400 Ultimate shear stress in concrete vc


Part 4 : 1990 by linear interpolation
Table 8 100As/bd v c (N/mm2)
0.25 0.4
0.50 0.5
0.410 0.46

vc = 0.46 N/mm2
ξs vc = 1.07 x 0.46
2
= 0.50 N/mm < v

Provide φ10mm tor steel shear stirups,2 legs,

2
fyv = 460 N/mm

BS 5400 v > ξs vc
Part 4 : 1990 Therefore,
Cl.5.3.3.2 Asv >= 0.4bsv(v+.4-ξsvc)/0.87fyv
Table 07 sv <= Asv x 0.87fyv/0.4b(v+.4-ξsvc)
<= (0.87 Х 460 Х 2Х π Х 10^2/4)
0.4x900 (0.78+.4-0.5)
<= 102.76 mm No. of bars
Select sv = 100 mm T10 @
100
So, Provide 2 leg strirups at 100 mm spacing.

Asv,prov = 1570
For, 100As/bd = 0.46 >.12
Hence satisfy the nominal secondary rienforcement requirement
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
6.2 DESIGN OF PIER STEM AND BASE
6.2.1 Dry Condition Serviceability limit state

450 855
V1 V2

W1
A

1900
W2

400 900 B HFL 542.866

400
2500
W3

200 1700

200
C

2500
W4

200 2100 D
200
300-2000
VARIES

W5

500 2500 E
600

W6
534.300 F
3500

Fig. 6.1 Section of Pier

The stuctural design is made for Serviceability loads.


BS 5400 Part 2 Table 6.4 Calculation of Serviceability loads
Table 1 Load type Nominal γFL γf3 Design
Load (kn/m) Load (kn/m)
BS 5400 Vertical Forces
Part 4 : 1990 Deck dead load 115.53 1.00 1.00 115.53
Cl. 4.2.2 Superimposed dead load 5.86 1.20 1.00 7.03
Live load 70.70 1.20 1.00 84.84
Capping beam, W1 10.04 1.00 1.00 10.04
Pier - W2 38.39 1.00 1.00 38.39
Pier - W3 108.95 1.00 1.00 108.95
Pier - W4 128.19 1.00 1.00 128.19
Pier - W5 123.92 1.00 1.00 123.92
Pier - W6 67.50 1.00 1.00 67.5
Sub Total 684.39
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
Longitudinal Forces
Tractive force 23.14 1.00 1.00 23.14
Sub Total 23.14

V1 = Dead load + Superimposed dead load + Live load


V2 = Dead load + Superimposed dead load

6.2.1.1 Analysis of Pier section 2 for Stability


Specimen calculation for section 2 per unit width of the Pier

Table 6.5 Moments about point B


Load type Design load Length Moment (kNm/m)
(kN/m) from Stability Over turning
A (m) Ms Mo
Vertical Forces
V1 192.09 0.205 39.38
V2 121.39 0.695 84.37
Capping beam, W1 10.04 0.450 4.52
Pier - W2 38.39 0.450 17.28
Longitudinal Forces
Tractive force 23.14 2.350 54.38
Sub Total 145.55 54.38
Total bending moment M 91.2 kNm/m M
= 91.2
kNm/m
Total bending moment = 91.2 kNm/m

6.2.1.1a Check for Stability

Factor of safety against overturning


RDA Bridge
Design Manual F.O.S = Stability moment / Over turning F.O.S
Cl. 2.1 = 145.55 / 54.4 = 2.7
= 2.7 > 1.3

Therefore section is safe in stability.

6.2.1.1b Check for StressesKz


z
z 


 d
d
d













0
0

b

.
.0
5
5
d


.
M
5
2






f
0
0.
.
cu
2
2



5
5

0
.
.
.
004
0
2
0
0
5
.
.
1
9
9


3














 0
K
. 9







Total vertical force, V = 361.91 kN/m


Eccentricity of the resultant force from the edge of the section (e')

e' = Ms – Mo
V
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT

e' = 145.6 - 54.4


361.9

e' = 0.252 m e'


= 0.252
Eccentricity of the vertical force from the centre of the section (e) m

e = b/2 - e'
e = 0.9 /2 - 0.25
e = 0.198 m e
= 0.198
m
Second moment of innertia , I
3
I = 1/12 x b x d

3
I = 0.9 X 1.00
12

4
I = 0.0608 m

Bending moment, M
M = V× e
M = 361.9 X 0.198
M = 71.7 kNm/m

Bending stress, σ b
σb = Mxy
I
σb = 71.7 X 0.45
0.061

2
σb = 531.0 kN/m /m

Direct stress, σ d
σd = V
bd
σd = 361.9
0.9 X 1.00

2
σd = 402.12 kN/m /m
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
Maximum stress, σ max
σ max = σd + σb
= 402.12 + 531.03 σ max
2
= 933.16 kN/m /m = 933.16
kN/m 2 /m

Minimum stress, σ min


σ min = σd - σb
= 402.12 - 531.03 σ min
= -128.9 kN/m 2 /m = -128.9
< 360 2 2
kN/m kN/m /m
Hence OK

6.2.1.2 Analysis of Pier section 3 for Stability


Specimen calculation for section 3 per unit width of the Pier

Table 6.6 Moments about point C


Load type Design load Length Moment (kNm/m)
(kN/m) from Stability Over turning
A (m) Ms Mo
Vertical Forces
V1 192.09 0.605 116.21
V2 121.39 1.095 132.92
Capping beam, W1 10.04 0.850 8.53
Pier - W2 38.39 0.850 32.63
Pier - W3 108.95 0.850 92.61
Longitudinal Forces
Tractive force 23.14 5.250 121.49
Sub Total 382.90 121.49
Total bending moment M 261.4 kNm/m M
= 261.4
kNm/m
Total bending moment = 261.4 kNm/m

6.2.1.2a Check for Stability

Factor of safety against overturning


RDA Bridge
Design Manual F.O.S = Stability moment / Over turning F.O.S
Cl. 2.1 = 382.90 / 121.5 = 3.2
= 3.2 > 1.3
Therefore section is safe in stability.
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
6.2.1.2b Check for Stresses Kz
z
z 


 d
d
d













0
0

b

.
.0
5
5
d


.
M
5
2






f
0
0.
.
cu
2
2



5
5

0
.
.
.
004
0
2
0
0
5
.
.
1
9
9


3














 0
K
. 9







Total vertical force, V = 361.91 kN/m

Eccentricity of the resultant force from the edge of the section (e')

e' = Ms – Mo
V

e' = 382.9 - 121.5


361.9

e' = 0.7223 m e'


= 0.722
Eccentricity of the vertical force from the centre of the section (e) m

e = b/2 - e'
e = 1.700 /2 - 0.72
e = 0.128 m e
= 0.128
m
Second moment of innertia , I
I = 1/12 x b 3 x d

3
I = 1.7 X 1.00
12

4
I = 0.409 m

Bending moment, M
M = V× e
M = 361.9 X 0.128
M = 46.2 kNm/m

Bending stress, σ b
σb = Mxy
I
σb = 46.2 X 0.85
0.409

2
σb = 95.9 kN/m /m
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
Direct stress, σ d
σd = V
bd
σd = 361.9
1.7 X 1.00

2
σd = 212.89 kN/m /m

Maximum stress, σ max


σ max = σd + σb
= 212.89 + 95.94 σ max
2
= 308.83 kN/m /m = 308.83
2
kN/m /m

Minimum stress, σ min


σ min = σd - σb
= 212.89 - 95.94 σ min
2
= 116.9 kN/m /m = 116.9
< 360 kN/m 2 kN/m 2 /m
Hence OK

6.2.1.3 Analysis of Pier section 4 for Stability


Specimen calculation for section 4 per unit width of the Pier

Table 6.7 Moments about point D


Load type Design load Length Moment (kNm/m)
(kN/m) from Stability Over turning
A (m) Ms Mo
Vertical Forces
V1 192.09 0.805 154.63
V2 121.39 1.295 157.20
Capping beam, W1 10.04 1.050 10.54
Pier - W2 38.39 1.050 40.31
Pier - W3 108.95 1.050 114.40
Pier - W4 128.19 1.050
Longitudinal Forces
Tractive force 23.14 7.950 183.96
Sub Total 477.08 183.96
Total bending moment M 293.1 kNm/m M
= 293.1
kNm/m
Total bending moment = 293.1 kNm/m
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
6.2.1.3a Check for Stability

Factor of safety against overturning


RDA Bridge
Design Manual F.O.S = Stability moment / Over turning F.O.S
Cl. 2.1 = 477.08 / 184.0 = 2.6
= 2.6 > 1.3

Therefore section is safe in stability.

6.2.1.3b Check for Stresses Kz


z
z 


 d
d
d













0
0

b

.
.0
5
5
d


.
M
5
2






f
0
0.
.
cu
2
2



5
5

0
.
.
.
004
0
2
0
0
5
.
.
1
9
9


3














 0
K
. 9







Total vertical force, V = 361.91 kN/m

Eccentricity of the resultant force from the edge of the section (e')

e' = Ms – Mo
V

e' = 477.1 - 184.0


361.9

e' = 0.810 m e'


= 0.810
Eccentricity of the vertical force from the centre of the section (e) m

e = b/2 - e'
e = 2.100 /2 - 0.810
e = 0.240 m e
= 0.240
m
Second moment of innertia , I
3
I = 1/12 x b x d

3
I = 2.100 X 1.00
12

I = 0.772 m4

Bending moment, M
M = V× e
M = 361.9 X 0.240
M = 86.9 kNm/m
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT

Bending stress, σ b
σb = Mxy
I
σb = 86.9 X 1.05
0.772

2
σb = 118.2 kN/m /m

Direct stress, σ d
σd = V
bd
σd = 361.9
2.1 X 1.00

2
σd = 172.34 kN/m /m

Maximum stress, σ max


σ max = σd + σb
= 172.34 + 118.21 σ max
2
= 290.55 kN/m /m = 290.55
2
kN/m /m

Minimum stress, σ min


σ min = σd - σb
= 172.34 - 118.21 σ min
2
= 54.1 kN/m /m = 54.1
< 360 kN/m 2 kN/m 2 /m
Hence OK

6.2.1.4 Analysis of Pier section 5 for Stability


Specimen calculation for section 5 per unit width of the Pier

Table 6.8 Moments about point E


Load type Design load Length Moment (kNm/m)
(kN/m) from Stability Over turning
A (m) Ms Mo
Vertical Forces
V1 192.09 1.005 193.05
V2 121.39 1.495 181.48
Capping beam, W1 10.04 1.250 12.55
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
Pier - W2 38.39 1.250 47.99
Pier - W3 108.95 1.250 136.19
Pier - W4 128.19 1.250 160.24
Pier - W5 123.92 1.250 154.90
Longitudinal Forces
Tractive force 23.14 10.15 234.87
Sub Total 886.40 234.87
Total bending moment M 651.5 kNm/m M
= 651.5
kNm/m
Total bending moment = 651.5 kNm/m

6.2.1.4a Check for Stability

Factor of safety against overturning


RDA Bridge
Design Manual F.O.S = Stability moment / Over turning F.O.S
Cl. 2.1 = 886.40 / 234.9 = 3.8
= 3.8 > 1.3

Therefore section is safe in stability.

6.2.1.4b Check for StressesKz


z
z 


 d
d
d













0
0

b

.
.0
5
5
d


.
M
5
2






f
0
0.
.
cu
2
2



5
5

0
.
.
.
004
0
2
0
0
5
.
.
1
9
9


3














 0
K
. 9







Total vertical force, V = 361.91 kN/m

Eccentricity of the resultant force from the edge of the section (e')

e' = Ms – Mo
V

e' = 886.4 - 234.9


361.9

e' = 1.800 m e'


= 1.800
Eccentricity of the vertical force from the centre of the section (e) m

e = b/2 - e'
e = 2.500 /2 - 1.80
e = 0.550 m e
= 0.550
m
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
Second moment of innertia , I
3
I = 1/12 x b x d

3
I = 2.500 X 1.00
12

I = 1.3021 m4

Bending moment, M
M = V× e
M = 361.9 X 0.550
M = 199.1 kNm/m

Bending stress, σ b
σb = Mxy
I
σb = 199.1 X 1.25
1.302

2
σb = 191.2 kN/m /m

Direct stress, σ d
σd = V
bd
σd = 361.9
2.5 X 1.00

2
σd = 144.76 kN/m /m

Maximum stress, σ max


σ max = σd + σb
= 144.76 + 191.18 σ max
= 335.94 kN/m 2 /m = 335.94
kN/m 2 /m

Minimum stress, σ min


σ min = σd - σb
= 144.76 - 191.18 σ min
2
= -46.4 kN/m /m = -46.4
< 360 kN/m 2 kN/m 2 /m
Hence OK
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT

6.2.1.5 Analysis of Pier Foundation for Stability

Table 6.9 Moments about point F


Load type Design load Length Moment (kNm/m)
(kN/m) from Stability Over turning
A (m) Ms Mo
Vertical Forces
V1 192.09 1.505 289.10
V2 121.39 1.995 242.17
Capping beam, W1 10.04 1.750 17.57
Pier - W2 38.39 1.750 67.18
Pier - W3 108.95 1.750 190.66
Pier - W4 128.19 1.750 224.33
Pier - W5 123.92 1.750 216.86
Pier - W6 67.5 1.750 118.13
Longitudinal Forces
Tractive force 23.14 10.95 253.38
Sub Total 1366.00 253.38
Total bending moment M 1112.6 kNm/m M
= 1112.6
kNm/m
Total bending moment = 1112.6 kNm/m

6.2.1.5a Check for Stability

Factor of safety against overturning


RDA Bridge
Design Manual F.O.S = Stability moment / Over turning F.O.S
Cl. 2.1 = 1366.00 / 253.4 = 5.39
= 5.39 > 1.3

Therefore section is safe in stability.

6.2.1.5b Check for StressesKz


z
z 


 d
d
d













0
0

b

.
.0
5
5
d


.
M
5
2






f
0
0.
.
cu
2
2



5
5

0
.
.
.
004
0
2
0
0
5
.
.
1
9
9


3














 0
K
. 9







Total vertical force, V = 790.47 kN/m

Eccentricity of the resultant force from the edge of the section (e')

e' = Ms – Mo
V
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT

e' = 1366.0 - 253.4


790.5

e' = 1.408 m e'


= 1.408
Eccentricity of the vertical force from the centre of the section (e) m

e = b/2 - e'
e = 3.500 /2 - 1.408
e = 0.342 m e
= 0.342
X
m

1000
F
X
3500

Fig. 6.3 Axis of Bending of Pier Foundation

Second moment of innertia , I


3
I = 1/12 x b x d

3
I = 3.500 X 1.00
12

4
I = 3.5729 m

Bending moment, M
M = V× e
M = 684.4 X 0.342
M = 234.4 kNm/m

Bending stress, σ b
σb = Mxy
I
σb = 234.4 X 1.75
3.573

2
σb = 114.80 kN/m /m
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT

Direct stress, σ d
σd = V
bd
σd = 684.4
3.5 X 1.00

2
σd = 195.54 kN/m /m

Maximum stress, σ max


σ max = σd + σb
= 195.54 + 114.80 σ max
2
= 310.34 kN/m /m = 310.34
kN/m 2 /m
Minimum stress, σ min
σ min = σd - σb
= 195.54 - 114.80 σ min
2
= 80.74 kN/m /m = 80.74
< 360 kN/m 2 kN/m /m 2

Hence OK

Stress Redistribution under the Foundation at Serviceability


Limit State

Le
V
2 e' e'

3.500

Fig. 6.4 Stress Redistribution under the Foundation at SLS

Let the redistributed maximum bearing pressure under


the foundation be σ and effective length be Le (m)
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
L e /3 = e'

Therefore V = 1/2×σ×Le
σ = 2V
3e'
= 2 X 790.47
3 X 1.41
= 374.40 kN/m 2

Allowable Bearing Capacity of Foundation


Reynolds Hand Since hard rock has been exposed, Bearing capacity of rock
Book Table 191 can be taken as( igneous and gniessic: sound) 10000 kN/m2
But due to rock fractures ,unforeseen condition etc.
allowable bearing capacity under foundation is limited to 600kN/m 2

Before staring construction of Piers allowble bearing


capacity of rock can be made sure by conduductin RQD
( Rock Quality Designation) Test, if there is a question arised,
due to the precsence of fracture of rock

The permissible bearing pressure under foundation is


600 kN/m2 > 374.40 kN/m2
Hence Satisfactory.

6.2.1.5c Checking for sliding


Foundation Design,
Total Horizontal force (H) = 23.14 kN/m
J.E. Bowels Friction angle δ between concrete interface
0
Table 11-6 δ = 30
μ = tan (30 0 )
= 0.58

Reynolds Frictional force (R) = µ x Vertical force


Hand Book = 0.58 x 790.47
Table 187 = 456.1 kN/m

F.O.S = Frictional force (R)


Horizontal force (H)
F.O.S = 456.10
23.14
F.O.S = 19.7 > 1.5
Hence Section is safe against sliding.
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
6.2 DESIGN OF PIER STEM AND BASE
6.2.2 Dry Condition Ultimate limit state

450 855
V1 V2

W1
A

1900
W2

400 900 B HFL 542.866

400
2500
W3

200 1700

200
C

2500
W4

200 2100 D
200
300-2000
VARIES

W5

500 2500 E
600

W6
534.300 F
3500

Fig. 6.1 Section of Pier

The stuctural design is made for Ultimate loads.

BS 5400 Part 2 Table 6.10 Calculation of Ultimate loads


Table 1 Load type Nominal γFL γf3 Design
Load (kn/m) Load (kn/m)
BS 5400 Vertical Forces
Part 4 : 1990 Deck dead load 115.53 1.15 1.10 146.15
Cl. 4.2.2 Superimposed dead load 5.86 1.75 1.10 11.28
Live load 70.70 1.50 1.10 116.66
Capping beam, W1 10.04 1.15 1.10 12.7
Pier - W2 38.39 1.15 1.10 48.56
Pier - W3 108.95 1.15 1.10 137.82
Pier - W4 128.19 1.15 1.10 162.16
Pier - W5 123.92 1.15 1.10 156.76
Pier - W6 67.50 1.15 1.10 85.39
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
Sub Total 877.48
Longitudinal Forces
Tractive force 23.14 1.25 1.10 31.82
Sub Total 31.82

V1 = Dead load + Superimposed dead load + Live load


V2 = Dead load + Superimposed dead load

6.2.2.1 Analysis of Pier section 2 for Stability


Specimen calculation for section 2 per unit width of the Pier

Table 6.11 Moments about point B


Load type Design load Length Moment (kNm/m)
(kN/m) from Stability Over turning
A (m) Ms Mo
Vertical Forces
V1 192.09 0.205 39.38
V2 121.39 0.695 84.37
Capping beam, W1 12.7 0.450 5.72
Pier - W2 48.56 0.450 21.85
Longitudinal Forces
Tractive force 31.82 2.350 74.78
Sub Total 151.32 74.78
Total bending moment M 76.5 kNm/m M
= 76.5
kNm/m
Total bending moment = 76.5 kNm/m

6.2.2.1a Check for Stability

Factor of safety against overturning


RDA Bridge
Design Manual F.O.S = Stability moment / Over turning F.O.S
Cl. 2.1 = 151.32 / 74.8 = 2.0
= 2.0 > 1.3

Therefore section is safe in stability.

6.2.2.1b Check for StressesKz


z
z 


 d
d
d













0
0

b

.
.0
5
5
d


.
M
5
2






f
0
0.
.
cu
2
2



5
5

0
.
.
.
004
0
2
0
0
5
.
.
1
9
9


3














 0
K
. 9







Total vertical force, V = 374.74 kN/m


MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
Eccentricity of the resultant force from the edge of the section (e')

e' = Ms – Mo
V

e' = 151.3 - 74.8


374.7

e' = 0.204 m e'


= 0.204
Eccentricity of the vertical force from the centre of the section (e) m

e = b/2 - e'
e = 0.9 /2 - 0.20
e = 0.246 m e
= 0.246
m
Second moment of innertia , I
3
I = 1/12 x b x d

3
I = 0.9 X 1.00
12

4
I = 0.061 m

Bending moment, M
M = V× e
M = 374.7 X 0.246
M = 92.1 kNm/m

Bending stress, σ b
σb = Mxy
I
σb = 92.1 X 0.45
0.061

2
σb = 682.2 kN/m /m

Direct stress, σ d
σd = V
bd
σd = 374.7
0.9 X 1.00
2
σd = 416.38 kN/m /m
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
Maximum stress, σ max
σ max = σd + σb
= 416.38 + 682.17 σ max
2
= 1098.5 kN/m /m = 1098.5
kN/m 2 /m

Minimum stress, σ min


σ min = σd - σb
= 416.38 - 682.17 σ min
= -265.8 kN/m 2 /m = -265.8
< 360 2 2
kN/m kN/m /m
Hence OK

6.2.2.2 Analysis of Pier section 3 for Stability


Specimen calculation for section 3 per unit width of the Pier

Table 6.12 Moments about point C


Load type Design load Length Moment (kNm/m)
(kN/m) from Stability Over turning
A (m) Ms Mo
Vertical Forces
V1 192.09 0.605 116.21
V2 121.39 1.095 132.92
Capping beam, W1 12.70 0.850 10.80
Pier - W2 48.56 0.850 41.28
Pier - W3 137.82 0.850 117.15
Longitudinal Forces
Tractive force 31.82 5.250 167.06
Sub Total 418.36 167.06
Total bending moment M 251.3 kNm/m M
= 251.3
kNm/m
Total bending moment = 251.3 kNm/m

6.2.2.2a Check for Stability

RDA Bridge Factor of safety against overturning


Design Manual F.O.S = Stability moment / Over turning F.O.S
Cl. 2.1 = 418.36 / 167.1 = 2.5
= 2.5 > 1.3
Therefore section is safe in stability.
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
6.2.2.2b Check for Stresses Kz
z
z 


 d
d
d













0
0

b

.
.0
5
5
d


.
M
5
2






f
0
0.
.
cu
2
2



5
5

0
.
.
.
004
0
2
0
0
5
.
.
1
9
9


3














 0
K
. 9







Total vertical force, V = 374.74 kN/m

Eccentricity of the resultant force from the edge of the section (e')

e' = Ms – Mo
V

e' = 418.4 - 167.1


374.7

e' = 0.6706 m e'


= 0.6706
Eccentricity of the vertical force from the centre of the section (e) m

e = b/2 - e'
e = 1.700 /2 - 0.67
e = 0.179 m e
= 0.179
m
Second moment of innertia , I
I = 1/12 x b 3 x d

3
I = 1.7 X 1.00
12

4
I = 0.4094 m

Bending moment, M
M = V× e
M = 374.7 X 0.179
M = 67.2 kNm/m

Bending stress, σ b
σb = Mxy
I
σb = 67.2 X 0.85
0.409

2
σb = 139.6 kN/m /m
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
Direct stress, σ d
σd = V
bd
σd = 374.7
1.7 X 1.00

2
σd = 220.44 kN/m /m

Maximum stress, σ max


σ max = σd + σb
= 220.44 + 139.58 σ max
2
= 360.01 kN/m /m = 360.01
2
kN/m /m

Minimum stress, σ min


σ min = σd - σb
= 220.44 - 139.58 σ min
2
= 80.9 kN/m /m = 80.9
< 360 kN/m 2 kN/m 2 /m
Hence OK

6.2.2.3 Analysis of Pier section 4 for Stability


Specimen calculation for section 4 per unit width of the Pier

Table 6.13 Moments about point D


Load type Design load Length Moment (kNm/m)
(kN/m) from Stability Over turning
A (m) Ms Mo
Vertical Forces
V1 192.09 0.805 154.63
V2 121.39 1.295 157.20
Capping beam, W1 12.70 1.050 13.34
Pier - W2 48.56 1.050 50.99
Pier - W3 137.82 1.050 144.71
Pier - W4 162.16 1.050
Longitudinal Forces
Tractive force 31.82 7.950 252.97
Sub Total 520.87 252.97
Total bending moment M 267.9 kNm/m M
= 267.9
kNm/m
Total bending moment = 267.9 kNm/m
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
6.2.2.3a Check for Stability

Factor of safety against overturning


RDA Bridge
Design Manual F.O.S = Stability moment / Over turning F.O.S
Cl. 2.1 = 520.87 / 253.0 = 2.1
= 2.1 > 1.3

Therefore section is safe in stability.

6.2.2.3b Check for Stresses Kz


z
z 


 d
d
d













0
0

b

.
.0
5
5
d


.
M
5
2






f
0
0.
.
cu
2
2



5
5

0
.
.
.
004
0
2
0
0
5
.
.
1
9
9


3














 0
K
. 9







Total vertical force, V = 374.74 kN/m

Eccentricity of the resultant force from the edge of the section (e')

e' = Ms – Mo
V

e' = 520.9 - 253.0


374.7

e' = 0.715 m e'


= 0.715
Eccentricity of the vertical force from the centre of the section (e) m

e = b/2 - e'
e = 2.100 /2 - 0.71
e = 0.335 m e
= 0.335
m
Second moment of innertia , I
I = 1/12 x b 3 x d

3
I = 2.100 X 1.00
12

I = 0.7718 m4

Bending moment, M
M = V× e
M = 374.7 X 0.335
M = 125.6 kNm/m
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
Bending stress, σ b
σb = Mxy
I
σb = 125.6 X 1.05
0.772

2
σb = 170.85 kN/m /m

Direct stress, σ d
σd = V
bd
σd = 374.7
2.1 X 1.00

2
σd = 178.45 kN/m /m

Maximum stress, σ max


σ max = σd + σb
= 178.45 + 170.85 σ max
2
= 349.30 kN/m /m = 349.30
kN/m 2 /m
Minimum stress, σ min
σ min = σd - σb
= 178.45 - 170.85 σ min
2
= 7.6 kN/m /m = 7.6
< 360 2 2
kN/m kN/m /m
Hence OK

6.2.2.4 Analysis of Pier section 5 for Stability


Specimen calculation for section 5 per unit width of the Pier

Table 6.14 Moments about point E


Load type Design load Length Moment (kNm/m)
(kN/m) from Stability Over turning
A (m) Ms Mo
Vertical Forces
V1 192.09 1.005 193.05
V2 121.39 1.495 181.48
Capping beam, W1 12.70 1.250 15.88
Pier - W2 48.56 1.250 60.70
Pier - W3 137.82 1.250 172.28
Pier - W4 162.16 1.250 202.70
Pier - W5 156.76 1.250 195.95
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
Longitudinal Forces
Tractive force 31.82 10.15 322.97
Sub Total 1022.04 322.97
Total bending moment M 699.1 kNm/m M
= 699.1
kNm/m
Total bending moment = 699.1 kNm/m

6.2.2.4a Check for Stability

Factor of safety against overturning


RDA Bridge
Design Manual F.O.S = Stability moment / Over turning F.O.S
Cl. 2.1 = 1022.04 / 323.0 = 3.2
= 3.2 > 1.3

Therefore section is safe in stability.

6.2.2.4b Check for StressesKz


z
z 


 d
d
d













0
0

b

.
.0
5
5
d


.
M
5
2






f
0
0.
.
cu
2
2



5
5

0
.
.
.
004
0
2
0
0
5
.
.
1
9
9


3














 0
K
. 9







Total vertical force, V = 374.74 kN/m

Eccentricity of the resultant force from the edge of the section (e')

e' = Ms – Mo
V

e' = 1022.0 - 323.0


374.7

e' = 1.865 m e'


= 1.865
Eccentricity of the vertical force from the centre of the section (e) m

e = b/2 - e'
e = 2.500 /2 - 1.87
e = 0.615 m e
= 0.615
m
Second moment of innertia , I
I = 1/12 x b 3 x d
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
3
I = 2.500 X 1.00
12

I = 1.302 m4

Bending moment, M
M = V× e
M = 374.7 X 0.615
M = 230.6 kNm/m

Bending stress, σ b
σb = Mxy
I
σb = 230.6 X 1.25
1.302

2
σb = 221.4 kN/m /m

Direct stress, σ d
σd = V
bd
σd = 374.7
2.5 X 1.00

2
σd = 149.90 kN/m /m

Maximum stress, σ max


σ max = σd + σb
= 149.90 + 221.42 σ max
= 371.32 kN/m 2 /m = 371.32
2
kN/m /m

Minimum stress, σ min


σ min = σd - σb
= 149.90 - 221.42 σ min
2
= -71.5 kN/m /m = -71.5
< 360 kN/m 2 kN/m 2 /m
Hence OK
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
6.2.2.5 Analysis of Pier Foundation for Stability

Table 6.15 Moments about point F


Load type Design load Length Moment (kNm/m)
(kN/m) from Stability Over turning
A (m) Ms Mo
Vertical Forces
V1 192.09 1.505 289.10
V2 121.39 1.995 242.17
Capping beam, W1 12.70 1.750 22.23
Pier - W2 48.56 1.750 84.98
Pier - W3 137.82 1.750 241.19
Pier - W4 162.16 1.750 283.78
Pier - W5 156.76 1.750 274.33
Pier - W6 85.39 1.750 149.43
Longitudinal Forces
Tractive force 31.82 10.95 348.43
Sub Total 1587.21 348.43
Total bending moment M 1238.8 kNm/m M
= 1238.8
kNm/m
Total bending moment = 1238.8 kNm/m

6.2.2.5a Check for Stability

Factor of safety against overturning


RDA Bridge
Design Manual F.O.S = Stability moment / Over turning F.O.S
Cl. 2.1 = 1587.21 / 348.4 = 4.56
= 4.6 > 1.3

Therefore section is safe in stability.

6.2.2.5b Check for StressesKz


z
z 


 d
d
d













0
0

b

.
.0
5
5
d


.
M
5
2






f
0
0.
.
cu
2
2



5
5

0
.
.
.
004
0
2
0
0
5
.
.
1
9
9


3














 0
K
. 9







Total vertical force, V = 916.87 kN/m

Eccentricity of the resultant force from the edge of the section (e')

e' = Ms – Mo
V
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
e' = 1587.2 - 348.4
916.9

e' = 1.351 m e'


= 1.351
Eccentricity of the vertical force from the centre of the section (e) m

e = b/2 - e'
e = 3.500 /2 - 1.35
e = 0.399 m e
X = 0.399
m

1000
F
X
3500

Fig. 6.3 Axis of Bending of Pier Foundation

Second moment of innertia , I


I = 1/12 x b 3 x d

3
I = 3.500 X 1.00
12

4
I = 3.5729 m

Bending moment, M
M = V× e
M = 877.5 X 0.399
M = 350.0 kNm/m

Bending stress, σ b
σb = Mxy
I
σb = 350.0 X 1.75
3.573

2
σb = 171.44 kN/m /m
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
Direct stress, σ d
σd = V
bd
σd = 877.5
3.5 X 1.00

2
σd = 250.71 kN/m /m

Maximum stress, σ max


σ max = σd + σb
= 250.71 + 171.44 σ max
2
= 422.15 kN/m /m = 422.15
2
kN/m /m
Minimum stress, σ min
σ min = σd - σb
= 250.71 - 171.44 σ min
2
= 79.27 kN/m /m = 79.27
< 360 kN/m 2 kN/m /m 2

Hence OK

Stress Redistribution under the Foundation at Ultimate


Limit State

Le
V
2 e' e'

3.500

Fig. 6.4 Stress Redistribution under the Foundation at ULS

Let the redistributed maximum bearing pressure under


the foundation be σ and effective length be Le (m)
Le/3 = e'
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
Therefore V = 1/2×σ×Le
σ = 2V
3e'
2 X 916.87
3 X 1.35
= 452.41 kN/m 2

Allowable Bearing Capacity of Foundation


Reynolds Hand Since hard rock has been exposed, Bearing capacity of rock
Book Table 191 can be taken as( igneous and gniessic: sound) 10000 kN/m2
But due to rock fractures ,unforeseen condition etc.
allowable bearing capacity under foundation is limited to 600kN/m 2

Before staring construction of Piers allowble bearing


capacity of rock can be made sure by conduductin RQD
( Rock Quality Designation) Test, if there is a question arised,
due to the precsence of fracture of rock

The permissible bearing pressure under foundation is


600 kN/m2 > 452.41 kN/m2
Hence Satisfactory.

6.2.2.5c Checking for sliding

Foundation Design,
Total Horizontal force (H) = 31.82 kN/m
J.E. Bowels Friction angle δ between concrete interface
0
Table 11-6 δ = 30
μ = tan (30 0 )
= 0.58

Reynolds Frictional force (R) = µ x Vertical force


Hand Book = 0.58 x 916.87
Table 187 = 529.03 kN/m
F.O.S = Frictional force (R)
Horizontal force (H)

F.O.S = 529.03
31.82
F.O.S = 16.6 > 1.5
Hence Section is safe against sliding.
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
6.2 DESIGN OF PIER STEM AND BASE
6.2.3 Wet Condition Serviceability limit state

450 855
V1 V2

W1
A

1900
W2
WATER CURRENT PRESSURE
P1 = 52 K V2
400 900 B HFL 542.866

400
1200
DEBRIS FORCE PRESSURE
P2 = 52 K V2

2500
W3

200 1700

200
C

2500
W4

200 2100 D

200
300-2000
VARIES

W5

500 2500 E DEEPEST SCOUR LEVEL


600

W6
534.300 F
3500

Fig. 6.5 Section of Pier


The stuctural design is made for Serviceability loads.

RDA Bridge Force due to Water Current & Debries and Log Impact
Design Manual Force due to water current & force due to debries are acting
0
Cl. 2.2.5 on a pier with an angle of 20 .

Essentials of Bridge Pressure due to water current = 52 kv2 kg/m 2


Eng. By D.J. Victor V= √2 xMean velocity of water(vm)
4th Edition, 1991 = √2 x 1.6
Cl 3.14 = 2.26 m/s
k= 0.66 (Semi circular cut ways)

2
Water current Pressure = 52 x 0.66 x 2.26
= 175.29 kg/m 2
= 1.72 kg/m 2

Water Current affecting height, h


h = HFL-deepest Scour level
= 542.866 - 534.053
= 8.813 m
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT

Water current force, P1 = 1/2 x P1 x h


= 1/2 x 1.72 x 8.813
= 7.58 kN/m

Effective component of water current force Water


0
= P1 Sin20 current
= 7.58 x Sin200 force
= 2.59 kN/m = 2.59
kN/m
2 2
RDA Bridge Pressure due to Floating debris = 52 kv kg/m
Design Manual V= √2 xMean velocity of water(vm)
Cl. 2.2.5 = √2 x 1.6
= 2.26 m/s
k= 1.0 (Semi circular cut ways)

2
Floating debris Pressure = 52 x 1 x 2.26
2
= 265.6 kg/m
2
= 2.61 kg/m

Floating debris affecting height, h


h = HFL-deepest Scour level-1.2m
= 542.866 - 534.053 - 1.2 m
= 7.613 m

Floating debris force, P2 = 1/2 x P1 x h


= 1/2 x 2.61 x 7.613
= 9.93 kN/m

Effective component of Floating debris force Floating


0
= P1 Sin20 debris
= 9.93 x Sin200 force
= 3.4 kN/m = 3.4
kN/m
RDA Bridge Log impact Force P3 = 0.1 W .V
Design Manual V= √2 xMean velocity of water(vm)
Cl. 2.2.5 = √2 x 1.6
= 2.26 m/s
W = Wieght of drifting items ; 2 ton (assumed)
W = 2 x 9.81 x 1000/1000 kN
W = 19.6 kN

Log impact Force P3 = 0.1 x 19.62 x 2.26


= 4.43 kN/m
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT

Effective component of Log impact force


0
= P1 Sin20 Log impact
= 4.43 x Sin200 force
= 1.52 kN/m = 1.52
kN/m
BS 5400 Part 2 Table 6.16 Calculation of Serviceability loads
Table 1 Load type Nominal γFL γf3 Design
Load (kn/m) Load (kn/m)
BS 5400 Vertical Forces
Part 4 : 1990 Deck dead load 115.53 1.00 1.00 115.53
Cl. 4.2.2 Superimposed dead load 5.86 1.20 1.00 7.03
Live load 70.70 1.20 1.00 84.84
Capping beam, W1 10.04 1.00 1.00 10.04
Pier - W2 38.39 1.00 1.00 38.39
Pier - W3 63.66 1.00 1.00 63.66
Pier - W4 74.91 1.00 1.00 74.91
Pier - W5 72.41 1.00 1.00 72.41
Pier - W6 39.44 1.00 1.00 39.44
Sub Total 506.25
Longitudinal Forces
Tractive force 23.14 1.00 1.00 23.14
Sub Total 23.14
V1 = Dead load + Superimposed dead load + Live load
V2 = Dead load + Superimposed dead load

6.2.3.1 Analysis of Pier section 2 for Stability


Specimen calculation for section 2 per unit width of the Pier
Table 6.17 Moments about point B
Load type Design load Length Moment (kNm/m)
(kN/m) from Stability Over turning
A (m) Ms Mo
Vertical Forces
V1 192.09 0.205 39.38
V2 121.39 0.695 84.37
Capping beam, W1 10.04 0.450 4.52
Pier - W2 38.39 0.450 17.28
Longitudinal Forces
Tractive force 23.14 2.350 54.38
Sub Total 145.55 54.38
Total bending moment M 91.2 kNm/m M
= 91.2
kNm/m
Total bending moment = 91.2 kNm/m
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
6.2.3.1a Check for Stability

Factor of safety against overturning


RDA Bridge
Design Manual F.O.S = Stability moment / Over turning F.O.S
Cl. 2.1 = 145.55 / 54.4 = 2.7
= 2.7 > 1.3

Therefore section is safe in stability.

6.2.3.1b Check for Stresses Kz


z
z 


 d
d
d













0
0

b

.
.0
5
5
d


.
M
5
2






f
0
0.
.
cu
2
2



5
5

0
.
.
.
004
0
2
0
0
5
.
.
1
9
9


3














 0
K
. 9







Total vertical force, V = 361.91 kN/m

Eccentricity of the resultant force from the edge of the section (e')

e' = Ms – Mo
V

e' = 145.6 - 54.4


361.9

e' = 0.252 m e'


= 0.252
Eccentricity of the vertical force from the centre of the section (e) m

e = b/2 - e'
e = 0.9 /2 - 0.25
e = 0.198 m e
= 0.198
m
Second moment of innertia , I
I = 1/12 x b 3 x d

3
I = 0.9 X 1.00
12

I = 0.0608 m4

Bending moment, M
M = V× e
M = 361.9 X 0.198
M = 71.7 kNm/m
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
Bending stress, σ b
σb = Mxy
I
σb = 71.7 X 0.45
0.061

2
σb = 531.0 kN/m /m

Direct stress, σ d
σd = V
bd
σd = 361.9
0.9 X 1.00

2
σd = 402.12 kN/m /m

Maximum stress, σ max


σ max = σd + σb
= 402.12 + 531.03 σ max
2
= 933.16 kN/m /m = 933.16
kN/m 2 /m

Minimum stress, σ min


σ min = σd - σb
= 402.12 - 531.03 σ min
2
= -128.9 kN/m /m = -128.9
< 360 kN/m 2 kN/m 2 /m
Hence OK

6.2.3.2 Analysis of Pier section 3 for Stability


Specimen calculation for section 3 per unit width of the Pier

Table 6.18 Moments about point C


Load type Design load Length Moment (kNm/m)
(kN/m) from Stability Over turning
A (m) Ms Mo
Vertical Forces
V1 192.09 0.605 116.21
V2 121.39 1.095 132.92
Capping beam, W1 10.04 0.850 8.53
Pier - W2 38.39 0.850 32.63
Pier - W3 63.66 0.850 54.11
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
Longitudinal Forces
Tractive force 23.14 5.250 121.49
force 1.425 1.545 2.2
force 3.02 0.886 2.68
force 1.52 2.900 4.41
Sub Total 344.40 130.78
Total bending moment M 213.6 kNm/m M
= 213.6
kNm/m
Total bending moment = 213.6 kNm/m

6.2.3.2a Check for Stability

Factor of safety against overturning


RDA Bridge
Design Manual F.O.S = Stability moment / Over turning F.O.S
Cl. 2.1 = 344.40 / 130.8 = 2.6
= 2.6 > 1.3

Therefore section is safe in stability.

6.2.3.2b Check for StressesKz


z
z 


 d
d
d













0
0

b

.
.0
5
5
d


.
M
5
2






f
0
0.
.
cu
2
2



5
5

0
.
.
.
004
0
2
0
0
5
.
.
1
9
9


3














 0
K
. 9







Total vertical force, V = 425.57 kN/m

Eccentricity of the resultant force from the edge of the section (e')

e' = Ms – Mo
V

e' = 344.4 - 130.8


425.6

e' = 0.502 m e'


= 0.502
Eccentricity of the vertical force from the centre of the section (e) m

e = b/2 - e'
e = 1.700 /2 - 0.50
e = 0.348 m e
= 0.348
m
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
Second moment of innertia , I
3
I = 1/12 x b x d

3
I = 1.7 X 1.00
12

I = 0.409 m4

Bending moment, M
M = V× e
M = 425.6 X 0.348
M = 148.1 kNm/m

Bending stress, σ b
σb = Mxy
I
σb = 148.1 X 0.85
0.409

2
σb = 307.5 kN/m /m

Direct stress, σ d
σd = V
bd
σd = 425.6
1.7 X 1.00

2
σd = 250.34 kN/m /m

Maximum stress, σ max


σ max = σd + σb
= 250.34 + 307.50 σ max
= 557.84 kN/m 2 /m = 557.84
kN/m 2 /m
Minimum stress, σ min
σ min = σd - σb
= 250.34 - 307.50 σ min
2
= -57.2 kN/m /m = -57.2
< 360 kN/m 2 kN/m /m 2

Hence OK
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
6.2.3.3 Analysis of Pier section 4 for Stability
Specimen calculation for section 4 per unit width of the Pier

Table 6.19 Moments about point D


Load type Design load Length Moment (kNm/m)
(kN/m) from Stability Over turning
A (m) Ms Mo
Vertical Forces
V1 192.09 0.805 154.63
V2 121.39 1.295 157.20
Capping beam, W1 10.04 1.050 10.54
Pier - W2 38.39 1.050 40.31
Pier - W3 63.66 1.050 66.84
Pier - W4 74.91 1.050 78.66
Longitudinal Forces
Tractive force 23.14 7.950 183.96
force 2.247 3.535 7.94
force 6.257 2.498 15.63
force 1.52 5.600 8.51
Sub Total 508.18 216.04
Total bending moment M 292.1 kNm/m M
= 292.1
kNm/m
Total bending moment = 292.1 kNm/m

6.2.3.3a Check for Stability

Factor of safety against overturning


RDA Bridge
Design Manual F.O.S = Stability moment / Over turning F.O.S
Cl. 2.1 = 508.18 / 216.0 = 2.4
= 2.4 > 1.3

Therefore section is safe in stability.

6.2.3.3b Check for StressesKz


z
z 


 d
d
d













0
0

b

.
.0
5
5
d


.
M
5
2






f
0
0.
.
cu
2
2



5
5

0
.
.
.
004
0
2
0
0
5
.
.
1
9
9


3














 0
K
. 9







Total vertical force, V = 361.91 kN/m


Eccentricity of the resultant force from the edge of the section (e')

e' = Ms – Mo
V
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT

e' = 508.2 - 216.0


361.9

e' = 0.807 m e'


= 0.807
Eccentricity of the vertical force from the centre of the section (e) m

e = b/2 - e'
e = 2.100 /2 - 0.81
e = 0.243 m e
= 0.243
m
Second moment of innertia , I
3
I = 1/12 x b x d

3
I = 2.100 X 1.00
12

4
I = 0.7718 m

Bending moment, M
M = V× e
M = 361.9 X 0.243
M = 87.9 kNm/m

Bending stress, σ b
σb = Mxy
I
σb = 87.9 X 1.05
0.772

2
σb = 119.5 kN/m /m

Direct stress, σ d
σd = V
bd
σd = 361.9
2.1 X 1.00

2
σd = 172.34 kN/m /m
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT

Maximum stress, σ max


σ max = σd + σb
= 172.34 + 119.54 σ max
2
= 291.88 kN/m /m = 291.88
kN/m 2 /m

Minimum stress, σ min


σ min = σd - σb
= 172.34 - 119.54 σ min
= 52.8 kN/m 2 /m = 52.8
< 360 2 2
kN/m kN/m /m
Hence OK

6.2.3.4 Analysis of Pier section 5 for Stability


Specimen calculation for section 5 per unit width of the Pier

Table 6.20 Moments about point E


Load type Design load Length Moment (kNm/m)
(kN/m) from Stability Over turning
A (m) Ms Mo
Vertical Forces
V1 192.09 1.005 193.05
V2 121.39 1.495 181.48
Capping beam, W1 10.04 1.250 12.55
Pier - W2 38.39 1.250 47.99
Pier - W3 63.66 1.250 79.58
Pier - W4 74.91 1.250 93.64
Pier - W5 72.41 1.250 90.51
Longitudinal Forces
Tractive force 23.14 10.15 234.87
force 2.557 4.932 12.61
force 7.478 4.124 30.84
force 1.52 7.800 11.86
Sub Total 698.80 290.18
Total bending moment M 408.6 kNm/m M
= 408.6
Total bending moment = 408.6 kNm/m kNm/m

6.2.3.4a Check for Stability

Factor of safety against overturning


MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
RDA Bridge F.O.S = Stability moment / Over turning F.O.S
Design Manual = 698.80 / 290.2 = 2.4
Cl. 2.1 = 2.4 > 1.3

Therefore section is safe in stability.

6.2.3.4b Check for Stresses Kz


z
z 


 d
d
d













0
0

b

.
.0
5
5
d


.
M
5
2






f
0
0.
.
cu
2
2



5
5

0
.
.
.
004
0
2
0
0
5
.
.
1
9
9


3














 0
K
. 9







Total vertical force, V = 361.91 kN/m

Eccentricity of the resultant force from the edge of the section (e')

e' = Ms – Mo
V

e' = 698.8 - 290.2


361.9

e' = 1.129 m e'


= 1.129
Eccentricity of the vertical force from the centre of the section (e) m

e = b/2 - e'
e = 2.500 /2 - 1.13
e = 0.121 m e
= 0.121
m
Second moment of innertia , I
I = 1/12 x b 3 x d

3
I = 2.500 X 1.00
12

4
I = 1.302 m

Bending moment, M
M = V× e
M = 361.9 X 0.121
M = 43.8 kNm/m

Bending stress, σ b
σb = Mxy
I
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
σb = 43.8 X 1.25
1.302

2
σb = 42.0 kN/m /m

Direct stress, σ d
σd = V
bd
σd = 361.9
2.5 X 1.00

2
σd = 144.76 kN/m /m

Maximum stress, σ max


σ max = σd + σb
= 144.76 + 42.02 σ max
2
= 186.78 kN/m /m = 186.78
kN/m 2 /m

Minimum stress, σ min


σ min = σd - σb
= 144.76 - 42.02 σ min
2
= 102.7 kN/m /m = 102.75
< 360 kN/m 2 kN/m 2 /m
Hence OK

6.2.3.5 Analysis of Pier Foundation for Stability

Table 6.21 Moments about point F


Load type Design load Length Moment (kNm/m)
(kN/m) from Stability Over turning
A (m) Ms Mo
Vertical Forces
V1 192.09 1.505 289.10
V2 121.39 1.995 242.17
Capping beam, W1 10.04 1.750 17.57
Pier - W2 38.39 1.750 67.18
Pier - W3 63.66 1.750 111.41
Pier - W4 74.91 1.750 131.09
Pier - W5 72.41 1.750 126.72
Pier - W6 39.44 1.750 69.02
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
Longitudinal Forces
Tractive force 23.14 10.95 253.38
force 2.59 5.876 15.22
force 3.4 5.075 17.26
force 1.52 8.813 13.4
Sub Total 1054.26 299.26
Total bending moment M 755.0 kNm/m M
= 755.0
kNm/m
Total bending moment = 755.0 kNm/m

6.2.3.5a Check for Stability

Factor of safety against overturning


RDA Bridge
Design Manual F.O.S = Stability moment / Over turning F.O.S
Cl. 2.1 = 1054.26 / 299.3 = 3.5
= 3.5 > 1.3

Therefore section is safe in stability.

6.2.3.5b Check for StressesKz


z
z 


 d
d
d













0
0

b

.
.0
5
5
d


.
M
5
2






f
0
0.
.
cu
2
2



5
5

0
.
.
.
004
0
2
0
0
5
.
.
1
9
9


3














 0
K
. 9







Total vertical force, V = 612.33 kN/m

Eccentricity of the resultant force from the edge of the section (e')

e' = Ms – Mo
V

e' = 1054.3 - 299.3


612.3

e' = 1.233 m e'


= 1.233
Eccentricity of the vertical force from the centre of the section (e) m

e = b/2 - e'
e = 3.500 /2 - 1.23
e = 0.517 m e
= 0.517
m
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
X

1000
F
X
3500

Fig. 6.3 Axis of Bending of Pier Foundation

Second moment of innertia , I


I = 1/12 x b 3 x d

3
I = 3.500 X 1.00
12

4
I = 3.573 m

Bending moment, M
M = V× e
M = 506.3 X 0.517
M = 261.7 kNm/m

Bending stress, σ b
σb = Mxy
I
σb = 261.7 X 1.75
3.573

2
σb = 128.20 kN/m /m

Direct stress, σ d
σd = V
bd
σd = 506.3
3.5 X 1.00

2
σd = 144.64 kN/m /m

Maximum stress, σ max


σ max = σd + σb
= 144.64 + 128.20 σ max
2
= 272.84 kN/m /m = 272.84
2
kN/m /m
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT

Minimum stress, σ min


σ min = σd - σb
= 144.64 - 128.20 σ min
2
= 16.45 kN/m /m = 16.45
< 360 kN/m 2 kN/m 2 /m
Hence OK

Stress Redistribution under the Foundation at Serviceability


Limit State

Le
V
2 e' e'

3.500

Fig. 6.4 Stress Redistribution under the Foundation at SLS

Let the redistributed maximum bearing pressure under


the foundation be σ and effective length be Le (m)
Le/3 = e'
Therefore
V = 1/2×σ×Le
σ = 2V
3e'
2 X 612.33
3 X 1.23
= 331.08 kN/m 2
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
Allowable Bearing Capacity of Foundation
Reynolds Hand Since hard rock has been exposed, Bearing capacity of rock
Book Table 191 can be taken as( igneous and gniessic: sound) 10000 kN/m2
But due to rock fractures ,unforeseen condition etc.
2
allowable bearing capacity under foundation is limited to 600kN/m

Before staring construction of Piers allowble bearing


capacity of rock can be made sure by conduductin RQD
( Rock Quality Designation) Test, if there is a question arised,
due to the precsence of fracture of rock

The permissible bearing pressure under foundation is


600 kN/m2 > 331.08 kN/m2
Hence Satisfactory.

6.2.3.5c Checking for sliding

Foundation Design,
Total Horizontal force (H) = 30.65 kN/m
J.E. Bowels
Table 11-6 Friction angle δ between concrete interface
0
δ = 30
0
μ = tan (30 )
= 0.58

Reynolds Frictional force (R) = µ x Vertical force


Hand Book = 0.58 x 612.33
Table 187 = 353.31 kN/m

F.O.S = Frictional force (R)


Horizontal force (H)

F.O.S = 353.31
30.65
F.O.S = 11.5 > 1.5

Hence Section is safe against sliding.


MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
6.2 DESIGN OF PIER STEM AND BASE
6.2.4 Wet Condition Ultimate limit state

450 855
V1 V2

W1
A

1900
W2
WATER CURRENT PRESSURE
P1 = 52 K V2
400 900 B HFL 542.866

400
1200
DEBRIS FORCE PRESSURE
P2 = 52 K V2

2500
W3

200 1700

200
C

2500
W4

200 2100 D

200
300-2000
VARIES

W5

500 2500 E DEEPEST SCOUR LEVEL


600

W6
534.300 F
3500

Fig. 6.5 Section of Pier

The stuctural design is made for Ultimate loads.

RDA Bridge Force due to Water Current & Debries and Log Impact
Design Manual Force due to water current & force due to debries are acting
0
Cl. 2.2.5 on a pier with an angle of 20 .

Essentials of Bridge Pressure due to water current = 52 kv2 kg/m 2


Eng. By D.J. Victor V= √2 xMean velocity of water(vm)
4th Edition, 1991 = √2 x 1.6
Cl 3.14 = 2.26 m/s
k= 0.66 (Semi circular cut ways)
2
Water current Pressure = 52 x 0.66 x 2.26
= 175.29 kg/m 2
= 1.72 kg/m 2

Water Current affecting height, h


h = HFL-deepest Scour level
= 542.866 - 534.053
= 8.813 m
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
Water current force, P1 = 1/2 x P1 x h
= 1/2 x 1.72 x 8.813
= 7.58 kN/m

Effective component of water current force Water


0
= P1 Sin20 current
= 7.58 x Sin200 force
= 2.59 kN/m = 2.59
kN/m
2 2
RDA Bridge Pressure due to Floating debris = 52 kv kg/m
Design Manual V= √2 xMean velocity of water(vm)
Cl. 2.2.5 = √2 x 1.6
= 2.26 m/s
k= 1.0 (Semi circular cut ways)

2
Floating debris Pressure = 52 x 1 x 2.26
= 265.6 kg/m 2
2
= 2.61 kg/m

Floating debris affecting height, h


h = HFL-deepest Scour level-1.2m
= 542.866 - 534.053 - 1.2 m
= 7.613 m

Floating debris force, P2 = 1/2 x P1 x h


= 1/2 x 2.61 x 7.613
= 9.93 kN/m

Effective component of Floating debris force Floating


0
= P1 Sin20 debris
= 9.93 x Sin200 force
= 3.4 kN/m = 3.4
kN/m
RDA Bridge Log impact Force P3 = 0.1 W .V
Design Manual V= √2 xMean velocity of water(vm)
Cl. 2.2.5 = √2 x 1.6
= 2.26 m/s
W = Wieght of drifting items
W = 2 ton (assumed)
W = 2 x 9.81 x 1000/1000 kN
W = 19.6 kN

Log impact Force P3 = 0.1 x 19.62 x 2.26


= 4.43 kN/m
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
Effective component of Log impact force
= P1 Sin200 Log impact
= 4.43 x Sin200 force
= 1.52 kN/m = 1.52
kN/m
BS 5400 Part 2 Table 6.22 Calculation of Ultimate loads
Table 1 Load type Nominal γFL γf3 Design
Load (kn/m) Load (kn/m)
BS 5400 Vertical Forces
Part 4 : 1990 Deck dead load 115.53 1.15 1.10 146.15
Cl. 4.2.2 Superimposed dead load 5.86 1.75 1.10 11.28
Live load 70.70 1.50 1.10 116.66
Capping beam, W1 10.04 1.15 1.10 12.7
Pier - W2 38.39 1.15 1.10 48.56
Pier - W3 63.66 1.15 1.10 80.53
Pier - W4 74.91 1.15 1.10 94.76
Pier - W5 72.41 1.15 1.10 91.6
Pier - W6 39.44 1.15 1.10 49.89
Sub Total 652.13
Longitudinal Forces
Tractive force 23.14 1.25 1.10 31.82
Sub Total 31.82

V1 = Dead load + Superimposed dead load + Live load


V2 = Dead load + Superimposed dead load

6.2.4.1 Analysis of Pier section 2 for Stability


Specimen calculation for section 2 per unit width of the Pier

Table 6.23 Moments about point B


Load type Design load Length Moment (kNm/m)
(kN/m) from Stability Over turning
A (m) Ms Mo
Vertical Forces
V1 192.09 0.205 39.38
V2 121.39 0.695 84.37
Capping beam, W1 12.7 0.450 5.72
Pier - W2 48.56 0.450 21.85
Longitudinal Forces
Tractive force 31.82 2.350 74.78
Sub Total 151.32 74.78
Total bending moment M 76.5 kNm/m M
= 76.5
Total bending moment = 76.5 kNm/m kNm/m
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
6.2.4.1a Check for Stability

Factor of safety against overturning


RDA Bridge
Design Manual F.O.S = Stability moment / Over turning F.O.S
Cl. 2.1 = 151.32 / 74.8 = 2.0
= 2.0 > 1.3

Therefore section is safe in stability.

6.2.4.1b Check for Stresses Kz


z
z 


 d
d
d













0
0

b

.
.0
5
5
d


.
M
5
2






f
0
0.
.
cu
2
2



5
5

0
.
.
.
004
0
2
0
0
5
.
.
1
9
9


3














 0
K
. 9







Total vertical force, V = 374.74 kN/m

Eccentricity of the resultant force from the edge of the section (e')

e' = Ms – Mo
V

e' = 151.3 - 74.8


374.7

e' = 0.204 m e'


= 0.204
Eccentricity of the vertical force from the centre of the section (e) m

e = b/2 - e'
e = 0.9 /2 - 0.20
e = 0.246 m e
= 0.246
m
Second moment of innertia , I
I = 1/12 x b 3 x d

3
I = 0.9 X 1.00
12

I = 0.0608 m4

Bending moment, M
M = V× e
M = 374.7 X 0.246
M = 92.1 kNm/m
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
Bending stress, σ b
σb = Mxy
I
σb = 92.1 X 0.45
0.061

2
σb = 682.2 kN/m /m

Direct stress, σ d
σd = V
bd
σd = 374.7
0.9 X 1.00

2
σd = 416.38 kN/m /m

Maximum stress, σ max


σ max = σd + σb
= 416.38 + 682.17 σ max
2
= 1098.5 kN/m /m = 1098.5
kN/m 2 /m
Minimum stress, σ min
σ min = σd - σb
= 416.38 - 682.17 σ min
2
= -265.8 kN/m /m = -265.8
< 360 2 2
kN/m kN/m /m
Hence OK

6.2.4.2 Analysis of Pier section 3 for Stability


Specimen calculation for section 3 per unit width of the Pier

Table 6.24 Moments about point C


Load type Design load Length Moment (kNm/m)
(kN/m) from Stability Over turning
A (m) Ms Mo
Vertical Forces
V1 192.09 0.605 116.21
V2 121.39 1.095 132.92
Capping beam, W1 12.70 0.850 10.80
Pier - W2 48.56 0.850 41.28
Pier - W3 80.53 0.850 68.45
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
Longitudinal Forces
Tractive force 31.82 5.250 167.06
force 1.425 1.545 2.2
force 3.02 0.886 2.68
force 1.52 2.900 4.41
Sub Total 369.66 176.35
Total bending moment M 193.3 kNm/m M
= 193.3
kNm/m
Total bending moment = 193.3 kNm/m

6.2.4.2a Check for Stability

Factor of safety against overturning


RDA Bridge
Design Manual F.O.S = Stability moment / Over turning F.O.S
Cl. 2.1 = 369.66 / 176.4 = 2.1
= 2.1 > 1.3

Therefore section is safe in stability.

6.2.4.2b Check for StressesKz


z
z 


 d
d
d













0
0

b

.
.0
5
5
d


.
M
5
2






f
0
0.
.
cu
2
2



5
5

0
.
.
.
004
0
2
0
0
5
.
.
1
9
9


3














 0
K
. 9







Total vertical force, V = 455.27 kN/m

Eccentricity of the resultant force from the edge of the section (e')

e' = Ms – Mo
V

e' = 369.7 - 176.4


455.3

e' = 0.425 m e'


= 0.425
Eccentricity of the vertical force from the centre of the section (e) m

e = b/2 - e'
e = 1.700 /2 - 0.42
e = 0.425 m e
= 0.425
m
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
Second moment of innertia , I
3
I = 1/12 x b x d

3
I = 1.7 X 1.00
12

I = 0.409 m4

Bending moment, M
M = V× e
M = 455.3 X 0.425
M = 193.7 kNm/m

Bending stress, σ b
σb = Mxy
I
σb = 193.7 X 0.85
0.409

2
σb = 402.1 kN/m /m

Direct stress, σ d
σd = V
bd
σd = 455.3
1.7 X 1.00

2
σd = 267.81 kN/m /m

Maximum stress, σ max


σ max = σd + σb
= 267.81 + 402.08 σ max
= 669.89 kN/m 2 /m = 669.89
kN/m 2 /m

Minimum stress, σ min


σ min = σd - σb
= 267.81 - 402.08 σ min
2
= -134.3 kN/m /m = -134.3
< 360 kN/m 2 kN/m 2 /m
Hence OK
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
6.2.4.3 Analysis of Pier section 4 for Stability
Specimen calculation for section 4 per unit width of the Pier

Table 6.25 Moments about point D


Load type Design load Length Moment (kNm/m)
(kN/m) from Stability Over turning
A (m) Ms Mo
Vertical Forces
V1 192.09 0.805 154.63
V2 121.39 1.295 157.20
Capping beam, W1 12.70 1.050 13.34
Pier - W2 48.56 1.050 50.99
Pier - W3 80.53 1.050 84.56
Pier - W4 94.76 1.050 99.50
Longitudinal Forces
Tractive force 31.82 7.950 252.97
force 2.247 3.535 7.94
force 6.257 2.498 15.63
force 1.52 5.600 8.51
Sub Total 560.22 285.05
Total bending moment M 275.2 kNm/m M
= 275.2
kNm/m
Total bending moment = 275.2 kNm/m

6.2.4.3a Check for Stability

Factor of safety against overturning


RDA Bridge
Design Manual F.O.S = Stability moment / Over turning F.O.S
Cl. 2.1 = 560.22 / 285.1 = 2.0
= 2.0 > 1.3
Therefore section is safe in stability.

6.2.4.3b Check for StressesKz


z
z 


 d
d
d













0
0

b

.
.0
5
5
d


.
M
5
2






f
0
0.
.
cu
2
2



5
5

0
.
.
.
004
0
2
0
0
5
.
.
1
9
9


3














 0
K
. 9







Total vertical force, V = 374.74 kN/m

Eccentricity of the resultant force from the edge of the section (e')

e' = Ms – Mo
V
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
e' = 560.2 - 285.1
374.7

e' = 0.7343 m e'


= 0.7343
Eccentricity of the vertical force from the centre of the section (e) m

e = b/2 - e'
e = 2.100 /2 - 0.73
e = 0.316 m e
= 0.316
m
Second moment of innertia , I
3
I = 1/12 x b x d

3
I = 2.100 X 1.00
12

4
I = 0.7718 m

Bending moment, M
M = V× e
M = 374.7 X 0.316
M = 118.3 kNm/m

Bending stress, σ b
σb = Mxy
I
σb = 118.3 X 1.05
0.772

2
σb = 161.0 kN/m /m

Direct stress, σ d
σd = V
bd
σd = 374.7
2.1 X 1.00

2
σd = 178.45 kN/m /m
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
Maximum stress, σ max
σ max = σd + σb
= 178.45 + 160.96 σ max
2
= 339.41 kN/m /m = 339.41
kN/m 2 /m

Minimum stress, σ min


σ min = σd - σb
= 178.45 - 160.96 σ min
= 17.5 kN/m 2 /m = 17.5
< 360 2 2
kN/m kN/m /m
Hence OK

6.2.4.4 Analysis of Pier section 5 for Stability


Specimen calculation for section 5 per unit width of the Pier

Table 6.26 Moments about point E


Load type Design load Length Moment (kNm/m)
(kN/m) from Stability Over turning
A (m) Ms Mo
Vertical Forces
V1 192.09 1.005 193.05
V2 121.39 1.495 181.48
Capping beam, W1 12.70 1.250 15.88
Pier - W2 48.56 1.250 60.70
Pier - W3 80.53 1.250 100.66
Pier - W4 94.76 1.250 118.45
Pier - W5 91.60 1.250 114.50
Longitudinal Forces
Tractive force 31.82 10.15 322.97
force 2.557 4.932 12.61
force 7.478 4.124 30.84
force 1.52 7.800 11.86
Sub Total 784.72 378.28
Total bending moment M 406.4 kNm/m M
= 406.4
Total bending moment = 406.4 kNm/m kNm/m

6.2.4.4a Check for Stability

Factor of safety against overturning


MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
RDA Bridge
Design Manual F.O.S = Stability moment / Over turning F.O.S
Cl. 2.1 = 784.72 / 378.3 = 2.1
= 2.1 > 1.3

Therefore section is safe in stability.

6.2.4.4b Check for Stresses Kz


z
z 


 d
d
d













0
0

b

.
.0
5
5
d


.
M
5
2






f
0
0.
.
cu
2
2



5
5

0
.
.
.
004
0
2
0
0
5
.
.
1
9
9


3














 0
K
. 9







Total vertical force, V = 374.74 kN/m

Eccentricity of the resultant force from the edge of the section (e')

e' = Ms – Mo
V

e' = 784.7 - 378.3


374.7

e' = 1.085 m e'


= 1.085
Eccentricity of the vertical force from the centre of the section (e) m

e = b/2 - e'
e = 2.500 /2 - 1.08
e = 0.165 m e
= 0.165
Second moment of innertia , I m
3
I = 1/12 x b x d

3
I = 2.500 X 1.00
12

4
I = 1.3021 m

Bending moment, M
M = V× e
M = 374.7 X 0.165
M = 62.0 kNm/m

Bending stress, σ b
σb = Mxy
I
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
σb = 62.0 X 1.25
1.302

2
σb = 59.5 kN/m /m

Direct stress, σ d
σd = V
bd
σd = 374.7
2.5 X 1.00

2
σd = 149.90 kN/m /m

Maximum stress, σ max


σ max = σd + σb
= 149.90 + 59.51 σ max
2
= 209.40 kN/m /m = 209.40
kN/m 2 /m

Minimum stress, σ min


σ min = σd - σb
= 149.90 - 59.51 σ min
2
= 90.4 kN/m /m = 90.4
< 360 kN/m 2 kN/m 2 /m
Hence OK

6.2.4.5 Analysis of Pier Foundation for Stability

Table 6.27 Moments about point F


Load type Design load Length Moment (kNm/m)
(kN/m) from Stability Over turning
A (m) Ms Mo
Vertical Forces
V1 192.09 1.505 289.10
V2 121.39 1.995 242.17
Capping beam, W1 12.70 1.750 22.23
Pier - W2 48.56 1.750 84.98
Pier - W3 80.53 1.750 140.93
Pier - W4 94.76 1.750 165.83
Pier - W5 91.60 1.750 160.30
Pier - W6 49.89 1.750 87.31
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
Longitudinal Forces
Tractive force 31.82 10.95 348.43
force 2.59 5.876 15.22
force 3.4 5.075 17.26
force 1.52 8.813 13.4
Sub Total 1192.85 394.31
Total bending moment M 798.5 kNm/m M
= 798.5
kNm/m
Total bending moment = 798.5 kNm/m

6.2.4.5a Check for Stability

Factor of safety against overturning


RDA Bridge
Design Manual F.O.S = Stability moment / Over turning F.O.S
Cl. 2.1 = 1192.85 / 394.3 = 3.0
= 3.0 > 1.3

Therefore section is safe in stability.

6.2.4.5b Check for StressesKz


z
z 


 d
d
d













0
0

b

.
.0
5
5
d


.
M
5
2






f
0
0.
.
cu
2
2



5
5

0
.
.
.
004
0
2
0
0
5
.
.
1
9
9


3














 0
K
. 9







Total vertical force, V = 691.52 kN/m

Eccentricity of the resultant force from the edge of the section (e')

e' = Ms – Mo
V

e' = 1192.9 - 394.3


691.5

e' = 1.155 m e'


= 1.155
Eccentricity of the vertical force from the centre of the section (e) m

e = b/2 - e'
e = 3.500 /2 - 1.15
e = 0.595 m e
= 0.595
m
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
X

1000
F
X
3500

Fig. 6.3 Axis of Bending of Pier Foundation

Second moment of innertia , I


I = 1/12 x b 3 x d

3
I = 3.500 X 1.00
12

4
I = 3.573 m

Bending moment, M
M = V× e
M = 652.1 X 0.595
M = 388.2 kNm/m

Bending stress, σ b
σb = Mxy
I
σb = 388.2 X 1.75
3.573

2
σb = 190.13 kN/m /m

Direct stress, σ d
σd = V
bd
σd = 652.1
3.5 X 1.00

2
σd = 186.32 kN/m /m

Maximum stress, σ max


σ max = σd + σb
= 186.32 + 190.13 σ max
2
= 376.45 kN/m /m = 376.45
2
kN/m /m
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT

Minimum stress, σ min


σ min = σd - σb
= 186.32 - 190.13 σ min
2
= -3.80 kN/m /m = -3.80
< 360 kN/m 2 kN/m 2 /m
Hence OK

Stress Redistribution under the Foundation at Ultimate


Limit State

Le
V
2 e' e'

3.500

Fig. 6.4 Stress Redistribution under the Foundation at ULS

Let the redistributed maximum bearing pressure under


the foundation be σ and effective length be Le (m)
Le/3 = e'
Therefore
V = 1/2×σ×Le
σ = 2V
3e'
2 X 691.52
3 X 1.15
= 399.23 kN/m 2
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
Allowable Bearing Capacity of Foundation
Reynolds Hand Since hard rock has been exposed, Bearing capacity of rock
Book Table 191 can be taken as( igneous and gniessic: sound) 10000 kN/m2
But due to rock fractures ,unforeseen condition etc.
2
allowable bearing capacity under foundation is limited to 600kN/m

Before staring construction of Piers allowble bearing


capacity of rock can be made sure by conduductin RQD
( Rock Quality Designation) Test, if there is a question arised,
due to the precsence of fracture of rock

The permissible bearing pressure under foundation is


600 kN/m2 > 399.23 kN/m2
Hence Satisfactory.

6.2.4.5c Checking for sliding

Foundation Design,
Total Horizontal force (H) = 39.33 kN/m
J.E. Bowels
Table 11-6 Friction angle δ between concrete interface
0
δ = 30
0
μ = tan (30 )
= 0.58

Reynolds Frictional force (R) = µ x Vertical force


Hand Book = 0.58 x 691.52
Table 187 = 399 kN/m

F.O.S = Frictional force (R)


Horizontal force (H)

F.O.S = 399.00
39.33
F.O.S = 10.1 > 1.5

Hence Section is safe against sliding.


MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
6.2.5 DESIGN OF REINFORCEMENT FOR PIER
FOUNDATION

This is calculated for Ultimate Limit State

Diameter of tor steel bar = 16 mm

Nominal cover = 50 mm

Depth of foundation = 600 mm

Effective Depth
d = (600 -50- 16/2)
= 542 mm

Width of the considered foundation section


b = 1000 mm

Width of the foundation


b = 3500 mm

(From 6.2.2 Dry Condition Ultimate limit state)

Ultimate Vertical Load (Vu) = 916.9 kN/m

Ultimate Stability Moment (Msu) = 1587.2 kNm/m

Ultimate Over Turning Moment (Mou) = 348.4 kNm/m

Eccentricity of the resulten force from the edge of the section


e' = 1.351 m

Eccentricity of the vertical force from the centre of the section


e = 0.399 m

2
Maximum stress, σ umax = 422.15 kN/m /m

2
Minimum stress, σ min = 79.27 kN/m /m

m
Rredistrubuted max bearing pressure under the foundation
σu = 452.41 kN/m 2
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT

Lu

Vu
2e' e'

Y
σu

0.50

0.6

b 3.50 Y
Figure 6.7 Stress distribution diagram of left Pier
foundation under Ultimate Limit stage

Bending moment M x at any section given by

X2 X2
  U   X   2
1
MX X 
2 2 3

But,  X 
 X  U 
1  

 Le 

Hence,
U X 2  X 
MX   3  
6  Le 

Ultimate bending moment @ Section Y-Y, MY-Y

When, X = 0.5 m

2
MY-Y = 452.41 x 0.5 x (3 - 0.5 / 4.053)
6

= 54.23 kNm
Kz 
 d

b
 d


 0
M
. 5
2

f cu



0 . 25 
0
K
. 9







BS 8110 K' = 0.156


Part 1 : 1997
M
Cl. 3.4.4.4 K  2
bd f cu
fcu = 25 N/mm2

K = 54.2
1000Х 542^2 Х 25
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT

= 0.0074

K < K'
Therefore, compression reinforcement is not required.


  K  
Lever arm, z  d  0 .5   0 . 25  

  0 .9  


  .012
z  d0.5 0.25 

  0.9 

z = 537.52 mm

But z should not exceed 0.95d


0.95 d = 0.95 x 542
= 515 mm
Therefore get, z = 515 mm

Required tension reinforcement , As = M


0.95  f y  z

AS = 54.2 x 106
0.95 x 460 x 515

AS = 241 mm2

100AS = 100 x 241


bd 1000 x 542

= 0.04 < 0.15

Hence nominal reinforcement shall be provided.

6.2.5.1 Main Reinforcement

BS 5400 Minimum main reinforcement requirement


Part 4 : 1990 AS = 0.15 x bd/100 mm2
Cl. 5.8.4.1 = 0.15 x 1000 x 542
100
= 813 mm2
No. of bars in section = 813/(π x 16^2/4)
= 4.05
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
Main bars
T16 @175
Provde T 16 @ 175 mm

Therefore Provide16mm Φ tor steel bars at 175mm intervals

provided As = (π x 16^2/4) Х 5.71 mm2


= 1149.4 mm2

Provided 100As/bd= 100x 1149 /(542x1000) As,prov


= 0.212 = 1149.4
mm2

6.2.5.2 Secondary Reinforcement

BS 5400 Minimum secondary reinforcement requirement


Part 4 : 1990 AS = 0.12 x bd/100 mm2
Cl. 5.8.4.2 = 0.12 x 1000 x 542
100
2
= 650 mm
No. of bars per 1m = 650 /(π x 16^2/4) Second. bars
= 3.24 T16 @250
Provde T 16 @ 250 mm

Therefore Provide16mm Φ tor steel bars at 250mm intervals

provided As = (π x ^2/4) Х 4 mm2


= 804.57 mm2

Provided 100As/bd= 100x 805 /(542x1000) As,prov


= 0.148 = 804.57
mm2
6.2.5.3 longitudinal Reinforcement for faces
BS 5400
Part 4 : 1990 Depth of side face > 600mm
Cl. 5.8.4.2 Minimum reinforcement requirement
AS = 0.05 x bd/100 mm2
= 0.12 x 1000 x 542
100
2
= 650 mm
No. of bars = 650 /(π x 16^2/4) No of. bars
= 3.24 4 T 16
Provde 4 T 16 @ 200 mm @200
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
Therefore Provide16mm Φ tor steel bars at 200mm intervals

provided As = (π x 16^2/4) Х 4 mm
2
2
= 804.57 mm As,prov
= 804.57
mm2
BS 5400 6.2.5.4 Check Shear for Pier Foundation
Part 4 : 1990
Cl. 5.3.3.1 Refer Figure 6.7
Shear stress at distance X from the edge of the foundation is Vx

Stress at any point


 X 
 X   U 1  
 Le 

And Shear force at any point of foundation

VX 
 U   X  X
2
U X  X 
VX   2  
2  Le 

Shear stress at any point of foundation

U X  X 
vX   2  
2d  Le 

When X = 0.500 m
vx = 452.41 x 0.500 x ( 2 - 0.500 )
2 x 0.542 4.05

vx = 391.61 KN/m2 vx =
3
= 0.392 N/mm 0.392
N/mm2
When X = 0.250 m
vx = 452.41 x 0.250 x ( 2 - 0.250 )
2 x 0.542 4.05

vx = 202.24 KN/m2
= 0.2 N/mm3

0.75√(fcu) = 0.75√(25)
= 3.75 N/mm2 > vx
Hence OK
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
Depth factor, ξs = (500/d)^(1/4)
= 500 ^(1/4)
542
= 0.98

Provided 100As/bd = 0.21

BS 5400 Ultimate shear stress in concrete vc


Part 4 : 1990 by linear interpolation
Table 8 100As/bd v c (N/mm2)
0.15 0.34
0.25 0.4
0.21 0.38

vc = 0.38 N/mm2
E s .vc = 0.98 x 0.38
2
= 0.37 N/mm
BS 5400 = 369.69 KN/m3 > v
Part 4 : 1990
Cl.5.4.4.1 Hence, shear rienforcement is not required



 M   . 022 
 K  

Kz
z 

 d
d
0.0
5 
. 5 
 0. 25
0 . 25 
  

b 2
 d f cu  0.9 
0 . 9  

6.2.5.5 Check for crack width of foundation

SLS BM due to live loads (Mq) = 107 kN/m


SLS BM due to dead loads (Mg) = 1005.4 kN/m
Total SLS BM for Crack width = 1112.6 kN/m
Bar Spacing = 175 mm
Main R/F diameter = 16 mm
Cover for R/F = 50 mm
Effective depth(d) = 542 mm
Section thickness(h) = 600 mm
Width of section (b) = 1000 mm
As provided = 1149 mm2
Reinforcement ratio ( ϕ = As/bh ) = 0.0021
2
BS 5400 Grade of concrete fcu = 25 N/mm
Part 4 : 1990 Static modulus of concrete (Ec) = 26 kN/mm2
Table 03 Modulus of elasticity of steel (Es) = 200 kN/mm2
Cl.4.3.2.1 Modular ratio (α = Es /(Ec/2) ) = 15.38
Cl.4.3.2.2 Characteristic strenth of R/F = 460 N/mm2

ɛc
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
ɛc fcb

h d Neutral axis

ɛs fs

ɛ1

Figure 6.8 Stress Strain Diagram

x/d = -αϕ + [αϕ(2+αϕ)]^(1/2)

x = -15.38x0.0021 +
542 [15.38x0.0021(2+15.38x0.0021)]^(1/2)

x = 0.223903 x 542
= 121 mm

Leaver arm ,z = d-x/3


= 542 - 121 /3
= 502 mm

At Servicebility limit state

700mm
110

235

3500 mm
4850mm

σ
= 110+(235-110)*(4.85-.7)/4.85
= 217 kN/m2
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
Moment at Servicebility limit state,M
M = 0.7x0.7x217/2+0.7x0.7/2x2/3x(235-217)
= 56.11 kNm

Steel tension stress, fs = M


As z
56.11 x 106
1149 x 502.00
= 97.278 N/mm2

0.87fy = 0.87 x 460


2
= 400.2 N/mm
BS 5400
Part 4 : 1990 fs < 0.87fy
Cl.5.3.2.3 Hence O.K

Concrete Compression Stress, fcb = 2M


fcb = 2M xbz
xbz
= 2 x 56.11 x 106
121 x 1000 x 502

= 1.85 N/mm2

0.45fcu = 0.45 x 25.00


= 11.25 N/mm2

fcb < 0.45fcu


Hence O.K

Calculated stain at notational surface,ɛ1

ɛ1 = fs h-x
Es d-x

= 97.278 600 - 121


200 x 103 542 - 121

= 0.000553
MÄGA ENGINEERING (PVT) LTD. Design of Halaba Bridge at 8+380 Sheet No
200, Nawala Road, Narahenpita Badulla Kandy New Raja mawatha
Colombo - 05, Sri Lanka. Designed by : Date :
Tel: 2808835 to 44 Fax: 2808846 & 47 Checked by : Date :
REFERANCE CALCULATIONS OUT PUT
Calculated strain in the tension reinforcement ,ɛs
ɛs = fs
Es
= 97.278
3
200 x 10

= 0.000486

Moment at the section considered due to permenent loads,Mg


Mg = 1348 x 56.11 kNm
1366

= 55.4 kNm

Moment at the section considered due to live loads,Mq


Mq = 18 x 56.11 kNm
1366

= 0.7 kNm

dc = x = 121 mm

a' = 600 - 50
= 550 mm

BS 5400 Calculated stain at cracking surface,ɛm


Part 4 : 1990
Cl.5.8.8.2 ɛm = ɛ1 - 3.8bth(a'-dc) 1- Mq 10-9
Equation 25 ɛsAs(h-dc) Mg

= 0.000553 - 3.8 x1000X600(550-121)


0.000486x1149(600-121)

x 1 - 1 x 10-9
55

= 0.000553 - 0.003609145
= -0.003056
ɛm < 0
Hence section is uncracked