SIA-B

Standard CT’s
Overcurrent & Earth Fault Protection
Relay for Secondary Distribution
Reliable OC&EF Dual & Self Powered
Protection Relay

ANSI CODE PROTECTIONS Overcurrent & Earth Fault Protection Relay

50 Instantaneus phase Secondary Distribution Protection, RMU’s, MRMU’s and SF6 insulated
overcurrent
switchgears
50/51 Inverse time phase
overcurrent
•T
 he SIA-B is an overcurrent protection relay with self powered and dual
50G Instantaneus measured
neutral overcurrent powered (Self-powering + Auxiliary power) options.

Inverse time measured •T


 he relay is self powered using the operating current through three /1 (<2VA)
50/51G neutral overcurrent standard current transformers fitted on the lines. These transformers are also
used to obtain current measurements. Besides, SIA-B relay can be used with
46 Phase balance current auxiliary power supply (24-230 Vac/dc). The relay can be also supplied by
a USB cable connected to the laptop, with the USB KITCOM adapter or an
49 Thermal image
standard power bank.
CLP Cold Load Pick-up • Internal commissioning battery included. (Lithium battery: 20 years lifetime).
SHB Second Harmonic Blocking •M
 icro USB front port connection (Modbus RTU protocol) for local
communication. Remote communication through rear RS485 port (Modbus
50BF Circuit Breaker opening RTU or DNP 3.0 selectable by general setting) as optional.
failure
• Configurable inputs and outputs.
52 Circuit Breaker monitoring
• Specific test menu is provided.
49T External Trip
• High electromagnetic compatibility (EMC).
TB Trip Block for switch
disconnector •T
 he installation and subsequent maintenance of external batteries is
eliminated. The operating costs of the centre are reduced.
68 Zone selection interlocking
•R
 eally low start-up levels: 75 mA in three phase system /160 mA in single
PGC Programmable logic control phase system.
•T
 he line opening mechanism is activated by means of a striker PRT, operated
by the energy supplied by the relay.
•4
 configurable bistable LEDs. When the relay is switched off, their previous
states can be checked by powering the relay up (by self-powering the relay,
through USB cable, auxiliary voltage or pressing commissioning battery).

26
• Self diagnosis of the status (Watchdog) through leds and physical outputs.
• The SIA-B is fitted with the demand of current (Load Data Profiling) with the following characteristics:
Number of records: 168
Recording mode: circular
Sampling rate (interval): configurable through communications: 1-60 min.
• Stores up to 1024 events and DFR (20 fault reports in data format and 10 reports
in COMTRADE format) in Non-volatile RAM memory, maintaining date & time
thanks to its internal RTC (Real Time Clock) even without power supply.

Multiple options for powering and communication

Functions diagram SIA-B

Battery 5 Vdc

Tx Rx
Events
50_1 50_2* 50/51 RTC (1 ms)
CLP* DFR
SHB 46* 49 4 Settings groups
Power Demand
50G_1 50G_2* 50/51G
Leds config.

68* PGC Out config.


TB* 52 50BF*
Input config.
Test
49T*
Hmi
LCD 20x2
RS485* 8 keys
Vaux* RTC Trip
* optional

*Available through
configurable inputs

27
Technical parameters SIA-B

Function Enable: yes/no/SHB Function Enable: yes/no


Current tap: 0.07 to 20 x In (step 0.01 x In) Current tap: 0.10 to 2.40 x In (step 0.01)
Time delay: 0.02 to 300 s (step 0.01 s) ζ heating: 3 to 600 minutes (step 1 min)
Activation level 100% ζ cooling: 1 to 6 x ζ heating (step 1)
Function 50_1 Function 49
Deactivation level 95% Alarm: 20 to 99% (step 1 %)
Instantaneous deactivation
Function 50_2 (*) Trip level: 100%
Timing accuracy:
Trip reset: 95% of alarm level
Without SHB permitted: ± 30 ms or ± 0.5% (greater
of both). Timing accuracy: ± 5% regarding theoretical value
With SHB permitted: ± 50 ms or ± 0.5% (greater of Function Enable: yes/no
both).
Current Tap: 5% to 50% (step 1%)
Function Enable: yes/no/SHB Function SHB
Reset Time: 0.00 to 300 s (step 0.02 s)
Current tap: 0.05 to 10 x In (step 0.01 x In)
Block Threshold: 0.07 to 20 x In (step 0.01 x In)
Time delay: 0.02 to 300 s (step 0.01 s)
Maximum number of openings: 1 to 10000 (step 1)
Activation level 100%
Function 50G_1 Maximum accumulated amps: 0 to 100000 (M(A²)) (step 1)
Deactivation level 95%
Opening time: 0.02 to 30 s (step 0.01 s)
Instantaneous deactivation Function 52
Function 50G_2 (*) Closing time: 0.02 to 30 s (step 0.01 s)
Timing accuracy:
Maximum repeated openings: 1 to 10000 (step 1)
Without SHB permitted: ± 30 ms or ± 0.5% (greater
of both). Time of max. repeated openings: 1 to 300 min (step 1 min)
With SHB permitted: ± 50 ms or ± 0.5% (greater of Function Enable: yes/no
both).
Settings group: 1 to 4 (step 1)
Function Enable: yes/no/SHB
No load time: 0.02 to 300 s (step 0.01 s)
Current tap: 0.07 to 7 x In (step 0.01 x In) Function CLP (*)
Cold load time: 0.02 to 300 s (step 0.01 s)
Curves: IEC 60255-151 and IEEE
CLP activation threshold: 60 mA
Curve type: IEC Inverse curve, IEC very inverse curve,
IEC extremely inverse curve, IEC long time inverse, IEEE CLP reset threshold: 80 mA
Inverse curve, IEEE very inverse curve, IEEE extremely Function Enable: yes/no
inverse curve.
Current tap: 0.10 to 7.00 xIn (step 0.01)
Time delay: 0.02 to 300 s (step 0.01 s)
Curves IEC 60255-151 and IEEE
Time dial (TMS): 0.01 to 1.5 (step 0.01)
Curve type: IEC Inverse curve, IEC very inverse curve,
Function 50/51 Curve, activation level 110% IEC extremely inverse curve, IEC long time inverse, IEEE
Curve, deactivation level 100% Inverse curve, IEEE very inverse curve, IEEE extremely
inverse curve.
Defined time, activation level 100%
Function 46 (*) Time delay: 0.02 to 300 s (step 0.01 s)
Defined time, deactivation level 95%
Time dial (TMS): 0.01 to 1.5 (step 0.01)
Instantaneous deactivation Curve, activation level 110%
Timing accuracy: Curve, deactivation level 100%
Without SHB permitted: ± 30 ms or ± 5% (greater
of both). Defined time, activation level 100%
With SHB permitted: ± 50 ms or ± 5% (greater of Defined time, deactivation level 95%
both). Instantaneous deactivation
Function Enable: yes/no/SHB Function 49T Available through configurable inputs
Current tap: 0.05 to 7 x In (step 0.01 x In) Available through configurable inputs and outputs
Function 68
Curves: IEC 60255-151 and IEEE thanks to programable logic

Curve type: IEC Inverse curve, IEC very inverse curve, Blocking: yes/no
IEC extremely inverse curve, IEC long time inverse, IEEE Trip Block (*)
Current tap: 1.5 to 20 x In (step 0.01)
Inverse curve, IEEE very inverse curve, IEEE extremely
inverse curve. Function Enable: yes/no
Time delay: 0.02 to 300 s (step 0.01 s) Function 50BF (*) Time delay: 0.02 to 1.00 s (step 0.01 s)
Time dial (TMS): 0.01 to 1.5 (step 0.01) Open circuit breaker activation threshold: 60 mA

Curve, activation level 110% OR4, OR4_LATCH, OR4_PULSES, OR4_TIMERUP,


Function 50/51G OR4_PULSE, NOR4, NOR4_TIMERUP, NOR4_PULSE,
Programmable
Curve, deactivation level 100% NOR4_PULSES, AND4, AND4_LATCH, AND4_PULSES,
logic control (PGC)
AND4_TIMERUP, AND4_PULSE, NAND4, NAND4_
Defined time, activation level 100% TIMERUP, NAND4_PULSE.
Defined time, deactivation level 95% Settings groups 4 settings groups: Activated by inputs or by general settings
Instantaneous deactivation Events 1024 events
Timing accuracy: Disturbance Fault 20 fault reports, 16 events in each
Without SHB permitted: ± 30 ms or ± 5% (greater Recording (DFR) 10 Oscillographic records (50 cycles each)
of both).
With SHB permitted: ± 50 ms or ± 5% (greater of
both).

28
Technical parameters SIA-B

Demand of current with the following characteristics: Micro USB front port: Modbus RTU
Communication
• Number of records: 168 RS485 port: Modbus RTU or DNP3.0 Serial (*)
• Recording mode circular Auxiliary power 24-230 Vac/dc +10% / -20%
• Sampling rate (interval): configurable through supply
communications: 1 – 60 min With USB KITCOM adapter or standard power bank
Load Data Battery supply
• Record format: Internal commissioning battery
Profiling (Current
Demand) - Date/Time
Self-power from Three phase self-power level:
- IMAX (in interval)
current I > 75mA
- IMAX (actual)
- IA Operating temperature: -40 to 70ºC
- IB Environment Storage temperature: -40 to 80 ºC
- IC
- IN Humidity: 95%

Trip output For Striker: 24 Vdc-135 mJ Transformers Power supply and measurement CT /1

3 changeover outputs (output 1, output 2 and output 3): Metallic box

Signaling outputs Panel Mounting


250 Vac – 8 A
220 Vdc – 8 A Height x Width:
Mechanical
3 inputs: They are activated by short-circuiting the 90 x 245 (mm)
Signaling inputs features
terminals without external supply Depth:
Frequency Selectable by general settings 139.4 (mm)
Fundamental values (DFT) IP-54
Sampling: 16 samples/cycle Weight 3 Kg.
Current
measurement Accuracy of ±2% on a band of ±20% over the nominal
current and ±4% or ± 5mA (greater of both) over the
rest of the range.

Connections diagram SIA-B


• 3 CT power supply-measurement
• Striker
• Rigid neutral

(*) Example of connections diagram


29
Dimensions and cutout SIA-B

CUTOUT
PANEL CUTOUT

30
Selection & Ordering data SIA-B

SIA-B
Overcurrent & Earth Fault Protection PROTECTION FUNCTIONS
Relay - Dual & Self Powered 50_1 + 50/51 + 50G_1 + 50/51G + PGC
PHASE MEASUREMENT
1 In= 1 A: (0.10 - 30.00 A)
NEUTRAL MEASUREMENT
1
In= 1 A: (0.05 - 16.00 A)
NET FREQUENCY
0
Defined by General Settings
POWER SUPPLY
A Self-powered + Commissioning battery
Self-powered + 24-230 Vac/dc (Dual) + Commissioning battery
F
ADDITIONAL FUNCTIONS
C + 49 + SHB + 4 Settings groups + LDP + DFR + 52

D + 49 + SHB + 4 Settings groups + LDP + DFR + 52 + 46 + Trip


Block for switch disconnector + 50_2 + 50G_2 + CLP + 50BF
COMMUNICATIONS
0 USB (Modbus RTU)
2 USB (Modbus RTU) + RS485 (Modbus RTU or DNP3.0 Serial)
INPUTS AND OUTPUTS
3 4 LEDs + Trip (Striker) + 3 Outputs + 3 Inputs
MECHANICAL ASSEMBLY
2 Extended Horizontal Assembly
6 Extended Horizontal Assembly with anticorrosive treatment
LANGUAGE
A English, Spanish and German
B English, Spanish and Turkish
C English , Spanish and French
D English , Spanish and Russian
ADAPTATION
C Standard CTs /1

Example of ordering code:


SIA B 1 1 0 F C 0 3 2 A C SIA B 1 1 0 F C 0 3 2 A C