Sie sind auf Seite 1von 29

TCI

 Services,  Inc.  
Kevin  Kupitz  
Levi  Laughlin    
Tank  Inspection  Decision  Process  
Simplified  

Federal,  State,  Local  


Regulations  

Good  Engineering  Practices  


Best  Practice  

Industry  Accepted  Practices  


for  ASTs  

American  Petroleum  Institute   Steel  Tank  Industry  


API-­‐653   STI  SP001  5th  Edition  
“Tank  Inspection,  Repair,   “Standard  for  the  Inspection  of  
Alteration  and  Construction”   Above  Ground  Storage  Tanks”  
•         Vertical,  cylindrical,  Above  Ground,  
Closed  and  Open  Top,  Welded  
Storage  Tanks  in  various  sizes  and  
capacities  for  internal  pressure  
approximate  of  atmospheric    
pressure.      
 
•       Max  design  temp  of  200°F.  
 
•       For  storage  of  petroleum,  
petroleum  products  and  other  liquid  
products.  
 
•       Field  Erected    
•         Applies  to  the  inspection  of  Above  
Ground  Storage  tanks.    
 
•       These  storage  tanks  include  shop-­‐
fabricated  tanks,  field  erected  tanks  and  
portable  containers  as  defined  in  this  
standard,  as  well  as  their  containment  
systems.  

•       For  ASTs  storing  stable,  flammable  


and  combustible  liquids  at  atmospheric  
pressure  with  a  specific  gravity  less  than  
1.0.      
 
•       For  temperatures  between  ambient  
and  200°F.    
API  653   Field  Erected  Tank   STI-­‐  SP001  
API  653   Vertical  Tank   STI-­‐  SP001  
  Shop-­‐  Built  Tank   STI-­‐  SP001  
  Horizontal  Tank   STI-­‐  SP001  
API  653   API-­‐650  Name  plate    
API  653   Over  30’  Diameter    
API  653   Over  50’  Tall    
API  653   More  than  50,000  gallons    
API  653   Small  Vertical  Tank  with  manway    
API-­‐653   Rests  on  grade    
  On  concrete  pad   STI-­‐  SP001  
   
 
Certified  API-­‐653  Inspector  
¡  Internal  Inspection      20  Years  
¡  External  Inspection      5  Years  
Owners  inspector  
¡  Periodic  –  [SPCC  Plan]    Monthly    
     
¡  Visual  
§  Roof  
§  Shell  
§  Nozzles  
§  Appurtenances,  etc.    
¡  Ultrasonic  Thickness  
§  Shell  
§  Roof  (If  needed)  
§  Other  (If  needed)  
¡  Final  Report  
¡  Initial  Internal   Within  10  years  of  Initial  Service  
§  (API  Certified  Inspector)   Date  
(Could  go  longer  with  safeguards)  
   
¡  Subsequent  Internal   20  Years    
(Can  be  30  years  with  RPB  6.4.22.1  but  
Inspection  Interval   need  to  check  with  state  regulations  
§  (API  Certified  Inspector)   first)  
¡  Visual  
§  Shell  Internal  and  External  Roof  Internal  and  External  Floor  
Internal  
§  Appurtenances  
§  Nozzles  Etc.    
 
¡  Ultrasonic  Thickness  
§  Shell  
§  Roof  
§  Nozzles  
§  Repads  
§  Floor  
§  Other  
¡  Magnetic  Flux  Leakage  
§  Floor  
¡  Vacuum  Box  
§  Floor  
¡  Magnetic  Particle  
§  Floor/Shell  
 
¡  External  Inspections    STI  Certified  Inspector  
¡  Internal  Inspections    STI  Certified  Inspector  
¡  Periodic  Inspections    Owners  Inspector  

¡  Categories  (Risk  Based)  


1.  Spill  Control  and  CRDM  
2.  Spill  Control  and  No  CRDM  
3.  No  Spill  Control  and  No  CRDM  
¡  Spill  Control  
§  Remote  Impounding  
§  Secondary  Containment  dike/BERM  
§  Secondary  Containment  AST  
§  Secondary  Containment  System  
 
¡  CRDM  (Continuous  Release  Detection  System)  
§  RPB-­‐  Release  Prevention  Barrier  
§  Secondary  Containment  AST  (Double  Walls,  Double  Button)  
§  Elevated  AST  
¡  Access  to  all  sides  
¡  Double  wall  
¡  Outside  
¡  On  concrete  pad  
¡  3,000  gallon  
¡  Built  1989  
¡  RPB/Double  Wall  
¡  SC  No  
¡  No  tank  info  
¡  Outside  
¡  On  curbed  concrete  
pad  
¡  5,000  Gallon  
¡  Access  to  all  sides  
¡  Double  wall  
¡  Built  1999  
¡  SC/No  
¡  RPB/Double  Wall  
¡  4,000  gallon    
¡  Built  1962  
¡  No  other  information  
¡  SC/dike  
¡  RPB/None  
¡  12,700  gallon  
¡  No  other  information  
¡  Single  Bottom  
¡  SC/Dike  
¡  RPB/None  
¡  Outside  
¡  Secondary  containment  
¡  RPB/  Concrete  Pad  and  
Base  
¡  2500  gallon  
¡  Built  1997  
¡  Field  Erected?  
¡  Outside  
¡  ≤  1,100  
¡  On  legs  
¡  SC/Yes  
¡  RPB/access  to  all  sides  
¡  12,000  gallon  tank  
¡  Insulated  Tank  
¡  Outside  
¡  RPB/Access  to  all  
sides?  
¡  SC/None  