CLIENT REVIEW
Table of Contents
1. Executive Summary ....................................................................................................................... 1
2. Introduction ..................................................................................................................................... 3
3. Scope of Work................................................................................................................................. 3
3.1 Battery Limit ............................................................................................................................ 3
3.2 Deliverables ............................................................................................................................ 4
6. Conclusion .................................................................................................................................... 30
List of Tables
Table 4-1: List of Reference Document .................................................................................................. 4
Table 5-1: Structural General Arrangement ............................................................................................ 8
Table 5-2: Earthquake Design Parameters........................................................................................... 16
Table 5-3: Spectrum Response ............................................................................................................ 17
Table 5-4: Maximum Height of Buried Trestle ...................................................................................... 19
Table 5-5: Extreme Stockpile Formation ............................................................................................... 20
Table 5-6: Load Combination without Coal Lateral Pressure ............................................................... 21
Table 5-7: Load Combination without Coal Lateral Pressure ............................................................... 22
List of Figures
Figure 1-1: Model View ........................................................................................................................... 2
Figure 3-1: Scope of Work, Gantry Structure Conveyor CV02 ............................................................... 3
Figure 5-1: General Arrangement ........................................................................................................... 8
Figure 5-2: Space Gass Model ............................................................................................................. 12
Figure 5-3: Coal Profile on Conveyor (Normal)..................................................................................... 14
Figure 5-4: Coal Profile on Conveyor (Flooded) ................................................................................... 14
Figure 5-5: Tripper Wheel Location ...................................................................................................... 15
Figure 5-6: Tripper Load Input to Model ............................................................................................... 15
Figure 5-7: Response Spectrum Design ............................................................................................... 17
H356799-00000-200-230-0002, Rev. A,
Page i
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
List of Appendices
H356799-00000-200-230-0002, Rev. A,
Page ii
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
1. Executive Summary
Hatch was assigned by KPC to provide detailed engineering services to upgrade the CV02
Tripper car’s travelling drive, including to assess on the required power demand, to select
of the new travelling drive components (i.e. motor, gearbox, brake, chains, and sprocket)
and to assess the required modification on the structural member attaching to the travelling
drive components. These scopes were fully completed, and all drawings and reports have
been submitted to KPC. The new drive system and the required structural modification
works (including counterweight to balance the new drive installation) increase the tripper
car’s weight by approximately 3.5t from the original design at approximately 40t.
As an additional scope, Hatch has been assigned by KPC to complete structural calculation
and modelling on the existing conveyor CV02 galleries and trestles (which support the
tripper car).
The structural analysis has been performed by using Space Gass v12.80 with the following
assumptions.
• The boundary for structural model starts from the existing backstay acting as
longitudinal restraint at the west and the drive tower at east side.
• All members are modelled and connected to provide complete load path from tripper
car transmitting to tripper-frame support and continued to gantry and the trestles.
• The support system on the trestle end has been model as pinned connection,
(considering its connection detail as shown on the as built drawing).
• The tripper car will travel along the rail beam, the load from tripper car has been
modeled as an automatic moving load in Space Gass.
• The existing drawing has indicated the trestle leg will be filled with concrete after
erection. However, there is no information on concrete filling preparation, procedure
and strength. Based on this fact the concrete contribution to steel strength is not
accounted in this assessment.
H356799-00000-200-230-0002, Rev. A,
Page 1
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
Conclusion
• There is no overstress occurs in the gantry structure from all load cases.
• The tripper support beam will undergo overstress by 30% due to both lateral coal
pressure and no lateral coal pressure. The location of overstressed bracing can be
seen in Appendix E.
Without considering the coal lateral pressure, the trestle will not overstress
By considering the coal lateral pressure, the trestle legs at grid 8 will undergo
overstress by more than 100%. The trestle at grid 6 and 7 is also overstress but
not as significant as grid 8.
Recommendation
H356799-00000-200-230-0002, Rev. A,
Page 2
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
The trestle leg strengthening could be complicated and time consuming. Therefore,
for time being, limiting the stock pile height on buried trestle shall be conducted.
Limiting the buried trestle height from asymmetric formation to maximum of 11m will
result the stress ratio still under the limit. (Note: the load factor for coal lateral
pressure has been reduced from 1.5 to 1.2 for this option)
Strengthening the trestle by “steel jacketing” which consists of existing trestle pile
(ø800x12) covered by additional circular hollow steel section (ø1000x14). The gap
between existing and new steel plate shall be filled with concrete 30 MPa includes
shear connector installation to maintain the composite action between two members.
Detail of the strengthening presented in Appendix G.
2. Introduction
Hatch was assigned by KPC to provide detailed engineering services to upgrade the CV02
Tripper car’s travelling drive, including to assess on the required power demand, to select
of the new travelling drive components (i.e. motor, gearbox, brake, chains, and sprocket)
and to assess the required modification on the structural member attaching to the travelling
drive components. These scopes were fully completed, and all drawings and reports have
been submitted to KPC. The new drive system and the required structural modification
works (including counterweight to balance the new drive installation) increase the tripper
car’s weight by approximately 3.5t from the original design at approximately 40t.
As an additional scope, Hatch has been assigned by KPC to complete structural calculation
and modelling on the existing conveyor CV02 galleries and trestles (which support the
tripper car).
3. Scope of Work
3.1 Battery Limit
Hatch’s boundary of work included gantry structure carrying tripper car from backstay at
grid 4 to grid 9 with additional modelling of drive tower as lateral resistance.
H356799-00000-200-230-0002, Rev. A,
Page 3
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
The structural analysis only conducted to the structural element above the ground level.
3.2 Deliverables
• Technical Memo, submitted to KPC on 11th February 2020
4. Referenced Document
Reference is made to the following data as provided by KPC.
Table 4-1: List of Reference Document
H356799-00000-200-230-0002, Rev. A,
Page 4
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
H356799-00000-200-230-0002, Rev. A,
Page 5
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
H356799-00000-200-230-0002, Rev. A,
Page 6
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
H356799-00000-200-230-0002, Rev. A,
Page 7
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
5. Structural Analysis
5.1 General Arrangement
A full set structural model was created to accommodate all load combinations and its
possibility on primary structural members during tripper movement. Tripper car traveling
in limited span only between grid 4 through 9. Therefore, trestles and galleries within this
area were being assess. In order to develop overall lateral stiffness of structure, the drive
tower on east side and backstay on west side (grid 4) were also included in structural
model.
The structural model has been prepared based on the received as-built drawings with the
general arrangement as shown in Figure 5-1.
In General, the structure is divided into 3 major components; Trestle, Gantry and Tripper
Support Beam. General arrangement of these structural components is described in
Table 5-1.
Table 5-1: Structural General Arrangement
Trestle Height
Grid 4 = 17.5 m
Grid 5 = 19.2 m
Grid 6 = 20.9 m
Grid 7 = 22.6 m
Grid 8 = 24.3 m
Grid 9 = 26.0 m
H356799-00000-200-230-0002, Rev. A,
Page 8
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
Trestle on Grid 4
Vertical Trestle
(CHSø800x12)
Trestle on Grid 5
through Grid 9
Vertical Trestle
(CHSø800x12)
Distance between
each leg
2.29m at top
10.0m on bottom
H356799-00000-200-230-0002, Rev. A,
Page 9
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
End Portal
(HB200x200)
Diagonal Vertical
Bracing
(2Ls130x130x12)
Vertical Bracing
(HB150x150)
Bottom Lateral
Bracing
(2Ls80x80x8) at
mid span
(2Ls 100x100x10)
at end span
H356799-00000-200-230-0002, Rev. A,
Page 10
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
Cross Beam
supporting Column
(HB200x200)
Stringer Column
(HB150x150)
Stringer Beam
(C250x90)
Stringer Diaphragm
(HB150x150)
Stringer Lateral
Bracing
(L100x100x10)
Vertical Bracing
(L100x100x10)
H356799-00000-200-230-0002, Rev. A,
Page 11
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
Longitudinal
Walkway Support
(C200x80)
Intermediate Cross
Beam (WF200x100)
Separator Rod
(ø30)
Grating 32 mm thick
5.2 Assumption
The structural analysis has been performed by using Space Gass v12.80 with the following
assumptions.
H356799-00000-200-230-0002, Rev. A,
Page 12
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
• The boundary for structural model starts from the existing backstay acting as
longitudinal restraint at the west and the drive tower at east side.
• All members are modelled and connected to provide complete load path from tripper
car transmitting to tripper-frame support and continued to gantry and the trestles.
• The support system on the trestle end has been model as pinned connection,
(considering its connection detail as shown on the as built drawing).
• The tripper car will travel along the rail beam, the load from tripper car has been
modeled as an automatic moving load in Space Gass.
• The existing drawing has indicated the trestle leg will be filled with concrete after
erection. However, there is no information on concrete filling preparation, procedure
and strength. Based on this fact the concrete contribution to steel strength is not
accounted in this assessment.
• Permanent Load (structural self-weight, grating, handrail, idler, belt, pulley, tripper
equipment)
• Imposed Load (live load on walkway, service load, coal load on conveyor, coal
spillage, coal load on chute, conveyor belt tension, thermal load)
H356799-00000-200-230-0002, Rev. A,
Page 13
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
Thus, material loads carried on conveyor taken as 4.2kN/m. The loads applied on stringer
column. Therefore, load of 5 kN shall be applied on each stringer column.
Thus, material loads carried on conveyor taken as 9.2kN/m. The loads applied on stringer
column. Therefore, load of 11kN shall be applied on each stringer column.
H356799-00000-200-230-0002, Rev. A,
Page 14
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
A 20% additional load also applied for compensate impact load from moving tripper.
Tripper Load has been distributed to 27 location along its rail (grid 4 through grid 9) for
each load combination. As can be seen in Figure 5-6, tripper load input to structural
model as moving load and each color group represent tripper load at specific period.
T-17 T-25
T-9 T-13
T-1 T-5
T-21
H356799-00000-200-230-0002, Rev. A,
Page 15
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
The maximum operating wind speed is wind speed at which plant operation is
stopped. This shutdown is generally conducted in a controlled and orderly manner.
The maximum operating wind speed is 20m/s based on KPC standard specification
(KPC-C-01).
The serviceability wind speed is used to check serviceability criteria for structure. The
serviceability wind speed is 32m/s (V25).
The ultimate wind speed is the wind speed used for ultimate strength limit state
calculations. This ultimate wind speed shall be taken as V500 which is 40m/s.
Terrain category 2 are taken as parameter in this exercise. The wind on particular
direction will hit the perpendicular area of structure and creates pressure on structure.
The detailed calculation is presented in Appendix B.
H356799-00000-200-230-0002, Rev. A,
Page 16
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
H356799-00000-200-230-0002, Rev. A,
Page 17
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
The “spill-through abutment” approach has been adopted for determination of lateral load
from coal stockpile on buried trestles. The analysis of the trestle legs were performed in
two conditions, the first condition is analyzing all load combination including lateral load
from stockpile and secondly without lateral load from stockpile with the objective to
provide clear information whether the structures is overstressed as a result from
additional load from tripper car only or includes coal pressure which existed long time
before the tripper car being modified.
Symmetric loading on
trestles (balance pressure)
Randolph method of “spill-through abutment is used for this exercise. The net lateral force
due to coal lateral pressure can be determined by this following formula.
𝛾𝛾𝐻𝐻2
𝑊𝑊 = 𝐾𝐾𝑎𝑎 𝐸𝐸𝐸𝐸
2
where,
𝐾𝐾𝑚𝑚−𝐾𝐾𝑠𝑠 𝑠𝑠
= 3.8 for ≥8
𝐾𝐾𝑎𝑎 𝑑𝑑
H356799-00000-200-230-0002, Rev. A,
Page 18
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
Tripper will discharge the coal only at designate point which is right in the middle of each
gantry span on grid 4 through 8. In contrast, the loading point on gantry span between
grid 8 and 9 is located 12m from grid 8, instead of the middle point. Particular stockpile
formation is created when it was fully filled as shown in Figure 5-9 with maximum height
of buried trestle as describe in Table 4-1.
Table 5-4: Maximum Height of Buried Trestle
4 4.3
5 6.0
6 7.7
7 9.4
8 15.6
9 8.0
H356799-00000-200-230-0002, Rev. A,
Page 19
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
In this analysis, couple of extreme stockpile formations are considered, those formation
are presented in Table 5-5.
Table 5-5: Extreme Stockpile Formation
H356799-00000-200-230-0002, Rev. A,
Page 20
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
Q(Tr) BNR, NW
Q (Tr) BO, NW
Q (Tr) BNR, W
Q (Tr) BS, NW
Q (Tr) BES, B
Q (Tr) BES, S
Q (Tr) BES, F
Q (Tr) M, NW
Q (Tr) BO, W
Q (Tr) M, W
Q(Tr) DLO
Comb No. Description G (D, ME)
Q (ML1)
G (D, S)
Q (FB)
Q (S)
Q (L)
Q(T)
SW
Wo
Wu
Ws
Ex
Ez
Strength Limit State Load Combination - Normal Operational
1.35
1.35
1.35
1.0
6001-6027 Dead Load Only
Belt Not
0.75
1.2
1.2
1.2
1.5
1.5
1.0
6031-6057 Running, No
Wind
Belt Not
1.2
1.2
1.2
1.5
1.5
1.5
1.0
1.0
6061-6177
Running, Wind
Belt Operating,
1.2
1.2
1.2
1.5
1.5
1.5
1.0
6181-6207
No Wind
Belt Operating,
1.2
1.2
1.2
1.5
1.5
1.5
1.0
1.0
6211-6327
Wind
Belt Start, No
1.2
1.2
1.2
1.5
1.5
1.5
1.0
6331-6357
Wind
Maintenance,
1.2
1.2
1.2
1.5
1.5
1.0
6361-6387 No Operating
Wind
Maintenance,
1.2
1.2
1.2
1.5
1.5
1.0
1.0
6391-6507
Operating Wind
Belt Extreme
1.2
1.2
1.2
1.5
1.2
1.0
6511-6537
Start, Flooded
Belt Extreme
1.2
1.2
1.2
1.5
1.0
6541-6567
Start, Blocked
Belt Extreme
1.2
1.2
1.2
1.5
1.0
6571-6597
Start, Spillage
1.2
1.2
1.5
1.5
1.5
1.5
Ultimate Wind
1.2
1.2
1.2
1.5
1.0
4020-4023
Load
1.0
1.0
1.0
1.0
1.0
1.0
1.0
0.3
4030 Earthquake X1
H356799-00000-200-230-0002, Rev. A,
Page 21
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
Q(Tr) BNR, NW
Q (Tr) BO, NW
Q (Tr) BNR, W
Q (Tr) BS, NW
Q (Tr) BES, B
Q (Tr) BES, S
Q (Tr) BES, F
Q (Tr) M, NW
Q (Tr) BO, W
Q (Tr) M, W
Q(Tr) DLO
G (D, ME)
Comb No. Description
Q (ML1)
G (D, S)
Q (FB)
Q (S)
Q (L)
Q(T)
SW
Wo
Wu
Ws
Ex
Ez
-0.3
1.0
1.0
1.0
1.0
1.0
1.0
1.0
4031 Earthquake X2
-1.0
1.0
1.0
1.0
1.0
1.0
1.0
0.3
4032 Earthquake X3
-1.0
-0.3
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
0.3
1.0
4034 Earthquake Z1
-0.3
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
0.3
4036 Earthquake Z3
-0.3
-1.0
1.0
1.0
1.0
1.0
1.0
1.0
4037 Earthquake Z4
Q(Tr) BNR, NW
Q (Tr) BO, NW
Q (Tr) BNR, W
Q (Tr) BS, NW
Q (Tr) BO, W
Q(Tr) DLO
G (D, ME)
Q (FB)
Q (S)
Q (L)
Co 1
Q(T)
Co2
SW
Wo
Wu
Ws
Ex
Ez
Strength Limit State Load Combination - Normal Operational with Coal Lateral Pressure 1
1.35
1.35
1.35
1.0
1.5
7001-7027 Dead Load Only
0.75
1.2
1.2
1.5
1.5
1.0
1.5
7031-7057
No Wind
1.2
1.2
1.5
1.5
1.5
1.0
1.0
1.5
7061-7177
Wind
Belt Operating,
1.2
1.2
1.2
1.5
1.5
1.5
1.0
1.5
7181-7207
No Wind
Belt Operating,
1.2
1.2
1.2
1.5
1.5
1.5
1.0
1.0
1.5
7211-7327
Wind X+
Belt Start, No
1.2
1.2
1.2
1.5
1.5
1.5
1.0
1.5
7331-7357
Wind
H356799-00000-200-230-0002, Rev. A,
Page 22
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
Q(Tr) BNR, NW
Q (Tr) BO, NW
Q (Tr) BNR, W
Q (Tr) BS, NW
Q (Tr) BO, W
Q(Tr) DLO
G (D, ME)
Comb No. Description
Q (ML1)
G (D, S)
Q (FB)
Q (S)
Q (L)
Co 1
Q(T)
Co2
SW
Wo
Wu
Ws
Ex
Ez
Strength Limit State Load Combination - Normal Operational with Coal Lateral Pressure 2
1.35
1.35
1.35
1.0
1.5
7501-7527 Dead Load Only
1.2
1.2
1.5
1.5
1.0
1.5
7531-7557
No Wind
1.2
1.2
1.5
1.5
1.5
1.0
1.0
1.5
7561-7677
Wind
Belt Operating,
1.2
1.2
1.2
1.5
1.5
1.5
1.0
1.5
7681-7707
No Wind
Belt Operating,
1.2
1.2
1.2
1.5
1.5
1.5
1.0
1.0
1.5
7711-7827
Wind X+
Belt Start, No
1.2
1.2
1.2
1.5
1.5
1.5
1.0
1.5
7831-7857
Wind
Note:
SW Structural Self-weight
G (D, S) Permanent Dead Load, Structural
G (D, ME) Permanent Dead Load, Mechanical Equipment
Q (L) Imposed Live Load
Q (S) Service Load, Electrical and Piping
Q (ML1) Material Load carried on Conveyors
Q (FB) Flooded Conveyor Belt Load
Q(T) Thermal Load
Ex, Ez Earthquake Load on respective direction X & Z
Wo, Ws, Wu Wind Load with respective wind speed (shut down wind speed, serviceability wind
speed, ultimate wind speed)
Q(Tr) DLO Tripper Load, dead load only combination
Q(Tr) BNR, NW Tripper Load, belt not running, no wind combination
Q(Tr) BNR, W Tripper Load, belt not running, wind with 4 major direction combination
Q(Tr) BO, NW Tripper Load, belt operating, no wind combination
Q(Tr) BO, W Tripper Load, belt operating, wind with 4 major direction combination
Q(Tr) BS, NW Tripper Load, belt start, no wind combination
Q(Tr) M, NW Tripper Load, maintenance, no wind combination
Q(Tr) M, W Tripper Load, maintenance, wind with 4 major direction combination
Q(Tr) BES, F Tripper Load, belt extreme start, flooded combination
Q(Tr) BES, B Tripper Load, belt extreme start, blocked combination
Q(Tr) BES, S Tripper Load, belt extreme start, spillage combination
Co1, Co2 Coal Lateral Pressure scenario 1 and 2
H356799-00000-200-230-0002, Rev. A,
Page 23
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
• All steel grade is 240 MPa, (There is no indication of steel grade on the drawings.
However, most of the existing structural members are identical to “Gunung Garuda”
steel section which has 240 MPa Grade).
Graphic of the model frame elements, pinned end support and materials are shown in
Figure 5-10.
H356799-00000-200-230-0002, Rev. A,
Page 24
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
5.6.1 Trestle
The most critical condition is when the tripper position on top of each trestle. The
dominant stress on trestle is due to coal lateral pressure. As shown in Figure 5-11, the
maximum stress ratio on trestle was 2.18 on grid 8 (based on load combination no.7204:
from combination of belt operating with no wind and coal lateral pressure 1).
This indicate that trestle legs in grid 8 were overstress, some countermeasure needs to
be performed in order to maintain acting stress will not exceed member stress capacity.
Basically, 2 options may be carried out, the first one is to limiting acting stress on member
by controlling height of buried trestle with asymmetric formation; The other one is to
increase member capacity by strengthen it. Both options were carried out in this analysis.
H356799-00000-200-230-0002, Rev. A,
Page 25
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
Figure 5-12: Trestle Steel Stress Check - Limiting Height of Buried Trestle to 11m
H356799-00000-200-230-0002, Rev. A,
Page 26
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
5.6.2 Gantry
The maximum stress ratio on gantry was 1.075 (from load combination no.7183:
combination of belt operating with no wind and coal lateral pressure 1), this shown in
Figure 5-14. The slightly overstress member was located on end span at diagonal bracing
(2Ls130x130x12). This steel member was modelled as back-to-back angle instead stared
angle as per installed to simplify the model. The capacity of stared angle is greater than
back-to-back angle. Therefore, the steel member was analyzed separately as stared
angle with the identical actual stress, the stress ratio is 0.93. Detail calculation is
presented in Appendix F.
H356799-00000-200-230-0002, Rev. A,
Page 27
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
Hatch recommend addition vertical bracing at particular locations to distribute the load
better in order to increase tripper support beam capacity. Steel angle L120x120x12 shall
be installed along tripper support beam. The strengthening detail location can be seen in
Appendix E. The maximum stress after additional vertical bracing is reduced to 0.94
which is acceptable.
The maximum shear force occurred at end pinned connection is 950kN. The analysis
consists of bolt in shear check and ply in bearing check, the bolt shear strength
determined the capacity of the connection. The total of bolt shear capacity is 1122kN
which is greater than ultimate shear force occurred. Therefore, the connection is sufficient
to withstand all load case in the assessment. Detail calculation is presented in Appendix I.
H356799-00000-200-230-0002, Rev. A,
Page 28
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
The maximum shear load occurred at end pinned connection is 800kN. The analysis
consists of pin in shear check, pin in bearing check, and ply in bearing check, the pin
shear strength determined the capacity of the connection. The pin shear capacity is
1363kN which is greater than maximum shear force occurred. Therefore, the connection
is sufficient to withstand the all load case. Detail calculation is presented in Appendix H.
H356799-00000-200-230-0002, Rev. A,
Page 29
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
6. Conclusion
The structural analysis has revealed the following conclusion.
• There is no overstress occurs in the gantry structure from all load cases.
• The tripper support beam will undergo overstress by 30% due to both lateral coal
pressure and no lateral coal pressure. The location of overstressed bracing can be
seen in Appendix E.
Without considering the coal lateral pressure, the trestle will not overstress
By considering the coal lateral pressure, the trestle legs at grid 8 will undergo
overstress by more than 100%. The trestle at grid 6 and 7 is also overstress but
not as significant as grid 8.
7. Recommendation
• The force in overstressed members at tripper support bracing shall be reduced by
installing additional steel angle L120 x120x12. See Appendix E for detail location.
The strengthening could be conducted during regular maintenance period.
The trestle leg strengthening might be more complicated and time consuming.
Therefore, for time being, limiting the stock pile height on buried trestle shall be
conducted. Limiting the buried trestle height from asymmetric formation to maximum
of 11m will result the stress ratio still under the limit. (Note: the load factor for coal
lateral pressure has been reduced from 1.5 to 1.2 for this option)
• Trestle Leg – Long Term Recommendation
Strengthening the trestle by “steel jacketing” will consist of existing trestle pile
(ø800x12) covered by additional circular hollow steel section (ø1000x14). The gap
between existing and new steel plate shall be filled with concrete 30 MPa includes
shear connector installation to maintain the composite action between two members.
Detail of the strengthening presented in Appendix G.
H356799-00000-200-230-0002, Rev. A,
Page 30
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
Appendix A
Structure Self-weight Calculation
H356799-00000-200-230-0002, Rev. A,
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
H356799-00000-200-230-0002, Rev. A,
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
Appendix B
Wind Load Calculation
H356799-00000-200-230-0002, Rev. A,
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
Wind Speed
State V Md Mz Ms Mt Vsit
m/s m/s
Shutdown 20 1 1.12 1 1 22.4
Service 32 1 1.12 1 1 35.8
Ultimate 40 1 1.12 1 1 44.8
H356799-00000-200-230-0002, Rev. A,
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
Appendix C
Coal Lateral Load Calculation
H356799-00000-200-230-0002, Rev. A,
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
H356799-00000-200-230-0002, Rev. A,
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
H356799-00000-200-230-0002, Rev. A,
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
H356799-00000-200-230-0002, Rev. A,
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
H356799-00000-200-230-0002, Rev. A,
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
H356799-00000-200-230-0002, Rev. A,
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
H356799-00000-200-230-0002, Rev. A,
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
Appendix D
Load Case Location
H356799-00000-200-230-0002, Rev. A,
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
Load
Definition Graphic
Case
SW
101
Self-Weight
G (D, S)
102 Permanent Dead
Load, Structural
G (D, S)
103 Permanent Dead
Load, Structural
Q (L)
201 Live Load on
Walkway
H356799-00000-200-230-0002, Rev. A,
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
Load
Definition Graphic
Case
Q (S)
202
Service Load
Q (ML1)
203 Material Load
carried on
Conveyor
Q (FB)
204 Flooded Conveyor
Load
Q(T)
214
Thermal Load
H356799-00000-200-230-0002, Rev. A,
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
Load
Definition Graphic
Case
EX
301 Earthquake Load in
X Direction
EZ
302 Earthquake Load in
Z Direction
Co 1
303 Coal Lateral
Pressure 1
H356799-00000-200-230-0002, Rev. A,
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
Load
Definition Graphic
Case
Co 2
304 Coal Lateral
Pressure 2
Wou X+
401 Shut Down Wind
Load X+ Direction
Wou X-
402 Shut Down Wind
Load X- Direction
Wou Z+
403 Shut Down Wind
Load Z+ Direction
H356799-00000-200-230-0002, Rev. A,
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
Load
Definition Graphic
Case
Wou Z+
404 Shut Down Wind
Load Z+ Direction
Wou X+
405 Serviceability Wind
Load X+ Direction
Wou X-
406 Serviceability Wind
Load X- Direction
Wou Z+
407 Serviceability Wind
Load Z+ Direction
H356799-00000-200-230-0002, Rev. A,
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
Load
Definition Graphic
Case
Wou Z+
408 Serviceability Wind
Load Z+ Direction
Wou X+
409 Ultimate Wind
Load X+ Direction
Wou X-
410 Ultimate Wind
Load X- Direction
Wou Z+
411 Ultimate Wind
Load Z+ Direction
H356799-00000-200-230-0002, Rev. A,
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
Load
Definition Graphic
Case
Wou Z+
412 Ultimate Wind
Load Z+ Direction
Tripper Load –
9001-
Dead Load Only
9027
Combination
H356799-00000-200-230-0002, Rev. A,
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
Load
Definition Graphic
Case
H356799-00000-200-230-0002, Rev. A,
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
Load
Definition Graphic
Case
H356799-00000-200-230-0002, Rev. A,
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
Load
Definition Graphic
Case
Tripper Load –
9361-
Maintenance, No
9387
Wind Combination
Tripper Load –
9391-
Maintenance, Wind
9417
X+ Combination
Tripper Load –
9421-
Maintenance, Wind
9447
X- Combination
H356799-00000-200-230-0002, Rev. A,
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
Load
Definition Graphic
Case
Tripper Load –
9451-
Maintenance, Wind
9477
Z+ Combination
Tripper Load –
9481-
Maintenance, Wind
9507
Z- Combination
Tripper Load –
9511-
Maintenance, Wind
9537
X+ Combination
H356799-00000-200-230-0002, Rev. A,
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
Load
Definition Graphic
Case
H356799-00000-200-230-0002, Rev. A,
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
H356799-00000-200-230-0002, Rev. A,
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
H356799-00000-200-230-0002, Rev. A,
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
H356799-00000-200-230-0002, Rev. A,
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
H356799-00000-200-230-0002, Rev. A,
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
H356799-00000-200-230-0002, Rev. A,
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
Appendix E
Tripper Support Beam – Strengthening
Works
H356799-00000-200-230-0002, Rev. A,
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
H356799-00000-200-230-0002, Rev. A,
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
H356799-00000-200-230-0002, Rev. A,
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
H356799-00000-200-230-0002, Rev. A,
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
Appendix F
Stared Angle Capacity Calculation
H356799-00000-200-230-0002, Rev. A,
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
H356799-00000-200-230-0002, Rev. A,
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
H356799-00000-200-230-0002, Rev. A,
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
H356799-00000-200-230-0002, Rev. A,
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
H356799-00000-200-230-0002, Rev. A,
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
H356799-00000-200-230-0002, Rev. A,
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
H356799-00000-200-230-0002, Rev. A,
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
Appendix G
Trestle Strengthening
H356799-00000-200-230-0002, Rev. A,
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
The exercise only considers steel pile without concrete as its capacity as
shown in figure below.
N* = 1121.59 kN (Compact)
Vx* = 947.76 kN (not considered) Vy* = -2.69 kN
Mx* = -256.24 kNm (Non-compact) My* = 3637.82 kNm (Non-compact)
H356799-00000-200-230-0002, Rev. A,
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
1.4
𝑀𝑀𝑥𝑥∗ 1.4 𝑀𝑀𝑦𝑦∗
� � +� � = 0.02 + 0.93 = 0.95 < 1.00 → 𝑃𝑃𝑃𝑃𝑃𝑃𝑃𝑃! Member biaxial bending (8.4.5.1)
𝜙𝜙𝑀𝑀𝑐𝑐𝑐𝑐 ϕMiy
H356799-00000-200-230-0002, Rev. A,
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
Trestle Strengthening
See the following sketch no H356799-00000-230-260-0001.
H356799-00000-200-230-0002, Rev. A,
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
Appendix H
Gantry-Trestle Pinned Connection
Calculation
H356799-00000-200-230-0002, Rev. A,
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
The consists of 1 Pin (Mild steel Grade 350 kN) with 100mm diameter and 38mm thick base plate.
𝑉𝑉𝑓𝑓∗ ≤ ɸ𝑉𝑉𝑓𝑓
𝑉𝑉𝑓𝑓 = Nominal shear capacity of a pin
𝑉𝑉𝑓𝑓 = 0.62 × 𝑓𝑓𝑦𝑦𝑦𝑦 × 𝑛𝑛𝑠𝑠 × 𝐴𝐴𝑝𝑝 = 1704.3 𝑘𝑘𝑘𝑘
ɸ𝑉𝑉𝑓𝑓 = 1363.45 𝑘𝑘𝑘𝑘 > 𝑉𝑉𝑓𝑓∗ (= 800 𝑘𝑘𝑘𝑘) PASS!
H356799-00000-200-230-0002, Rev. A,
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
The connection still capable to withstand the load working at gantry-trestle intersection with pin in
shear as critical case.
H356799-00000-200-230-0002, Rev. A,
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
Appendix I
Trestle Base Plate Calculation
H356799-00000-200-230-0002, Rev. A,
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.
PT Kaltim Prima Coal Engineering Report
Structural Analysis Conveyor CV02 Structural Engineering
H356799 Calculation Report
Base plate consists of 8 Anchor bolts (assumed to be Grade 4.6 steel) with 30mm diameter and
32mm thick base plate.
𝑉𝑉𝑓𝑓∗ ≤ ɸ𝑉𝑉𝑓𝑓
𝑉𝑉𝑓𝑓 = Nominal shear capacity of a bolt
𝑉𝑉𝑓𝑓 = 0.62 × 𝑓𝑓𝑢𝑢𝑢𝑢 × 𝑛𝑛𝑠𝑠 × 𝐴𝐴𝑓𝑓 = 1402.4 𝑘𝑘𝑘𝑘
ɸ𝑉𝑉𝑓𝑓 = 1121.9 𝑘𝑘𝑘𝑘 > 𝑉𝑉𝑓𝑓∗ (= 950𝑘𝑘𝑘𝑘) PASS!
The connection still capable to withstand the load working at trestle base plate with bolt in shear as
critical case.
H356799-00000-200-230-0002, Rev. A,
Ver: 04.03
© Hatch 2020 All rights reserved, including all rights relating to the use of this document or its contents.