SERVICE MANUAL

IMVF CONDENSING UNIT 208V

VERSION: C
DATA: Feb.13th,2015
Contents

Part 1 General Information.................................................................................................................................1


Part 2 Outdoor units......................................................................................................................................... 9
2.1 Specification............................................................................................................................................10
2.2 Piping diagram........................................................................................................................................19
2.3 Wiring diagram........................................................................................................................................22
2.4 Field wiring............................................................................................................................................. 24
2.5 Operation range......................................................................................................................................25
2.6 Sound pressure level...............................................................................................................................26
2.7 Installation...............................................................................................................................................27
Part 3 Control system......................................................................................................................................54
3.1 Dip switch setting...................................................................................................................................55
3.2 Outdoor unit control.............................................................................................................................. 64
Part 4 Trouble shooting....................................................................................................................................66
4.1 Failure code............................................................................................................................................67
4.2 Failure diagnose.....................................................................................................................................76
APPENDIX I....................................................................................................................................................105

1
Contents

Part 1 General Information

1.1 Safety...........................................................................................................................................................3
1.2 Feature.........................................................................................................................................................5
1.3 Products Lineup...........................................................................................................................................9

2
1.1 Safety

• This manual should always be accessible and close to this air condition equipment.
• There are two types of indications, " WARNING" and " CAUTION". The indication preventing from death or
heavy injury is listed as " WARNING". Even the indication listed as " CAUTION" may also cause serious accident.
Both of them are related to safety, and should be strictly followed.
•After installation and start-up commissioning, please handover the manual to the user. The manual should be well
kept in safe place and close to the unit.

WARNING

• The installation or the maintenance should be performed by an authorized agency. The wrong operation of this air
condition equipment may cause water leakage, electric shock or fire.
• Please install the unit on the top of a solid foundation or structure which is strong enough to support the unit.
• The installation of this air condition equipment should follow local construction codes.
• Use the right cable size, secure the terminal firmly, organize the cables well and make sure no tension is added on
cables. Cable insulation should not be damaged. The incorrect installation may lead to overheat or fire.
• When installing or moving the unit, the refrigerant system should be vacuumed and recharged with R-410A
refrigerant. If any other gas enters the system, it may lead to abnormal high pressure which may cause damage or
injury.
• Please use the proper manifolds or branches during the system installation. The wrong parts may cause refrigerant
leakage.
• Keep the drain pipe away from toxic gas vents to prevent possible pollution of indoor environment.
• During or after the installation, please check whether there is refrigerant leakage. If any leakage, please take any
measures for ventilation. The refrigerant may be toxic at some concentration levels.
• The unit is not explosion-proof. Please keep it away from flammable gases.
• The drain pipe should be installed per this manual to ensure proper drainage. The pipe should be well insulated to
avoid condensation. Wrong installation may lead to water leakage.
Both liquid pipe and the gas pipe should be also well insulated. Not enough insulation may lead to system performance
deterioration or humidity formation.
• This air condition equipment is not intended to be operated by persons with lack of experience and training, unless
they have supervision or instruction concerning use of this air condition equipment.
• Please keep children away from this air condition equipment.

3
CAUTION

• Grounding wire should be connected with the grounding bar. The grounding wire can not be connected to the gas
pipe, water pipe, lightening rod or the telephone grounding wire. Improper grounding may cause electric shock.
• Units installed on roof should have appropriate access and handrail.
• Use the wrench to fasten the nut and flare at proper torque. Excessive torque may cause flared section to broke
leading to refrigerant leakage.
• After refrigerant pipe installation, please take nitrogen leakage test to avoid refrigerant leakage.
• R-410A is the only permitted refrigerant.
• To avoid mischarging wrong refrigerant, the check valve diameter is changed for R-410A. To strengthen the pipe, the
flared pipe dimension is also changed. Please use R-410A specified tools as shown below.

R-410A specified tools Remarks


1 Gauge manifold Range: HP>4.5MPa,LP>2MPa

2 Charge hose Pressure: HP 5.3MPa, LP 3.5MPa

3 Electronic weight for charging R-410A No other means permitted

4 Torque wrench

5 Flare tool

6 Copper pipe gauge for adjusting projecting margin

7 Vacuum pump fitting Vacuum pump must be equipped with check valve

8 Leakage detector Only Helium detector permitted

• When charging refrigerant, the refrigerant must be in liquid state from the tank.
• To prevent EMC interference on other appliances, please keep indoor unit, outdoor unit, power cable and connecting
wire at least 1m away from those appliances.
• Fluorescent lamp (reverse phase or rapid start type) may interfere with the remote controller's signal. Please install
indoor unit away from fluorescent lamp. The farther the better.

4
1.2 Feature

1.2.1 High efficiency DC inverter scroll compressor, high efficiency, low noise.
The highly efficient scroll compressor is equipped with a "Frame Compliance Mechanism "that allows
movement in the axial direction of the frame supporting the cradle scroll. This greatly reduces both
leakage and friction loss, ensuring very high efficiency throughout the speed range.

1.2.2 New big diameter "aviation" fan


The new fan could reduce air loss, air resistance and noise, increase heat exchange efficiency
Adopt the 4-way air returned heat exchanger technology; the compressor and condenser are placed
in separated compartments; this structure of outdoor unit can realize lower air resistance, higher
heat efficiency and lower noise level.

1.2.3 High efficiency DC fan motor


The speed of wide range DC fan motor can be adjust from 0 r/min to 1000 r/min. Compared to convertions AC motors,
a DC fan motor offers greater efficiency, especially during low-speed rotation. The effiency shall be 90%.

1.2.4 Efficient exchanger


W-mode Ф7.94 inner grooved tube, Hydrophilic Aluminum coil fin, it will increase efficiency of heat exchange by 5%

5
1.2.5 Heat exchanger adopts the sub-cooling technology, to keep the refrigerant in indoor unit flowing normally,
further to enhance the unit efficiency greatly.
Outdoor adopts the sub-cooling circuit utilizes little refrigerant to cool most of refrigerant in system and makes
it further cooling, improves sub-cooling degree of refrigerant, it can avoid energy loss due to refrigerant flash
evaporating when it goes through PMV (pressure modulation valve); It will increase cooling capacity by 6%, reduce
refrigerant circulation amounts, so that it can increase the efficiency of system.

1.2.6 Flexible installation and design


Indoor quantity can be up to 64 sets in maximum. And the indoor total capacity can be 50% ~ 30% of outdoor capacity.
If there are multiple outdoors, the outdoors will be in running by turns, ~ much longer life. Multiple types of indoor can
be chosen for different requirements

1.2.7 Allowable pipe length and height difference

For modular VRF, allowable pipe length and height drop

when the distance between outdoors is over 2m, the oil trap must
be set (upright projecting pipe, 200mm high), as the figure:

6
Max. length Pipe in above figure

L1+L2+ L3+ L4+ L5+ L6+ L7+L8+ L9+ L10+ L11+


Single way total pipe length 300
L12+ L13+ L14+ L15

Single way max. pipe equivalent length 175 L1+ L3+ L5+ L7+ L14+ L13

Max. pipe length after 1st branch pipe 40 L7+L13+L14

Main pipe equivalent length 135 L5

Height difference between indoors 15 —

Height difference between outdoors 5 —

1.2.8 Easier maintenance


a. Backup operation
If one outdoor unit malfunction happens, the other units keep emergent operation until repair achieved. In one model
system, also can realize back up operation when fix speed compressor error happens.
b. Auto check function.
Failure codes displayed by LED in outdoor PCB or controllers are so detailed for us to find the fail place more quickly,
and can judge the failure content easily.
1.2.9 Reliable performance
a. Approved for RoHS certificate
All the parts in the unit have been approved for RoHS certificate. The parts are in conformance with RoHS directive.
Thus York Amazon VRF will be environmental for human and nature.
The directive is to approximate the laws of the Member States on the restrictions of the use of hazardous substances
in electrical and electronic equipment and to contribute to the protection of human health and the environmentally
sound recovery and disposal of waste electrical and electronic equipment.
b. Less chance of refrigerant leakage
The connection type of outdoor gas check valve is brazed, therefore it is not easy to leak any refrigerant.

7
1.3 Products Lineup

CA43BV224/280-V5J1H CA43BV335/400/450-V5J1H

CA43BV504/560-V5J1H CA43BV615/680/730-V5J1H

Outdoor
CA43BV800/850/900-V5J1H CA43BV960/1010-V5J1H

CA43BV1080/1130/1180-V5J1H CA43BV1235/1300/1350-V5J1H

Model 504 560 615 680 730 800 850 900


224 280 280 280 280 400 400 450
Combination model
280 280 335 400 450 400 450 450

Model 960 1010 1080 1130 1180 1235 1300 1350


280 280 335 280 280 335 400 450
Combination model 280 280 400 400 450 450 450 450
400 450 400 450 450 450 450 450

8
Part 2 Outdoor Unit

2.1 Specification ...........................................................................................................................................10


2.2 Piping diagram .......................................................................................................................................19
2.3 Wiring diagram .......................................................................................................................................22
2.4 Field wiring............................................................................................................................................ 24
2.5 Operation range .....................................................................................................................................25
2.6 Sound pressure level ..............................................................................................................................26
2.7 Installation...............................................................................................................................................27

9
2.1 Specification
Model CA43BV224-V5J1H CA43BV280-V5J1H CA43BV335-V5J1H
Capacity range HP 8 10 12
Capacity Cooling kW 22.6 28 33.5
Heating kW 25 31.5 37.5
Power supply Ph/V/Hz 3/208-230/60 3/208-230/60 3/208-230/60
Rated power input kW 5.6 8.5 10
Max power input kW 12.5 14.5 16.5
Cooling
Rated current A 15.15 23.35 27.55
Max current A 38.6 44.7 50.9
Electrical
Rated power input kW 5.9 8.8 10.3
Parameters
Max power input kW 12.5 14.5 16.5
Heating
Rated current A 16.05 24.25 28.45
Max current A 38.6 44.7 50.9
EER 4.04 3.29 3.35
COP 4.24 3.58 3.64
Air flow (H) m3/h 11100 11100 14100
Performance Sound pressure level (H) dB(A) 57 57 60
Sound power level (H) dB(A) 73 73 76
External dimensions(W/D/H) mm 990/750/1808 990/750/1808 1390/750/1808
Shipping dimensions(W/D/H) mm 1090/860/1990 1090/860/1990 1490/860/1990
Net/Shipping weight kg 240/255 240/255 368/386
Compressor type DC INV SCROLL DC INV SCROLL DC INV SCROLL
Compressor brand MITSUBISHI ELECTRIC MITSUBISHI ELECTRIC MITSUBISHI ELECTRIC
Compressor quantity 1 INV 1 INV 1 INV +1 FIX
Refrigerant type R410A R410A R410A
Installation Refrigerant charge kg 10 10 10
Refrigerant liquid pipe mm 9.52 9.52 12.7
Refrigerant gas pipe mm 22.22 22.22 25.4
Oil equalization pipe mm 9.52 9.52 9.52
Total pipe length m 300 300 300
Max. pipe length(Equivalent/Actual) m 175/150 175/150 175/150
Max drop between I.U.&O.U *1 m 50/40 50/40 50/40
External static pressure Pa 50 50 50
Connection Connectable indoor unit ratio % 50%-130% 50%-130% 50%-130%
Ratio Maximum number of indoor units 13 16 19
Cooling ℃ -5~43 -5~43 -5~43
Working temp.
Heating ℃ -15~21 -15~21 -15~21

10
Model CA43BV400-V5J1H CA43BV450-V5J1H CA43BV504-V5J1H
Capacity range HP 14 16 18
Capacity Cooling kW 40 45 50.6
Heating kW 45 50 56.5
Power supply Ph/V/Hz 3/208-230/60 3/208-230/60 3/208-230/60
Rated power input kW 12 14 14.1
Max power input kW 18.5 20 27
Cooling
Rated current A 32.75 38.95 38.5
Max current A 57.1 61.7 83.3
Electrical
Rated power input kW 12.6 14.5 14.7
Parameters
Max power input kW 18.5 20 27
Heating
Rated current A 34.65 39.85 40.3
Max current A 57.1 61.7 83.3
EER 3.33 3.21 3.59
COP 3.57 3.45 3.84
3
Air flow (H) m /h 14100 14100 22200
Performance Sound pressure level (H) dB(A) 60 60 60
Sound power level (H) dB(A) 76 76 77

990/750/1808+
External dimensions(W/D/H) mm 1390/750/1808 1390/750/1808
990/750/1808

1090/860/1990+
Shipping dimensions(W/D/H) mm 1490/860/1990 1490/860/1990
1090/860/1990
Net/Shipping weight kg 368/386 368/386 480/510
Compressor type DC INV SCROLL
Compressor brand MITSUBISHI ELECTRIC
Compressor quantity 1 INV +1 FIX 1 INV +1 FIX 1 INV +1 INV
Installation
Refrigerant type R410A R410A R410A
Refrigerant charge kg 10 10 20
Refrigerant liquid pipe mm 12.7 12.7 15.88
Refrigerant gas pipe mm 25.4 28.58 28.58
Oil equalization pipe mm 9.52 9.52 9.52
Total pipe length m 300 300 300
Max. pipe length(Equivalent/Actual) m 175/150 175/150 175/150
Max drop between I.U.&O.U *1 m 50/40 50/40 50/40
External static pressure Pa 50 50 50
Connection Connectable indoor unit ratio % 50%-130% 50%-130% 50%-130%
Ratio Maximum number of indoor units 23 26 29
Cooling ℃ -5~43 -5~43 -5~43
Working temp.
Heating ℃ -15~21 -15~21 -15~21

11
Model CA43BV560-V5J1H CA43BV615-V5J1H CA43BV680-V5J1H
Capacity range HP 20 22 24
Capacity Cooling kW 56 61.5 68
Heating kW 63 69 76.5
Power supply Ph/V/Hz 3/208-230/60 3/208-230/60 3/208-230/60
Rated power input kW 17 18.5 20.5
Max power input kW 29 31 33
Cooling
Rated current A 46.7 50.9 56.1
Max current A 89.4 95.6 101.8
Electrical
Rated power input kW 17.6 19.1 21.4
Parameters
Max power input kW 29 31 33
Heating
Rated current A 48.5 52.7 58.9
Max current A 89.4 95.6 101.8
EER 3.29 3.32 3.32
COP 3.58 3.61 3.57
3
Air flow (H) m /h 22200 25200 25200
Performance Sound pressure level (H) dB(A) 60 61 61
Sound power level (H) dB(A) 77 78 78

" 990/750/1808+ " 990/750/1808+ " 990/750/1808+


External dimensions(W/D/H) mm
990/750/1808" 1390/750/1808" 1390/750/1808"

"1090/860/1990+ "1090/860/1990+ "1090/860/1990+


Shipping dimensions(W/D/H) mm
1090/860/1990" 1490/860/1990" 1490/860/1990"
Net/Shipping weight kg 480/510 608/641 608/641
Compressor type DC INV SCROLL
Compressor brand MITSUBISHI ELECTRIC
Compressor quantity 1 INV +1 INV (1 INV) +(1 INV+1 FIX) (1 INV) +(1 INV+1 FIX)
Installation Refrigerant type R410A R410A R410A
Refrigerant charge kg 20 20 20
Refrigerant liquid pipe mm 15.88 15.88 15.88
Refrigerant gas pipe mm 28.58 28.58 28.58
Oil equalization pipe mm 9.52 9.52 9.52
Total pipe length m 300 300 300
Max. pipe length(Equivalent/Actual) m 175/150 175/150 175/150
Max drop between I.U.&O.U *1 m 50/40 50/40 50/40
External static pressure Pa 50 50 50
Connection Connectable indoor unit ratio % 50%-130% 50%-130% 50%-130%
Ratio Maximum number of indoor units 33 36 39
Working Cooling ℃ -5~43 -5~43 -5~43
temp. Heating ℃ -15~21 -15~21 -15~21

12
Model CA43BV730-V5J1H CA43BV800-V5J1H
Capacity range HP 26 28
Capacity Cooling kW 73 80
Heating kW 81.5 90
Power supply Ph/V/Hz 3/208-230/60 3/208-230/60
Rated power input kW 22.5 24
Max power input kW 34.5 37
Cooling
Rated current A 62.3 65.5
Max current A 106.4 114.2
Electrical
Rated power input kW 23.3 25.2
Parameters
Max power input kW 34.5 37
Heating
Rated current A 64.1 69.3
Max current A 106.4 114.2
EER 3.24 3.33
COP 3.50 3.57
3
Air flow (H) m /h 25200 28200
Performance Sound pressure level (H) dB(A) 61 62
Sound power level (H) dB(A) 78 79

" 990/750/1808+ "1390/750/1808+


External dimensions(W/D/H) mm
1390/750/1808" 1390/750/1808"

"1090/860/1990+ "1490/860/1990+
Shipping dimensions(W/D/H) mm
1490/860/1990" 1490/860/1990"
Net/Shipping weight kg 608/641 736/772

Compressor type DC INV SCROLL DC INV SCROLL

Compressor brand MITSUBISHI ELECTRIC MITSUBISHI ELECTRIC


Installation
Compressor quantity (1 INV) +(1 INV+1 FIX) (1 INV+1 FIX) +(1 INV+1 FIX)
Refrigerant type R410A R410A
Refrigerant charge kg 20 20
Refrigerant liquid pipe mm 19.05 19.05
Refrigerant gas pipe mm 31.8 31.8
Oil equalization pipe mm 9.52 9.52
Total pipe length m 300 300
Max. pipe length(Equivalent/Actual) m 175/150 175/150
Max drop between I.U.&O.U *1 m 50/40 50/40
External static pressure Pa 50 50
Connection Connectable indoor unit ratio % 50%-130% 50%-130%
Ratio Maximum number of indoor units 43 46
Working Cooling ℃ -5~43 -5~43
temp. Heating ℃ -15~21 -15~21

13
Model CA43BV850-V5J1H CA43BV900-V5J1H
Capacity range HP 30 32
Capacity Cooling kW 85 90
Heating kW 95 100
Power supply Ph/V/Hz 3/208-230/60 3/208-230/60
Rated power input kW 26 28
Max power input kW 38.5 40
Cooling
Rated current A 71.7 77.9
Max current A 118.8 123.4
Electrical
Rated power input kW 27.1 29
Parameters
Max power input kW 38.5 40
Heating
Rated current A 74.5 79.7
Max current A 118.8 123.4
EER 3.27 3.21
COP 3.51 3.45
3
Air flow (H) m /h 28200 28200
Performance Sound pressure level (H) dB(A) 62 62
Sound power level (H) dB(A) 79 79

"1390/750/1808+ "1390/750/1808+
External dimensions(W/D/H) mm
1390/750/1808" 1390/750/1808"

"1490/860/1990+ "1490/860/1990+
Shipping dimensions(W/D/H) mm
1490/860/1990" 1490/860/1990"
Net/Shipping weight kg 736/772 736/772

Compressor type DC INV SCROLL DC INV SCROLL

Compressor brand MITSUBISHI ELECTRIC MITSUBISHI ELECTRIC


Installation
Compressor quantity (1 INV+1 FIX) +(1 INV+1 FIX) (1 INV+1 FIX) +(1 INV+1 FIX)
Refrigerant type R410A R410A
Refrigerant charge kg 20 20
Refrigerant liquid pipe mm 19.05 19.05
Refrigerant gas pipe mm 31.8 31.8
Oil equalization pipe mm 9.52 9.52
Total pipe length m 300 300
Max. pipe length(Equivalent/Actual) m 175/150 175/150
Max drop between I.U.&O.U *1 m 50/40 50/40
External static pressure Pa 50 50
Connection Connectable indoor unit ratio % 50%-130% 50%-130%
Ratio Maximum number of indoor units 50 53
Working Cooling ℃ -5~43 -5~43
temp. Heating ℃ -15~21 -15~21

14
Model CA43BV960-V5J1H CA43BV1010-V5J1H
Capacity range HP 34 36
Capacity Cooling kW 96 101
Heating kW 108 113
Power supply Ph/V/Hz 3/208-230/60 3/208-230/60
Rated power input kW 29 31
Max power input kW 47.5 49
Cooling
Rated current A 79.5 85.7
Max current A 146.5 151.1
Electrical
Rated power input kW 30.2 32.1
Parameters
Max power input kW 47.5 49
Heating
Rated current A 83.2 88.4
Max current A 146.5 151.1
EER 3.31 3.26
COP 3.58 3.52
3
Air flow (H) m /h 36300 36300
Performance Sound pressure level (H) dB(A) 63 63
Sound power level (H) dB(A) 81 81

990/750/1808+ 990/750/1808+
External dimensions(W/D/H) mm 990/750/1808+ 990/750/1808+
1390/750/1808 1390/750/1808

1090/860/1990+ "1090/860/1990+
Shipping dimensions(W/D/H) mm 1090/860/1990+ 1090/860/1990+
1490/860/1990" 1490/860/1990"

Net/Shipping weight kg 848/896 848/896

Compressor type DC INV SCROLL DC INV SCROLL

Installation Compressor brand MITSUBISHI ELECTRIC MITSUBISHI ELECTRIC

Compressor quantity 1 INV+1 INV+(1 INV+1 FIX) 1 INV+1 INV+(1 INV+1 FIX)
Refrigerant type R410A R410A
Refrigerant charge kg 30 30
Refrigerant liquid pipe mm 19.05 19.05
Refrigerant gas pipe mm 31.8 38.1
Oil equalization pipe mm 9.52 9.52
Total pipe length m 300 300
Max. pipe length(Equivalent/Actual) m 175/150 175/150
Max drop between I.U.&O.U *1 m 50/40 50/40
External static pressure Pa 50 50
Connection Connectable indoor unit ratio % 50%-130% 50%-130%
Ratio Maximum number of indoor units 56 59
Working Cooling ℃ -5~43 -5~43
temp. Heating ℃ -15~21 -15~21

15
Model CA43BV1080-V5J1H CA43BV1130-V5J1H
Capacity range HP 38 40
Capacity Cooling kW 108 113
Heating kW 121.5 126.5
Power supply Ph/V/Hz 3/208-230/60 3/208-230/60
Rated power input kW 32.5 34.5
Max power input kW 51.5 53
Cooling
Rated current A 88.9 95.1
Max current A 158.9 163.5
Electrical
Rated power input kW 34 35.9
Parameters
Max power input kW 51.5 53
Heating
Rated current A 93.6 98.8
Max current A 158.9 163.5
EER 3.32 3.28
COP 3.57 3.52
Air flow (H) m3/h 39300 39300
Performance Sound pressure level (H) dB(A) 63 63
Sound power level (H) dB(A) 81 81

990/750/1808+ 990/750/1808+
External dimensions(W/D/H) mm 1390/750/1808+ 1390/750/1808+
1390/750/1808 1390/750/1808
1090/860/1990+ 1090/860/1990+
Shipping dimensions(W/D/H) mm 1490/860/1990+ 1490/860/1990+
1490/860/1990 1490/860/1990
Net/Shipping weight kg 976/1027 976/1027

Compressor type DC INV SCROLL DC INV SCROLL

Compressor brand MITSUBISHI ELECTRIC MITSUBISHI ELECTRIC


Installation

1 INV+(1 INV+1 FIX)+(1 INV+1


Compressor quantity 1 INV+(1 INV+1 FIX)+(1 INV+1 FIX)
FIX)
Refrigerant type R410A R410A
Refrigerant charge kg 30 30
Refrigerant liquid pipe mm 19.05 19.05
Refrigerant gas pipe mm 38.1 38.1
Oil equalization pipe mm 9.52 9.52
Total pipe length m 300 300
Max. pipe length(Equivalent/Actual) m 175/150 175/150
Max drop between I.U.&O.U *1 m 50/40 50/40
External static pressure Pa 50 50
Connection Connectable indoor unit ratio % 50%-130% 50%-130%
Ratio Maximum number of indoor units 63 64
Working Cooling ℃ -5~43 -5~43
temp. Heating ℃ -15~21 -15~21

16
Model CA43BV1180-V5J1H CA43BV1235-V5J1H
Capacity range HP 42 44
Capacity Cooling kW 118 123.5
Heating kW 131.5 137.5
Power supply Ph/V/Hz 3/208-230/60 3/208-230/60
Rated power input kW 36.5 38
Max power input kW 54.5 56.5
Cooling
Rated current A 101.3 105.5
Max current A 168.1 174.3
Electrical
Rated power input kW 37.8 39.3
Parameters
Max power input kW 54.5 56.5
Heating
Rated current A 104.0 108.2
Max current A 168.1 174.3
EER 3.23 3.25
COP 3.48 3.50
Air flow (H) m3/h 39300 42300
Performance Sound pressure level (H) dB(A) 63 64
Sound power level (H) dB(A) 81 82

990/750/1808+ 1390/750/1808+
External dimensions(W/D/H) mm 1390/750/1808+ 1390/750/1808+
1390/750/1808 1390/750/1808

1090/860/1990+ 1490/860/1990+
Shipping dimensions(W/D/H) mm 1490/860/1990+ 1490/860/1990+
1490/860/1990 1490/860/1990

Net/Shipping weight kg 976/1027 1104/1158

Compressor type DC INV SCROLL DC INV SCROLL

Installation Compressor brand MITSUBISHI ELECTRIC MITSUBISHI ELECTRIC

(1 INV+1 FIX)+
Compressor quantity 1 INV+(1 INV+1 FIX)+(1 INV+1 FIX)
(1 INV+1 FIX)+(1 INV+1 FIX)

Refrigerant type R410A R410A


Refrigerant charge kg 30 30
Refrigerant liquid pipe mm 19.05 19.05
Refrigerant gas pipe mm 38.1 38.1
Oil equalization pipe mm 9.52 9.52
Total pipe length m 300 300
Max. pipe length(Equivalent/Actual) m 175/150 175/150
Max drop between I.U.&O.U *1 m 50/40 50/40
External static pressure Pa 50 50
Connection Connectable indoor unit ratio % 50%-130% 50%-130%
Ratio Maximum number of indoor units 64 64
Working Cooling ℃ -5~43 -5~43
temp. Heating ℃ -15~21 -15~21

17
Model CA43BV1300-V5J1H CA43BV1350-V5J1H
Capacity range HP 46 48
Capacity Cooling kW 130 135
Heating kW 145 150
Power supply Ph/V/Hz 3/208-230/60 3/208-230/60
Rated power input kW 40 42
Max power input kW 58.5 60
Cooling
Rated current A 110.7 116.9
Max current A 180.5 185.1
Electrical
Rated power input kW 41.6 43.5
Parameters
Max power input kW 58.5 60
Heating
Rated current A 114.4 119.6
Max current A 180.5 185.1
EER 3.25 3.21
COP 3.49 3.45
Air flow (H) m3/h 42300 42300
Performance Sound pressure level (H) dB(A) 64 64
Sound power level (H) dB(A) 82 82

1390/750/1808+ 1390/750/1808+
External dimensions(W/D/H) mm 1390/750/1808+ 1390/750/1808+
1390/750/1808" 1390/750/1808

1490/860/1990+ 1490/860/1990+
Shipping dimensions(W/D/H) mm 1490/860/1990+ 1490/860/1990+
1490/860/1990 1490/860/1990

Net/Shipping weight kg 1104/1158 1104/1158

Compressor type DC INV SCROLL DC INV SCROLL

Installation Compressor brand MITSUBISHI ELECTRIC MITSUBISHI ELECTRIC

(1 INV+1 FIX)+(1 INV+1 FIX)+(1 (1 INV+1 FIX)+(1 INV+1 FIX)+(1


Compressor quantity
INV+1 FIX) INV+1 FIX)
Refrigerant type R410A R410A
Refrigerant charge kg 30 30
Refrigerant liquid pipe mm 19.05 19.05
Refrigerant gas pipe mm 38.1 38.1
Oil equalization pipe mm 9.52 9.52
Total pipe length m 300 300
Max. pipe length(Equivalent/Actual) m 175/150 175/150
Max drop between I.U.&O.U *1 m 50/40 50/40
External static pressure Pa 50 50
Connection Connectable indoor unit ratio % 50%-130% 50%-130%
Ratio Maximum number of indoor units 64 64
Working Cooling ℃ -5~43 -5~43
temp. Heating ℃ -15~21 -15~21

18
2.2 Piping diagram

CA43BV224/280-V5J1H

one-way valve drier


Toci1 LEVa1 accumulator sub-cooler liquid pipe
outdoor
Toci2 Tdef Tsco Tliqsc

Tao LEVa2
LEVb
SV6/6A

4WV SV1/2A

Pd Sensor
Ps Sensor
Ts
O/Si
HPSi
Tsuc
SV11/2A

Tsi
Tdi

Comp

INV
Toil
CHi Cha SV10/2A
segregator gas pipe
SV9/2A
Φ6.35
Toilp oil equipoiser

〈outdoor1〉
TC1 Tai TC2 LEV
(Note) ・ :connect
・ :disconnect

〈indoor1〉

19
CA43BV335/400/450-V5J1H

one-way valve drier


Toci1 LEVa1 accumulator sub-cooler liquid pipe
outdoor
Toci2 Tdef Tsco Tliqsc

Tao LEVa2
LEVb
SV6/6A

4WV SV1/2A

Pd Sensor
Ps Sensor
Ts
O/Si
HPSi
Tsuc
SV11/2A

Tsi
Tdi

Comp

INV
Toil
CHi Cha SV10/2A
segregator gas pipe
SV9/2A
Φ6.35
Toilp oil equipoiser

〈outdoor1〉
TC1 Tai TC2 LEV
(Note) ・ :connect
・ :disconnect

〈indoor1〉

20
Part name Sign Function Data
Capacity control,meet indoor load request by adjusting the
Compressor MC resistor of 3-phase coil:0.583Q(20C)
frequency

Hs High pressure protection 4.15MPa, OFF


Pressure Switch
Ls Low pressure protection 0.05 MPa,OFF

In heating,compressor frequency adjustment abnormal


Pd PS8051A150NH4-H4
pressure protection
Pressure Sensor
In cooling, compressor frequency adjustment, abnormal
Ps PS8051A150NH4-L2
pressure protection

PMV1 in heating,refrigerant flow control 10TON

Electronic 1. Sub-cooling valve. In cooling, be controlled due to air


Expansion Valve return sub-cooling degree. Ø2.4(8-14HP)
PMV2
2. Refrigerant spraying when discharging temp. Or oil temp. Is Ø3.0(16HP)
too high

1. Keep balance of high/low pressure when compressor starts


up or stops;
SV1
2. High/low pressure protection, and auxiliary oil return when
fqy is over 85hz.

When equalizing oil, the discharging oil outdoor starts up and


SV8
make high pressure for the oil groove. AC220V, open when power is on; close when
Solenoid Valve
SV9 When equalizing oil among modules, sv9 will open. power is off
SV10 Oil equalization route
In heating, sv11 in the stop unit will open to balance the
SV11
pressure at the low pressure side against liquid return

Open at non-oil equalization to balance pressure between oil


SV12
tank and compressor

AC220V, electrified in heating; not electrified in


4-Way Valve 4WV Change over between cooling and heating
cooling or defrosting

Toil Check refrigerant oil temp. At compressor bottom


R(25˚C)=10K B(25/50˚C)=3700K
Te Check frost condition of outdoor heat exchanger

Td Detect the discharge temp. Of compressor R(80˚C)=50K B(25/80˚C)=4450K

Ts Detect the suction temp. Of compressor


Temp. Sensor R(25˚C)=10K B(25/50˚C)=3700K
Detect ambient temp.,Set primary setting for fan speed,
Ta
target pressure and eev open angle

Detect the condenser gas pipe temp., And control mpv1 in


Toci R(50˚C)=17K
heating mode

Tin Detect the radiator temp. B(25/80˚C)=4170K

CH1 Used to heat liquid refrigerant in gas-liquid segregator 40W, 220V


Heater
CH2 Used to heat oil in compressor 40W, 220V

21
M

CN21 HPS1 R CN50


43 2 1 B FAN1
Inverter

P
CN608

1 2 1 2
High CN20 HPSi R BL CN49
U V W pressure 4WV
2.3 Wiring diagram
sensor CN19 HPS2 R LD1 LD2 LD3 LD4
5
4 SW9 SW 10 SW11 CN48
3 CN603 W
2 CN18 WQS R SV1
1 S W2 SW 1
Fan Driver CN12 Toci1 W CN11 Y UP DOWN CN47
CA43BV224/280-V5J1H

1 2 3
Tao R SV6
CN10 TSi BL CN13 G LED1 LED2 LED3
DCN Tliqsc
ACN
B COMP
ACL
CN14 BL outdoor indoor INV Y CN46
SV9 U W
CN15 Toilp R Tsco V
R
DCP CN16 G
CN17 Toil R Tdef W SCVN1405

1 2 3 1 2 3
CN7
High Toci U V W
pressure
sensor
CN4 R
CN5 Pd R BL CN44

1 2 3
Tdi SV11 G
Low CN3 CN7

2 3
pressure R LED1 LED2 LED3 Fuse Radiator
sensor
CN6 Ps BL Td1 Y CN43 P
SV13i T3.15A-250V Temperature
CN2 Sensor
R N

1 2 3
Tsuc

1 2
CN1 Ts BL W CN42
CN8 SV3i

1 2 3
CT2 Y R CN41
CN9 CT1 W

1 2 3
W BR (pump)SV3
CN8 Inverter
CN51 750W W R CN40
C o n tr ol B o ad COMP1
- + B CN39
CN30 APY-COM W COMP2 B CN2 Y CN3 W CN1
CN38

22
Capacitor board G Y BL

1 2
CN29 R CHa
CN26 LEVA2
CN25 LEVA1 CN37 Capacitor
R G CHi

2 3 4 51 6
R AC Contactor

12 3 4 5 6
- + CN33 R
W CH1
R Shunt
Fuse CN53 W Y
CN24 LEVB B Resistance
T15A-250VAC CN52
Y

12 3 4 5 6
R R R + Y PTC Y
R ~
CN32 CN31 CN27 S W W
BUS1 BL W T6.3A-250VAC B ~
Reactor
Power T B W W
CN28 CN34
-
P Reactifier

W BL ~
INV COM


375W FAN W N
Reactor

7
6
5
4
3
1
2
W W

R
W
B

R W B

Notice :
R BL OR Y BL
1.The filter in the dashed part is optional.
P Q A B C L1 L2 L3 2.The colours use these letters for short
W:white B:Black R Red GR :Gray B L:Blue
Y:Yellow G :Green BR:Brown OR:Orange。
Indoor Outdoor Power:3N~,220V, 60Hz
Units Units
0 15 0 5104 81
Fixed Frequency
High pressure

P
sesor
CN2 1 HPS 1 C N50
F AN1

P
Inverter

1 2 1 2
High pressure CN2 0 HPS i CN 49
D C FA N Sensor 4WV
CN1 9 HPS 2 LD1 LD2 LD3 LD4
M M SW 9 SW 10 SW 11 C N48
CN1 8 WQS S V1
SW2 SW1

1
2
2

3
4
1
3
4

5
6
5
6
C N12 T oci 1 CN 11 UP DOW N C N47

1 2 3
CN8 CN7 Ta o S V6
FA N -R FA N -L C N10 T Si CN 13 L ED1 L ED2 LED 3
CA43BV335/400/450-V5J1H

CN 9 Tl iq sc COMP
CN 14 C N46
Fan Driver o u td o or i n do o r INV S V9 U W
C N 1 5 T oi l p

7 6 5 43 2 1
1 2 3
Ts co V
CN 16 C N45
+310V CN5 CN6 GND C N17 T oil Td ef S V10

1 2 3
CN 7
High To ci U V W
pressure
sensor
CN 4 C N44
C N5 Pd

1 2 3
Td i S V11
Low CN 3 G CN7

2 3
pressure CN 43 L ED1 L ED2 LED 3 Fuse Ra di ato r
sensor
C N6 Ps Td 1 P
SV 13i T3.15A-250V Temperature
CN 2 S ens or
+ N

1 2 3
R Ts uc CN 42

1 2
C N1 Ts
- CN 8 SV3i

1 2 3
CT 2 CN 41
B C N9 CT 1

1 2 3
W BR ( pump ) S V 3
CN8 Inverter
CN 40
C N51 7 50W
Control board C OM P1
- + CN 39
C N30 A PY- CO M C OM P2 CN2 CN3 CN1
BR W
C N3 8 Y
Capacitor board C N2 9 BL

1 2
C Ha
W R

23
CN 26 L EVA 2

1 6
CN 25 LE VA 1 CN 37 Cap acito r
CH i

2 3 4 5
AC Contactor

12 3 4 5 6
- + CN 33
CH 1
B S h unt
CN 52 R Y
CN 24 L EV B R esi stanc e
Fuse CN5 3

12 3 4 5 6
T1 5A -25 0V AC R R + Y PTC Y Y
R ~
CN 32 CN31 CN 27 S W W
BUS1 B ~
B B Reactor
T6 .3A -2 50V AC
电源 T B
CN 28 CN34
-

P Reactifier

INV COM 375W FAN N BL


Reactor
B B

7
6
5
4
3
1
2
AC Contactor
R R
W
Filter B W R U
B
W V
R W B
B W
Fixed
R BL OR Y BL CT F req u e ncy
Terminal Block for L1 L2 L3 Notice : Co mpress or
P Q A B C
Communication
1.The filter in the dashed part is optional.
2.The colours use these letters fo r short
In door O utdoor Power:3N~,220V, 60Hz W :white B:Black R Red GR :Gray B L:Blue
U n its U n i ts Y:Yellow G :Green BR:Brown OR:Orange 。 0150510483
2.4 Field wiring

Wiring of indoor units( for example)

Wiring of outdoor units( for example)

24
2.5 Operation range

Cooling
45

40 Heating
35 20

30 15
Consecutive operation
outdoor air DB(℃ )

25 10

Consecutive operation
20 outdoor air DB(℃ ) 5

15 0

10 -5

5 -10

0 -15

-5
10 15 20 25 30
10 15 20 25 30
Indoor air DB(℃ ) Indoor air DB(℃ )

25
2.6 Outdoor unit group

(1)Testing illustration

(2)Testing condition:
a. Unit running in the nominal condition
b. Test in the semi-anechoic chamber
c. Noise level varies from the actual factors such as room structure,etc

(3)Noise level dB(A):


Air speed 8HP 10HP 12HP 14HP 16-20HP 22-26HP 28-32HP 34-42HP 44-48HP
H 57 57 60 60 60 61 62 63 64

(4)Octave band level

CA43BV224/280-V5J1H
YV2VYH024/029KAJ-D-X CA43BV335/400/450-V5J1H
YV2VYH035/42/45KAJ-D-X
Octave band sound pressure level DB
Octave band sound pressure level DB

limit of audible limit of audible


continuous continuous
noise noise

Octave band center frequency(HZ) Octave band center frequency(HZ)

26
Safety

This manual should always be accessible and close to this air condition equipment.

There are two types of indications, " WARNING" and " CAUTION". The indication preventing from death or heavy
injury is listed as " WARNING". Even the indication listed as " CAUTION" may also cause serious accident. Both of
them are related to safety, and should be strictly followed.

After installation and start-up commissioning, please handover the manual to the user. The manual should be well
kept in safe place and close to the unit.

WARNING

The installation or the maintenance should be performed by an authorized agency. The wrong operation of this air
condition equipment may cause water leakage, electric shock or fire.
Please install the unit on the top of a solid foundation or structure which is strong enough to support the unit.
The installation of this air condition equipment should follow local construction codes.
Use the right cable size, secure the terminal firmly, organize the cables well and make sure no tension is added on
cables. Cable insulation should not be damaged. The incorrect installation may lead to overheat or fire.
When installing or moving the unit, the refrigerant system should be vacuumed and recharged with R-410A
refrigerant. If any other gas enters the system, it may lead to abnormal high pressure which may cause damage or
injury.
Please use the proper manifolds or branches during the system installation. The wrong parts may cause refrigerant
leakage.
Keep the drain pipe away from toxic gas vents to prevent possible pollution of indoor environment.
During or after the installation, please check whether there is refrigerant leakage. If any leakage, please take any
measures for ventilation. The refrigerant may be toxic at some concentration levels.
The unit is not explosion-proof. Please keep it away from flammable gases.
The drain pipe should be installed per this manual to ensure proper drainage. The pipe should be well insulated to
avoid condensation. Wrong installation may lead to water leakage.
Both liquid pipe and the gas pipe should be also well insulated. Not enough insulation may lead to system
performance deterioration or humidity formation.
This air condition equipment is not intended to be operated by persons with lack of experience and training, unless
they have supervision or instruction concerning use of this air condition equipment.
Please keep children away from this air condition equipment.

27
Safety

CAUTION
Grounding wire should be connected with the grounding bar. The grounding wire cannot be connected to the gas
pipe, water pipe, lightening rod or the telephone grounding wire. Improper grounding may cause electric shock.
Units installed on roof should have appropriate access and handrail.
Use the wrench to fasten the nut and flare at proper torque. Excessive torque may cause flared section broken,
leading to refrigerant leakage.
After refrigerant pipe installation, please take nitrogen leakage test to avoid refrigerant leakage.
R-410A is the only permitted refrigerant.
To avoid mischarging wrong refrigerant, the check valve diameter is changed for R-410A. To strengthen the pipe, the
flared pipe dimension is also changed. Please use R-410A specified tools as shown below.

R-410A specified tools Remarks


1 Gauge manifold Range: HP>4.5MPa,LP>2MPa

2 Charge hose Pressure: HP 5.3MPa,LP 3.5MPa


Electronic weight for
3 No other means permitted
charging R410A
4 Torque wrench
5 Flare tool
Copper pipe gauge for
6
adjusting projecting margin
7 Vacuum pump fitting Vacuum pump must be equipped with check valve

8 Leakage detector Only Helium detector permitted

When charging refrigerant, the refrigerant must be in liquid state from the tank.
To prevent EMC interference on other appliances, please keep indoor unit, outdoor unit, power cable and connecting
wire at least 1m away from those appliances .
Fluorescent lamp (reverse phase or rapid start type) may interfere the remote controller's signal. Please install indoor
unit away from fluorescent lamp. The farther the better.

28
Installation instruction

Installation & Startup Quick Guides


1. Installation Procedure
1.1 Drafting of diagram, select the installing place including the wiring and piping
1.2 Pre-installation, including pipe protective sleeves, hooks, supports, etc.
1.3 Indoor installation
1.3.1 Indoor DIP Switch settings
1.3.2 Indoor unit installation
1.3.3 Refrigerant piping installation
1.3.4 Drain piping installation
1.3.5 Duct work when install the duct indoor unit
1.3.6 Heat insulation work, including refrigerant pipe and drain pipe
1.3.7 Electric wiring work
1.4 Outdoor installation
1.4.1 Outdoor unit foundation work
1.4.2 Outdoor unit installation
1.4.3 Refrigerant piping connection
1.4.4 Leakage test
1.4.5 Vacuum drying
1.4.6 Additional refrigerant charging
1.4.7 Outdoor maintenance panel installation
1.5 Installation double check, indoor, outdoor, piping, and wiring
2. Startup Procedure
2.1 Check the power cables connection of each indoor unit
2.2 Check the communication wires connection of each indoor unit
2.3 Check the wired controller wires connection of each indoor unit
2.4 Set Protocol Translator dip switches If connected with Central controller or BMS system
2.5 Check the central controller or BMS setting if the central controller or BMS device are used
2.6 Check the power cables connection of each outdoor
2.7 Check the P,Q connection and the communication among outdoors A,B, c connection
2.8 Check the indoor control type
2.9 Check the indoor communication address when in central control
2.10 Check the indoor central control address when in central control
2.11 Check the indoor group control address when in group control
2.12 Check the outdoor pipe length switch on outdoor PCB
2.13 Check the outdoor capacity over match switch setting on outdoor PCB
2.14 Check the outdoor unit address: the master unit must be No. 1
2.15 Check the outdoor units searching when multi units in combination
2.16 Check the outdoor capacity
2.17 Start commissioning according to the rotary switch function
Warning:
Please set Indoor DIP Switches before installing Indoor units into its final position

29
Installation instruction

For installation, please review the items below:


Is the connected units quantity and the total capacity in the allowable range?
Is the refrigerant pipe length in the limited range?
Is the pipe size proper? And if the pipe installed horizontally?
Is the branch pipe installed horizontally or vertically?
Is the additional refrigerant counted correctly and weighed by the standard balance?
Is there refrigerant leakage?
Is all the indoor power supplies can be on/off simultaneously?
Is the power voltage in compliance with the data marked on the rating label?
Is the address of indoors and outdoors has been set?

(1) Accessories

No. Name Quantity


1 12 inches big tie wrap 3
2 4 inches small tie wrap 4
3 Installation manual 1
4 T Shape pipe, only use for commination modules 1

(2) Before installation


1) Before installation, check if the model, power supply, pipe, wires and parts purchased respectively are correct.
2) Check if the indoors and outdoors can be combined as the following.

Name Model Function For what units


Outdoor branch HZG-20A Refrigerant 2 Modules
pipe HZG-30A gathering 3 Modules

Outdoor Indoor
Capacity Total indoor Gather pipe
Combination type Indoor Qty
(100W) capacity (100W)
226 Single 13 113-293
280 Single 16 140-364
335 Single 19 167-436
400 Single 23 200-520
450 Single 26 225-585
506 Combination (226+280) 29 252-656 HZG-20A
560 Combination (280+280) 33 280-728 HZG-20A
615 Combination (335+280) 36 307-800 HZG-20A
680 Combination (400+280) 39 340-884 HZG-20A
730 Combination (450+280) 43 365-949 HZG-20A
785 Combination (450+335) 46 393-1021 HZG-20A
850 Combination (400+450) 50 425-1105 HZG-20A
900 Combination (450+450) 53 450-1170 HZG-20A

30
Installation instruction

Outdoor Indoor
Capacity Total indoor Gather pipe
Combination type Indoor Qty
(100W) capacity (100W)
960 Combination (400+280+280) 56 480-1248 HZG-30A
1010 Combination (450+280+280) 59 505-1313 HZG-30A
1065 Combination (450+335+280) 63 533-1385 HZG-30A
1130 Combination (400+280+450) 64 565-1469 HZG-30A
1180 Combination (450+450+280) 64 590-1534 HZG-30A
1235 Combination (335+450+450) 64 617-1606 HZG-30A
1300 Combination (400+450+450) 64 650-1690 HZG-30A
1350 Combination (450+450+450) 64 675-1755 HZG-30A

(3) Installation place selection

Air-conditioner can't be The unit should be installed at the


installed in the place with place with good ventilation. No The unit should be installed at the strong
inflammable gas. Or it will obstacle at the enough place. Or it will cause vibration and
cause fire hazard. air inlet/outlet. And no strong wind noise.
blows the unit.

The installation space refers to the The unit is better not be installed at the
latter info. below places, or it will
The unit should be installed
cause damage.
at the place where the cold/
The place where there is
hot air or noise will not The place where the water can
corrosive gas (spa area etc).
interfere the neighbours. flow fluently.
The place blowing salty air
The place where no other heat
(seaside etc).
source will affect the unit.
Pay attention to the snow against Exists the strong coal smoke.
clogging the outdoor. The place with high humidity.
In installation, install the anti- The place where there is device emitting
vibration rubber between the unit Hertzian waves.
and the bracket. The place where voltage changes greatly.

31
Installation instruction

Note:
1. Install adapter to change wind direction at the gas short circuit place.
2. When installing multiple units, there should be enough air inlet place
against air in short circuit.
3. In snowy area, install the unit under the bracket or the snow-proof
cover against the accumulative snow on the unit.
4. Do not install the unit at the place where the flammable gas will leak.
5. Install the unit at the strong enough place.
6. Install the unit at the flat place.
7. When the refrigerant pipe is leaded out from the bottom of the unit,
the below section should be a bracket with over 500mm height, see
below figure.
8. When being installed at the place with strong wind, set the air outlet of the unit and the wind direction vertical. Also
fix the unit with the screw.
9. When opening the electric box cover for maintenance, please fix the cover with screw firmly.

(4) Transportation
In transportation, please don't dismantle the packaging, and move
the unit to the installation location as closely as possible.
Don't hang the unit only at two points. When hanging the unit,
don't sit on the unit. The unit should be upright.
When removing the unit with the forklift, put the fork into the
special hole at bottom of the unit. When being hanged, the rope
should be 4 pieces of steel cable with over 6mm diameter.
Put the cushion at the contact section between steel cable and
the unit against the distortion or damage.

Note:
There should be no obstacles in 2000mm above the top of outdoor
unit;
Obstacles around outdoor should be less than 800mm to the
bottom of unit.
When multiple modules are installed, the outdoor should be in
ranked as the capacity, the larger capacity is closer to the main pipe
of gather pipe.

32
Exterior and installation dimensions

1. 8~10HP exterior and installation dimensions


(CA43BV224-V5J1H CA43BV280-V5J1H)

2. 12~16HP exterior and installation dimensions


(CA43BV335-V5J1H CA43BV400-V5J1H CA43BV450-V5J1H)

Note:
The distance between two outdoor units in the same line and the distance from unit to the wall can be increased for
easy maintenance and better heart exchange if there is enough space.

33
Exterior and installation dimensions

3. Combination installation dimensions


(1) When outer wall is lower than the outdoor condenser
A. Sites for one-row layout

B. Sites for two-row layout

C. Sites for three-row layout

34
Exterior and installation dimensions

(2) Wall higher than the outdoor condenser


A. Place with air inlet hole
Notes:
a. Fan speed Vs at air inlet is 1.5m/s or below.
b. Air outlet height HD=H-h and below 1m.

B. Place without air inlet hole


Notes:
a. Set a 500~1000mm bracket.
b. Air outlet height HD=H-h and below 1m.

35
Installation procedure

A. Refrigerant pipe connection


When fastening and loosing the nut,
Pipe connection method: operate with double spanners,
To ensure the efficiency, the pipe should be as short as possible. because only one spanner cannot
Daub the Refrigerant Oil on the connector and the flare nut. execute firmly.
When bending the pipe, the bending semi-diameter should be as large
as possible against the pipe being broken or bent.
When connecting the pipe, aim at the center to thread the nut by hand
and tighten it with the double spanners.
Fastening torque please refers to "pipe specs and fastening torque" on
page 17. If threading the nut as not aiming
Don't let the impurity such as sand, water etc into the pipe. Antifouling at the center, the screw thread will
measures refer to Page 10. be damaged, further it will cause
leakage.

Cautions in piping installation:


1. When welding the pipe with hard solder, charge nitrogen into the pipe against oxidation. The pressure gauge should
be set at 0.02MPa.Perform the procedure with nitrogen circulation. Otherwise, the oxide film in the pipe may clog
the capillary and expansion valve resulting in accident.
2. The refrigerant pipe should be clean. If the water and the other impurity enter the pipe, charge the nitrogen to clean
the pipe. The nitrogen should flow under the pressure of about 0.5Mpa and when charging the nitrogen, stop up
the end of the pipe by hand to enhance the pressure in the pipe, then loose the hand (meanwhile stop up the other
end).
3. The piping installation should be executed after the stop valves are closed.
4. When welding the valve and the pipe, cool down the valve with wet towel.
5. When the connection pipe and the branch pipe need to be cut down, please use the special shears and cannot use
the saw.
6. When welding copper pipe, use the phosphor copper welding rod without any welding flux. (welding flux will
damage the piping system. The welding flux containing chlorine will corrode pipe, especially, the welding flux with
fluorine will damage refrigeration oil.)

Pipe material and specs selection


1. Please select the refrigerant pipe of the below material.
Material: the phosphoric oxidize seamless copper pipe, model: C1220T-1/2H (diameter is over 19.05); C1220T-
0(diameter is below 15.88).
2. Thickness and specs:
Confirm the pipe thickness and specs according to the pipe selection method(the unit is with R410A, if the pipe over
19.05 is 0-type, the pressure preservation will be bad, thus it must be 1/2H type and over the min. thickness.
3. The branch pipe and the gather pipe must be from JCI.
4. When installing the stop valve, refer to the relative operation instruction.
5. The pipe installation should be in the allowable range.
6. The installation of branch pipe and gather pipe should be performed according to the relative manual.

36
Installation procedure

Anti-fouling measures
First, clean the pipe.
Position Installation period Measures
More than 1 month Flat the pipe end
Outdoor
Less than 1 month Flat the pipe end or
Indoor Nothing to do with period Seal with adhesive tape

Pipe specification:

1. Pipe " a” diameter(between indoor and branch


pipe) (depends on indoor pipe)
Indoor (x100W) Gas pipe (mm) Liquid pipe (mm)
22~28 Ø9.52 Ø6.35
36~56 Ø12.7 Ø6.35
71~140 Ø15.88 Ø9.52
Note:
CH43BV022-HYJ1H CH43BV028-HYJ1H gas pipe: Ø12.7mm
CH43BV056-HYJ1H gas pipe/ liquid pipe: Ø15.88mm/9.52mm
2. Pipe “b” diameter (between branch pipes)
Total indoor capacity after the branch pipe (kW) Gas pipe (mm) Liquid pipe (mm)
<16.8kW Ø15.88 Ø9.52
16.8kW≤X<22.4kW Ø19.05 Ø9.52
22.4kW≤X<33.0kW Ø22.22 Ø9.52
33.0kW≤X<47.0kW Ø28.58 Ø12.7
47.0kW≤X<71.0kW Ø28.58 Ø15.88
71.0kW≤X<101.0kW Ø31.8 Ø19.05
≥101.0kW Ø38.1 Ø19.05

Note: Adjust the diameter on field (changing pipe is needed)


When the latter indoor total capacity is less than 14.0kW, pipe b will use the specs as the pipe a.

37
Installation procedure

3. Pipe “c”diameter (main pipe, between outdoor gather pipe and the first branch pipe)

Main pipe Enlarged main pipe


Outdoor capacity
Gas pipe (mm) Liquid pipe (mm) Gas pipe (mm) Liquid pipe (mm)
22.6kW Ø22.22 Ø9.52 Ø22.22 Ø12.7
28.0kW Ø22.22 Ø9.52 Ø25.4 Ø12.7
33.5kW Ø28.58 Ø12.7 Ø28.58 Ø12.7
40.0kW Ø28.58 Ø12.7 Ø28.58 Ø12.7
45.0kW Ø28.58 Ø12.7 Ø31.8 Ø12.7
50.6kW Ø28.58 Ø15.88 Ø31.8 Ø15.88
56.0kW Ø28.58 Ø15.88 Ø31.8 Ø15.88
61.5kW Ø28.58 Ø15.88 Ø31.8 Ø15.88
68.0kW Ø28.58 Ø15.88 Ø31.8 Ø15.88
73.0kW Ø31.8 Ø19.05 Ø38.1 Ø19.05
78.5kW Ø31.8 Ø19.05 Ø38.1 Ø19.05
85.0kW Ø31.8 Ø19.05 Ø38.1 Ø19.05
90.0kW Ø31.8 Ø19.05 Ø38.1 Ø19.05
96.0kW Ø31.8 Ø19.05 Ø38.1 Ø19.05
101.0kW Ø38.1 Ø19.05 Ø38.1 Ø22.22
106.5kW Ø38.1 Ø19.05 Ø38.1 Ø22.22
113.0kW Ø38.1 Ø19.05 Ø38.1 Ø22.22
118.0kW Ø38.1 Ø19.05 Ø38.1 Ø22.22
123.5kW Ø38.1 Ø19.05 Ø38.1 Ø22.22
130.0kW Ø38.1 Ø19.05 Ø38.1 Ø22.22
135.0kW Ø38.1 Ø19.05 Ø38.1 Ø22.22

Note:
When the distance from outdoor to the longest indoor is over 90m, the main pipe should be the enlarged diameter.

4. Pipe “d” diameter (between outdoor branch pipe)

Total outdoor capacity before the gather pipe Liquid pipe(a, c) (mm) Gas pipe(b,d) (mm)
~68.0kW Ø15.88 Ø28.58
69.0~90.0kW Ø19.05 Ø31.8

38
Installation procedure

5. Pipe “e” diameter (between outdoor and the outdoor branch pipe)
Outdoor capacity Gas pipe (mm) Liquid pipe (mm) Oil equalization pipe (mm)
CA43BV224-V5J1H
Ø22.22 Ø9.52
CA43BV280-V5J1H
Ø9.52
CA43BV335-V5J1H
CA43BV400-V5J1H Ø28.58 Ø12.7
CA43BV450-V5J1H
Copper pipe selection:
Material O type pipe: soft pipe
Pipe diameter (mm) Ø6.35 Ø9.52 Ø12.7 Ø15.88 Ø19.05
Thickness (mm) 0.8 0.8 1.0 1.0 1.1

Material Hard pipe


Pipe diameter (mm) Ø19.05 Ø22.22 Ø25.4 Ø28.58 Ø31.8 Ø34.9 Ø38.1 Ø41.3
Thickness (mm) 1.0 1.0 1.0 1.0 1.1 1.3 1.4 1.5

Long pipe and high drop

1. Applicable range

Model All outdoors


Item

Single way total pipe length 300m


Single way pipe length Max.: 175m (Equivalent length)
Main pipe beween outdoor to 1st branch Max.: 175m (Equivalent length)
Pipe length between outdoors Less than 10m to 1st branch pipe
Height difference between Outdoor is above Max. 50m
indoor and outdoor Outdoor is below Max. 40m
Height difference between outdoors
Within 5m (better be horizontal)
(in the same system)
Max. pipe length from 1st branch pipe to indoor Max. 40m
Height difference between indoors Max. 15m

39
Installation procedure

2. Pipe length between outdoors

Gas/liquid pipe: L1+L3<10m, L2+L3<10m


Oil equalization pipe: L5+L6<10m
Height difference between outdoors: h<5m
Note:
a. HZG-30A includes HZG-20A;
b. The connection pipe among outdoors can't be higher than the outdoor unit stop valve to avoid over oil return to
compressor;
c. The piping should be installed horizontal or with slope toward the interior units (less than 15degree).

40
Installation procedure

Piping installation with positive slope is not allowed.

d. For installations with outdoors at different heights, please follow either of the layouts below:

41
Installation procedure

When changing the height of the pipe connecting


different outdoors at different heights,please do as the
figure shows: Oil trap (upright projecting pipe, 200mm
high), for maximum outdoor
unit height difference,
please refer to Page 124

Installation below is not allowed

3. Allowable piping length and drop between indoor and outdoor

When the distance between outdoors is over 2m, the oil trap must
be set (upright projecting pipe, 200mm high), as the figure:

42
Installation procedure

Max. length Pipe in above figure

L1+L2+ L3+ L4+ L5+ L6+ L7+L8+ L9+


Single way total pipe length 300
L10+ L11+ L12+ L13+ L14+ L15

Single way max. pipe equivalent length 175 L1+ L3+ L5+ L7+ L14+ L13
Max. pipe length after 1st branch pipe 40 L7+L13+L14
Main pipe equivalent length 135 L5
Height difference between indoors 15 --
Height difference between outdoors 5 --

Outdoor pipe dimension

The pipe " a, b, c, d” should be confirmed as to the below table.

Total outdoor capacity before the gather pipe (kW) Liquid pipe(a, c) (mm) Gas pipe(b,d) (mm)
~62.0 Ø12.7 Ø28.58
62.0~96.0 Ø15.88 Ø31.8
96.0~101.0 Ø15.88 Ø38.1
over 101.0 Ø19.05 Ø38.1

Note: When the single pipe length is over 90m, the above pipe should be enlarged as the former information.

Oil equalization pipe connection

Oil equalization pipeØ9.52mm Oil equalization pipeØ9.52mm

43
Installation procedure

Unit pipe spec and connection method (unit:mm)

A. Outdoor unit
Gas pipe Liquid pipe Oil pipe
Model Diameter Connecting Diameter Connecting Diameter Connecting
(mm) method (mm) method (mm) method
CA43BV224-V5J1H Ø22.22 Ø9.52 Ø9.52
CA43BV280-V5J1H Ø22.22 Ø9.52 Ø9.52
CA43BV335-V5J1H Ø28.58 Braze Ø12.7 Flared Ø9.52 Flared
CA43BV400-V5J1H Ø28.58 Ø12.7 Ø9.52
CA43BV450-V5J1H Ø28.58 Ø12.7 Ø9.52

B. Indoor unit
Model Gas pipe Liquid pipe
Capacity
(kBtu/h) Diameter (mm) Connecting method Diameter (mm) Connecting method
07 Ø9.52 Ø6.35
09 Ø9.52 Ø6.35
12 Ø12.7 Ø6.35
16 Ø12.7 Ø6.35
18 Ø12.7 Ø6.35
24 Ø15.88 Flared Ø9.52 Flared
28 Ø15.88 Ø9.52
30 Ø15.88 Ø9.52
38 Ø15.88 Ø9.52
48 Ø15.88 Ø9.52
72 Ø25.4 Ø9.52
Braze
96 Ø25.4 Ø9.52

CH43BV022-HYJ1H, CH43BV028-HYJ1H gas pipe: 12.7mm


CH43BV056-HYJ1H gas pipe/ liquid pipe: 15.88mm/9.52mm

C. Pipe spec and the torque


Diameter (mm) Torque (N·m)
Ø6.35 16~20
Ø9.52
40~50
Ø12.7
Ø15.88 90~120
Ø19.05 100~140
Not less than Ø22.22 No requirement, due to braze connector

44
Installation procedure

Manifold pipe

Manifold pipe selection:


Total indoor capacity(100W) Model(optional)
Less than 335 FQG-B335A
More than 335, less than 506 FQG-B506A
More than 506, less than 730 FQG-B730A
More than 730 FQG-B1350A

Outdoor unit type


The master unit will choose the closest one to the 1st manifold pipe.
Note:
1. When connecting the outdoor branch pipe and the outdoor, please pay attention to the outdoor pipe dimension.
2. When adjusting the diameter among outdoor branch pipe and among the units, please must execute at the branch
pipe side.
3. Please install the outdoor branch pipe (gas/liquid side) in horizontal or vertical direction.
4. When welding with hard solder, please must blow nitrogen. If not, a number of oxide will be produced and cause
heavy damage.Besides,to prevent water and dust into the pipe, please make the brim as outer roll.

Pipe installation
When doing the piping connection, please do the following:
Please don't let the pipe and the parts in the unit collide each other.
When connecting the pipes, close the valves fully.
Protect the pipe end against the water, impurity into the pipes (welding after being flat, or being sealed with adhesive
tape).
Bend the pipe as large semi-diameter as possible(over 4 times of the pipe diameter).
The connection between outdoor liquid pipe and the distributing pipe is flared type. Please expand the pipe with the
special tool for R410A after installing the expanding nut. But if the projecting pipe length has been adjusted with the
copper pipe gauge, you can use the original tool to expand the pipe.
Since the unit is with R410A, the expanding oil is ester oil, not the mineral oil.

45
Installation procedure

When doing the flare connection, please do the following: When connecting the expanding pipe, fasten the pipes with
double-spanner. The torque refers to the former info.
Expanding pipe:A(mm) Projecting length of pipe to be expanded:B(mm)
Pipe outer 0 Pipe outer When it is hard pipe
Diameter A -0.4 Diameter Special tool The former
(mm) (mm) for R410A Tool
Ø6.35 9.1 Ø6.35
Ø9.52 13.2 Ø9.52
0-0.5 1.0-1.5
Ø12.7 16.6 Ø12.7
Ø15.88 19.7 Ø15.88
The outdoor gas pipe and the refrigerant distributing pipe, as well the refrigerant distributing pipe and the branch pipe
should be welded with hard solder.
When doing the braze connection, please do the following: Brazing the pipe at the same time charge the nitrogen. Or
it will cause a number of impurity (a film of oxidation) to clog the capillary and the expansion valve, further cause the
deadly failure.
Operation procedure
Brazing the pipe at the same time charge the nitrogen. Or it will cause a number of impurity (a film of oxidation) to
clog the capillary and the expansion valve, further cause the deadly failure.
Seal the pipe end with adhesive tape or the stopper
to increase the resistance, fill up the pipe with nitrogen.

Only nitrogen
gas can be used
Protect the pipe end against the water, impurity into the pipes (brazing after being flat, or being sealed with adhesive
tape).

The refrigerant pipe should be clean. The nitrogen should flow under the pressure of about 0.5Mpa and when
charging the nitrogen, stop up the end of the pipe by hand to enhance the pressure in the pipe, then loose the hand
(meanwhile stop up the other end).

When connecting the pipes, close the valves fully.


When welding the valve and the pipes, use the wet cloth to cool down the valve and the pipes.

46
Installation procedure

B. Leakage test
1. The outdoor unit has been executed the leakage test in the factory. The pipe should be executed leakage test
individually and forbidden to test after connecting with stop valve.
2. Refer to the below figure to charge the nitrogen into the unit to take a test. Never use the chlorine, oxygen,
flammable gas in the leakage test. Apply pressure both on the gas pipe and the liquid pipe.
3. Apply the pressure step by step to the target pressre.
a. Apply the pressure to 0.5MPa for more than 5 minutes, confirm if pressure goes down.
b. Apply the pressure to 1.5MPa for more than 5 minutes, confirm if pressure goes down.
c. Apply the pressure to the target pressure (4.15MPa), record the temp. And the pressure.
d. Leave it at 4.15MPa for over 1 day, if pressure does not go down, the test is passed. Meanwhile, when the temp.
changes for 1degree, pressure will change 0.01MPa as well. Correct the pressure.
e. After confirmation of a~d, if pressure goes down, there is leakage. Check the brazing position, flared position by
laying on the soap. modify the leakage point and take another leakage test.
4. After leakage test, must execute the evacuation.

C. Evacuation
Evacuate at the check valve of liquid stop valve and both sides of the gas stop valve. The oil equalization pipe also
must be vacuum (executed at the oil equalization pipe check valve respectively).

Operation procedure:

After reaching -101KPa or less Leave it for over 1


(below -755mmHg), let the hour, vacuum
vacuum pump running pointer does not
continuously for over 1hour. arise.

If vacuum pointer arises, it shows there is water or leakage in the


system, please check and modify it, and then evacuate again.

47
Installation procedure

Because the unit is with refrigerant R410A, the below issues should be paid attention:
To prevent the different oil into the pipe, please use the special tool for R410A, especially for gauge manifold and
charging hose.
To prevent the compressor oil into the refrigerant cycle, please use the anti-counter-flow adapter.
When maintaining the outdoor, release refrigerant from check valve. When taking vacuum evacuation, set the
relative dip switch, the detailed refers to Page 38.

D. Check valve operation

Open/close method:(The gas pipe stop valve for CA43BV335-


V5J1H CA43BV400-V5J1H CA43BV450-V5J1H)

Take down the valve cap, gas pipe turns to "open" state as right figure.
Turn the liquid pipe and the oil equalization pipe with hexangular spanner
until it stops. If opening the valve strongly, the valve will be damaged.
Tighten the valve cap.

Tighten torque as the table below:


Tighten torque N•m
Shaft (valve body) Cap (cover) T-shape nut (check joint)
For gas pipe Less than 7 Less than 30 13
For liquid pipe 7.85 (MAX15.7) 29.4 (MAX39.2) 8.8 (MAX14.7)
For oil equalization pipe 4.9 (MAX11.8) 16.2 (MAX24.5) 8.8 (MAX14.7)

Note: The gas pipe stop valve for YV2VYH077BAH-D-X YV2VYH096BAH-D-X is screw type, rotate the rod clockwise
totally, the valve is close; rotate the rod counterclockwise totally, the valve is open; if the rod is not rotated clockwise
totally and also not rotated counterclockwise totally, the check valves of indoor, outdoor and the stop valve are
connected.

E. Additional refrigerant charging


Charge the additional refrigerant as liquid state with the gauge.
If the additional refrigerant cannot be charged totally when the outdoor stops, charge it at the trial mode.
If the unit runs for a long period in the state of lack of refrigerant, compressor will occur failure.
( the charging must be finished within 30 minutes especially when the unit is running, meanwhile charging the
refrigerant).

The unit is charged only part of the refrigerant at the factory, also need additional refrigerant at the installation site.
W1: Refrigerant charging volume to outdoor unit at factory.
W2: Refrigerant charging volume to outdoor unit on site.
W3: Refrigerant charging volume to liquid pipe base on different piping length calculation.
W3=actual length of liquid pipe×additional amount per meter liquid pipe=
L1×0.35+L2×0.25+L3×0.17+L4×0.11+L5×0.054+L6×0.022

48
Installation procedure

L1: Total length of 22.22 liquid pipe;


L2: Total length of 19.05 liquid pipe;
L3: Total length of 15.88 liquid pipe;
L4: Total length of 12.7 liquid pipe;
L5: Total length of 9.52 liquid pipe;
L6: Total length of 6.35 liquid pipe;
Total refrigerant volume charging on site during installation=W2+W3
W: Total refrigerant volume charging on site for maintenance.
Refrigerant record form
W1: W2: W3: Refrigerant charging volume to Total W: Total
Refrigerant Refrigerant liquid pipe base on different piping refrigerant refrigerant
charging charging length calculation volume volume
Model
volume to volume to Liquid pipe Additional refrigerant charging on charging on
outdoor unit outdoor unit diameter amount site during site for
at factory on site (mm) (kg) installation maintenance
CA43BV224-V5J1H 10kg 0kg Ø6.35 0.022kg/m×__m=__kg
CA43BV280-V5J1H 10kg 1kg Ø9.52 0.054kg/m×__m=__kg
CA43BV335-V5J1H 10kg 2kg Ø12.7 0.11kg/m×__m=__kg
CA43BV400-V5J1H
W2+W3= W1+W2+
10kg 2kg Ø15.88 0.17kg/m×__m=__kg
CA43BV450-V5J1H
___kg W3=___kg
10kg 4.5kg Ø19.05 0.25kg/m×__m=__kg
Ø22.22 0.35kg/m×__m=__kg
W3=__kg
Note:
To prevent the different oil into the pipe, please use the special tool for R410A, especially for gauge manifold and
charging hose.
Mark the refrigerant type in different colour on the tank. R410A is pink.
Must not use the charging cylinder, because the R410A will change when transferring to the cylinder.
When charging refrigerant, the refrigerant should be taken out from the tank as liquid state.
Mark the counted refrigerant volume due to the distributing pipe length on the label.

Heat insulation
Gas pipe and liquid pipe should be heat insulated separately. Liquid pipe shall be heat insulated at all
times and the only exception when the customer is totally sure the unit will only deliver COOLING.
The material for gas pipe should endure the high temperature over 120℃ .
That for liquid pipe should be over 70℃ .
The material thickness should be over 10mm, when ambient temp. is 30℃ , and the relative
humidity is over 80%, the material thickness should be over 20mm.
The material should cling the pipe closely without gap, then be wrapped with adhesive
tape. The connection wire cannot be put together with the heat insulation material
and should be far at least 20cm.
Fix the refrigerant pipe
In operation, the pipe will vibrate and expand or shrink. If not being fixed, the
refrigerant will focus on one part to cause the broken pipe.
To prevent the central stress, fix the pipe for every 2-3m.

49
Electric wiring and the application

Communication wiring figure

Outdoor units are in parallel through 3 polar wires. The outdoor and all indoor units are in parallel through 2 non-polar
wires.
Three wiring methods between wired controller and indoor unit:
A. 1 to multi (group control): one wired controller controls 2~16 indoors, as shown in above figure, indoor 1~indoor 5:
indoor 5 is wired control master unit, the others are wired control slave units. Wired controller and the master indoor
(directly connected to wired controller) is connected by 3 polar wires; the other indoors and the master indoors are
connected by 2 polar wires.
B. 1 to 1 (one wired controller controls one indoor): as shown in above figure, indoor 6~ indoor
19, indoor and wired controller are connected by 3 polar wires.
C. 2 to 1 (two wired controller controls one indoor): as shown in above figure, indoor 20. Either of wired controllers can
be set as master wired controller, and the other is slave wired controller. Master/slave wired controller, and master/indoor
are connected by 3 polar wires.
When indoor is controlled by remote controller, refer to the "wired control master unit/wired control slave unit/remote
control unit table". A, B, C on signal terminal block need not wires and not connect the wired controller.

50
Electric wiring and the application

Power wiring figure

Indoor and outdoor use their individual power source.


All indoors use one power source.
Must install the leakage breaker and the over current breaker, or electric shock will occur.

Outdoor power source and power cable

Rated current of residual


Item Power Ground wire
Wire Circuit circuit breaker(A)
Power cable
length breaker Ground fault interrupter
Source section Section
(m) (A) (mA) Screw
Model (mm2)
Response time(S) (mm2)
CA43BV224-
10 60 38.6 40A 30mA below 0.1S 3.5 M5
V5J1H
CA43BV280-
Individual power

3~, 16 60 44.7 50A 30mA below 0.1S 3.5 M5


V5J1H 208-
CA43BV335- 230V, 16 60 50.9 60A 30mA below 0.1S 3.5 M5
V5J1H 60Hz
CA43BV400-
16 60 57.1 60A 30mA below 0.1S 3.5 M5
V5J1H
CA43BV450-
25 60 61.7 70A 30mA below0.1S 3.5 M5
V5J1H
Power cable must be fixed firmly.
Each outdoor must be earthed well.
When power cable exceeds the range, thicken it appropriately.

51
Electric wiring and the application

Requirements for pulse Ammeter

1. Three-phase four-line active pulse Ammeter


A. The Ammeter shall be suitable for metering three-phase AC active electric energy at a rated frequency of 50 Hz.
B. The number of pulses outputted by the Ammeter for one kWh of electricity shall be constant.
C. The amplitude of the pulse signal shall be 5 Vdc and the width of every pulse shall not be less than 80 ms.
D. The pulse signal from the Ammeter shall be passive, that is, an external pulse signal is required for the Ammeter to
generate the required control power supply.

2. Both mechanical and electronic Ammeters shall be used as long as it meets the above requirements. According to the
total power input of all the outdoor units, the parameters of Ammeter shall be defined such as rating current.
The wiring of Ammeter includes 3 methods:
Direct connection;
Connection via current transformer;
Connection via current and voltage transformers (seldom used).
Direct connection method has low cost as there are no current and voltage transformers employed. However, if the
operation current is out of Ammeter current range, the transformers are required.

3. The recommended ranges of Ammeter for different horsepower of outdoor unit are shown in the following table; if
the range of Ammeter is insufficient in direct connection method, transformer method shall be used.

Total horsepower of outdoor units Range of Ammeter


≤20 10-60A
≤30 20-80A
≤40 30-100A
≤48 30-120A

4. Example of Ammeter used in China


For total 36 Horsepower outdoor units system.
If use Ammeter Capacity 30(100)A, 200Pulse/kWh, pulse width 80+/-20ms, Direct
Connection type is feasible.
If use Ammeter Capacity 20(80)A, current transformers are required.

52
Electric wiring and the application

Indoor power source and communication wiring

Item Rated Rated current of residual Communication wire section


Power Wire current of
cable length circuit breaker(A)
Indoor overcurrent Ground fault interrupter
total section (m) breaker Outdoor/indoor Indoor/indoor
(mm2) (mA)
current (A) (A) Response time(S) (mm2) (mm2)

<10 2 23 20 20A, 30mA, below 0.1s


≥10 and <15 3.5 24 30 30A, 30mA, below 0.1s 2-core × (0.75-2.0mm2)
shielded wire
≥15 and <22 5.5 27 40 40A, 30mA, below 0.1s
≥22 and <27 10 42 50 50A, 30mA, below 0.1s

Power cable and communication wire must be fixed firmly.


Each indoor must be grounded well.
When power cable exceeds the range, increase the gauge appropriately.
Shielded layer of communication wires must be connected together and be earthed at single point.
Communication wire total length cannot exceed 1000m.

Communication wire for wired controller

Wire length(m) Wire spec Wire length(m) Wire spec


2
<100 0.3Mm ×(3-core) shielded wire ≥300 And <400 1.25Mm2 ×(3-core) shielded wire
≥100 And <200 0.5Mm2 × (3-core) shielded wire ≥400 And <600 2Mm2 × (3-core) shielded wire
≥200 And <300 0.75Mm2 × (3-core) shielded wire
Shielded layer of communication wire must be grounded at one end.
The total length cannot exceed 600m.

53
Part 3 Control system

3.1 Dip switch setting ................................................................................................................................55


3.2 Outdoor unit control ........................................................................................................................... 64

54
3.1 lnstruction and function of selection switch

ldentification:
Master unit: by setting dip switch, the unit number is 0. lt is used to communicate with indoor unit, also it is the
organizer of outdoor communications as communication master unit.
Slave unit: by setting dip switch, the unit number is not 0.
Dip switch definition:
BM1 is usually set by the personnel on site; BM2, BM3, BM4 are pre-set in the factory.
BM1_1: Master outdoor unit searches the total outdoor units after power ON at first time. The quantity of total outdoor
units is floating from right to left on LED. ”1=0” is one outdoor unit, ”2=01” is two outdoor units, ”3=012” is three
outdoor units.
BM1_2: Master outdoor unit searches the total indoor units after power ON at first time. The quantity of total indoor
units is floating from right to left on LED. ”-04-” is 4 indoor units, ”-06-” is 6 indoor units, ”-15-” is 15 indoor units.
BM1_3: The setting is 0 or 1.Default is 0. Once power off, unit software shall reset to*OFF* automatically ignoring
BM1_3 setting.
1)BM1 instruction
Outdoor searching 0 Begin to search outdoor
BM1-1
after startup 1 Stop searching outdoor and lock the quantity
Indoor searching 0 Begin to search indoor
BM1-2
after startup 1 Stop searching indoor and lock the quantity
Default condition: Unit shall startup after 6 hours preheat or oil superheat above 20℃ .
Power on, no action (Oil Superheat=Oil temperature@compressor sink-Refrigerant saturation
Start
BM1-3 temperature@ambient)
up
Power on, Change 0 to 1 or change
Unit shall startup after 6 hours preheat or oil superheat above 15℃ .
from 1 to 0 then to 1
0 Ambient Temp.>25℃ heating function normally
BM1-4 Heating function
1 Ambient Temp.>25℃ ,heating running forbidden
0 Indoor capacity divisity >130%, system function normally
BM1-5 Over match setting
1 Indoor capacity>130%, system alarm
0 Allow
BM1-6 Sensor backup running
1 Do not use
BM1-7 BM1-8 Unit number
0 0 0# (physical master unit)
BM1-7
Address setting 0 1 1#
BM1-8 1 0 2#
1 1 3#

Note:
1. Sensor backup running
a. When an outdoor unit is in combination or as a single unit, if the outdoor unit shows a failure, as described in 1-b,
and the dip switch BM1-6 is in position 0, then the unit will automatically switch to backup mode.
b. Backup running condition:
When system is working, the following failures will make the unit to run in backup mode:
Cooling: 20(Tdef: defrost sensor failure), 25-1(Toci1: sensor 1 of condenser piping temperature failure), 25-2(Toci2:
sensor 2 of condenser piping temperature failure ), 35 (4-way valve reversing failure)
Heating: 22-1(Ts: suction temperature sensor failure), 32-1(Tsco: branch sub cooler sensor failure), 32-2(Tliqsc: sub
cooler sensor failure)
2. Oil temperature too low protection
See BM1-3(BM1 introduction table)

55
2)BM2 instruction
BM2 Definition Introduction
0 System function normally without quiet function
BM2-1 Quiet running function
1 Quiet running function

0 System function normally without anti-snow function


BM2-2 Anti-snow function
1 Anti-snow function

BM2-3 No definition 0 Default is 0,1 is Forbidden

BM2-4 No definition 0 Default is 0,1 is Forbidden

BM2-5 BM2-6

0 0 Default setting (Normal installation condition )


BM2-5 Outdoor installation
0 1 Low humidification in winter condition
BM2-6 condition selection
1 0 High humidification in winter condition

1 1 Default setting (Normal installation condition )

BM2-7 BM2-8

0 0 Default setting (Medium piping length)


BM2-7
Piping length selection 0 1 Long piping length
BM2-8
1 0 Short piping length

1 1 Default setting (Medium piping length)

3)BM3 instruction
BM3 Definition Introduction
BM3-1 No definition 0 Default is 0,1 is Forbidden
BM3-2 No definition 0 Default is 0,1 is Forbidden
BM3-3 No definition 0 Default is 0,1 is Forbidden
BM3-4 No definition 0 Default is 0,1 is Forbidden

0 50Hz
BM3-5 Switch over power supply of 50/60Hz
1 60Hz
BM3-6 BM3-7 BM3-8 T1 T3
0 0 0 6HP
0 0 1 8HP
0 1 0 10HP 8HP
BM3-6 BM3-7 BM3-8 Outdoor horse power setting 0 1 1 12HP 10HP
1 0 0 14HP
1 0 1 16HP 12HP
1 1 0 18HP
1 1 1 20HP

56
4)BM4 instruction

BM4 Definition Introduction


Locking indoor 0 Locking indoor connection quantity
BM4-1
connection quantity 1 Do not Lock indoor connection quantity
BM4-2 No definition 0 Default is 0,1 is Forbidden
Outdoor external 0 50Pa
BM4-3
pressure selection 1 80Pa
0 T1
BM4-4 Condition selection
1 T3
0 380 ~ 400V
BM4-5 Switch over power supply
1 208 ~ 230V
BM4-6 No definition 0 Default is 0,1 is Forbidden
BM4-7 Switch over power supply 0 1 is 460V
BM4-8 No definition 0 Default is 0,1 is Forbidden

5)BM5 instruction
BM5-1 BM5-1 BM5-2 BM5-3 BM5-4 Selection item
~ Outdoor motor selection 1 1 0 0 Dual fan motor(375W)
BM5-4 0 0 1 1 Single fan motor(750W)
BM5-5 BM5-5 BM5-6 BM5-7 BM5-8 Selection item
~ Inverter board selection
1 1 0 0 HAIER inverter board
BM5-8 0 0 1 1 APY inverter board

Monitor tooIs
The following switches are included in the master PCB board of the outdoor unit.
Press button: SW2, SW1 are the button switch
Rotary switch: SW9, SW10, SW11, 0~15 can be set.
Display section: LD1, LD2, LD3, LD4, nixie tube. During start-up and commissioning, you can identify failures in the
system by selecting the indoor unit to review with switch as SW9 and SW10, and to select the function to review with
SW11.
Indoor parameter
Check the parameters of indoor whose address is from 1 to 64.
SW11 is set from 3~15 to check indoor parameter.
SW9 and SW10 shows indoor unit number.
SW9 SW10 System address
0 1-16
1 17-32
0-15
2 33-48
3 49-64

57
SW11 Function Digital tube LD1~4 display
Communication available, display 1111;
3 Indoor communication checking
Indoor unavailable, display ----
4 Indoor abnormal Display indoor failure code; no failure, display 0
5 Indoor capacity Indoor capacity, 1.5HP displays 1.5
6 Indoor EEV open angle Electronic expansion valve(EEV) open angle
7 Indoor ambient temp. Tai Ambient temperature -2degree displays -2
8 Indoor gas pipe temp. Tc1 Gas pipe temperature -2degree displays -2
9 Indoor liquid pipe temp. Tc2 Liquid pipe temperature -2degree displays -2
10 Indoor mode Cooling: COOL; heating: HEAT, shutoff: OFF
11 Indoor set temp. Tset Set temperature, 16 degree displays 16
12 Indoor SCODE code 0~15
13 Wrong wiring inspection 0 shows no failure, 79 shows wiring connection failure (indoor no display)
14 No definition insignificance
15 No definition insignificance

Outdoor parameter
SW9 is used to select outdoor unit number, SW10 and SW11 working together to show outdoor parameter.
For example, SW9 is set 0, that shows No.0 outdoor parameter; set as 1, that shows No.1 outdoor parameter...
(master unit can display the other outdoor parameter and indoor parameter, but the slave unit only displays itself
parameter).
Start up for commissioning, search slave units and display flashing 0 from left to right. If one slave unit is found, display
1, two slave units are found, display 2, and so on, the max. number is 8. After searching slave units, display outdoor
failure code; if no failure, display 0. 0~2 of SW9 is used to select outdoor unit number.

58
SW9 SW10 SW11 Function Digital tube LD1~4 display
Unit No. Failure code transmitted by outdoor bus data. If no failure, display the time
0 0 Display outdoor failure code
0-2 as second counting down fromt the 6 hours for pre-heating

Display priority of outdoor


2 0 Display outdoor priority
number

3 0 Display operation mode HEAT: heating; COOL: cooling; OFF: stop

4 0 Outdoor capacity 16.0 shows 16HP, 8.0 shows 8HP


5 0 Outdoor capacity output ratio 60 shows 60% of capacity output

110.0 shows 110.0HZ. Press SW2(UP) for 2s continuously, display 1111,


then to set: flashing and press SW2(UP) once, the frequency will go up 1Hz;
press SW1(DN) once, the frequency will decrease 1Hz; 5 min later, quit the
Current frequency of
1 0 setting state automatically.
Inverter compressor
Press SW1(DN) for 2s continuously, display 0000, then quit the setting
state, and stop flashing. When system failures, compressor is forbidden to
start up.

6 0 Speed of outdoor fan motor 1


345 shows 345rpm.
Press SW2(UP) for 2s continuously, display 1111, then to set: flashing
and press SW2(UP) once, the frequency will go up 1Hz; press SW1(DN)
once, the frequency will decrease 1Hz; 5 min later, quit the setting state
7 0 Speed of outdoor fan Motor 2 automatically.
Press SW1(DN) for 2s continuously, display 0000, then quit the setting
state, and stop flashing.

LD1: 4WV: 1 ON 0 OFF--left side


Outdoor solenoid valve output LD2: SV1: 1 ON 0 OFF
8 0
indication LD3: SV6: 1 ON 0 OFF
LD4: SV9: 1 ON 0 OFF

59
SW9 SW10 SW11 Function Digital tube LD1~4 display
LD1: SV10: 1 ON 0 OFF
Outdoor solenoid valve LD2: SV11: 1 ON 0 OFF
9 0
output indication LD3: SV13i: 1 ON 0 OFF
LD4: SV3i: 1 ON 0 OFF

Outdoor LEVa1 valve 0--500 steps.


10 0 Press SW2(UP) for 2s continuously, display 1111, then to set: flashing and
open angle
press SW2(UP), valve opens fully; press SW1(DN), valve closes fully; 2 mins
later, quit the setting state automatically.
Outdoor LEVa2 valve Press SW1(DN) for 2s continuously, display 0000, then quit the setting
11 0
open angle state, and stop flashing.

LD1: SV3(pump): 1 ON 0 OFF


Outdoor solenoid valve output
LD2: FAN_PTC: 1 ON 0 OFF
12 0 indication fixed frequency
LD3: COMP1: 1 ON 0 OFF
compressor output indication
LD4: COMP2: 1 ON 0 OFF
LD1: CHi: 1 ON 0 OFF
LD2: CHa: 1 ON 0 OFF
13 0 Heater output
LD3: CH1: 1 ON 0 OFF
LD4: CH2: 1 ON 0 OFF
0--500 steps.
Press SW2(UP) for 2s continuously, display 1111, then to set: flashing and
Outdoor LEV b valve press SW2(UP), valve opens fully; press SW1(DN), valve closes fully; 2 min
14 0
open angle later, quit the setting state automatically.
Press SW1(DN) for 2s continuously, display 0000, then quit the setting
state, and stop flashing.
15 0 Unit number address 1 shows 1# unit
0 1 Pd pressure 10.00 shows 10.00kg
1 1 Ps pressure 10.00 shows 10.00kg
2 1 Tdi discharging temp. 25 shows 25degree
3 1 Tsi suction temp. 25 shows 25degree
4 1 Tdef defrosting temp. 25 shows 25degree
5 1 Tao ambient temp. 25 shows 25degree
6 1 Toilp temp. 25 shows 25degree
7 1 Toil temp. 25 shows 25degree
8 1 Toci1 temp. 25 shows 25degree
9 1 Toci2 temp. 25 shows 25degree
10 1 Tsco temp. 25 shows 25degree
11 1 Tliqsc temp. 25 shows 25degree
12 1 Td1 temp. 25 shows 25degree
13 1 Tsuc temp. 25 shows 25degree
14 1 Im compressor current 10.2 shows 10.2A
15 1 CT1 fixed compressor current 10.2 shows 10.2A
15 1 backup running ---- outdoor normal operation 1111 outdoor backup operation

60
Master unit information center: display parameters of the whole system

SW9 SW10 SW11 Function Digital tube LD1~4 display

407C stands for R407C


0 0 2 Refrigerant type 410A stands for R410A(default)
R22 stands for R22
0 1 2 Outdoor total capacity 48.0 stands for 48HP

0 2 2 Outdoor QTY in one system e.g.: 4 outdoors (including master outdoor)

0 3 2 Indoor QTY in one system e.g.: 64 indoors

0 4 2 Running indoor QTY Thermostat ON indicates indoor running

Indoor QTY whose operation modes


0 5 2 e.g.: 13 indoors
are as the same as that of outdoor
0 6 2 Pre-set --

0 7 2 Pre-set --

Refrigerant evacuation
setting Press SW2(UP) for 2s continuously, display 1111 and start up; digital tube
*only for outdoor evacuation. If displays "YES", detailed response: SV9, SV10, SV11 open; LEVa1,2, LEVb
0 8 2
indoor evacuation, do not set. When open for 100pls, the other valves close compulsorily. Press SW1(DN) for 2s
it finishes, cancel the setting or re- continuously, display 0000 and stops (setting is invalid when unit is running)
electricity.
Refrigerant charging
setting Press SW2(UP) for 2s continuously, display 1111 and start up; digital tube
*only for gas charged outdoor. If displays "YES", detailed response: LEVa1,2 open for 500pls, the other valves
0 9 2
indoor is charged, do not set. When it close compulsorily. Press SW1(DN) for 2s continuously, display 0000 and
finishes, stops (setting is invalid when unit is running)
cancel the setting or re-electricity.

0 10 2 Wrong wiring inspection in cooling


Press SW2(UP) for 2s continuously, display 1111 and start up; digital tube
counts down judging time at second; after time arrives, display the result:
"00.00" shows the result is in conformity with the actual connection; "01.05"
shows one outdoor and 5 indoors are abnormal, to check the abnormal
units by digital tube (indoor: X_X_13, outdoor X_0_0); Press SW1(DN) for 2s
continuously, display 0000 and stops
0 11 2 Wrong wiring inspection in heating

61
SW9 SW10 SW11 Function Digital tube LD1~4 display
Indoor expansion valve Press SW2(UP) for 2s continuously, display 1111 and indoor valves open fully for 2
0 12 2
open fully minutes, then indoor valves close automatically.
All indoor units running Press SW2(UP) for 2s continuously, display 1111 and start up;
0 13 2
in cooling Press SW1(DN) for 2s continuously, display 0000 and stops.
All indoor units running Press SW2(UP) for 2s continuously, display 1111 and start up;
0 14 2
in heating Press SW1(DN) for 2s continuously, display 0000 and stops.
Press SW2(UP) for 2s continuously, display 1111 and start up; Press SW1(DN) for
Cancel all manual 2s continuously, display 0000 and stops. Cancel items: wrong wiring inspection
0 15 2
controls(running type) in cooling/heating mode; indoor running/stop totally; compulsory operation; rated
operation, etc.
Capacity correction 0 shows short piping length; 1 shows medium piping length;
15 0 2
class 2 shows long piping length
Defrosting
15 1 2 10, 8, 6
compensation
Set temperature in
15 2 2 25 shows 25 degree
cooling
Set temperature in
15 3 2 25 shows 25 degree
heating
Electricity limitation 100 show 100% output,
15 4 2
(allow max.output) 0 shows no output allowed
15 5 2 Over match inspection 135 stands for limitation; 0: without limitation
Heating limit when
15 6 2 outdoor temp.over 25 shows limitation; 0 shows no limitation
25degree
15 7 2 Silent operation setting 0: without silent operation; 1: with silent operation
Snow-proof operation
15 8 2 0: without snow-proof operation; 1: with snow-proof operation
setting
15 13 2 Inverter board selection 0: HAIER inverter board; 1: APY inverter board
Outdoor model
15 14 2 01: single unit; the others are in combination
selection
15 15 2 Software version 1.0 shows Ver 1.0
Power supply of 50 shows 50Hz
15 12 2
50/60hz 60 shows 60Hz

15 13 2 No definition Insignificance

15 14 2 No definition Insignificance

15 15 2 Software version 1.0 shows Ver 1.0

62
In each outdoor we’re able to review the following functions
SW9 SW10 SW11 Function Digital tube LD1 ~ 4 display
6 0 2 SV1 open by hand

6 1 2 SV6 open by hand

6 2 2 SV9 open by hand Display current state of components; 1: open; 0: close. Press SW2(UP) for 2s
continuously, display 1111 then to set and flash. Press SW2(UP) to open; press
6 3 2 SV10 open by hand SW1 (DN) to close; 2 minutes later, quit the setting state automatically. Press
SW1(DN) for 2s continuously, display 0000 then quit the set, and stop flashing(if
6 4 2 SV11 open by hand system failures, compressor is forbidden to start up).

6 5 2 SV13 open by hand

6 6 2 No definition

6 7 2 No definition Insignificance

6 8 2 COMP1 running by hand Control method the same as electromagnetic valve open manually

6 9 2 No definition Insignificance

6 10 2 4WV open by hand Control method the same as electromagnetic valve open manually

6 11 2 No definition Insignificance

6 12 2 No definition Insignificance

6 13 2 No definition Insignificance

6 14 2 No definition Insignificance

Press SW2(UP) for 2s continuously, display 1111 then to quit. Or press SW1(DN)
to 2s continuously, display 0000 then quit the set, Cancel items: movable
Cancel all the manual controls
6 15 2 component control by hand, such as compressor, motor, electronic expansion
(component type)
valve LEV, solenoid valve SV and so on (including evacuation, charging, excluding
rated operation, compulsory operation, indoor run/stop etc.)

63
3.2 Outdoor unit control

3.2.1 Compressor startup control


On startup, inverter compressor will keep for 3 min at 60rps, then if TdiSH is still less than 25degree, compressor will
increase frequency up to 100rps. If startup is for 15min or TdiSH is more than 25degree, quit startup and enter normal
operation. In startup operation, the limitation frequency operation will be in priority, such as high pressure too high,
discharging temp. too high, suction pressure too low, over current.
After entering normal operation, when inverter compressor frequency arrives 100rps, fixed frequency compressor
starts up, but if inverter compressor frequency is down to below 30rps, fixed frequency compressor is OFF.

3.2.2 Compressor operation control


It will be controlled by the target pressure. In heating mode, the target high pressure:
When Ta>-7degree, target high pressure is 28Kg 0.8Kg; When Ta<=-7degree, target high pressure is 24Kg 0.8Kg In
cooling mode, the target low pressure
When the running indoor capacity is over 5HP, if Ta>=21degree, target pressure Ps=8Kg (4degree) 0.5Kg; if
21degree>Ta>=15degree, target pressure Ps=7Kg(0degree) 0.5Kg.

3.2.3 Fan motor control


a. In cooling mode
Startup procedure: When compressor starts up, outdoor motor will not run right now, when high pressure reaches
2.1MPa, outdoor motor begins to run.
In operation, the motor will be controlled by high pressure. When high pressure reaches 2.1MPa, outdoor motor will
run at class-1 speed; if pressure is more than 2.1MPa, outdoor motor will increase one class at interval of 60 seconds;
if pressure is over 2.6MPa, outdoor motor will rise up to class-7. If pressure is less than 1.9MPa for 60 seconds, fan
motor will decrease one class. If less than 1.8MPa for 60 seconds, fan motor will stop.
b. In heating mode
Motor control in startup procedure: Pd<set pressure+0.3MPa.If Pd goes up, decrease outdoor motor speed. 1 minute
later, if Pd>=(set pressure +0.50MPa), outdoor motor stops. When defrosting is over, after 4-way valve opens, fan
motor starts up.
In operation, the motor will be controlled by low pressure. When low pressure is over 0.95MPa, fan motor will stop;
when low pressure is less than 0.75MPa, for every 60 seconds, fan speed will increase one class; when it is less than
0.65MPa for 60 seconds, fan speed will be class-7 directly.
In defrosting, outdoor motor will stop. After the defrosting is over, 4-way vavle opens, outdoor motor will start up at
heating mode.

3.2.4 Rosting control


When one of the running outdoors reaches the defrosting condition, it will send defrosting signal to the master unit.
After the master unit receives defrosting signal, it will send defrosting signal to the running outdoor. Then the slave
outdoor will begin defrosting.
Entering condition:
When the unit has run in heating mode for 33 minutes and the compressor has run for 50 minutes accumulatively since
the last defrosting. By measuring the defrosting sensor TE and outdoor ambient temp. sensor TA, any outdoor can
meet the below conditions for 5 minutes, all the outdoors will enter defrosting operation.
a. When TE<= -6degree for 5 minutes;
b. When -6<TA<5, -13.6<TE<-6 for 5 minutes, enter defrosting;
c. TA<-6, TE<= -15 for 5 minutes, and compressor has run for 90 minutes between the two defrostings;

64
In defrosting operation:
a.4-way valve OFF
b. Outdoor motor OFF
c. Anti-cold air control of indoor motor OFF
d. Outdoor EEV OFF
Quit defrosting
Any of the below conditions can be met, the unit will quit defrosting.
a. After defrosting begins, 10 minutes later, defrosting is over;
b. Detect the defrosting condition of outdoor heat exchanger by TE, all the temperatures at the defrosting point are
over 10 degree for 60 seconds or reaches 15 degree or 10 seconds, quit defrosting;
c. High pressure Pd is over 35kgG/cm2, quit defrosting.

3.2.5 Oil return operation control


1.Entering condition
When outdoor total running capacity is over 25% and less than 75% for 4 hours, or outdoor total running capacity is
less than 25% for 2 hours, the system will enter oil return operation.
*When outdoor total running capacity is over 75% for 10 minutes continuously, the oil return time will be cleared.
*In defrosting operation, when outdoor total running capacity is over 75% for 5 minutes continuously, the oil return
time will be cleared.
2.Oil return procedure:
All outdoors start up, and run with 75% of total capacity in cooling mode; In oil return course, outdoor leva1, 2 open to
250pls;
In oil return course, THERMO ON, indoor valves 250pls, THERMO OFF, indoor valves 125pls; when Tdi or Toil is over
105degree, indoor valve will open larger 10%.
In oil return, Levb OFF.

65
Part 4 Trouble Shooting

4.1 Failure code ............................................................................................................................................67


4.2 Failure diagnose ..................................................................................................................................... 76

66
4.1 Failure code

Failure code description: (failure code of the whole system is showed as 8 bits, so totally 256 codes. Indoor failure code
should be judged by the table and the unit number)
Outdoor failure code exists in EEPROM, in which 5 failure codes can be kept. Indoor failure code exists in EEPROM, in
which 5 failure codes can be kept.

Failure codes are distributed as following:


0~19: indoor failure code
20~99: outdoor failure code
100~109: DC motor failure code
110~125: inverter module failure code
126~127: software auto-check failure code
Physical master unit:
Dip switches SW9, SW10, SW11 are at 0, 0, 0, LD displays failure code 20~127, it is the master failure code.
Dip switches SW9, SW10, SW11 are 1, 0, 0, LD displays failure code 20~127, it is failure code of No. 1 slave unit.
Dip switches SW9, SW10, SW11 are 2, 0, 0, LD displays failure code 20~127, it is failure code of No. 2 slave unit.
Physical slave unit:
Dip switches SW9, SW10, SW11 are at 0, 0, 0, LD displays failure code 20~127, it is single slave unit failure code.
Outdoor failure code display principle on wired controller:
When outdoor compressor is running, indoor wired controller will display the failure code of outdoor with higher
priority. When compressor stops, it displays all indoor failures. The indoor failures will be classified as below: sensor
failure, inverter board failure, fan motor driving board failure, any protections etc.

Inverter outdoor unit failure code


Digital tube
Indication on wired Failure code
indication on Failure description Remarks
controller (hex) definition
master unit
AD value is below 11(open circuit) or over 1012(short circuit) for
Defrosting temp. 60seconds, in cooling mode, if the sensor is abnormal, the unit
20 14 Resumable
sensor Tdef failure does not deal with it, besides, in defrosting and within 3 minutes
after defrosting, no alarm

AD value is below 11(open circuit) or over 1012(short circuit) for


Ambient temp.
21 15 60seconds, in defrosting and within 3 minutes after defrosting, no Resumable
sensor Ta failure
alarm

AD value is below 11(open circuit) or over 1012(short circuit) for


Suction temp.
22-0 16 60seconds, in defrosting and within 3 minutes after defrosting, no Resumable
sensor Tsi failure
alarm

67
Digital tube Indication on
Failure code
indication on wired controller Failure description Remarks
definition
master unit (hex)
Suction temp.sensor Ts
22-1 16
failure AD value is below 11(open circuit) or over 1012(short circuit) for
60seconds, in defrosting and within 3 minutes after defrosting, Resumable
Suction temp.sensor
22-2 16 no alarm
Tsuc failure

Discharging temp.
23-0 17
sensor Tdi failure
After compressor is running for 5 minutes, AD value is below
Discharging temp. 11(open circuit) or over 1012(short circuit) for 60seconds,
23-1 17 Resumable
sensor Td1 failure in course of startup, defrosting and within 3 minutes after
defrosting, no alarm
Discharging temp.
23-2 17
sensor Td2 failure

Oil temp.sensor Toilp


24-1 18
failure AD value is below 11(open circuit) or over 1012(short circuit)
for 60seconds, if Ta<=-10degree or ET<=-10degree, within 5 Resumable
Oil temp.sensor Toil minutes, no alarm
24-2 18
failure

Inlet temp.of heat AD value is below 11(open circuit) or over 1012(short circuit)
25-1 19
exchanger Toci1 failure for 60seconds, in cooling mode, if the sensor is abnormal, the
Resumable
unit does not deal with it, besides, in defrosting and within 3
Inlet temp.of heat minutes after defrosting, no alarm
25-2 19
exchanger Toci2 failure

26-0 1A For continuous 200 cycles, can not find connected indoors

For continuous 270seconds, the searched indoor quantity is


26-1 1A Indoor communication
less than the set quantity. Resumable
failure

For continuous 170seconds, the searched indoor quantity is


26-2 1A
more than the set quantity.

Toil>=120degree(E) at interval of 25msec for twice


Once
Oil temp. too high continuously, and over the set value, then stop and alarm; 3
27 1B confirmation,
protection(Toil) minutes later, resume automatically. If it occurs 3 times in an
un-resumable
hour, confirm the failure.

68
Indication
LD indication
on wired Failure code
on master Failure description Remarks
controller definition
unit
(hex)

AD value is below 11(open circuit) or over 1012(short


High pressure sensor Pd
28 1C circuit) for 30seconds, in defrosting and within 3 minutes Resumable
failure
after defrosting, no alarm

AD value is below 11(open circuit) or over 1012(short


Low pressure sensor Ps
29 1D circuit) for 30seconds, in defrosting and within 3 minutes Resumable
failure
after defrosting, no alarm

High pressure switch HPSi


30-0 1E
failure

Once
High pressure switch HPS1 If disconnect for 50ms continuously, alarm. If alarm 3 times
30-1 1E confirmation,
failure in an hour, confirm the failure
un-resumable

High pressure switch HPS2


30-2 1E
failure

Outlet temp.of subcooler


32-1 20
Tsco failure
AD value is below 11(open circuit) or over 1012(short
circuit) for 30seconds, in defrosting and within 3 minutes Resumable
Liquid pipe SC temp.of after defrosting, no alarm
32-2 20
subcooler Tliqsc failure

33-0 21 EEPROM communication failure

Once
33-1 21 EEPROM data check failure(model code, check sum etc.)
EEPROM (AT24C04) failure confirmation,
un-resumable
EEPROM data check failure(data beyond limit, reverse
33-2 21
sequence etc.)

Discharging temp.too high


34-0 22
protection (Tdi)

Toil>=120degree(E) at interval of 25msec for twice


Once
Discharging temp.too high continuously, and over the set value, then stop and alarm;
34-1 22 confirmation,
protection (Td1) 3 minutes later, resume automatically. If it occurs 3 times in
un-resumable
an hour, confirm the failure.

Discharging temp.too high


34-2 22
protection (Td2)

69
Indication
Ld indication
on wired Failure code
On master Failure description Remarks
controller definition
unit
(hex)

After 4-way valve is electrified for 3 minutes, if the below conditions


can be met for continuous 10 seconds, that is conversing successfully:
4-way valve Once confirmation,
35 23 1. this outdoor compressor is running normally
reversing failure un-resumable
2. Tsuc-Tdef¨R10¡æ or Pd-Ps¨R0.6MPa
Otherwise, the system alarms reversing failure.

In normal operation, if Td<CT+10 for continuous 5 minutes, the unit


Oil temp. too low Once confirmation,
36 24 stops and alarms.2 minutes and 50 seconds later, resume automatically.
protection (Toil) un-resumable
If it occurs 3 times in an hour, confirm the failure
37-1 Lack of phase of Lack of phase S
3N power supply Once confirmation,
37-2 25 Lack of phase T
or wrong phase un-resumable
37-3 sequence Phase s, t in reverse

High pressure In normal operation, Pd<1.5Mpa for continuous 5 minutes, alarm and
Once confirmation,
38 26 sensor Pd too low stop. 2 minutes and 50 seconds later, resume automatically, if it occurs
un-resumable
protection 3 times in an hour, confirm the failure.

After compressor is running (except for residual operation), if in cooling,


Low pressure
Ps<0.10Mpa; in heating, Ps<0.05Mpa; in oil return, Ps<0.035Mpa for Once confirmation,
39-0 27 sensor Ps too low
continuous 5 minutes, alarm and stop. 2 minutes and 50 seconds later, un-resumable
protection
resume automatically, if it occurs 3 times in an hour, confirm the failure.

After compressor is running, compression ratio 8. for continuous


Compression ratio Once confirmation,
39-1 27 5 minutes stop and alarm.2 minutes and 50 seconds later, resume
too high protection un-resumable
automatically, if it occurs 3 times in an hour, confirm the failure.

In normal operation, compression ratio


Compression ratio <1. for continuous 5 minutes,s stop and alarm.2 minutes and 50 Once confirmation,
39-2 27
too low protection seconds later, resume automatically, if it occurs 3 times in an hour, un-resumable
confirm the failure.

70
Indication on
LD indication Failure code
wired controller Failure description Remarks
on master unit definition
(hex)
In normal operation, Pd>=4.15Mpa for continuous
High pressure sensor Pd 50ms, alarm and stop. 2 minutes and 50 seconds Once confirmation,
40 28
too high protection later, resume automatically, if it occurs 3 times in an un-resumable
hour, confirm the failure.
Discharging temp.
43-0 2B sensor Tdi too low
protection
Discharging temp. In normal operation, if Td<CT+10oC for continuous
43-1 2B sensor Td1 too low 5 minutes, the unit stops and alarms.2 minutes and
protection 50 seconds later, resume automatically. If it occurs
3 times in an hour, confirm the failure. After fixed Once confirmation,
frequency compressor alarms, inverter compressor un-resumable
will continue to run. If fixed frequency compressor
Discharging temp.
has been locked for 3 times, the unit will stop and
43-2 2B sensor Td2 too low
alarm.
protection

In normal operation, if Ps>1.05MPa for continuous


Low pressure sensor PS 5 minutes, unit stops and alarms, 2 minutes and 50 Once confirmation,
44 2C
too high protection seconds later, resume automatically. If it occurs 3 un-resumable
times in an hour, alarm and confirm the failure.
Communication among
45 2D No communication within 3 minutes continuously Resumable
outdoors failure
Communication with
46 2E No communication within 30 seconds continuously Resumable
inverter board failure
Before startup, SV1 opens for 2 minutes, if Pd-
Unloading valve SV1
48 30 Ps>=0.2MPa, display failure code, when Pd- Resumable
failure
Ps<0.2MPa, resume.
Current detector CT1 Fixed frequency compressor is OFF, if
53-1 35
failure CT>=4.0(EE)3.0A for 2s(not detecting in 90s after
fixed frequency compressor is from ON to OFF);
fixed frequency compressor is ON, if CT<=2.0(EE) Resumable
Current detector CT2
53-2 35 for 2s(not detecting in 90s after fixed frequency
failure
compressor is from OFF to ON), it alarms failure of
CT in short circuit.

71
LD indication Indication on wired Failure code
Failure description Remarks
on master unit controller (hex) definition
Current of fixed frequency compressor is over the limitation
64-1 40 CT1 over current
twice at the interval of 25msecond, unit will stop, but 3 Once
minutes later, resume to be normal automatically. If it occurs confirmation,
64-2 40 CT2 over current 3 times in an hour, alarm and stop. But, in 4 seconds after un-resumable
startup, not detect.

Communication with
67 43 motor driving board Without communication for 4 minutes
failure

Left DC motor
71-1 47
blocked Running at speed below 20rpm for 30s, or at speed of
Once
70% lower than the target for 2 minutes, 2 minutes and 50
confirmation,
seconds later after stop, resume automatically. It occurs 3
un-resumable
times in an hour, confirm the failure.
Right DC motor
71-2 47
blocked

In 1 minute after inverter compressor starts up, Pd-


No pressure drop Once
Ps<=0.1MPa. 2 minutes and 50 seconds later after unit stops,
75-0 4B between high confirmation,
resume automatically, if it occurs twice continuously, confirm
pressure and low one un-resumable
the failure.
Slave unit quantity/address/horse power are not in
76-1 4C conformance with data in EEPROM of master unit: quantity
incorrect.

Slave unit quantity/address/horse power are not in


76-2 4C Incorrect outdoor conformance with data in EEPROM of master unit: address
address or capacity incorrect. Reset
setting

Slave unit quantity/address/horse power are not in


76-3 4C conformance with data in EEPROM of master unit: horse
power incorrect.

ToilA - ToilB<=10degree, unit alarms and stops, not detecting


Oil equalization in the course of startup, defrosting and oil return control, Once
77 4D protection among and in 10 minutes after oil return finishes. 2 minutes and confirmation,
outdoors 50 seconds later after unit stops, resume automatically. If it un-resumable
alarms twice continuously, confirm the failure.

72
LD
Indication on
indication
wired controller Failure code definition Failure description Remarks
on master
(hex)
unit
Compressor running in cooling mode, Ps<0.1MPa for
30 minutes; compressor running in heating mode,
78 4E Lack of refrigerant Tsi - ET>20; LEV will fully open for 60 minutes, the --
unit will output lack of refrigerant alarm, unit will not
stop.

30 minutes later after incorrect wiring is inspected,


outdoor: if Tdi<=Tao+30K, display failure code.
79 4F Incorrect wiring Resumable
indoor: if in cooling, Tc2>=Tai - 20K, display failure
code; in heating, Tc1<=Tai+20K, display failure code.

99-X
63 Software self-check Software self-check Resumable
(X=0~5)
DC motor driving board alarms because of over
current or modular temperature too high, resume
DC motor driving board IPM Once confirmation, un-
100 64 automatically 2 minutes and 50 seconds later after
alarm resumable
unit stops. It occurs 3 times in an hour, confirm the
failure.

Resume automatically 2 minutes and 50 seconds


DC motor driving board Once confirmation, un-
101 65 later after unit stops. It occurs 3 times in an hour,
detecting out of control resumable
confirm the failure.

Resume automatically 2 minutes and 50 seconds


DC motor driving board EEPROM Once confirmation, un-
102 66 later after unit stops. It occurse 3 times in an hour,
faulty resumable
confirm the failure.

If current of DC motor driving board is over 5A, unit


DC motor driving board over
alarms. 2 minutes and 50 seconds later after unit Once confirmation, un-
103 67 current or current detector
stops, resume automatically, if it occurs three times resumable
damaged
in an hour, confirm the failure.

If voltage of DC motor driving board is below 280V,


Voltage too low protection of DC unit alarms. 2 minutes and 50 seconds later after Once confirmation, un-
104 68
motor driving board unit stops, resume automatically, if it occurs three resumable
times in an hour, confirm the failure.

If voltage of DC motor driving board is over 400V,


Voltage too high protection of unit alarms. 2 minutes and 50 seconds later after Once confirmation, un-
105 69
DC motor driving board unit stops, resume automatically, if it occurs three resumable
times in an hour, confirm the failure.

73
Ld indication Indication on
Failure code
on master wired controller Failure description Remarks
definition
unit (hex)

Fan motor rate can not be detected. 2 minutes


DC motor driving board and 50 seconds later after unit stops, resume Once confirmation,
106 6A
blocked automatically, if it occurs three times in an hour, un-resumable
confirm the failure.

Protection of motor rate over Fan motor rate is higher than 1100 for 5 seconds, Once confirmation,
107 6B
limitation unit alarms. un-resumable

IPM modular over current, in short circuit, over


110 6E IPM modular protection (F0)
heat, voltage too low of control circuit.

In the course of compressor startup or running,


111 6F Compressor out of control the unit can not detect the rotor position, or not
connecting compressor.

3 times in an hour,
Radiator of transducer temp.
112 70 Radiator temp. too high confirm failure;
too high
once confirmation,
un-resumable
113 71 Transducer overload Output current of transducer is too high

Voltage too low of DC bus


114 72 Voltage of power source is too low
line of transducer

Voltage too high of DC bus


115 73 Voltage of power source is too high
line of transducer

Communication abnormal
116 74 between transducer and Communication is disconnected Resumable
control PCB

Compressor startup fails for 5 times continuously,


Transducer over current
117 75 or compressor is running down till stops caused by
(software)
over current or over heat

The sensor used for current detecting of 3 times in an hour,


118 76 Compressor startup failure transducer is abnormal, disconnected or incorrectly confirm failure;
connection once confirmation,
un-resumable
Inverter current detect circuit
119 77 Current sensor not connected or abnormal
abnormal

Power supply of transducer Power supply of transducer is broken down


120 78
abnormal instantly

74
Indication
Ld indication
on wired Failure code
on master Failure description Remarks
controller definition
unit
(hex)
Power supply of
121 79 inverter board is Power supply of inverter board is broken down instantly
3 times in an hour,
abnormal
confirm failure; once
Radiator temp.
confirmation, un-
sensor of Resistor of temp.sensor abnormal or temp.sensor
122 7A resumable
transducer disconnected
abnormal
Frequency not Current frequency target frequency+3Hz, or target
125 7D Resumable
matching frequency 0, but current frequency=0
If master unit inspects that MCU of slave unit is reset, and the
slave unit is running, master unit will alarm MCU reset failure,
MCU reset then the whole system will stop; if in heating mode, when Once confirmation,
127 7F
abnormal restart up, 4-way valve will be not electrified, the whole un-resumable
system will execute 4-way valve reversing operation again. if
it occurs three times in an hour, alarm and confirm the failure.
Software need The software is not compatible, you need to update the
128 80
updating software

When there is no failure, if the starting condition can not be met, digital tube on master unit will display stand-by
code:

555.0 Standby state of capacity overmatch When capacity is over 135% or lower than 50%, the system is standby.

When it is in heating mode with ambient temperature over 26 degree, the system
555.1 Standby state of 26 degree heating mode
is standby.
Standby state of super low pressure (lack of When the unit starts in cooling with ps<0.23Mpa or heating with ps<0.12Mpa, the
555.2
refrigerant) system is standby.
High ambient models, the unit can't open if ambient temp. above 54 degree ,7-
555.3 54 Degree cooling standby
segment board display :"555.3"

75
4.2 Failure diagnose

76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
Appendix I: Sensor Resistance Table
Code Resistance Description
10450194 10K Defrosting temp.sensor

10451307 10K Sunction air temp.sensor

10450192 10K Outdoor ambient temp.sensor

10451329 10K Pipe temp.sensor

10451303 50K Discharging temp.sensor

10450949 10K Indoor pipe temp.sesor

10451328 10K Pipe temp.sensor

10452099 10K Gas pipe temp.sensor

10400885 23K Sensor

10401922 10K Indoor coil pipe temp.sensor

10451305 10K Oil temp.sensor

10451327 23K Ambient temp.sensor

10451591 10K Sensor

10452298 10K Gas pipe temp.sensor

10403671 10K Indoor temp.sensor

10451329 10K Pipe temp.sensor

10452099 10K Gas pipe temp.sensor

10451327 23K Ambient temp.sensor

105
R80=50KΩ±3% B25/80=4450K±3%
Temp Resistance(KΩ) % (Resist.tol)
(℃ ) Rmax R(t)Normal Rmin MAX(+) MIN(-)
0 1749.014 1921.993 2094.972 9 9

1 1651.431 1813.265 1975.099 8.93 8.93

2 1560.165 1711.646 1863.127 8.85 8.85

3 1474.737 1616.593 1758.449 8.78 8.78

4 1394.709 1527.611 1660.513 8.7 8.7

5 1319.683 1444.25 1568.817 8.63 8.63

6 1249.295 1366.096 1482.897 8.55 8.55

7 1183.21 1292.773 1402.336 8.48 8.48

8 1121.124 1223.935 1326.746 8.4 8.4

9 1062.756 1159.265 1255.774 8.33 8.33

10 1007.85 1098.474 1189.098 8.25 8.25

11 956.167 1041.293 1126.419 8.18 8.18

12 907.491 987.477 1067.463 8.1 8.1

13 861.621 936.799 1011.977 8.03 8.03

14 818.372 889.052 959.732 7.95 7.95

15 777.574 844.042 910.51 7.88 7.88

16 739.066 801.59 864.114 7.8 7.8

17 702.705 761.533 820.361 7.73 7.73

18 668.353 723.717 779.081 7.65 7.65

19 635.885 688.001 740.117 7.58 7.58

20 605.185 654.254 703.323 7.5 7.5

21 576.145 622.355 668.565 7.43 7.43

22 548.663 592.189 635.715 7.35 7.35

23 522.645 563.651 604.657 7.28 7.28

24 498.006 536.644 575.282 7.2 7.2

25 474.662 511.076 547.49 7.13 7.13

26 452.538 486.862 521.186 7.05 7.05

27 431.563 463.922 496.281 6.98 6.98

28 411.671 442.182 472.693 6.9 6.9

29 392.8 421.572 450.344 6.83 6.83

30 374.891 402.028 429.165 6.75 6.75

31 357.891 383.489 409.087 6.68 6.68

32 341.749 365.898 390.047 6.6 6.6

33 326.416 349.201 371.986 6.53 6.53

34 311.848 333.349 354.85 6.45 6.45

35 298.004 318.295 338.586 6.38 6.38

36 284.843 303.995 323.147 6.3 6.3

106
Temp Resistance(KΩ) % (Resist.tol)
(℃ ) Rmax R(t)Normal Rmin MAX(+) MIN(-)
37 272.329 290.407 308.485 6.23 6.23

38 260.427 277.493 294.559 6.15 6.15

39 249.104 265.216 281.328 6.08 6.08

40 238.329 253.541 268.753 6 6

41 228.073 242.437 256.801 5.93 5.93

42 218.308 231.873 245.438 5.85 5.85

43 209.01 221.82 234.63 5.78 5.78

44 200.154 212.252 224.35 5.7 5.7

45 191.715 203.142 214.569 5.63 5.63

46 183.674 194.467 205.26 5.55 5.55

47 176.009 186.204 196.399 5.48 5.48

48 168.703 178.333 187.963 5.4 5.4

49 161.735 170.832 179.929 5.33 5.33

50 155.089 163.682 172.275 5.25 5.25

51 148.748 156.866 164.984 5.18 5.18

52 142.698 150.367 158.036 5.1 5.1

53 136.924 144.168 151.412 5.03 5.03

54 131.411 138.255 145.099 4.95 4.95

55 126.148 132.613 139.078 4.88 4.88

56 121.122 127.229 133.336 4.8 4.8

57 116.32 122.089 127.858 4.73 4.73

58 111.732 117.181 122.63 4.65 4.65

59 107.347 112.494 117.641 4.58 4.58

60 103.157 108.018 112.879 4.5 4.5

61 99.15 103.741 108.332 4.43 4.43

62 95.319 99.654 103.989 4.35 4.35

63 91.655 95.748 99.841 4.28 4.28

64 88.149 92.014 95.879 4.2 4.2

65 84.795 88.443 92.091 4.13 4.13

66 81.584 85.028 88.472 4.05 4.05

67 78.511 81.761 85.011 3.98 3.98

68 75.569 78.636 81.703 3.9 3.9

69 72.752 75.645 78.538 3.83 3.83

70 70.052 72.781 75.51 3.75 3.75

71 67.466 70.04 72.614 3.68 3.68

107
R80=50KΩ±3% B25/80=4450K±3%
Temp Resistance(KΩ) % Resist.tol)
(℃ ) Rmax R(t)Normal Rmin MAX(+) MIN(-)
72 64.988 67.415 69.842 3.6 3.6

73 62.613 64.901 67.189 3.53 3.53

74 60.337 62.493 64.649 3.45 3.45

75 58.154 60.185 62.216 3.38 3.38

76 56.06 57.973 59.886 3.3 3.3

77 54.051 55.852 57.653 3.23 3.23

78 52.125 53.82 55.515 3.15 3.15

79 50.275 51.87 53.465 3.08 3.08

80 48.5 50 51.5 3 3

81 46.728 48.206 49.684 3.07 3.07

82 45.028 46.484 47.94 3.13 3.13

83 43.397 44.832 46.267 3.2 3.2

84 41.833 43.246 44.659 3.27 3.27

85 40.332 41.723 43.114 3.33 3.33

86 38.891 40.26 41.629 3.4 3.4

87 37.509 38.856 40.203 3.47 3.47

88 36.181 37.506 38.831 3.53 3.53

89 34.905 36.209 37.513 3.6 3.6

90 33.68 34.962 36.244 3.67 3.67

91 32.503 33.764 35.025 3.73 3.73

92 31.373 32.612 33.851 3.8 3.8

93 30.286 31.504 32.722 3.87 3.87

94 29.242 30.439 31.636 3.93 3.93

95 28.236 29.413 30.59 4 4

96 27.271 28.427 29.583 4.07 4.07

97 26.342 27.478 28.614 4.13 4.13

98 25.448 26.564 27.68 4.2 4.2

99 24.589 25.685 26.781 4.27 4.27

100 23.762 24.838 25.914 4.33 4.33

101 22.966 24.023 25.08 4.4 4.4

102 22.199 23.237 24.275 4.47 4.47

103 21.462 22.481 23.5 4.53 4.53

104 20.751 21.752 22.753 4.6 4.6

108
Temp Resistance(KΩ) % (Resist.tol)
(℃ ) Rmax R(t)Normal Rmin MAX(+) MIN(-)
105 20.067 21.049 22.031 4.67 4.67

106 19.408 20.372 21.336 4.73 4.73

107 18.773 19.72 20.667 4.8 4.8

108 18.162 19.091 20.02 4.87 4.87

109 17.573 18.485 19.397 4.93 4.93

110 17.005 17.9 18.795 5 5

111 16.459 17.337 18.215 5.07 5.07

112 15.931 16.793 17.655 5.13 5.13

113 15.422 16.268 17.114 5.2 5.2

114 14.933 15.763 16.593 5.27 5.27

115 14.46 15.275 16.09 5.33 5.33

116 14.005 14.804 15.603 5.4 5.4

117 13.565 14.349 15.133 5.47 5.47

118 13.141 13.911 14.681 5.53 5.53

119 12.733 13.488 14.243 5.6 5.6

120 12.339 13.08 13.821 5.67 5.67

121 11.958 12.685 13.412 5.73 5.73

122 11.591 12.305 13.019 5.8 5.8

123 11.238 11.938 12.638 5.87 5.87

124 10.897 11.584 12.271 5.93 5.93

125 10.567 11.242 11.917 6 6

126 10.249 10.911 11.573 6.07 6.07

127 9.943 10.593 11.243 6.13 6.13

128 9.647 10.285 10.923 6.2 6.2

129 9.362 9.988 10.614 6.27 6.27

130 9.087 9.701 10.315 6.33 6.33

131 8.822 9.425 10.028 6.4 6.4

132 8.566 9.158 9.75 6.47 6.47

133 8.319 8.9 9.481 6.53 6.53

134 8.08 8.651 9.222 6.6 6.6

135 7.85 8.411 8.972 6.67 6.67

136 7.629 8.18 8.731 6.73 6.73

137 7.416 7.957 8.498 6.8 6.8

138 7.209 7.741 8.273 6.87 6.87

139 7.011 7.533 8.055 6.93 6.93

140 6.82 7.333 7.846 7 7

109
R25=10KΩ±3% B25/50=3700K±3%
Temp Resistance(KΩ) % (Resist.tol)
(℃ ) Rmax R(t)Normal Rmin MAX(+) MIN(-)

-30 145.819 135.018 124.217 7 7

-29 138.071 129.126 120.181 6.93 6.93

-28 131.793 123.339 114.885 6.85 6.85

-27 125.665 117.684 109.703 6.78 6.78

-26 119.706 112.18 104.654 6.71 6.71

-25 113.933 106.843 99.753 6.64 6.64

-24 108.361 101.687 95.013 6.56 6.56

-23 102.997 96.719 90.441 6.49 6.49

-22 97.847 91.946 86.045 6.42 6.42

-21 92.915 87.371 81.827 6.35 6.35

-20 88.2 82.994 77.788 6.27 6.27

-19 83.702 78.815 73.928 6.2 6.2

-18 79.417 74.832 70.247 6.13 6.13

-17 75.342 71.041 66.74 6.05 6.05

-16 71.471 67.437 63.403 5.98 5.98

-15 67.798 64.015 60.232 5.91 5.91

-14 64.316 60.769 57.222 5.84 5.84

-13 61.017 57.692 54.367 5.76 5.76

-12 57.895 54.778 51.661 5.69 5.69

-11 54.942 52.019 49.096 5.62 5.62

-10 52.149 49.409 46.669 5.55 5.55

-9 49.51 46.941 44.372 5.47 5.47

-8 47.016 44.607 42.198 5.4 5.4

-7 44.659 42.4 40.141 5.33 5.33

-6 42.433 40.315 38.197 5.25 5.25

-5 40.332 38.345 36.358 5.18 5.18

-4 38.346 36.482 34.618 5.11 5.11

-3 36.472 34.723 32.974 5.04 5.04

-2 34.7 33.059 31.418 4.96 4.96

-1 33.027 31.487 29.947 4.89 4.89

110
Temp Resistance(KΩ) % (Resist.tol)
(℃ ) Rmax R(t)Normal Rmin MAX(+) MIN(-)
0 31.445 30 28.555 4.82 4.82
1 29.951 28.594 27.237 4.75 4.75
2 28.538 27.264 25.99 4.67 4.67
3 27.202 26.006 24.81 4.6 4.6
4 25.938 24.815 23.692 4.53 4.53
5 24.742 23.687 22.632 4.45 4.45
6 23.61 22.619 21.628 4.38 4.38
7 22.538 21.607 20.676 4.31 4.31
8 21.522 20.647 19.772 4.24 4.24
9 20.559 19.737 18.915 4.16 4.16
10 19.646 18.874 18.102 4.09 4.09
11 18.779 18.054 17.329 4.02 4.02
12 17.958 17.276 16.594 3.95 3.95
13 17.177 16.537 15.897 3.87 3.87
14 16.436 15.834 15.232 3.8 3.8
15 15.731 15.166 14.601 3.73 3.73
16 15.061 14.53 13.999 3.65 3.65
17 14.424 13.925 13.426 3.58 3.58
18 13.817 13.349 12.881 3.51 3.51
19 13.24 12.8 12.36 3.44 3.44
20 12.69 12.277 11.864 3.36 3.36
21 12.166 11.778 11.39 3.29 3.29
22 11.666 11.302 10.938 3.22 3.22
23 11.189 10.848 10.507 3.15 3.15
24 10.734 10.414 10.094 3.07 3.07
25 10.3 10 9.7 3 3
26 9.898 9.604 9.31 3.06 3.06
27 9.514 9.226 8.938 3.13 3.13
28 9.147 8.864 8.581 3.19 3.19
29 8.796 8.519 8.242 3.25 3.25
30 8.459 8.188 7.917 3.31 3.31
31 8.137 7.871 7.605 3.38 3.38
32 7.828 7.568 7.308 3.44 3.44
33 7.532 7.277 7.022 3.5 3.5
34 7.248 6.999 6.75 3.56 3.56
35 6.977 6.733 6.489 3.63 3.63
36 6.716 6.477 6.238 3.69 3.69
37 6.466 6.232 5.998 3.75 3.75
38 6.227 5.998 5.769 3.81 3.81
39 5.997 5.773 5.549 3.88 3.88
40 5.776 5.557 5.338 3.94 3.94
41 5.564 5.35 5.136 4 4

111
Appendix II

R25=10KΩ±3% B25/50=3700K±3%
Temp Resistance(KΩ) % (Resist.tol)
(℃ ) Rmax R(t)Normal Rmin MAX(+) MIN(-)
42 5.36 5.151 4.942 4.06 4.06

43 5.166 4.961 4.756 4.13 4.13

44 4.978 4.778 4.578 4.19 4.19

45 4.799 4.603 4.407 4.25 4.25

46 4.625 4.434 4.243 4.31 4.31

47 4.46 4.273 4.086 4.38 4.38

48 4.301 4.118 3.935 4.44 4.44

49 4.148 3.969 3.79 4.5 4.5

50 4.001 3.826 3.651 4.56 4.56

51 3.86 3.689 3.518 4.63 4.63

52 3.724 3.557 3.39 4.69 4.69

53 3.594 3.431 3.268 4.75 4.75

54 3.468 3.309 3.15 4.81 4.81

55 3.349 3.193 3.037 4.88 4.88

56 3.233 3.081 2.929 4.94 4.94

57 3.123 2.974 2.825 5 5

58 3.015 2.87 2.725 5.06 5.06

59 2.913 2.771 2.629 5.13 5.13

60 2.815 2.676 2.537 5.19 5.19

61 2.721 2.585 2.449 5.25 5.25

62 2.63 2.497 2.364 5.31 5.31

63 2.543 2.413 2.283 5.38 5.38

64 2.459 2.332 2.205 5.44 5.44

65 2.379 2.255 2.131 5.5 5.5

66 2.301 2.18 2.059 5.56 5.56

67 2.228 2.109 1.99 5.63 5.63

68 2.156 2.04 1.924 5.69 5.69

69 2.088 1.974 1.86 5.75 5.75

70 2.021 1.91 1.799 5.81 5.81

71 1.958 1.849 1.74 5.88 5.88

72 1.897 1.791 1.685 5.94 5.94

73 1.839 1.735 1.631 6 6

74 1.782 1.68 1.578 6.06 6.06

112
Temp Resistance(KΩ) % (Resist.tol)
(℃ ) Rmax R(t)Normal Rmin MAX(+) MIN(-)
75 1.728 1.628 1.528 6.13 6.13

76 1.676 1.578 1.48 6.19 6.19

77 1.626 1.53 1.434 6.25 6.25

78 1.578 1.484 1.39 6.31 6.31

79 1.531 1.439 1.347 6.38 6.38

80 1.486 1.396 1.306 6.44 6.44

81 1.443 1.355 1.267 6.5 6.5

82 1.401 1.315 1.229 6.56 6.56

83 1.362 1.277 1.192 6.63 6.63

84 1.323 1.24 1.157 6.69 6.69

85 1.285 1.204 1.123 6.75 6.75

86 1.249 1.169 1.089 6.81 6.81

87 1.214 1.136 1.058 6.88 6.88

88 1.181 1.104 1.027 6.94 6.94

89 1.148 1.073 0.998 7 7

90 1.116 1.042 0.968 7.06 7.06

91 1.085 1.013 0.941 7.13 7.13

92 1.056 0.985 0.914 7.19 7.19

93 1.026 0.957 0.888 7.25 7.25

94 0.998 0.93 0.862 7.31 7.31

95 0.971 0.904 0.837 7.38 7.38

96 0.944 0.879 0.814 7.44 7.44

97 0.918 0.854 0.79 7.5 7.5

98 0.893 0.83 0.767 7.56 7.56

99 0.867 0.806 0.745 7.63 7.63

100 0.843 0.783 0.723 7.69 7.69

101 0.819 0.76 0.701 7.75 7.75

102 0.796 0.738 0.68 7.81 7.81

103 0.772 0.716 0.66 7.88 7.88

104 0.749 0.694 0.639 7.94 7.94

105 0.727 0.673 0.619 8 8

113
R25=23KΩ±3% B25/50=4200K±3%

Temp Resistance(KΩ) % (Resist.tol)

(℃ ) Rmax R(t)Normal Rmin MAX(+) MIN(-)

-30 538.771 513.115 487.459 5 5

-29 502.577 478.894 455.211 4.95 4.95

-28 469.29 447.408 425.526 4.89 4.89

-27 438.613 418.379 398.145 4.84 4.84

-26 410.288 391.564 372.84 4.78 4.78

-25 384.088 366.751 349.414 4.73 4.73

-24 359.817 343.754 327.691 4.67 4.67

-23 337.296 322.407 307.518 4.62 4.62

-22 316.375 302.567 288.759 4.56 4.56

-21 296.916 284.105 271.294 4.51 4.51

-20 278.794 266.905 255.016 4.45 4.45

-19 261.904 250.866 239.828 4.4 4.4

-18 246.146 235.895 225.644 4.35 4.35

-17 231.433 221.911 212.389 4.29 4.29

-16 217.685 208.838 199.991 4.24 4.24

-15 204.831 196.609 188.387 4.18 4.18

-14 192.805 185.163 177.521 4.13 4.13

-13 181.548 174.443 167.338 4.07 4.07

-12 171.005 164.399 157.793 4.02 4.02

-11 161.126 154.983 148.84 3.96 3.96

-10 151.866 146.153 140.44 3.91 3.91

-9 143.184 137.87 132.556 3.85 3.85

-8 135.04 130.096 125.152 3.8 3.8

-7 127.398 122.799 118.2 3.75 3.75

-6 120.225 115.946 111.667 3.69 3.69

-5 113.492 109.51 105.528 3.64 3.64

-4 107.168 103.462 99.756 3.58 3.58

-3 101.228 97.779 94.33 3.53 3.53

-2 95.647 92.437 89.227 3.47 3.47

-1 90.403 87.415 84.427 3.42 3.42

0 85.472 82.691 79.91 3.36 3.36

114
Temp Resistance(KΩ) % (Resist.tol)
(℃ ) Rmax R(t)Normal Rmin MAX(+) MIN(-)
1 80.837 78.248 75.659 3.31 3.31
2 76.478 74.067 71.656 3.25 3.25
3 72.377 70.133 67.889 3.2 3.2
4 68.52 66.43 64.34 3.15 3.15
5 64.889 62.943 60.997 3.09 3.09
6 61.47 59.659 57.848 3.04 3.04
7 58.253 56.566 54.879 2.98 2.98
8 55.222 53.651 52.08 2.93 2.93
9 52.366 50.904 49.442 2.87 2.87
10 49.676 48.314 46.952 2.82 2.82
11 47.14 45.872 44.604 2.76 2.76
12 44.749 43.569 42.389 2.71 2.71
13 42.494 41.395 40.296 2.65 2.65
14 40.366 39.343 38.32 2.6 2.6
15 38.358 37.406 36.454 2.55 2.55
16 36.463 35.577 34.691 2.49 2.49
17 34.673 33.848 33.023 2.44 2.44
18 32.982 32.215 31.448 2.38 2.38
19 31.385 30.671 29.957 2.33 2.33
20 29.874 29.21 28.546 2.27 2.27
21 28.445 27.828 27.211 2.22 2.22
22 27.095 26.521 25.947 2.16 2.16
23 25.816 25.283 24.75 2.11 2.11
24 24.606 24.111 23.616 2.05 2.05
25 23.46 23 22.54 2 2
26 22.396 21.947 21.498 2.04 2.04
27 21.386 20.949 20.512 2.09 2.09
28 20.429 20.003 19.577 2.13 2.13
29 19.52 19.104 18.688 2.18 2.18
30 18.657 18.252 17.847 2.22 2.22
31 17.837 17.442 17.047 2.26 2.26
32 17.059 16.674 16.289 2.31 2.31
33 16.318 15.943 15.568 2.35 2.35
34 15.614 15.249 14.884 2.39 2.39
35 14.944 14.588 14.232 2.44 2.44
36 14.306 13.96 13.614 2.48 2.48
37 13.699 13.362 13.025 2.53 2.53
38 13.123 12.794 12.465 2.57 2.57
39 12.572 12.252 11.932 2.61 2.61
40 12.048 11.736 11.424 2.66 2.66
41 11.548 11.244 10.94 2.7 2.7

115
R25=23KΩ±3% B25/50=4200K±3%
Temp Resistance(KΩ) % (Resist.tol)

(℃ ) Rmax R(t)Normal Rmin MAX(+) MIN(-)

42 11.072 10.776 10.48 2.74 2.74

43 10.617 10.329 10.041 2.79 2.79

44 10.184 9.904 9.624 2.83 2.83

45 9.77 9.497 9.224 2.88 2.88

46 9.376 9.11 8.844 2.92 2.92

47 8.999 8.74 8.481 2.96 2.96

48 8.639 8.387 8.135 3.01 3.01

49 8.296 8.05 7.804 3.05 3.05

50 7.967 7.728 7.489 3.09 3.09

51 7.654 7.421 7.188 3.14 3.14

52 7.354 7.127 6.9 3.18 3.18

53 7.067 6.846 6.625 3.23 3.23

54 6.793 6.578 6.363 3.27 3.27

55 6.531 6.322 6.113 3.31 3.31

56 6.281 6.077 5.873 3.36 3.36

57 6.041 5.842 5.643 3.4 3.4

58 5.811 5.618 5.425 3.44 3.44

59 5.592 5.404 5.216 3.49 3.49

60 5.383 5.199 5.015 3.53 3.53

61 5.182 5.003 4.824 3.58 3.58

62 4.989 4.815 4.641 3.62 3.62

63 4.806 4.636 4.466 3.66 3.66

64 4.629 4.464 4.299 3.71 3.71

65 4.461 4.3 4.139 3.75 3.75

66 4.3 4.143 3.986 3.79 3.79

67 4.145 3.992 3.839 3.84 3.84

68 3.997 3.848 3.699 3.88 3.88

69 3.856 3.71 3.564 3.93 3.93

70 3.72 3.578 3.436 3.97 3.97

116
Temp Resistance(KΩ) % (Resist.tol)
(℃ ) Rmax R(t)Normal Rmin MAX(+) MIN(-)
71 3.591 3.452 3.313 4.01 4.01

72 3.466 3.331 3.196 4.06 4.06

73 3.347 3.215 3.083 4.1 4.1

74 3.233 3.104 2.975 4.14 4.14

75 3.122 2.997 2.872 4.19 4.19

76 3.017 2.895 2.773 4.23 4.23

77 2.918 2.798 2.678 4.28 4.28

78 2.821 2.704 2.587 4.32 4.32

79 2.728 2.614 2.5 4.36 4.36

80 2.639 2.528 2.417 4.41 4.41

81 2.555 2.446 2.337 4.45 4.45

82 2.472 2.366 2.26 4.49 4.49

83 2.394 2.29 2.186 4.54 4.54

84 2.319 2.217 2.115 4.58 4.58

85 2.246 2.147 2.048 4.63 4.63

86 2.177 2.08 1.983 4.67 4.67

87 2.11 2.015 1.92 4.71 4.71

88 2.045 1.952 1.859 4.76 4.76

89 1.983 1.892 1.801 4.8 4.8

90 1.923 1.834 1.745 4.84 4.84

91 1.865 1.778 1.691 4.89 4.89

92 1.809 1.724 1.639 4.93 4.93

93 1.755 1.672 1.589 4.98 4.98

94 1.702 1.621 1.54 5.02 5.02

95 1.652 1.572 1.492 5.06 5.06

96 1.602 1.524 1.446 5.11 5.11

97 1.554 1.478 1.402 5.15 5.15

98 1.507 1.433 1.359 5.19 5.19

99 1.462 1.389 1.316 5.24 5.24

100 1.418 1.347 1.276 5.28 5.28

101 1.374 1.305 1.236 5.33 5.33

102 1.332 1.264 1.196 5.37 5.37

103 1.289 1.223 1.157 5.41 5.41

104 1.249 1.184 1.119 5.46 5.46

105 1.208 1.145 1.082 5.5 5.5

117
R25=5KΩ±3% B25/50=3450K±3%

Temp Resistance(KΩ) %(Resist.tol)

(℃ ) Rmax R(t)Normal Rmin MAX(+) MIN(-)

-30 67.148 62.209 57.268 7.94 7.94

-29 63.782 58.887 54.289 8.31 7.81

-28 60.323 55.769 51.487 8.17 7.68

-27 57.079 52.841 48.85 8.02 7.55

-26 54.036 50.088 46.367 7.88 7.43

-25 51.178 47.499 44.028 7.75 7.31

-24 48.492 45.062 41.822 7.61 7.19

-23 45.968 42.768 39.742 7.48 7.07

-22 43.592 40.606 37.78 7.35 6.96

-21 41.357 38.568 35.927 7.23 6.85

-20 39.251 36.646 34.176 7.11 6.74

-19 37.266 34.833 32.522 6.99 6.63

-18 35.395 33.12 30.959 6.87 6.53

-17 33.631 31.503 29.48 6.75 6.42

-16 31.965 29.975 28.081 6.64 6.32

-15 30.393 28.531 26.757 6.53 6.22

-14 28.908 27.165 25.503 6.42 6.12

-13 27.505 25.873 24.315 6.31 6.02

-12 26.178 24.65 23.19 6.2 5.92

-11 24.924 23.493 22.123 6.09 5.83

-10 23.737 22.396 21.112 5.99 5.73

-9 22.614 21.358 20.153 5.89 5.64

-8 21.551 20.373 19.243 5.78 5.55

-7 20.545 19.44 18.379 5.68 5.46

-6 19.591 18.555 17.559 5.58 5.37

-5 18.687 17.716 16.781 5.49 5.28

-4 17.83 16.919 16.041 5.39 5.19

-3 17.018 16.163 15.338 5.29 5.1

-2 16.247 15.445 14.67 5.2 5.02

-1 15.516 14.763 14.035 5.1 4.93

0 14.822 14.115 13.431 5.01 4.85

118
Temp Resistance(KΩ) %(Resist.tol)

(℃ ) Rmax R(t)Normal Rmin MAX(+) MIN(-)


1 14.163 13.499 12.856 4.92 4.76
2 13.537 12.914 12.31 4.83 4.68
3 12.943 12.357 11.789 4.74 4.6
4 12.378 11.828 11.294 4.65 4.52
5 11.841 11.324 10.822 4.56 4.44
6 11.33 10.845 10.372 4.48 4.36
7 10.845 10.388 9.944 4.39 4.28
8 10.382 9.954 9.536 4.31 4.2
9 9.943 9.54 9.147 4.22 4.12
10 9.524 9.146 8.775 4.14 4.05
11 9.126 8.77 8.421 4.06 3.97
12 8.746 8.412 8.084 3.98 3.9
13 8.384 8.07 7.761 3.9 3.83
14 8.04 7.744 7.454 3.82 3.75
15 7.711 7.433 7.16 3.74 3.68
16 7.398 7.137 6.879 3.66 3.61
17 7.099 6.854 6.611 3.58 3.54
18 6.814 6.583 6.355 3.51 3.47
19 6.542 6.325 6.11 3.43 3.4
20 6.283 6.079 5.876 3.36 3.33
21 6.035 5.843 5.652 3.29 3.26
22 5.798 5.618 5.438 3.21 3.2
23 5.572 5.403 5.233 3.14 3.13
24 5.356 5.197 5.038 3.07 3.07
25 5.15 5 4.85 3 3
26 4.959 4.812 4.665 3.06 3.06
27 4.776 4.632 4.487 3.12 3.11
28 4.601 4.459 4.318 3.18 3.17
29 4.433 4.294 4.156 3.24 3.22
30 4.273 4.136 4.001 3.3 3.28
31 4.119 3.985 3.852 3.36 3.33
32 3.971 3.84 3.71 3.41 3.38
33 3.829 3.701 3.574 3.47 3.44
34 3.694 3.568 3.444 3.52 3.49
35 3.563 3.44 3.319 3.58 3.54
36 3.439 3.318 3.199 3.63 3.59
37 3.319 3.201 3.085 3.68 3.64
38 3.204 3.088 2.975 3.73 3.68
39 3.093 2.981 2.869 3.78 3.73
40 2.987 2.877 2.768 3.83 3.78
41 2.885 2.778 2.671 3.88 3.82

119
R25=5KΩ±3% B25/50=3450K±3%

Temp Resistance(KΩ) %(Resist.tol)

(℃ ) Rmax R(t)Normal Rmin MAX(+) MIN(-)

42 2.788 2.682 2.578 3.93 3.87

43 2.694 2.591 2.489 3.98 3.91

44 2.604 2.503 2.404 4.03 3.96

45 2.517 2.418 2.321 4.07 4

46 2.433 2.337 2.243 4.12 4.05

47 2.353 2.259 2.167 4.16 4.09

48 2.276 2.184 2.094 4.21 4.13

49 2.202 2.112 2.024 4.25 4.17

50 2.131 2.043 1.957 4.3 4.21

51 2.062 1.976 1.892 4.34 4.25

52 1.996 1.912 1.83 4.38 4.29

53 1.933 1.851 1.771 4.42 4.33

54 1.871 1.791 1.713 4.46 4.37

55 1.813 1.734 1.658 4.5 4.4

56 1.756 1.68 1.605 4.54 4.44

57 1.701 1.627 1.554 4.58 4.48

58 1.649 1.576 1.505 4.62 4.51

59 1.598 1.527 1.457 4.65 4.55

60 1.549 1.48 1.412 4.69 4.58

61 1.502 1.434 1.368 4.73 4.62

62 1.456 1.39 1.326 4.76 4.65

63 1.413 1.348 1.285 4.8 4.68

64 1.37 1.307 1.245 4.83 4.72

65 1.33 1.268 1.208 4.87 4.75

66 1.29 1.23 1.171 4.9 4.78

67 1.252 1.193 1.136 4.94 4.81

68 1.216 1.158 1.102 4.97 4.85

69 1.18 1.124 1.069 5 4.88

70 1.146 1.091 1.038 5.03 4.91

120
Temp Resistance(KΩ) %(Resist.tol)
(℃ ) Rmax R(t)Normal Rmin MAX(+) MIN(-)
71 1.113 1.059 1.007 5.07 4.94

72 1.081 1.029 0.978 5.1 4.97

73 1.05 0.999 0.949 5.13 5

74 1.021 0.971 0.922 5.16 5.03

75 0.992 0.943 0.895 5.19 5.06

76 0.964 0.916 0.87 5.23 5.09

77 0.937 0.89 0.845 5.26 5.12

78 0.911 0.866 0.821 5.29 5.15

79 0.886 0.841 0.798 5.32 5.18

80 0.862 0.818 0.775 5.35 5.21

81 0.838 0.795 0.754 5.38 5.24

82 0.815 0.774 0.733 5.41 5.27

83 0.793 0.752 0.712 5.44 5.3

84 0.772 0.732 0.693 5.47 5.33

85 0.751 0.712 0.674 5.51 5.36

86 0.731 0.693 0.655 5.54 5.39

87 0.712 0.674 0.638 5.57 5.42

88 0.693 0.656 0.62 5.6 5.45

89 0.675 0.639 0.604 5.63 5.48

90 0.657 0.622 0.587 5.66 5.51

91 0.64 0.605 0.572 5.69 5.54

92 0.623 0.589 0.557 5.72 5.57

93 0.607 0.574 0.542 5.75 5.6

94 0.591 0.559 0.527 5.78 5.62

95 0.576 0.544 0.514 5.81 5.65

96 0.561 0.53 0.5 5.84 5.68

97 0.547 0.517 0.487 5.87 5.71

98 0.533 0.503 0.474 5.89 5.73

99 0.52 0.49 0.462 5.92 5.76

100 0.506 0.478 0.45 5.95 5.78

101 0.494 0.466 0.439 5.97 5.8

102 0.481 0.454 0.428 5.99 5.82

103 0.469 0.443 0.417 6.02 5.84

104 0.458 0.432 0.406 6.04 5.86

105 0.446 0.421 0.396 6.05 5.88

121
R50=17KΩ±2% B25/50=4170K±3%

Temp(℃ ) Rmin R(t)Normal Rmax Temp(℃ ) Rmin R(t)Normal Rmax

0 164.728 176.383 187.001 53 14.728 15.071 15.409

1 156.212 167.099 177.024 54 14.141 14.484 14.821

2 148.19 158.362 167.64 55 13.582 13.925 14.26

3 140.628 150.133 158.809 56 13.047 13.389 13.721

4 133.495 142.378 150.491 57 12.534 12.875 13.204

5 126.767 135.069 142.657 58 12.044 12.383 12.71

6 120.418 128.179 135.277 59 11.577 11.914 12.239

7 114.426 121.681 128.321 60 11.129 11.464 11.785

8 108.766 115.549 121.762 61 10.701 11.034 11.352

9 103.42 109.762 115.575 62 10.292 10.622 10.937

10 98.366 104.296 109.736 63 9.901 10.228 10.539

11 93.59 99.136 104.227 64 9.523 9.847 10.155

12 89.073 94.259 99.023 65 9.164 9.485 9.789

13 84.801 89.651 94.111 66 8.821 9.139 9.439

14 80.757 85.292 89.467 67 8.492 8.806 9.102

15 76.93 81.171 85.079 68 8.176 8.486 8.779

16 73.306 77.272 80.93 69 7.874 8.181 8.469

17 69.874 73.584 77.008 70 7.583 7.886 8.171

18 66.621 70.09 73.295 71 7.306 7.606 7.886

19 63.538 66.782 69.782 72 7.039 7.334 7.61

20 60.618 63.65 66.459 73 6.784 7.076 7.348

21 57.844 60.68 63.308 74 6.539 6.827 7.095

22 55.217 57.867 60.327 75 6.303 6.587 6.851

23 52.721 55.198 57.5 76 6.079 6.358 6.618

24 50.353 52.669 54.823 77 5.861 6.136 6.392

25 48.103 50.266 52.282 78 5.654 5.926 6.177

122
Temp(℃ ) Rmin R(t)Normal Rmax Temp(℃ ) Rmin R(t)Normal Rmax

26 45.967 47.989 49.874 79 5.454 5.722 5.97

27 43.938 45.826 47.59 80 5.262 5.525 5.769

28 42.01 43.773 45.422 81 5.078 5.337 5.577

29 40.177 41.823 43.366 82 4.903 5.158 5.394

30 38.433 39.969 41.411 83 4.732 4.984 5.216

31 36.776 38.209 39.557 84 4.569 4.816 5.044

32 35.197 36.534 37.793 85 4.412 4.655 4.879

33 33.696 34.942 36.118 86 4.262 4.501 4.722

34 32.268 33.429 34.528 87 4.116 4.352 4.568

35 30.905 31.987 33.013 88 3.978 4.209 4.422

36 29.61 30.617 31.574 89 3.843 4.071 4.28

37 28.376 29.313 30.206 90 3.714 3.938 4.143

38 27.198 28.07 28.902 91 3.591 3.811 4.013

39 26.078 26.888 27.664 92 3.47 3.686 3.884

40 25.008 25.76 26.483 93 3.356 3.568 3.763

41 23.986 24.685 25.357 94 3.244 3.453 3.644

42 23.014 23.661 24.287 95 3.139 3.344 3.532

43 22.085 22.686 23.267 96 3.036 3.238 3.422

44 21.2 21.755 22.295 97 2.937 3.136 3.317

45 20.354 20.867 21.369 98 2.841 3.036 3.214

46 19.546 20.021 20.485 99 2.75 2.941 3.116

47 18.775 19.212 19.643 100 2.662 2.851 3.022

48 18.037 18.44 18.839 101 2.577 2.762 2.931

49 17.334 17.704 18.072 102 2.495 2.676 2.842

50 16.66 17 17.34 103 2.416 2.595 2.757

51 15.986 16.328 16.667 104 2.34 2.516 2.675

52 15.342 15.684 16.023 105 2.266 2.439 2.595

123
CARRIER INTERAMERICA CORPORATION
MIAMI, FLORIDA, USA
C CIAC 2014

124