Ticket Information
Original Ticket
Ticket: 143966
Date: Saturday, July 6 2019
Time: 3:44:47 AM
Regards,
R. Sujatha
In order to generate the %dc in report we need to change the default report format for
incorporating the changes. We will need SAP Crystal Reports software to edit these
template files. Alternatively we can generate the values on the SLD using datablock.
Please refer the attachment.
Your Reply
User Reply: Dear Sir,
Regards,
R. Sujatha
Currently we can export the report to excel sheet and manually convert the values to
output %dc component .
I will try to check with my US team today for any other alternative.
Thanks
vasu
Date: Monday, July 8 2019
Time: 11:54:05 PM
Which calculation are you referring to IEC 61363 or IEC 60909? Can you show a screen
shot of your system or the summary?
Thank you
Regards
Raghu
Date: Wednesday, July 10 2019
Time: 10:36:53 AM
Your Reply
User Reply: Dear Sir,
Your Reply
User Reply: Dear Sir,
Pl. find attached the screen shot & summary. Doing it using IEC 60909.
Date: Wednesday, July 10 2019
Time: 11:56:14 PM
File Attachment: DC COMPONENT.zip File Type: application/zip Size: 214625 bytes
However, there is only way to see the Idc (Current in kA) results for the given bus and
with respect to min delay using the following option
1. Go to study case -> Standard page -> Check the "Report Ib vs Time Delays Based
on"
2. Run IEC device duty (not 60909) from the toolbar
3. Open short-circuit report
4. See the faulted bus and Idc values for each time delay option
Hope it helps
Thank you
Regards
Raghu
Your Reply
User Reply: Dear Sir,
Thank You.
Date: Monday, July 15 2019
Time: 2:45:41 AM