Sie sind auf Seite 1von 1

A

500 2000 4500 19000 4500 2000 500 1. THIS DRAWING SHOULD BE READ IN CONJUNCTION WITH

500
RELEVANT ARCH. DRAWING, CONTRACT TERMS, CONDITION
AND SPECIFICATIONS.
2. ALL DIMENSIONS ARE IN MILLIMETERS, UNLESS OTHERWISE
SPECIFIED.

2000
3. THE DRAWING IS NOT TO BE SCALED. ONLY WRITTEN

1200
DIMENSION SHOULD BE FOLLOWED.
UP 4. THE MIX FOR R.C.C WORK SHALL BE M30 FOR ALL MEMBER'S.
UP 5. ALL REINFORCING STEEL SHALL BE TOR STEEL FE 500 HYSD
BARS CONFIRMING TO THE REQUIREMENTS OF IS :1786.
1200 6. CLEAR COVER TO THE REINFORCEMENT SHALL BE AS PER
THE FOLLOWING

4500
i) FOOTING AND WALL - 75mm.
ii) BEAM - 30mm.
iii) SLAB - 20mm.
iv) COLUMN - 40mm.
v) GROUND BEAM(GB) & PEDESTAL - 40mm
7. MINIMUM DEVELOPMENT OVER LAP FOR TOR STEEL SHALL BE 50
D, WHERE "D" IS DIA OF MAIN REINFORCEMENT. THE LAP SHALL
BE STAGGERED AND AVOIDED AT THE POINT OF MAXIMUM
DOME-A DOME-A DOME-A BENDING MOMENT.
8. WATER IS TO BE USED FOR BRICK MASONRY AND CONCRETE
WORKS CONFORMING TO IS 456 - 2000.
9. DISCREPANCY IF ANY FOUND IN THIS DRAWING SHOULD
BROUGHT TO THE NOTICE OF THE OFFICE BEFORE EXECUTION.
10. IS 456-2000 AND S.P 34 MAY BE FOLLOWED FOR EXECUTION AND
DETAILING OF WORK.
MANHOLE-M1 MANHOLE-M1 MANHOLE-M1 11. LIVE LOAD AS PER IS: 875-1987 (PT-II) IN DESIGN OF STRUCTURE.
R.C STAIRCASE WITH 12. PLAIN CEMENT CONCRETE SHALL BE USED AS MENTIONED IN
DRAWING.
S.S. HANDRAIL(TYP.) 13. DUCTILE DETAILING OF REINFORCEMENT SHALL BE AS PER
IS:13920 OF LATEST VERSION.
14. THE SBC OF THE SOIL IS 7.5T/m² AT 2.0METER DEPTH AS
REPORTED BY THE CLIENT.
15. GEOT-EXTILE LAYER OF TERRAM 1000 OR EQUIVALENT SHALL BE
LAID AT FGL BEFORE COMMENCING SAND FILLING.
2000 2000 16. 1000 MICRON UPVC SHEET SHALL BE LAID ON MOUND TOP AND

N C N
SLOPE SURFACES OF COMPACTED SAND FILL WITH 200 MM MIN.
LAP AT JOINTS, HIGHER.
17. 75 DIA. G.I PIPE SLEEVE WEEP HOLES LAID WITH DOWNWARD
INCLINATION ARE TO BE PROVIDED AT A HEIGHT 300 MM ABOVE
GROUND AT A SPACING OF 1500 MM FOR DISSIPATING RAIN
WATER DURING CONSTRUCTION PERIOD IN ALL RETAINING
WALLS. THESE WEEP HOLES SHALL BE SEALED WHEN MOUND
CONSTRUCTION IS COMPLETED.
18. SULPHATE RESISTING CEMENT TO BE USED IN CONSTRUCTION.
250 WIDE DRAIN AT
RETAINING WALL TOP (TYP.)
C

37253
RETAINING WALL IN RCC
M30 ALL AROUND (TYP.)
B B

7000 7000
PAVEMENT
ALL AROUND
M M
S.S HANDRAIL
ALL AROUND

NAME OF THE PROJECT :-

CONSTRUCTION OF MOUNDED STORAGE VESSEL


AT TUTICORIN AND THANJAVUR LPG PLANTS
200 WIDE RCC BUILT-IN
DRAIN TROUGHT(TYP.) MANHOLE-M1 MANHOLE-M1 MANHOLE-M1
CLIENT :-

150Ø HALF CUT DOME-A DOME-A DOME-A BHARAT PETROLEUM CORPORATION LTD.
CONCRETE PIPE(TYP.)
DRAWING TITLE :-
150Ø PERFORATED
UPVC PIPE(TYP.) PLAN OF 300MT MSV TANK

D CONSULTANT :-
CREATIVE STUDIO
&
CREATIVE ENGINEERING AND CONSULTANCY
PLOT NO-4769,P.P-18 , PANDAV NAGAR, ROAD NO-4 , TANKAPANI ROAD,

3860
BHUBANESWAR -1 8 , P H .N O-(0674) 2434137, 2433101 ,MOB.No-9937233699
E-MAIL-creative_arch_studio@ yahoo.com
UP
1200 DRG. NO: CES/AR/ 01 DATE: 05.11.2019 SIZE : A3 SCALE:
CONSULTANT : CHECKED AND VETTED :
NTS
230 THK. REV. NO.
1600 X1450 R.C.C TUNNEL RCC PARDI (TYP.)
D IN RETAINING WALL (TYP.) 00
A SHEET NO.
PLAN CHECKED BY: 01