63KV LINE CORE1

IF:Fault Current:Isc(Max)=40000 A
Rated Voltage=63 kV
Class: X , Uk > 600 V
Instrument:7SA61 Burden:0.05 VA
Instrument CT Reqirements:

1 st: Vr(1)=(IF/I1)xaxI2x(Rct+2xRp+Rb)
Parameters : a=1
2 st: Vr(2)=(Iz1/I1)xbxI2x(Rct+2xRp+Rb)
Parameters : b=4
a=1 ,b=4 for Ts<30; a=2 ,b=5 for ts<50;
Rb:Resistant Of Connected Relays:0.1 Ohm
Connected Cable:4 mm²(35 m)
Rp:Total Path Resistance:1.2xL/(56xA)=0.188 Ohm

Distance Fault Calculation:


O.H.L. Length: 70 km
RL+jXL=0.192636+j0.3999757 Ohm/km
X/R(Network)=5.6

Zs=1.1xVn/[sqr(3)xIsc(max)] =1.27 Ohm


Rs=Zs/(1+(X/R)²)½ =0.22 Ohm
Xs=(Zs²-Rs²)½ =1.25 Ohm
Zline=0.85xOHL(km)×(RL+jXL)=11.46184+i23.79855 Ohm
Zzone1=Zline+Zs =11.68184+i25.04855 Ohm
Izone1=1.1xVn/[sqr(3)xZzone1] =1447.624 A

Calculation Result:

Vr(1)= Vr(2)=
Tap I1/I2 Rct Rp Rb Izone1 Vknee Status
(IF/I1)xaxI2x(Rct+2xRp+Rb) (Iz1/I1)xbxI2x(Rct+2xRp+Rb)
1 1200/1 3.2 0.188 0.05 1447.624 600 120.87 17.50 OK

MHT-L-CAL-CN-550-B
63KV LINE CORE1 PAGE: 36/47
63KV LINE CORE2

IF:Fault Current:Isc(Max)=40000 A
Rated Voltage=63 kV
Class: 5P20 , 20 VA
Instrument:7SJ64 Burden:0.05 VA
Instrument CT Reqirements:

CT Requierment Created as K'alfxI2x(Rct+Rb+2xRp)


1 st: Vr(1)=(IF/I1)xI2x(Rct+Rb+2xRp)
CT Requierment Created as K'alfxI2x(Rct+Rb+2xRp)
2 st: Vr(2)=20xI2x(Rct+Rb+2xRp)
Rb:Resistant Of Connected Relays:0.1 Ohm
Connected Cable:4 mm²(35 m)
Rp:Total Path Resistance:1.2xL/(56xA)=0.188 Ohm
VKnee=I2xKAlfx(VA+RctxI2^2)

Calculation Result:

Vknee= Vr(1)= Vr(2)=


Tap IF I1/I2 Rct Rp Rb Burden KAlf Status
I2xKAlfx(VA+RctxI2²) (IF/I1)xI2x(Rct+Rb+2xRp) 20xI2x(Rct+Rb+2xRp)
1 40000 1200/1 7.3 0.188 0.05 20 20 546 257.53 154.52 OK

MHT-L-CAL-CN-550-B
63KV LINE CORE2 PAGE: 37/47
63KV LINE CORE3

IF:Fault Current:Isc(Max)=40000 A
Rated Voltage=63 kV
Class: 0.2Fs5 , 30 VA
Connected Cable:4 mm²(35 m)
Rp:Total Path Resistance:1.2xL/(56xA)=0.188 Ohm

NO. NAME TYPE BURDEN S.C.W


1 NEXUS 1262 E.M 0.0125 100

S.C.W. (Tor) =Min(All Connected SCW)/sqr(Ts)


Where Ts is Backup Operated Time=0.1 s
Fs=5 Is Acuracy Limiting Factor
SCC(Max)=1.1*Fs*(Pi+Pn)/(Pi+Pb) Is Maximum Short Circuit Current(A)
F's Is Short Circuit Withstanding
SCC(Max)<SCW(Tor)
Pi=RctxI2^2
Pn=Burden Of Core
Pb=(Rb+Rp)xI2^2

Tap I1/I2 Pi Pn Pb (Pi+Pn)/(Pi+Pb) SCC (Max) SCW (Tor) 0.25xCT Burden CT Burden All Connected Burden Status

1 600/1 3.1 30 0.201 10.03 55.15 316.228 7.5 30 3.301 Not OK

If the nominal Burden was 10VA the status is OK.

MHT-L-CAL-CN-550-B
63KV LINE CORE3 PAGE: 38/47
63KV LINE CORE4

IF:Fault Current:Isc(Max)=40000 A
Rated Voltage=63 kV
Class: X , Uk > 600 V
Instrument:7SS525,7SS522 Burden:0.1 VA,0.1VA
Instrument CT Reqirements:

1 st: Vr(1)=0.5x(IF/I1)xI2x(Rct+Rb+2xRp)
2 st: Vr(2)=0.5x100xI2x(Rct+Rb+2xRp)
Rb:Resistant Of Connected Relays:0.2 Ohm
Connected Cable:4 mm²(35 m)
Rp:Total Path Resistance:1.2xL/(56xA)=0.188 Ohm

Calculation Result:

Vr(1)= Vr(2)=
Tap I1/I2 Rct Rp Rb Vknee Status
0.5x(IF/I1)xI2x(Rct+Rb+2xRp) 0.5x100xI2x(Rct+Rb+2xRp)
1 2000/1 4 0.188 0.2 600 45.76 54.576 OK

MHT-L-CAL-CN-550-B
63KV LINE CORE4 PAGE: 39/47