Sie sind auf Seite 1von 2

Power Supply Modules

3.8 Power Supply Modules


PS 407 10A; (6ES7 407-0KA01-0AA0) and
PS 407 10A R; (6ES7 407-0KR00-0AA0)

Function
The power supply modules PS 407 10A (standard) and PS 407 10A R
(redundancy-capable, see Section 3.2) are designed for connection to an AC line
voltage of 85 to 264 V or DC line voltage of 88 to 300 V and supply 5 VDC/10 A
and 24 VDC/1 A on the secondary side.

Controls and Displays of the PS 407 10A and thge PS 407 10A R

• Fixing screw
PS 407 10A
1 X 2
2
3 4
407-0KR00-0AA0

INTF

BAF
BATTF
BATTF • LEDs INTF,
5 VDC BAF, BATT1F, BATT2F,
24 VDC
5 VDC, 24 VDC

FMR • FMR pushbutton (Failure Message Reset)

• Standby switch (does not cut off mains)


BATT.1 BATT.2

+ + Under cover
• Battery compartment
– –

BATT. INDIC.
2 BATT
OFF
• Switches BATT. INDIC.
1 BATT
2 BATT, OFF, 1 BATT

• 3-pin plug-in power connector

• Fixing screw

Figure 3-4 Controls and Displays of the PS 407 10A and PS 407 10A R

Power Connection
In contrast to the instructions on installing a power supply module described in the
“S7-400, M7-400 Programmable Controllers, Hardware and Installation” manual,
an AC connector is used for connecting the PS 407 10A and the PS 407 10A R to
both an AC and a DC supply.

S7-400, M7-400 Programmable Controlers Module Specifications


A5E00069467-05 3-21
Power Supply Modules

Polarity Reversal of L+ and L-


The polarity reversal of L+ and L- with supply voltages of between 88 VDC
and 300 VDC has no effect on the function of the power supply. The connection
should be made as described in the instructions in the Installation Manual,
Chapter 6.

Technical Specifications of the PS 407 10A and the PS 407 10A R


Dimensions, Weight, and Cable Cross-Sections Output Variables
Dimensions WxHxD (mm) 50x290x217 Output voltages
Weight 1.36 kg • Rated values 5.1 VDC /24 VDC
Cable cross-section 3 x 1.5 mm2 (litz wire Output currents
with wire end ferrule • Rated values 5 VDC: 10 A
with insulating collar;
use only flexible sheath 24 VDC: 1.0 A
cable) Max. residual ripple 5 VDC: 50 mVSS
Cable diameter 3 to 9 mm 24 VDC: 200 mVSS
Input Rating Max. switching peaks 5 VDC: 150 mVS
Input voltage 24 VDC: 500 mVS
• Rated value 110/230 VDC Idle conditions 5 VDC: 200 mA base
• Permitted range 120/230 VAC load required
88 to 300 VDC, 24 VDC: Idling-proof
85 to 264 VAC (no base load required)
(long-range input) Other Parameters
Protection class in accordance I, with protective
System frequency with IEC 60536 grounding conductor
• Rated value 50 / 60 Hz Overvoltage category II
• Permitted range 47 to 63 Hz
Pollution severity 2
Rated input current
Rated voltage Ue Test Voltage
• At 120 VAC 1.2 A (0.9 A*)
0 < Ue ≤ 50 V 700 VDC
• At 110 VDC 1.2 A (1.0 A*) (secondary <–> PE)
• At 230 VAC 0.6 A (0.5 A*)
150 V < Ue ≤ 300 V 2300 VDC
• At 230 VDC 0.6 A (0.5 A*) (primary <–> PE)
Starting current inrush Buffering of power failures: > 20 ms
• At 230 VAC Peak value 230 A, Complies with the
half-value width 200 µs NAMUR
recommendation NE 21
Peak value 63 A*,
half-value width 1 ms* of August 1998 at a
repeat rate of 1 s
• At 300 VDC Peak value 230 A,
half-value width 200 µs Power input 105 W*

Peak value 58 A*, Power loss 29.7 W


half-value width 1 ms Backup current Max. 100 µA at power
Leakage current < 3.5 mA off
Overvoltage resistance In accordance with DIN Backup batteries (optional) 2 x Lithium AA, 3.6 V /
VDE 0160, curve W2 1.9 Ah
Protective separation Yes
to IEC 61131-2

* PS 407 10A: As of version 5


* PS 407 10A R: As of version 7

S7-400, M7-400 Programmable Controlers Module Specifications


3-22 A5E00069467-05