Beruflich Dokumente
Kultur Dokumente
H.J. Liao
Department of Civil and Construction and Engineering, National Taiwan University of Science and Technology,
Taipei, Taiwan
Chihping Kuo
Department and Institute of Civil Engineering and Environmental Informatics,
Minghsin University of Science and Technology, Hsinchu, Taiwan
ABSTRACT: To use the underground reservoir in Taipei basin as the cooling source for air conditioners, a full
scale test was carried out in the campus of NTUST to cool down a 15 RT (Refrigeration Tons) air conditioner. Two
types of circulating water system were adopted: one is open system; the other is closed system. The open system
pumps up groundwater directly from the underground reservoir. It offers a constant temperature cooling source
for air conditioners (AC units). After doing heat exchange with AC units, the heated groundwater is discharged
back to the reservoir through an open well. Test results showed that the open system has a high cooling capacity
and was capable of keeping a 15 RT AC unit running continuously. Since no groundwater was pumped out
from the reservoir, ground subsidence was no concern for the open system. In comparison, the closed system
discharges the exhaust heat from the AC units through a closed loop pipe which is submerged in the groundwater
inside a well. The heat is transmitted to the underground reservoir by means of the circulating water in the pipe
loop. However, the heat transmission rate of the water saturated ground is limited and it was unable to dissipate
all the exhaust heat from the 15 RT AC unit. As a result, the heat quickly built up around the pipe loop. The
AC unit was shut down after running for only a few hours due to overheat. Obviously, the cooling capacity of
the closed system is much lower than that of the same well system used by the open system. The groundwater
pumping rate of the open system could also be adjusted using a PLC unit based on the actual cooling need of AC
unit to further cut down the running cost of water circulation. Numerical simulation also confirms that the heat
exchange rate of the closed system is much lower than the open system even though the flow rate of groundwater
is capable to carry the same amount of heat away.
521
Figure 1. Schematic diagram of the basin profile.
522
to get the cool from the groundwater without let-
ting the groundwater flow into the air conditioner.
The PHE consisted of 17 heat exchange plates with
the heat exchange area of 1.92 m2 . The heat load of
this PHE unit was ∼80 kW. It was more than the
nominal heat exchange needed for this 15 RT air
conditioner (cooling capacity = 24 kWh). Inside the
PHE unit, the heated water from AC was separated
from the cool groundwater coming from the well
by corrugated stainless steel plates. As the heated
water flowing through the PHE unit, it exchanges heat
with cool groundwater inside the PHE. After that,
the exhaust heat from AC was brought down to the
gravel stratum by the circulating water. Two types of
circulation system were tested here: open system circu-
lates groundwater between aquifer and PHE via wells;
closed type circulation system circulates cooling water
in a closed loop pipe installed in the wells.
523
Figure 6. Temperatures measured from different sensors
during a full day operation.
524
the test well was divided into upper well and lower
well. A 40 m long double pipe with an inner diameter
of 10 cm was installed in the upper well; while a 60 m
long double pipe with an inner diameter of 12.7 cm was
in the lower well. The double pipes in the upper and
lower wells were connected in series manner. Seamless
steel pipe was used for the outer pipe and a PVC pipe of
5 cm in diameter was used as the inner pipe. PVC pipe
was used because it has a better heat isolation property
to minimize the heat exchange inside the double pipe.
Outside the double pipe, there was a PVC pipe of 20 cm
in diameter. It was perforated at the depth of GL −41
to −45 m and GL −52 to −60 m to allow groundwater Figure 8. Temperature curves and heat exchange curves of
flow in and out of the PVC pipe easily. The annular AC for the closed system tested here (AC is off but the water
space between PVC pipe and well wall was back filled circulation pump is on during the cool down period).
with gravel. Only the submerged length of the double
pipe in the well was counted as the effective length for
heat exchange between heated circulating water and
ground/groundwater. At the time of the experiment,
the groundwater water level was at GL −25 m. So the
submerged length (the effective length) of the double
pipe was about total to 50 m.
The schematic diagram for the closed type system
is shown in Figure 7. The same PHE unit as the open
system was used. A pump with 3 hp and flow rate
of 150 liter/min was installed on the well side of the
PHE unit to circulate the water in the closed system to
and fro the ground. No submergible pump was used
Figure 9. Water temperature in and out from the PHE
in the closed system. The heated water flowing out unit (during the cool down period both the AC and water
from the PHE unit was pumped to the PVC inner pipe circulation pump were off).
of the double pipe first and back from the annular space
between PVC pipe and outer steel pipe. On its way more than the heat exchange capacity of the closed
back to PHE unit, the heated water exchanged the heat system, the water temperature will keep increasing
with ground/groundwater through the outer steel pipe. until the AC automatically shut down for safety reason;
The heat load of the PHE unit used here was equal otherwise, the water temperature will only increase to
to 70∼79 kW. But the heat exchange capacity of 50 m a certain value and then remains there.
long submerged pipe was to be determined from this
experiment.
As shown in Figure 8, the water temperatures on the 5 NUMERICAL SIMULATION
AC side and the well side of the PHE unit increased
quickly when AC was running. Obviously, the heat Based on the measured local groundwater flow, a
generated from the AC and the water pump was beyond heat transport model established from the SHEMAT
the heat exchange capacity of this closed circulation (Simulator for HEat and MAss Transport, Clauser
system. After running for about 4 hours, the tempera- 2003) program was used to simulate the heat trans-
ture of the cooling water on the AC side of the PHE unit mission behavior which resulted from two types of
reached about 53◦ C; while the temperature of circulat- circulating water system for AC. 3-D ms consist-
ing water on the well side reached about 46◦ C. The AC ing of 144 × 142 × 3 cells were used. In the cen-
was shut down automatically to protect the compressor ter area (2000 m × 2000 m), each cell represented an
from overheating. After AC shut down, the water circu- area of 1 m × 1 m; outside the center area, each cell
lation pump on the well side stayed running to keep the represented an area of 10 m × 10 m or 20 m × 20 m
water in the closed pipe flowing. Under this circum- depending on the locations. The upper and lower
stance, it took 16.5 hours for the water temperature layers were treated as an aquitard, and the middle
drop back to 30◦ C. But the temperature was unable to layer was a confined aquifer. However, SHEMAT
drop back to the initial 23.5◦ C (i.e., the initial water can only be used in a layer of constant thickness for
temperature when the test started). This was caused the current version. So, a mean value of 30 m was
by the heat generated from the operating water pump. adopted to approximate the thickness of the aquifer.
However, if the water circulation pump was shut down To simulate the flowing groundwater condition in the
and no more heat contributed to the closed system, the Chingmei stratum with the SHEMAT program, a line
temperature was able to drop back to 23.5◦ C after 24 of virtual pumping wells was placed at the effluent
hours (Figure 9). From the phenomenon observed, it boundary of the study area to provide a groundwa-
can be concluded that if the generated heat from AC is ter flow with velocity = 0.005 m/sec. Meanwhile, a
525
line of virtually discharging wells were placed at
the inflow boundary. The parameters used in this
model were as follows: effective porosity = 0.25 and
conductivity = 102 cm/sec (Freeze & Cherry 1979),
thermal capacity = 1.875 MJ/m3◦ K and conductivity
= 1.308 W/m◦ K (Tindall & Kunkel 1999).
526
following conclusions can be drawn from the results
of this test.
1. The 23.5◦ C groundwater pumped up from the well
in the open system can provide a steady cooling
source for a 15 RT AC unit running all day long.
Using the same well, the heat discharged from the
closed system could not keep up with the heat gen-
erated from the AC. The water temperature in the
closed system kept increasing and caused the AC
to shut down due to overheat. The open system can
provide a much better cooling capacity to the AC
than the closed system
2. The submergible water pump in the open system
accounts for a large portion of power consumption.
By adjusting the pumping rate using a PLC unit
based on the cooling need of AC can reduce the
overall power consumption of the system.
3. Due to the slow heat exchange rate between
heated water and surrounding ground/groundwater
at NTUST campus, the cooling capacity of the
closed system is much lower than that of the same
well system used by the open system. An optimal
operation pattern for a closed system and its match-
ing airconditioners can be established in advance
through the temperature curve of circulation water
obtained from the field test or numerical analysis.
4. For the open system, the mineral contents of the
groundwater may cause scale or contamination
problem inside the PHE unit and the circulation
pipe. But it has a better heat dissipation capacity.
In comparison, water in the closed system has no
direct contact with groundwater. No contamination
in the pipeline has been experienced over the period
of this experiment.
REFERENCES
Chen, W.F. 2005.Groundwater in Taiwan. Taipei: Sinobooks.
(in Chinese)
Chen, T.C., Wang, S.Y., and Yen M.C. 2007. Enhancement
of Afternoon Thunderstorm Activity by Urbanization
in a Valley: Taipei”, Journal of Applied Meteorology
and Climatology, American Meteorological Society, 46,
1324–1340.
Clauser, Christoph (Ed.), Numerical Simulation of Reactive
Flow in Hot Aquifers, SHEMAT and Processing SHEMAT
Freeze, R.A. & Cherry, J.A. 1979. Groundwater. Prentice-
Hall. Englewood Cliffs NJ.
Hsieh, C.M., Aramakia, T, & Hanakia, K. 2007. Estimation
of heat rejection based on the air-conditioner use time and
its mitigation from buildings in Taipei City. Building and
Environment, 42, 3125–3137.
Figure 11. 2-D view of simulated short-term temperature Kuo, C.P. & Liao, H.J. 2012. The feasibility of using cir-
change and distribution for the closed type circulation system, culating groundwater as renewable energy sources for
the axis presents distance in meter. air-conditioning in Taipei basin. Renewable Energy 39 (1),
175–182.
Tindall, J.A. & Kunkel, J.R. 1999.Unsaturated Zone Hydrol-
ogy for Scientists and Engineers. Prentice-Hall, London.
6 CONCLUSIONS AND SUGGESTIONS Tsao,Y.S., Lin, C.N., Tan,Y.C. & Mao, A.S. 1985. Simulation
and application of mathematical groundwater model in
A full scale test on two types of cooling water circu- Taipei Basin. Ministry of Economic Affairs. Taipei. (in
lation system (open system and closed system) was Chinese)
carried out to cool down a 15 RT (Refrigeration Wang, C.C. 2007. Heat Exchange Design. Wu-Nan Books
Tons) air conditioner in the campus of NTUST. The Company. (in Chinese)
527