110V DC Station Battery and Charger Calculations

1 Input Data:

System Nominal Voltage = 110 V


Minimum Voltage, Vmin -15% = 93.5 V
Maximum Voltage, Vmax, +10% = 121 V
No of cells = 86
Voltage per Cell during float charging (Vfc) = 1.42 V/cell
Boost Charging Voltage (Vbc) = 1.60 V/cell
Minimum ambient Temperature = 20 °C
Maximum ambient temperature = 50 °C
Nominal Temperature = 20 °C
End Cell Voltage (Vf) = 1.10 V/cell

2 Calculation of Number of Battery Cells

Based on the Vmax criteria, the no. of cells


2.1 = Vmax/ Vbc
required
= 121 / 1.6
= 75.63 Cells

Based on the Vmin criteria, the no. of cells


= Vmin/Vf
required
= 93.5 / 1.1
= 85 Cells

Based on the Vmin criteria the no. of cells


2.2 = 86 Cells
considered
110V DC Station Battery and Charger Calculations

Summary of Load Details

Continuous Load
No. Feeder Total
Equipment Consumption(W) per Remarks
or Qty Consumption
Feeder
(W)

11kV swgr Feeder

Total load of typical feeder (5+2


6 84.7 508.2 As given by ABB swgr
spare)

Bus metering 1 46.4 46.4 As given by ABB swgr

Total Continuous Load in Watts 555 Watts

Total Continuous Load in Amps 5.04 Amps