Megger TTR® Calibration

and Functionality Tests


Introduction. This Application Note be used. To perform a quick simplified
discusses the Calibration and Functionality calibration check, the Megger Calibration
Tests of the Megger TTRs: C/Ns 550503 and Standard Cat No. 550555 may be used. The last
TTR100, their calibration approach and how standard has eleven selectable turns ratio
calibration procedures are implemented. (The settings which cover the turns ratio range from
calibration and functionality tests of the 1:1 to 2000:1. Using these Calibration
Megger Hand-cranked TTRs, C/Ns 550005 Standards will confirm these instruments’
and 550005B, are covered separately.) proper calibration.

Megger TTR test sets provide high accuracy Test Set Functional Test. From time to time
transformer turns ratio readings for the the customers want to check functionality of
widest range of transformer turns ratios in the their test sets in the field. Traditionally, for the
industry. Such wide range of turns ratio transformer turns ratio testers, a customer
measured requires calibration of hardware connected H and X test leads and ran the test.
portion of the test sets to eliminate residual The displayed test results were interpreted as a
inaccuracy essentially caused by the calibration check.
component parameter deviations.
These test sets were designed and optimized
Calibration. A software calibration approach for the transformer turns ratio testing. There are
is used in these three test sets. According to high impedance input and output transformer
this method of calibration, the full range of voltage monitoring circuits. The high
turns ratio is divided by the number of impedance of the monitoring circuits is
calibration boxes. Each calibration box optimized for the accurate transformer turns
contains its own calibration data. These ratio testing.
calibration data are saved in their internal
memories. The calibration data boxes are When performing a functional test, the H and
independent: even if one box is out of X test leads interconnect the input and output
calibration the rest of the calibration data are monitoring circuits (without a transformer
good. being connected). Such connection causes an
impedance mismatch and, as a result of the
A calibration is performed on each new or mismatch, the displayed turns ratio reading is
repaired unit before sending it to a customer. not exactly 1:1 as it may be expected. The
There are special final calibration procedures tested turns ratio may even exceed 0.1 %
which require NIST-traceable test equipment specified accuracy. A customer should be
to be used. As a result of such calibration aware that a functional test is not a real
procedure, each TTR may be NIST certified. transformer turns ratio test. Due to the input
It is recommended to check their calibration and output circuit impedance mismatching, a
at least once every year. This will ensure that functional test reading may be from 0.9980 to
these test sets are functioning and calibrated 1.0020. Functional test readings are in no way
properly over the entire measurement range. representative of the calibration. It merely
shows that the test sets function properly. To
To check the calibration at customer site or in check their calibration, a customer should use
the field, the Megger Calibration Standard the Calibration Standards mentioned above.
Cat.No550055 or equivalent standard should

Valley Forge Corporate Center, 2621 Van Buren Avenue, Norristown, PA 19403
Tel:1-610-676-8500 Fax: 1-610-676-8610 Email: ttr@megger.com
Megger TTR® Calibration
and Functionality Tests
Conclusion. Calibration checks and
Functional tests are two different tests.
Customers should be aware that the
Functional test readings may be out of
specified tolerances for the transformer turns
ratio readings. It may be explained by the
impedance mismatching of the monitoring
circuits. The Functional test readings do not
represent the real transformer test readings or
calibration of the Megger TTR test sets. A
calibration check may be performed at
customer site or in the field by using proper
calibration standards only.