Sie sind auf Seite 1von 3

CONFIDENTIAL INFORMATION INSTRUCTION MANUAL Publication:

OF BASLER ELECTRIC COMPANY, HIGHLAND, IL. FOR 9 2858 00 990


IT IS LOANED FOR CONFIDENTIAL USE, SUBJECT
TO RETURN ON REQUEST, AND WITH THE VOLTAGE REGULATOR © 1997, Basler Electric Co., Highland, IL 62249
MUTUAL UNDERSTANDING THAT IT WILL NOT BE Model: AVC63-4A First Printing June 1994
USED IN ANY MANNER DETRIMENTAL TO THE Revision: D September 1997
INTEREST OF BASLER ELECTRIC COMPANY.
Part Number: 9 2858 00 100 ECA: 16300

BASLER ELECTRIC, BOX 269, HIGHLAND, IL 62249 PHONE 618/654-2341 FAX 618/654-2351
INTRODUCTION diagram to protect wiring from faults before the 3. Adjust the generator frequency to the desired
regulator. A spare fuse is included with the kneepoint frequency.
The AVC63-4A Voltage Regulators are designed
AVC63-4A (internal fuse). It is mounted 4. Slowly adjust the UF ADJ rheostat clockwise
for use on 50/60 Hz brushless generators. The
"piggyback" to the original fuse. Refer to the (CW) until the generator voltage just begins to
regulator includes frequency compensation,
Outline Diagrams. decrease.)
overexcitation shutdown, a solid-state build-up
circuit, and EMI filtering. NOTE
Fuse must be installed per the
ELECTRICAL SPECIFICATIONS
interconnection diagrams to avoid inter-
Dc Output Power:
rupting the field current.
4 Adc at 63 Vdc (252W) maximum continuous,
7 Adc at 100 Vdc (700W) forcing one minute
(at 120 Vac input).
9 Adc at 134 Vdc (1206W) forcing for 10
seconds (at 153 Vac input).
Frequency Compensation Curves
Exciter Field Dc Resistance:
15 ohms, minimum; 100 ohms maximum. OVEREXCITATION SHUTDOWN

Ac Power Input: Overexcitation shutdown is included that


Operating range: 95 Vac to 139 Vac, ±10%, removes the output power if the exciter field
Single phase, 50/60 Hz, Burden: 450 VA. voltage exceeds 95 Vdc. If exciter field voltage
exceeds 95 Vdc ±5%, the regulator automatically
Sensing Input:
removes field current, after a time delay. The
95-139 Vac, ±10%, or 190-277 Vac, ±10%,
time delay is inversely proportional to the
single phase, 50/60 Hz.
magnitude of the detected overvoltage condition.
Regulation Accuracy: At 134 Vdc, the field voltage is removed after
Better than ±1.0% no load to full load. approximately 10 seconds. Refer to the following
Response Time: figure.
Less than 1.5 cycles for ±5% change in sensing
voltage.
EMI Suppression: AVC63-4A Outline Diagram (Top View)
Internal electromagnetic interference filter (EMI
filter).
Overexcitation Shutdown:
Field voltage shuts down after time delay if
exciter field voltage exceeds 95 Vdc, ±5% (See
Overexcitation Shutdown for inverse time delay
curve and description). Typical Time Delay Characteristic Curves
Voltage Build-up: After output power is removed, the regulator can
Internal provisions for automatic voltage build-up be reset by decreasing the input voltage to less
from generator residual voltages as low as 6 than 6 Vac for a minimum of 2 seconds; this may
Vac. be accomplished by stopping the prime mover or
Power Dissipation: by interrupting the regulator input with a reset
15 Watts maximum. switch.
Terminations: STABILITY ADJUST RHEOSTAT (STAB)
1/4 inch "Fast-On" terminals. An internal screwdriver adjustable potentiometer
PHYSICAL SPECIFICATIONS provides adjustment to the response rate of the
generator output voltage to a change in load.
Operating Temperature:
Clockwise rotation of this adjustment provides an
-25 C (-13 F) to +60 C (+140 F). AVC63-4A Outline Diagram (Side View) increase in the response time and therefore
Storage Temperature: decreases the amount of voltage overshoot
V/HZ "CORNER FREQUENCY" SELECTION
-40 C (-40 F) to +85 C (+185 F). (increased stability). Counterclockwise rotation of
AND ADJUSTMENT
Vibration: this adjustment provides a decrease in the re-
Withstands 1.2 Gs at 5 to 26 Hz; 0.036" double For 60 Hz systems, the regulator is preset at the
sponse time (faster response time) and therefore
amplitude at 27 to 52 Hz; and 5 Gs at 53 to 1000 factory for a 55 Hz "corner frequency". For 50 Hz
increases the amount of voltage overshoot
Hz. systems, a 45 Hz "corner frequency" is achieved
(decreased stability).
by connecting a jumper across terminals Hz1
Shock: OPERATION
and Hz2.
Withstands up to 20 Gs in each of three mutually The following system operation procedures
perpendicular axes. The corner frequency can be adjusted by the UF
provide instructions for adjusting the AVC63-4A
ADJ rheostat on the AVR. Clockwise rotation
Weight: voltage regulator. Symptoms resulting from a
results in raising the corner frequency (shifting
10 oz. (0.28 kg) Net. faulty regulator and certain generator system
the curve to the right). To set the UF rheostat:
FUSES problems are included, together with suggested
1. Adjust the UF Rheostat fully CCW. remedies.
Although the AVC63-4A has an internal fuse, it is
recommended that fuses with high interruption 2. Start the generator and set at rated voltage. Complete the following steps before proceeding
capability be installed per the interconnection with the system start-up.
SYSTEM START-UP 2. Adjust the regulator VAR and/or remote VAR,
CAUTION
and the STABILITY Adjust to maximum
Meggers and high potential test equipment 1. Perform preliminary set-up as described in
CCW.
must not be used. Incorrect use of such the above paragraphs.
3. Apply 120 V, 50/60 Hz power to the regulator.
equipment could damage the semi- NOTE
The light bulb should illuminate.
conductors contained in the regulator.
All voltage readings are to be taken with
4. Slowly adjust the regulator VAR control CW.
PRELIMINARY SET-UP an average reading voltmeter.
At the regulation point, the light bulb should
1. Verify that the voltage regulator specifications 2. Start prime mover and bring up to rated extinguish. Small adjustments above and below
conform with the generator system speed. this level should cause the light bulb to go off
requirements. RESULT: Voltage should build up. If not, and on. Note that the light bulb goes on and off
2. Ensure that the regulator wires are as follows: perform Field Flashing. rapidly.
a) If the remote voltage adjust rheostat is not 3. Slowly adjust the regulator VAR CW until the 5. Rotate the STABILITY ADJ fully CW. Now
to be connected, ensure terminals 6 and 7 generator output voltage reaches the nominal adjust the regulator VAR above and below the
are shorted with a jumper. value. If used, adjust the remote VAR to set regulation point. The light bulb should still go
b) If a 55 Hz "corner frequency" for 60 Hz the generator voltage to the exact value off and on, but the transition from off to on
systems is desired, ensure that the Hz1 desired. (and vice versa) should be much slower than
and Hz2 terminals are open. If a 45 Hz in the paragraph above.
RESULT: Voltage should build up to rated value.
"corner frequency" for 50 Hz systems is
If voltage does not build up to rated value, check The following notes (∆) apply to the intercon-
desired, ensure that the Hz1 and Hz2
generator for short or excessive load. nection diagrams:
terminals are shorted together with a
jumper. 4. Check regulator under normal operating and 1. If external pot is not used, short terminals 6
c) For 120 V nominal sensing, ensure that loading conditions. and 7.
terminals V1 and V2 are not connected. RESULT: Voltage regulation should be better 2. Short terminals Hz1 and Hz2 and leave open
For 240 V sensing, ensure that terminals than ±1.0% no-load to full-load. If regulation is for 60 Hz.
V1 and V2 are connected together. not within this range, perform the following steps: 3. Item not supplied by Basler Electric.
3. Ensure the voltage regulator is correctly 1. Voltage reduction under load may be due to 4. For 120 V nominal sensing, make no
connected to the generator system. speed change from no load to full load, connection to terminals V1 and V2.
4. Install the fuses as described in Fuses. causing the frequency compensation (V/Hz)
For 240 V nominal sensing, short terminals V1
5. Set the regulator VAR and external VAR (if circuit to reduce voltage at lower frequencies.
and V2 together.
used) as follows: 2. Replace voltage regulator.
5. Select fuses with high interrupting capacity.
Switch Initial Setting OPERATIONAL TEST
Regulator VAR Fully CCW 1. Connect the test setup as shown in the
following figure, Operational Test. Do not
Remote VAR Centered
apply power. Ensure that the light bulb is rated
for 120 V and is less than 100 W.

Operational Test Connections

Interconnection Diagram, 277/480 Vac Nominal,


3-Phase, 4-Wire, Wye Connection
Interconnection Diagram, 120/240 Vac Nominal, 1-Phase, 3-Wire

Interconnection Diagram, 120/208 Vac Nominal,


3-Phase, 4-Wirre, Wye Connection

Das könnte Ihnen auch gefallen