TECHNICAL REPORT

ON

INFRARED THERMOGRAPHY
FOR
SABAH GAS TERMINAL KOTA KINABALU

by

ASAGA CORPORATION SDN BHD


09th APRIL 2010

Report No: REP-10-152


Revision 0
TAB LE OF CONTENTS

1.0 INTRODUCTION ...... ......................... ........................ ................. 3


2.0 INSTRUMENTATION ....................... .......................... ................ 3
3.0 SUMMARY OF RESULTS ................. .......................... ................ 3
4.0 INFRARED THERMOGRAP HY SURV EY GUIDELINE ................. 4
5.0 EQ UIP MENT LIST ... ......................... ........................ ................. 5
6.0 REFERENCE LIST ... ......................... ........................ ................. 8

2
1.0 INTRODUCTION
Asaga Corporation Sdn Bhd was requested to perform an infrared
thermographic survey for Sabah Gas located within the compound. The survey was
performed on the 16th & 17th March 2010, and was assisted by representative from the
Maintenance & Facilities Department.
The prime objective of this inspection was to locate and identify areas of
abnormal heating which existed in electrical equipment in an on-line/on-load
condition at time of survey and accessible to the camera field of view.

2.0 INSTR UMENTATION


The survey was performed using a Thermoteknix VisIR infrared
thermography camera. All thermal images presented in the following report were
obtained using this camera.

3.0 SUMMARY OF RESULTS


These following faults were detected during the survey and are tabulated as
follows:

Thermogram
Equipment Fault Type Fault Status
No.
2TSM- Neutral Cable 567-
TR-01 UPS 7650 No 2 MINOR
Termination

Table 1: Summary of Faults

3
4.0 INF RARED THERMOGRAPHY SU RVEY
GU IDELINE
To date, there is no governing body or organization that has come up with an
international standard for the acceptance of temperature profile in infrared
thermographic technology. As a rule of thumb, the following is temperature
difference guideline used for condition acceptance.

Areas of fault which, with continuous


100C – 190C monitoring, will probably be safe and failure free 1. MINOR
within 6 months.

Areas of fault deemed to be of serious in nature


200C – 350C 2. INTERMEDIATE
with repairs required as soon as possible (ASAP)

Areas of fault deemed to be of serious in nature.


Immediate shutdown and repair of equipment
>35 0C 3. SEVERE
would be required to avert fire or catastrophic
failure.

Table 2: Infrared Survey Guideline

4
5.0 EQUIPMENT LIST

These are the list of equipments that were inspected. Each item that has been
identified as potential problem is marked in Red bold:

No Location Panel List Good Bad Remarks


1. Bilik LV Switch Panel L6 – Incoming Feeder ABC 7600C √ Ref 1
2. Room, Ground Panel L5 – GD 7500 √
3. Floor Panel L4 – DB 7609 √ Ref 2
4. MCC 7600 Panel L3 – DB 7604 NOP
5. Panel L2 – PM 5310A √
6. Panel L1 – Incoming Feeder ACB 7600A √
7. Panel L/R – ACB 7600D √ Ref 3
8. Panel L/R – Bus Termination √
9. Panel R1 – Central Unit √
10. Panel R2 – DB √ Ref 5
11. Panel R3 – DB 7604 NOP
12. Panel R4 – PM 3520B √ Ref 4
13. Panel GE – 7510 √
14. Panel R6 – Incoming Feeder ACB 7600B √ Ref 6
15. Panel R7 √
16. Panel R8 √
17. Panel R9 √
18. Panel R10 √ Ref 12
19. Panel R11 √
20. Panel L11 √ Ref 9

5
No Location Panel List Good Bad Remarks
21. Panel L10 √ Ref 13
22. Panel L9 √ Ref 8
23. Panel L8 √ Ref 7
24. Panel L7 √ Ref 11
25. Bilik LV Switch, Panel A √
Room, Ground Floor Panel B √ Ref 14,10
26. MTG 500 Switch Board Panel C √
27. Panel D √ Ref 15
Panel E √ Ref 16
28. Panel F NOP
29. DV 7702 Charger DV 7720 A Charger No 1 √
30. DV 7720B Charger No 2 √ Ref 18
31. DV 7720 DC 110V DB √
32. DU 7701 Charger DU 7701A Charger No 1 √
33. DU 7701B Charger No 2 √ Ref 19
34. DU 7701A DC 24V DB √
35. DU 7700 Charger DU 7700A Charger No 1 √
36. DU 7700B Charger No 2 √
37. DU 7700A DC 24 V DB √
38. UPS 7650 UPS No 1 NOP
39. UPS No 2 Ref 13,20

&TR-01
40. ALT Main Cubicle √

Legend

NOP - Not Operating

NA - Not Applicable / Not Accessible

* - Equipment was inspected but load was less than 30% of maximum rating, hence
the
scan result may not be reliable.

6
COMPONENT: 2TSM- NEUTRAL CABLE 567
Equipment UPS 7650 No 2
Created on 3/16/2010 6:27:25 PM
Location Bilik LV Switch Room

Celsius
100.00 46.08

40.00

30.00

20.00

10.00
Area 1
Max. Avg. Min.
0.00
36.09 29.20 25.49
-20.00 -2.79
Thermoteknix VisIR 6:27:25 PM 3/16/2010 e : 1.00 Bg : 24.95°C

Reference Image Infra-red Image

TR-01
Condition Minor
Spot Max Temp. 36.09°C
Emissivity 1.00
Background 25.0°C
Referance Temp 28°C
Difference Temp 8.0°C

Analysis

Probable Cause Likely poor contact at the termination neutral cable

Recommended Action Suggest re-tighten and cleaning the termination at the


next maintenance schedule.

7
6.0 R EF ERENCE LIST

Customer Sabah Gas Kota Kinabalu Location LV Switch Room


th th
Date 16 & 17 March 2010 Air temp/Emissivity ~30.00 / 1.00

Reference 1
Celsius
55.00 35.80

34.00
32.00
30.00
28.00
26.00
Area 1
24.00 Max. Avg. Min.
22.00 26.35 23.71 22.87

0.00 20.24
Thermoteknix VisIR 9:24:57 PM 3/15/2010 e : 1.00 Bg : 24.95°C

Reference 2
Celsius
70.00 44.42

40.00

35.00

30.00
Area 1
25.00 Max. Avg. Min.
37.44 28.40 24.63

-5.00 19.98
Thermoteknix VisIR 9:27:57 PM 3/15/2010 e : 1.00 Bg : 24.95°C

Reference 3
Celsius
90.00 52.16
50.00

45.00

40.00

35.00
Area 1
30.00 Max. Avg. Min.
25.00 60.25 30.32 25.92

-15.00 18.85
Thermoteknix VisIR 9:34:07 PM 3/15/2010 e : 1.00 Bg : 24.95°C

8
Reference 4

Celsius
42.00 29.86

28.00
26.00
24.00 Area 1
22.00 Max. Avg. Min.
21.31 20.46 19.50
20.00
6.00 18.75
Thermoteknix VisIR 10:41:24 PM 3/15/2010 e : 1.00

Reference 5
Celsius
90.00 52.16
50.00
45.00

40.00
35.00
Area 1
30.00
Max. Avg. Min.
25.00 39.52 30.67 25.27

-15.00 18.85
Thermoteknix VisIR 9:36:07 PM 3/15/2010 e : 1.00 Bg : 24.95°C

Reference 6
Celsius
90.00 55.65

50.00

45.00

40.00

35.00
Area 1
30.00 Max. Avg. Min.
46.26 26.60 24.19
25.00
-15.00 22.33
Thermoteknix VisIR 9:53:58 PM 3/15/2010 e : 1.00 Bg : 24.95°C

9
Reference 7
Celsius
90.00 55.65

50.00

45.00

40.00

35.00
Area 1
30.00 Max. Avg. Min.
45.37 25.35 23.31
25.00
-15.00 22.33
Thermoteknix VisIR 9:55:26 PM 3/15/2010 e : 1.00 Bg : 24.95°C

Reference 8
Celsius
55.00 34.98
34.00
32.00
30.00
28.00
26.00
Area 1
24.00
Max. Avg. Min.
22.00 24.63 23.14 20.86

0.00 19.42
Thermoteknix VisIR 10:21:19 PM 3/15/2010 e : 1.00 Bg : 24.95°C

Reference 9
Celsius
55.00 34.98
34.00
32.00
30.00
28.00
26.00
Area 1
24.00 Max. Avg. Min.
22.00 25.49 23.53 21.76

0.00 19.42
Thermoteknix VisIR 10:22:03 PM 3/15/2010 e : 1.00 Bg : 24.95°C

10
Reference 10
Celsius
85.00 55.83

50.00

45.00

40.00
Area 1
35.00 Max. Avg. Min.
43.03 38.61 30.32

0.00 29.15
Thermoteknix VisIR 5:56:04 PM 3/16/2010 e : 1.00 Bg : 24.95°C

Reference 11
Celsius
42.00 29.86

28.00

26.00

24.00

22.00 Area 1
Max. Avg. Min.
20.00 21.31 20.46 19.50

6.00 18.75
Thermoteknix VisIR 10:41:24 PM 3/15/2010 e : 1.00 Bg : 24.95°C

Reference 12
Celsius
48.00 32.00

30.00

28.00

26.00

24.00

22.00

20.00 Area 1
Max. Avg. Min.
21.09 20.23 19.50
2.00 17.65
Thermoteknix VisIR 10:50:36 PM 3/15/2010 e : 1.00 Bg : 24.95°C

11
Reference 13
Celsius
60.00 40.74

35.00

30.00 Area 1
Max. Avg. Min.
25.49 24.90 23.97
25.00

5.00 22.96
Thermoteknix VisIR 10:58:41 PM 3/15/2010 e : 1.00 Bg : 24.95°C

Reference 14
Celsius
75.00 48.30

45.00

40.00

35.00

30.00 Area 1
Max. Avg. Min.
25.00 35.70 28.37 25.49

-10.00 21.62
Thermoteknix VisIR 5:34:46 PM 3/16/2010 e : 1.00 Bg : 24.95°C

Reference 15
Celsius
75.00 48.30

45.00

40.00

35.00

30.00 Area 1
Max. Avg. Min.
25.00 32.35 26.85 24.41

-10.00 21.63
Thermoteknix VisIR 5:36:57 PM 3/16/2010 e : 1.00 Bg : 24.95°C

12
Reference 16
Celsius
80.00 48.57

45.00

40.00

35.00
Area 1
30.00
Max. Avg. Min.
32.95 28.54 24.84
25.00

-5.00 21.89
Thermoteknix VisIR 5:41:55 PM 3/16/2010 e : 1.00 Bg : 24.95°C

Reference 17
Celsius
140.00 77.28

70.00

60.00

50.00

40.00
Area 1
30.00 Max. Avg. Min.
54.61 34.81 25.92
20.00
-20.00 16.00
Thermoteknix VisIR 5:58:48 PM 3/16/2010 e : 1.00 Bg : 24.95°C

Reference 18
Celsius
130.00 62.10

50.00

40.00

30.00
Area 1
20.00 Max. Avg. Min.
47.49 23.55 22.21
10.00

-20.00 0.82
Thermoteknix VisIR 6:06:07 PM 3/16/2010 e : 1.00 Bg : 24.95°C

13
Reference 19
Celsius
220.00 113.71

100.00

80.00

60.00 Area 1
Max. Avg. Min.
40.00 99.30 48.42 28.04

20.00

-20.00 9.27
Thermoteknix VisIR 6:19:06 PM 3/16/2010 e : 1.00 Bg : 24.95°C

Reference 20
Celsius
100.00 48.63

40.00

30.00
Area 1
Max. Avg. Min.
20.00 34.73 27.39 24.19

10.00

-20.00 4.19
Thermoteknix VisIR 6:26:13 PM 3/16/2010 e : 1.00 Bg : 24.95°C

14