MATERIAL SUMMARY MATERIAL SUMMARY NOTES

(for 1-OFF installation only) 25 (for 1-OFF installation only)


1. EARTHING & BONDING SHALL BE MADE IN ACCORDANCE WITH MOTS 10,
APPENDIX B EARTHING AND BONDING WITH IEC 60364-5-54 AND EN 62204.
ITEM DESCRIPTION QTY UNIT ITEM DESCRIPTION QTY UNIT
5mm
CABLE LUG, TUBULAR TYPE, 600/1000 V, TINNED FLAT BAR 50 x 5 mm thk WITH 11mm 2. TYPICAL EARTHING DETAILS TO BE AS PER MOTS-10 ATTACHMENT 1.
LG01 A/R EA 1526 0.05 LM
COPPER, UNINSULATED, COMPRESSION TYPE, DIA HOLE (AISI 316 SS MATERIAL)
ONE HOLE, STANDARD BARREL, 10 MM2 , M10 STUD. 3. SKIDS/STEEL PEDESTAL, LIGHTING POLES, ETC DIRECTLY WELDED TO STEEL
(10 MM2 CABLES TOGETHER) DECK/ COLUMNS NEED NOT BE PROVIDED WITH SEPARATE PROTECTIVE EARTH
WELD ON STRUCTURAL TOTAL NO. OF INSTALLATION = 1No. BONDING CONDUCTOR.
CABLE LUG, TUBULAR TYPE, 600/1000 V, TINNED
ED-01

LG02 A/R EA STEELWORK OR


COPPER, UNINSULATED, COMPRESSION TYPE, 1526 1

DOUBLING PLATE ON 4. STEEL SURFACES SHALL BE THOROUGHLY CLEANED BEFORE MAKING A EARTHING
ONE HOLE, STANDARD BARREL, 16 MM2 , M10 STUD. MAIN STRUCTURE CONNECTION. DRILLED HOLES AND FIELD CUTS SHALL BE PROTECTED WITH AN
(16 MM2 CABLES TOGETHER) DRILL 11mmØ HOLE APPLICATION OF ZINC-CHROMATE RICH.
LG03 CABLE LUG, TUBULAR TYPE, 600/1000 V, TINNED A/R EA
COPPER, UNINSULATED, COMPRESSION TYPE, 5. ALL EXPOSED EARTH CONNECTIONS AND TIES SHALL BE COATED WITH A SUITABLE
ONE HOLE, STANDARD BARREL, 25 MM2, M10 STUD. CORROSION PREVENTIVE COATING (3M SCOTCH ELECTRICAL COATING OR EQUAL)
(25 MM2 CABLES TOGETHER) FOLLOWING FINAL INSTALLATION AND TESTING.

50
NOTE-10
LG04 CABLE LUG, TUBULAR TYPE, 600/1000 V, TINNED A/R EA 6. EQUIPMENT EARTHING CONDUCTOR IN MOTOR FEEDER CABLE TO BE EARTHED
COPPER, UNINSULATED, COMPRESSION TYPE, TO EARTHING BOLT INSIDE THE MOTOR TERMINAL BOX. FIELD SHALL EXERCISE
ONE HOLE, STANDARD BARREL, 50 MM2, M10 STUD.
(50 MM2 CABLES TOGETHER)
50 CARE IN SELECTING LOCATIONS FOR WELDING.

LG05 CABLE LUG, TUBULAR TYPE, 600/1000 V, TINNED A/R EA 7. EARTH PADS AND DRILLED HOLES IN EQUIPMENT AND TO SUPPORT STRUCTURES
COPPER, UNINSULATED, COMPRESSION TYPE, FOR EARTHING PURPOSES. SHARP BENDS SHALL BE AVOIDED IN ROUTING OF ALL
ONE HOLE, STANDARD BARREL, 70 MM2 , M10 STUD. GROUNDING.
(70 MM2 CABLES TOGETHER)
8. CONDUCTORS PRECAUTIONS SHOULD BE TAKEN TO PREVENT PHYSICAL DAMAGE
LG06 CABLE LUG, TUBULAR TYPE, 600/1000 V, TINNED A/R EA TO INSULATED CABLE JACKET BY SHARP METAL EDGES.
COPPER, UNINSULATED, COMPRESSION TYPE, ONE ED-18 EARTH LUG
HOLE, STANDARD BARREL, 120 MM2 , M10 STUD. 9. SHRINK SLEEVING TO BE USED OUTSIDE PANEL BETWEEN ALL LUGS AND
(120 MM2 CABLES TOGETHER)
INSULATIONS. SLEEVING COLORS AS FOLLOWS: GROUNDING - YELLOW /
LG07 CABLE LUG, TUBULAR TYPE, 600/1000 V, TINNED A/R EA GREEN POWER - BLACK.
COPPER, UNINSULATED, COMPRESSION TYPE, ONE
HOLE, STANDARD BARREL, 185 MM2 , M10 STUD. 10. ALL EARTH/BONDING CONNECTION TO BE COVERED WITH 3M SCOTCH COTE
(185 MM2 CABLES TOGETHER) ELECTRICAL COATING.
CABLE LUG SIZED TO
CONTAIN 2 EARTH
MATERIAL SUMMARY 2
WIRES ED-01

(for 1-OFF installation only) 11. ALL OUTDOOR GLANDS SHALL BE DELUGE PROOF IP 66.
S-BT-ER M10 ES04 2

12. WELDING OF EARTH BOSS OR STUD ACCORDING TO MOTS-12.


ED-01 ED-01 ED-01 ED-01 ED-01 ED-01

LG01 LG02 LG03 LG04 LG05 LG06 TOTAL NO. OF INSTALLATION = 1No.
** ITEM DESCRIPTION QTY UNIT
2 2 2 2 2 1

** LUGS SHOWN FOR REFERENCE ONLY, FOR QUANTITIES, UPPER NUT 13. ALL DIMENSIONS ARE IN MM UNLESS OTHER WISE SPECIFIED.
HILTI : MADE OF STAINLESS STEEL,THREADED
REFER RELEVANT DETAIL DRAWING.
LOCK WASHER
ED-01 ED-01

SCREW-IN STUD, THREAD DIAMETER 10 MM, 14. FOR EQUIPMENT WITHOUT EARTH STUD, THE EARTHING CABLE SHALL BE
CABLE LUG ES04 01 EA
8304 2

8305 2

** 2 NUTS AND 1 LOCK WASHER WITH ASSOCIATED TERMINATED AT THE EARTH TAG OF THE CABLE GLAND.
COMPONENTS. (MODEL NO. S-BT ER MW10)
8304 CABLE LUG, TUBULAR TYPE, 600/1000 V, TINNED A/R EA
≥6 MM THK COPPER, UNINSULATED, COMPRESSION TYPE,
BASE ONE HOLE, STANDARD BARREL, 10 MM2 , M10 STUD.
MATERIAL DISC
8305 CABLE LUG, TUBULAR TYPE, 600/1000 V, TINNED A/R EA
COPPER, UNINSULATED, COMPRESSION TYPE,
ONE HOLE, STANDARD BARREL, 16 MM2 , M10 STUD.
LEGEND
P001 PAINT : CORROSIVE PREVENTIVE COATING A/R LTR
ED-32 HILTI STANDARD EARTH BOSS
ED-17 TWO CABLES IN SAME LUG
TOTAL NO. OF INSTALLATION = 1 No.
BOLTED EARTH CONNECTION
** LUGS SHOWN FOR REFERENCE ONLY, FOR QUANTITIES, REFER RELEVANT
EARTHING LAYOUT DRAWING.

EARTHING CABLE

MATERIAL SUMMARY MATERIAL SUMMARY XXXX


ED-01

MATERIAL INDENTIFICATION MARKER


(for 1-OFF installation only) (for 1-OFF installation only)
EARTHING DETAIL
ITEM DESCRIPTION QTY UNIT ITEM DESCRIPTION QTY UNIT DETAIL NUMBER

EC05 UX 0.6/1KV UNARMOURED, TINNED ANNEALED A/R LM EC05 UX 0.6/1KV UNARMOURED, TINNED ANNEALED A/R LM ED-XX
STRANDED CIRCULAR COPPER CONDUCTOR, STRANDED CIRCULAR COPPER CONDUCTOR,
OUTER SHEATH FLAME RETARDANT, OUTER SHEATH FLAME RETARDANT, *-000X
HALOGEN-FREE AND MUD RESISTANT HALOGEN-FREE AND MUD RESISTANT DETAIL DRAWING NUMBER
THERMOSET COMPOUND, SHF2, UNARMOURED, THERMOSET COMPOUND, SHF2, UNARMOURED,
GREEN YELLOW 1C X 70 SQMM GREEN YELLOW 1C X 70 SQMM ABBREVIATIONS:

8309 CABLE LUG, TUBULAR TYPE, 600/1000 V, TINNED 4 EA (ED-01, STANDARD EARTH BOSS) QUANTITY A/R AS REQUIRED
4 EA
COPPER, UNINSULATED, COMPRESSION TYPE, SHALL BE INCLUDED IN ED-01 MTO EA EACH
ONE HOLE, STANDARD BARREL, 70 MM2 , M10 STUD. LM LENGTH IN METERS
8309 LUG: TERMINAL; 70 SQMM (M10) STUD, 4 EA
(ED-01, STANDARD EARTH BOSS) QUANTITY 4 EA 1-HOLE CRIMP, TINNED COPPER
SHALL BE INCLUDED IN ED-01 MTO
(ED-03, CABLE LADDER & CABLE TRAYS) 4 EA
QUANTITY SHALL BE INCLUDED IN
TOTAL NO. OF INSTALLATION = 1No. ED-03 MTO

* INDICATES DRAWING NUMBER PREFIX TO BE TWBY-07-10048


TOTAL NO. OF INSTALLATION = 1No.

TANK/HEAT EXCHANGER * INDICATES DRAWING NUMBER PREFIX TO BE TWBY-07-10048

TWYY-07-10001-0001 OVER ALL EARTHING SINGLE LINE DIAGRAM TYRA WEST


DK-TYYY-ELE-PHL-018-10000 EARTHING DESIGN PHILOSOPHY FOR WHRP

Drawing no. Reference dwgs.

BRIDGE BD-BA
(SIMILAR 4 PLACES) ED-16

ED-16

EC05 A/R

EC05 A/R

ED-01
Digitally signed by
Venkatavijayak
Chandrasekar Chandrasekar,
Digitally signed by Digitally signed by
Kumaraswamy, Kumaraswamy,

(TYP) 2 26-JUL-2019 ISSUED FOR CONSTRUCTION


Balakrishnan Venkatavijayakumar, Seethamsetty
umar, DN: cn=Venkatavijayakumar, Janakiraman
, Balakrishnan +05'30'
Date: 2019.07.26 17:34:35
Seethamsetty
Seethamsetty
Date: 2019.07.26 17:41:16 +05'30'
Janakiraman Date: 2019.07.29
10:10:45 +05'30'

*-0001 1 14-MAY-2019 DAR APA DRK ISSUED FOR CONSTRUCTION


NOTE 3 0 13-DEC-2018 DAR APA DRK ISSUED FOR CONSTRUCTION
(SIMILAR 4 PLACES)
A 26-SEP-2018 DAR APA DRK ISSUED FOR REVIEW

ED-01 Rev Date Drawn Chkd Appr Description

*-0001 CONTRACT NUMBER


SKID BEAM
TOP OF DECK
McDERMOTT, INC 8600006110
(BOTH SIDES OF BRIDGE)

STRUCTURE BRIDGE
SUPPORT PLTF. SIDE
EPC CONTRACT FOR TYRA REDEVELOPMENT PROJECT - WHRP
Title

ED-20 TYRA WEST, PLATFORM B


ED-19 BRIDGE
VERTICAL TANK OR VESSEL EARTHING AND BONDING DETAILS
TYPICAL EARTHING AND BONDING

Scale Size Drawing no. Rev.


NTS A1 TWBY-07-10048-0005 2