ABBREVIATIONS SYMBOLS
LIGHTNING SYSTEM SYMBOLS
DRILLED GROUND ROD LS LIMIT GENERAL ELECTRICAL DRAWING NOTES:
SWITCH
G GROUND GRID
A H P FS 1. EXACT EQUIPMENT CONDUIT CONNECTIONS ARE TO BE DETERMINED BY THE
DRIVEN GROUND ROD FLOW SWITCH AIR TERMINAL
AFF ABOVE FINISHED FLOOR HOA HAND-OFF-AUTOMATIC or PH PHASE ELECTRICAL INSTALLER BASED ON ACTUAL FIELD LOCATION OF EQUIPMENT. INSTALL
CONDUIT IN ACCORDANCE WITH SPECIFICATION SECTION 16110.
S SINGLE POLE SWITCH (P) PILOT
AC ALTERNATING CURRENT HZ HERTZ TR PNEUMATIC TIMING RELAY PS PRESSURE SWITCH 2. ALL PENETRATIONS THROUGH NON-FIRED RATED WALLS, CORE HOLE AND SEAL
LIGHT EARTH TERMINAL AROUND CONDUIT WITH NON-SHRINK GROUT. ANY PENETRATIONS THROUGH
AS AMMETER SWITCH HP HORSEPOWER P/I PNEUMATIC TO CURRENT 3 THREE-WAY EXTERIOR WALLS SHALL BE SEALED WATER TIGHT WITH SILICONE MASONRY
TRANSDUCER SWITCH VS VIBRATION SENSOR SEALANT. ALL PENETRATIONS THROUGH FIRE RATED WALLS SHALL BE SEALED WITH
ANN ANNUNCIATOR 4 FIRE STOPPING PER SPECIFICATION SECTION 16120 AND DETAILS ON SHEET E-307.
FOUR-WAY CABLE TURNING DOWN
( )P POLES ( ) NO OF POLES 3. EVERY EFFORT HAS BEEN MADE TO IDENTIFY REMOTE ITEMS TO BE CONNECTED BY
I SWITCH M MOTOR OPERATED
AA AUTOMATIC ALTERNATOR M OR MSS MOTOR STARTING SWITCH WITH OVERLOAD THE ELECTRICAL CONTRACTOR, EITHER IN THE ELEMENTARIES OR ON THE
ID IDENTIFICATION NUMBER PVC POLYVINYL CHLORIDE CONDUIT PROTECTION DAMPER SCHEDULES. HOWEVER, NOT ALL OF THE REMOTE DEVICES MAY HAVE BEEN SHOWN
MX AUXILIARY RELAY ON THE ELECTRICAL DRAWING. SEE DRAWINGS OF RESPECTIVE CONTRACTS TO
IF INFRARED HEATER PT POTENTIAL TRANSFORMER
M OR MMS
MANUAL MOTOR STARTER
TELEPHONE SYSTEM SYMBOLS LOCATE OR CONFIRM THEIR LOCATION.
S
CS CONTROL 4. IN GENERAL, ALL WORK SHOWN ON THE ELECTRICAL DRAWINGS IS THE WORK OF
I/O INPUT/OUTPUT PC( )-( ) POWER AND CONTROL CIRCUIT DUPLEX STATION THE ELECTRICAL TRADE UNLESS SPECIFICALLY STATED OTHERWISE. WORK FOR
B PHONE JACK (MOUNT AT 12" AFF,
( ) MCC ID/ ( ) ID RECEPTACLE THIS CONTRACT IS GENERALLY USING HEAVY LINE WEIGHTS, WITH THE WORK OF
SINGLE RECEPTACLE FOR FUTURE DESK PHONE BY
BKR BREAKER IC INTERRUPTING CAPACITY QUAD UTILITY POLE OWNER) OTHER CONTRACTS SHOWN WITH LIGHTER LINE WEIGHTS AND/OR CALLED OUT ON
P( )-( ) POWER CIRCUIT ( ) MCC RECEPTACLE THE PLANS.
ID/ ( ) ID W PHONE JACK (MOUNT AT 54" AFF, FOR 5. ALL ELECTRICAL WORK IN CLASS I, DIVISION 1, GROUP D AREAS SHALL BE IN STRICT
IT INTERCHANGEABLE TRIP
FUTURE WALL-MOUNTED PHONE BY ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE ARTICLE 501 AND THE
C OR INSTANTANEOUS TRIP
OWNER)
PF-( ) POWER FEEDER ( ) ID SPECIAL RECEPTACLE WITH UTILITY POLE W/STREET CONTRACT SPECIFICATIONS. ALL MATERIALS PROVIDED IN SUCH AREAS SHALL BE
CL CENTERLINE IMC INTERMEDIATE STEEL CONDUIT (CIR. NO.) DESIGNATION LIGHT LISTED AS SUITABLE FOR THE ENVIRONMENT IN WHICH THEY ARE INSTALLED. REFER
PRE POWER ROOF EXHAUSTER
L6-30R D (D INDICATES TWO JACKS, RJ11 & TO THE ROOM SCHEDULE ON SHEETS E-101 FOR AREA CLASSIFICATIONS.
CL 2 CHLORINE ETM RJ45, ON SINGLE WALLPLATE) 6. FASTENERS ON THE UNDERSIDE OF PRECAST/PRESTRESSED CONCRETE MEMBERS
P PRESSURE ELAPSED TIME METER
J (PLANKS OR DOUBLE TEES) WHICH SERVE FOR DIRECT ATTACHMENT OR FOR
CF(P OR L) CLOSE ON FALLING T THERMOSTAT TYPE RJ-31X JACK FOR FIRE ALARM HANGERS OF ELECTRICAL EQUIPMENT , CONDUIT, CHANNEL, ETC. MAY NOT BE
JB PS PRESSURE SWITCH X
(PRESSURE OR LEVEL) JUNCTION BOX DACT SIGNALS DRILLED OR SHOT IN THE VICINITY OF THE PRESTRESSING TENONS. THIS MEANS THAT
FLEXIBLE CONDUIT
PWV POWER WALL VENTILATOR FASTENERS AT CONCRETE PLANKS CAN ONLY BE PLACED AT THE JOINTS BETWEEN
CR(P OR L) CLOSE ON RISING SA CONTINUOUS RATING TELEPHONE AUXILIARY RINGER UNITS. CONTRACTOR SHALL PROVIDE INTERMEDIATE SUPPORTS NEEDED TO
(PRESSURE OR LEVEL) WIRES CONNECTED T
K PLC PROGRAMMABLE LOGIC MCP ACCOMPLISH THIS.
CONTROLLER MOTOR CIRCUIT
CH CONVECTION HEATER KVA KILOVOLT AMPERE
PROTECTOR-TRIP RANGE SETTING WIRES NOT CONNECTED
COMPT COMPARTMENT KV KILOVOLT BASED ON ACTUAL MOTOR FULL
Q LOAD AMPS
COND CONDUCTOR KVAR KILOVOLT AMPERES REACTIVE CURRENT LIMITING
QTY QUANTITY CONTACTOR TYPE AND NEMA SIZE FUSE
AS REQUIRED FOR MOTOR FULL
CDT CONDUIT KW KILOWATT SWITCH WITH CURRENT LIMITING
LOAD AND CHARACTERISTICS
FUSE
GENERAL NOTES:
C-( ) CONTRACT-( ) ID OVERLOAD HEATERS OR RELAY
L R START
MOLDED CASE CIRCUIT BREAKER 1. THIS IS A STANDARD SYMBOL LIST, SOME SYMBOLS MAY NOT APPEAR ON THE
CC-( ) CONTROL CONDUIT-( ) ID MOMENTARY OPEN PUSHBUTTON ACCOMPANYING DRAWINGS.
L LEVEL RECPT RECEPTACLE DS
(NORMALLY OPEN) DISCONNECT SWITCH 2. REFER TO SPECIFICATIONS FOR DETAILED REQUIREMENTS.
CPT CONTROL POWER TRANSFORMER STOP 3. PLAN & SECTION SYMBOLS MAY ALSO BE USED ON DIAGRAMS.
LP( )-( ) LIGHTING CIRCUIT ( ) R RED FIRE ALARM SYSTEM SYMBOLS 4. ON ONE-LINE DIAGRAMS FOR 3-PHASE SYSTEMS, DEVICE QUANTITY = 3 UNLESS
MOMENTARY CLOSED PUSHBUTTON
CR-( ) CONTROL RELAY-( ) ID OTHERWISE NOTED.
LP( ) LIGHTING PANELBOARD RTU REMOTE TERMINAL UNIT (NORMALLY CLOSED) 10 SQUIRREL CAGE INDUCTION
MOTOR AND HP HP, VARIES 5. WIRE SIZES SHOWN ARE AWG. (AMERICAN WIRE GAUGE)
I/I CURRENT TO CURRENT 6. FOR ADDITIONAL ABBREVIATIONS, REFER TO THE GENERAL DRAWINGS.
LS LIMIT SWITCH RSC RIGID STEEL CONDUIT HEAT DETECTOR
TRANSDUCER MAINTAINED CONTACT PUSHBUTTON 7. ALL WORK PERFORMED BY THE CONTRACTOR ON THIS PROJECT SHALL BE PERFORMED
RMS ROOT MEAN SQUARE WITH MECHANICAL INTERLOCK 5 RESISTANCE LOAD CR= CORROSION RESISTANT IN STRICT ACCORDANCE WITH THE CONTRACT DRAWINGS , SPECIFICATIONS, AND
I/P CURRENT TO PNEUMATIC LC LOUVER CONTROLLER
XP= EXPLOSION PROOF APPLICABLE CODES.
TRANSDUCER H
O
A
LM LOUVER MOTOR DRAW OUT FEATURE
CT CURRENT TRANSFORMER THREE POSITION MAINTAINED SMOKE DETECTOR
S XOO CONTACT SELECTOR SWITCH D= DUCTSMOKE DETECTOR
M SS SELECTOR SWITCH OOX
TRANSFORMER
D F FLAME DETECTOR
M MAIN CONTACTOR DESIGN CRITERIA:
DP DIFFERENTIAL PRESSURE SPDT SINGLE POLE, DOUBLE THROW F O
S A
MCM or kcmil THOUSAND CIRCULAR MILS GROUND PULLSTATION THE DESIGN TO PROVIDE A POWER DISTRIBUTION AND LIGHTING SYSTEM FOR THE CSO
DC DIRECT CURRENT SHLD TW PR SHIELDED TWISTED PAIR P CR= CORROSION RESISTANT
XOOO STORAGE FACILITY WILL BE GOVERNED BY, BUT NOT LIMITED TO THE FOLLOWING
MF-( ) MAIN FEEDER-( ) ID FOUR POSITION XP= EXPLOSION PROOF
DS DISCONNECT SWITCH SV SOLENOID VALVE REQUIREMENTS:
MAINTAINED CONTACT
mA MILLIAMPERES MOD MOTOR OPERATED DAMPER HORN ALARM
DPDT DOUBLE POLE, DOUBLE THROW S/S START/STOP
OXOO SELECTOR SWITCH • AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
MGD MILLION GALLONS PER DAY • AMERICAN SOCIETY FOR TESTING AND MATERIALS (ASTM)
S/SL START/STOP LOCKOUT S • ILLUMINATING ENGINEERING SOCIETY OF NORTH AMERICA (IESNA)
OOOX
LOUVER STROBE
MTD MOUNTED LUV • NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATES (NEMA)
E SL STOP LOCKOUT NORMALLY OPEN • NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
EMT ELECTRIC METALLIC TUBING TIME DELAY AFTER • OCCUPATION SAFETY AND HEALTH ACT (OSHA)
MCP MOTOR CIRCUIT PROTECTOR HAZARDOUS GAS DETECTION
SYM SYMMETRICAL COIL ENERGIZED • UNDERWRITERS LABORATORY, INC. (UL)
ETM ELAPSED TIME METER NORMALLY CLOSED ALARM HORN/AMBER BEACON HORN/STROBE COMBINATION ALARM
MCC MOTOR CONTROL CENTER C
CR= CORROSION RESISTANT
EUH ELECTRIC UNIT HEATER MTR MOTORIZED TIMING RELAY NORMALLY OPEN INTRUSION SYSTEM XP= EXPLOSION PROOF
EWC ELECTRIC WATER COOLER
T TIME DELAY AFTER DOOR CONTACT
MX MOTOR AUXILIARY RELAYS COIL
T-( ) TELEPHONE CONDUIT-( ) NORMALLY CLOSED
EWF ELECTRIC WALL FIN DE-ENERGIZED STOP/LOCKOUT PB STATION FACP FIRE ALARM CONTROL PANEL
SLO
TEMP TEMPERATURE NORMALLY OPEN CONTACT
N
T or T'STAT THERMOSTAT
F NP NAMEPLATE NORMALLY CLOSED CONTACT LIGHTING SYMBOLS
FOS FAST-OFF-SLOW TS TEMPERATURE SWITCH
NF NON FUSED LIGHTING FIXTURE TYPE, TYP.
TEMPERATURE X
F-S FAST-SLOW TCC TIME-CLOSE CONTACT SWITCH FLUORESCENT FIXTURE
NFDS NON FUSIBLE
DISCONNECT SWITCH LIMIT SWITCH
FT FEET TOC TIME-OPEN CONTACT X
N.C. NORMALLY CLOSED FLOAT SWITCH FLUORESCENT FIXTURE
F FLOW TR TIMING RELAY
W/ INTEGRAL BATTERY PACK
F-R FORWARD-REVERSE N.O. NORMALLY OPEN TRI SHIELDED TRIPLE CABLE PRESSURE
SWITCH
FR FRAME No. NUMBER TSP TWISTED SHIELDED PAIR S STANCHION MOUNTED FIXTURE
SOLENOID VALVE COIL
TYP TYPICAL
G O M POLE MOUNTED AREA/STREET FIXTURE
MOTOR OPERATED
( )OL OVERLOAD ( ) NUMBER OF U
GPM GALLONS PER MINUTE VALVE WALL MOUNTED FIXTURE
UH UNIT HEATER INDICATING LIGHT
G GREEN * *=COLOR
R - RED W - WHITE EXIT SIGN FIXTURE
GRD GROUND G - GREEN A - AMBER EX
V EXPLOSION POOF EXIT SIGN FIXTURE
GFI GROUND FAULT INTERRUPTER VFD VARIABLE FREQUENCY DRIVE * PUSH-TO-TEST INDICATING
EX-XP
1 LIGHT
VAC VOLTS ALTERNATING CURRENT
NP NAME PLATE
VA VOLT - AMPERE
RED MUSHROOM HEAD PUSHBUTTON
VDC VOLTS DIRECT CURRENT
(MAINTAINED)
VS VOLTMETER SWITCH
MOUNTING STAND
VT VOLTAGE TRANSFORMER

CR CONTROL RELAY
W
W WATT TR TIMER
WP WEATHERPROOF
TDR TIME DELAY RELAY

M MOTOR STARTER CONTACTOR COIL OTHER COIL


DESIGNATIONS:
SL- SLOW O - OPEN
FS- FAST C - CLOSED
F - FORWARD L - LOW
R - REVERSE H - HIGH
SCALE: MRW ONONDAGA COUNTY DEPARTMENT OF WATER ENVIRONMENT PROTECTION File Number
In charge of
006.64
NOT TO SCALE JEC
LOWER HARBOR BROOK CSO STORAGE FACILITY
Designed by
SYMBOLS, ABBREVIATIONS & NOTES Date

THIS DRAWING WAS PREPARED AT THE SCALE INDICATED IN THE


2
1
08/11
04/11
AS BID
ISSUED FOR APPROVAL
MRW
MRW
Drawn by
JEC
SYRACUSE, NEW YORK
08/11 E-001
TITLE BLOCK. INACCURACIES IN THE STATED SCALE MAY BE
INTRODUCED WHEN DRAWINGS ARE REPRODUCED BY ANY
NO. DATE REVISION INT. MRW
Checked by
MEANS. USE THE GRAPHIC SCALE BAR IN THE TITLE BLOCK TO NO ALTERATIONS PERMITTED HEREON EXCEPT AS PROVIDED UNDER SECTION 7209
DETERMINE THE ACTUAL SCALE OF THIS DRAWING. SUBDIVISION 2 OF THE NEW YORK STATE EDUCATION LAW ELECTRICAL
SEE SHEET E-202
FOR CONTINUATION

600
300 AMP MANUAL TRANSFER
UTILITY METERING SWITCH, SEE ONE-LINE SHEET E-301
ENCLOSURE (TYPICAL) MF-A
MOBILE GENERATOR ROOM/AREA CLASSIFICATION
CONNECTION BOX, SEE
1600A SERVICE DETAIL SHEET E-309 ROOM
DISCONNECT ROOM NAME CLASSIFICATION
NUMBER
UP TO ANTENNA MAST
#4/0 GROUND CONNECTION ON ROOF, SEE SHEET E-103 101 ELECTRIC ROOM UNCLASSIFIED
TO GROUND BAR FOR ANTENNA LOCATION
102 HALL UNCLASSIFIED
GROUND BAR MOUNTED 12" AFF,
SEE GROUND BAR DETAIL 103 VESTIBULE UNCLASSIFIED
SHEET E-307
104 STAIR CLASS 1, DIVISION 1, GROUP D
C-009 & P-21, STUB-UP #4/0 BARE TIN PLATED COPPER
6" AFF AND CAP GROUND CABLE, 2'-6" BELOW 105 MECHANICAL ROOM UNCLASSIFIED
FINISHED GRADE (TYPICAL) 106 BATH UNCLASSIFIED
SEE SHEET I-201 FOR
CONDUIT AND WIRING 107 OFFICE UNCLASSIFIED
REQUIREMENTS (TYPICAL FOR
BOTH FIT AND AIT'S) TELEPHONE STORAGE TANK STAIRWELL CLASS 1, DIVISION 1, GROUP D
TERMINATION
LEVEL TRANSMITTER
BOARD STORAGE TANK CLASS 1, DIVISION 1, GROUP D
LIT-200, LIT-201, LIT-202, LOUVER
P-2A LV-2 EUH-1
LIT-203 AND LIT-204 CLASS 1, DIV 2, GROUP D WITHIN 3'-0" OF ODOR
TRANSFORMER (T-1) CONTROL SYSTEM DUCTWORK BLOWERS,
FLOW TRANSMITTER
ELECTRIC P-2 P-8
75 KVA, 480V PRIMARY, ODOR CONTROL SCRUBBERS OR ANY OTHER POTENTIAL LEAK
FIT-200 208/120V SECONDARY SOURCE. OUTSIDE THIS 3'-0" ENVELOPE, IS
LP1-21 101 UNCLASSIFIED
P-2B
LP1-21 P-10
LIGHTING PANEL LP1,
LP1-21 SEE PANEL SCHEDULE
LP1-18 SHEET E-305
TANK DEWATERING PUMP LP1-18
NO.2 VFD AND HARMONIC LIGHTING PANEL LP2 SIGNAGE NOTE:
LP1-28 MOTOR CONTROL CENTER SEE PANEL SCHEDULE
FILTER
MCC-N, SEE ONE-LINE SHEET E-305 1. PROVIDE SIGNAGE ON THE DOOR IN ACCORDANCE WITH SPECIFICATION
MOTOR CONTROL CENTER SHEET E-301 P-10A SECTION 16196. LABEL AS "BEFORE ENTERING THE AREA BELOW,
P-11A PERSONNEL ARE REQUIRED TO PLACE THE VENTILATION SYSTEM IN
MCC-E, SEE ONE-LINE
C-001 MAINTENANCE MODE THROUGH THE SYSTEM PLC"
SHEET E-301
P-1 P-10B
C-002
EUH-3
P-11 SCADA SYSTEM
P-1A ENCLOSURE
LP1-20
C-003

AREA CLASSIFICATION NOTE


CENTER FLUSH HYDRAULIC CONTROL
PANEL. ECH-1 REQUIREMENTS FOR ELECTRICAL WORK AND
SEE SIGNAGE MATERIALS VARIES FOR EACH ROOM OR AREA.
NOTE
HALL REFER TO THE TABLE ON THIS SHEET FOR
TANK DEWATERING PUMP P-9
ROOM/AREA CLASSIFICATIONS
C-007 NO.1 VFD AND HARMONIC 102
STAIR FILTER
P-17 VESTIBULE VENTILATION SYSTEM
104 ALARM AND HORN
103
A
LP1-19
LP1-17
P-16
C-010 GENERAL NOTES:
FIRE ALARM CONTROL
GAS MONITOR TRANSMITTER/ PANEL AND BATTERY 1. IT IS THE CONTRACTORS RESPONSIBILITY TO COORDINATE AND SCHEDULE
INDICATOR (AIT-214) FOR CABINETS ALL WORK WITH THE OWNER, ENGINEER AND OTHER CONTRACTORS.
EUH-2 STORAGE TANK STAIRWELL 2. CONDUIT ROUTINGS SHOWN ARE SCHEMATIC ONLY, CONTRACTOR SHALL
ELECTRIC WATER
GAS SENSOR ROUTE CONDUIT BASED ON ACTUAL FIELD CONDITIONS AND IN
HEATER EWH-1
LP1-16 COORDINATION WITH ALL OTHER EQUIPMENT BEING INSTALLED UNDER
SF-5 THIS CONTRACT.
C-006
3. WHERE TRENCHING FOR ELECTRICAL IS REQUIRED, CONTRACTOR SHALL
OFFICE VERIFY EXISTENCE OF UNDERGROUND OBSTRUCTIONS PRIOR TO
MECHANICAL EXCAVATION.
107
4. CONTRACTOR SHALL FIELD VERIFY ALL LENGTHS AND DIMENSIONS NOT
105 LP1-15
SPECIFICALLY CALLED OUT ON THE DRAWINGS OR OTHERWISE NOTED.
EBH-1 5. ALL SPLICES IN UNDERGROUND CONDUCTORS (I.E. JUNCTION BOXES)
HEATING
BATH SHALL BE SEALED WITH 3M SCOTCHCAST.
COIL EDH-1 PTAC-1
6. WORKING CLEARANCE TO BE MAINTAINED IN FRONT OF ELECTRICAL
SUMP PUMP P-19 EQUIPMENT, PER NEC TABLE 110.26(A)(1).
CONTROL
106
PANEL P-18
C-206
LP1-25
LP1-10,12
M LP1-9,11
GROUNDING NOTES:
1. THE GROUNDING SYSTEM IS SHOWN DIAGRAMMATICALLY. EXACT
LOCATION OF CABLE GROUND RODS AND CONNECTIONS SHALL BE
LP1-22,24,26 DETERMINED IN THEFIELD.
LOUVER L-1 2. ALL BURIED GROUNDING CABLE CONNECTIONS SHALL BE CADWELD
DAMPER D-1 OR THERMOWELD. THE WELDED CONNECTIONS SHALL BE LEFT
EXPOSED FOR INSPECTION BY ENGINEER PRIOR TO BACKFILLING.
ALL BURIED GROUND CONDUCTOR SHALL BE TIN-PLATED COPPER.
SEE SPECIFICATION SECTION 16100.
BOND INCOMING WATER LINE 3. WHERE EXPOSED TO MECHANICAL INJURY, THE GROUNDING
TO BUILDING PERIMETER GROUND 10'-0"x3/4" DIAMETER CONDUCTOR SHALL BE SUITABLY PROTECTED BY PIPE OR OTHER
LOOP WITH #4/0 BARE TIN PLATED COPPER WELD GROUNDING MECHANICAL PROTECTION. EACH END OF PROTECTING CONDUIT (IF
COPPER GROUND CABLE ROD (TYPICAL) METALLIC) SHOULD BE GROUNDED TO THE BARE CABLE AT BOTH
SEE SHEET E-202
FOR CONTINUATION ENDS.
4. ALL EXPOSED CABLE LUGS AND CONNECTIONS SHALL BE OF THE
MECHANICAL OR COMPRESSION TYPE UNLESS OTHERWISE NOTED.
5. STEEL MUST BE CLEANED THOROUGHLY AND CABLE MUST BE
COMPLETELY DRY BEFORE MAKING WELD CONNECTIONS.
6. THE GROUNDING SYSTEM SHALL BE CONNECTED TO A METALLIC
WATERLINE WITH A MINIMUM OF 10 FEET LENGTH UNDERGROUND AND
TO THE GROUNDING ELECTRODES.
7. REMOVE PAINT FROM UNDER ALL GROUNDING LUGS, INCLUDING SHOP
FABRICATED PANELS.
POWER
SCALE: 1/4" = 1'-0"

(ADDENDUM NO. 1)

SCALE: MRW ONONDAGA COUNTY DEPARTMENT OF WATER ENVIRONMENT PROTECTION File Number
In charge of
006.64
2 0 2 4 6 8 10 LOWER HARBOR BROOK CSO STORAGE FACILITY
1/4"=1'-0" JEC
Designed by
UTILITIES BUILDING - POWER PLAN Date

THIS DRAWING WAS PREPARED AT THE SCALE INDICATED IN THE


2
1
08/11
04/11
AS BID
ISSUED FOR APPROVAL
MRW
MRW
Drawn by
JEC
SYRACUSE, NEW YORK
08/11 E-101
TITLE BLOCK. INACCURACIES IN THE STATED SCALE MAY BE
INTRODUCED WHEN DRAWINGS ARE REPRODUCED BY ANY
NO. DATE REVISION INT. MRW
Checked by
MEANS. USE THE GRAPHIC SCALE BAR IN THE TITLE BLOCK TO NO ALTERATIONS PERMITTED HEREON EXCEPT AS PROVIDED UNDER SECTION 7209
DETERMINE THE ACTUAL SCALE OF THIS DRAWING. SUBDIVISION 2 OF THE NEW YORK STATE EDUCATION LAW ELECTRICAL
GENERAL LIGHTING NOTES:
1. PROVIDE CONDUIT SLEEVE FOR EXTERIOR LIGHTING AND DEVICES.
2. VERIFY CLEARANCE REQUIREMENTS FOR ANY FIXTURE DIRECTLY
ABOVE EQUIPMENT.
3. REFER TO PANELBOARD SCHEDULE ON DRAWING E-305.
4. WALL MOUNTED EXIT SIGNS TO BE MOUNTED 8'-0" AFF AND CIRCUITED
TO POLE MOUNTE LIGHT FIXTURE TO PANEL AS SCHEDULED. SEE PANEL SCHEDULE SHEET E-305.
LOCATED AT FLAP VALVE STRUCTURE. 5. NIGHT LIGHT CIRCUIT IS ON THE UN-SWITCHED CIRCUIT, WIRE THIS
SEE SHEET E-002 FOR CONTINUATION. CIRCUIT DIRECTLY TO THE CIRCUIT BREAKER ASSIGNED.
6. EMERGENCY LIGHT IS TO BE CIRCUITED TO THE HOT LEG OF THE
CIRCUIT FEEDING THE LIGHTS IN THE SAME AREA.
7. LIGHT FIXTURE MOUNTING HEIGHTS ARE TO BE LISTED AS BOTTOM OF
FIXTURE.
8. INSTALL FIXTURES AT HEIGHT SHOWN IN TABLE UNLESS A SPECIFIC
MOUNTING HEIGHT IS CALLED OUT ON PLAN DRAWINGS.
LP1-30 9. INSTALL FIXTURES IN LOCATIONS AS SHOWN, AS NOTED OR AS CLOSE
S7 3 AS POSSIBLE TO THESE LOCATIONS. WHEN ADJUSTMENTS TO AVOID
LP1-1 EX INTERFERENCE ARE REQUIRED, FIXTURES SHALL BE INSTALLED LEVEL
AND PLUMB.
LP2-2 10. CLEAN EACH FIXTURE AT THE TIME OF SUBSTANTIAL COMPLETION.
E
LP1 -3 11. REPLACE AT THE TIME OF SUBSTANTIAL COMPLETION ANY LAMPS THAT
ARE OUT, REPLACEMENT LAMPS SHALL NOT COME FROM SPARE LAMPS
C C C BEING PROVIDED.
12. OPERATE EACH FIXTURE AFTER INSTALLATION AND CONNECTION.
INSPECT FOR AND REPAIR ALL IMPROPER CONNECTIONS AND
OPERATION.
13. INSTALL EXIT SIGNS IMMEDIATELY ABOVE THE EXITS SO THEY ARE
VISIBLE FROM THE DIRECTION OF TRAVEL TO THE EXIT.
ELECTRIC
LP1-1 LP1-1
101
SIGNAGE NOTES:

E 1. PROVIDE SIGNAGE ON THE DOOR IN ACCORDANCE WITH


SPECIFICATION SECTION 16196, LABEL AS "BEFORE ENTERING
C C C THE AREA BELOW, PERSONNEL ARE REQUIRED TO PLACE THE
PHOTOCELLS
VENTILATION SYSTEM IN MAINTENANCE MODE THROUGH THE
LP2-3
S7 PLANT PLC".

LP1-7
PC PC
SEE SIGNAGE NOTE LP1-1 EX
3 TO SITE LIGHTING
LP1-30 LP1-30 SEE SHEET E-002 LUMINARIES TYPES AND MOUNTING HEIGHTS
LP1-4 FOR CONTINUATION
EXP2 EX
ROOM ROOM TYPE OF MOUNTING HEIGHT TO
EX-XP LP1-30 BUILDING NAME VOLTS/PHASE
NUMBER DESIGNATION FIXTURE BOTTOM OF LUMINAIRE
STAIR LP1-5
EX
104 C C HALL C UTILITIES BUILDING 101 ELECTRIC ROOM 120/1 C 10' AFF
VESTIBULE
102
LP1-37 UTILITIES BUILDING 102 HALL 120/1 C 10' AFF
103 LP1-4 LP1-4

UTILITIES BUILDING 103 VESTIBULE 103 120/1 C 10' AFF


xp LP1-4 LP1-4 3
LP1-2

LP1-32 LP1 -5 UTILITIES BUILDING 107 OFFICE 120/1 C 10' AFF


LP1 -6
EX C
S7 LP1-4
LP1-30 UTILITIES BUILDING 106 BATH 120/1 EMX 10' AFF
C C

MECHANICAL
UTILITIES BUILDING 105 120/1 C 10' AFF
ROOM
GFI
MECHANICAL 8' ABOVE UPPER
LP1-6 UTILITIES BUILDING 104 STAIR 120/1 EXP2
C & LOWER LANDING
105
LP1-2 LP1-2
STORAGE TANK STAIR 120/1 EXP2 10' AFF
BATH OFFICE
107 9' ABOVE FINISHED
A 106 UTILITIES BUILDING EXTERIOR 120/1 S7
TANK ROOF
C C
EXP2 C UTILITIES BUILDING EXTERIOR CANOPY 120/1 E UNDERSIDE OF CANOPY
S7
LP1-4 LP1-2
EX ACCESS ROAD EXTERIOR 120/1 PM1 18' POLE
3
LP1-30

EMERGENCY BALLAST WIRING DIAGRAM

LINE

3-WAY 3-WAY

LIGHTING PLAN
SCALE: 1/4" = 1'-0"

AC BALLAST

EMERGENCY
BALLAST
AREA CLASSIFICATION NOTE
REQUIREMENTS FOR ELECTRICAL WORK AND FLUORESCENT FIXTURE
MATERIALS VARIES FOR EACH ROOM OR AREA.
REFER TO THE TABLE ON SHEET E-101 FOR
ROOM/AREA CLASSIFICATIONS COMMON

EMERGENCY BALLAST WIRING DIAGRAM


NOT TO SCALE

SCALE: MRW ONONDAGA COUNTY DEPARTMENT OF WATER ENVIRONMENT PROTECTION File Number
In charge of
006.64
2 0 2 4 6 8 10 LOWER HARBOR BROOK CSO STORAGE FACILITY
1/4"=1'-0" JEC
Designed by
UTILITIES BUILDING - LIGHTING PLAN Date

THIS DRAWING WAS PREPARED AT THE SCALE INDICATED IN THE


2
1
08/11
04/11
AS BID
ISSUED FOR APPROVAL
MRW
MRW
Drawn by
JEC
SYRACUSE, NEW YORK
08/11 E-102
TITLE BLOCK. INACCURACIES IN THE STATED SCALE MAY BE
INTRODUCED WHEN DRAWINGS ARE REPRODUCED BY ANY
NO. DATE REVISION INT. MRW
Checked by
MEANS. USE THE GRAPHIC SCALE BAR IN THE TITLE BLOCK TO NO ALTERATIONS PERMITTED HEREON EXCEPT AS PROVIDED UNDER SECTION 7209
DETERMINE THE ACTUAL SCALE OF THIS DRAWING. SUBDIVISION 2 OF THE NEW YORK STATE EDUCATION LAW ELECTRICAL
GENERAL NOTES:
#4 BARE COPPER GROUND CONDUCTOR
DOWN TO GROUND GRID, SEE SHEET 1. IT IS THE CONTRACTORS RESPONSIBILITY TO COORDINATE AND SCHEDULE
E-101 FOR CONTINUATION ALL WORK WITH THE OWNER, ENGINEER AND OTHER CONTRACTORS.
2. CONDUIT ROUTINGS SHOWN ARE SCHEMATIC ONLY, CONTRACTOR SHALL
ROUTE CONDUIT BASED ON ACTUAL FIELD CONDITIONS AND IN
COORDINATION WITH ALL OTHER EQUIPMENT BEING INSTALLED UNDER
ROOF MOUNTED THIS CONTRACT.
YAGI ANTENNA 3. CONTRACTOR SHALL FIELD VERIFY ALL LENGTHS AND DIMENSIONS NOT
SPECIFICALLY CALLED OUT ON THE DRAWINGS OR OTHERWISE NOTED.

PRE-1

LP1-13

PRE-2

LP1-13
PRE-3
LP1-14

DISCONNECT
SWITCH
(TYPICAL FOR 3)

ROOF PLAN - POWER


SCALE: 1/4" = 1'-0"

SCALE: MRW ONONDAGA COUNTY DEPARTMENT OF WATER ENVIRONMENT PROTECTION File Number
In charge of
006.64
2 0 2 4 6 8 10 LOWER HARBOR BROOK CSO STORAGE FACILITY
1/4"=1'-0" JEC
Designed by
UTILITIES BUILDING - ROOF PLAN Date

THIS DRAWING WAS PREPARED AT THE SCALE INDICATED IN THE


2
1
08/11
04/11
AS BID
ISSUED FOR APPROVAL
MRW
MRW
Drawn by
JEC
SYRACUSE, NEW YORK
08/11 E-103
TITLE BLOCK. INACCURACIES IN THE STATED SCALE MAY BE
INTRODUCED WHEN DRAWINGS ARE REPRODUCED BY ANY
NO. DATE REVISION INT. MRW
Checked by
MEANS. USE THE GRAPHIC SCALE BAR IN THE TITLE BLOCK TO NO ALTERATIONS PERMITTED HEREON EXCEPT AS PROVIDED UNDER SECTION 7209
DETERMINE THE ACTUAL SCALE OF THIS DRAWING. SUBDIVISION 2 OF THE NEW YORK STATE EDUCATION LAW ELECTRICAL
LEGEND FIRE ALARM SYSTEM NOTES:
T-1 TO INCOMING PRIMARY
1 JUNCTION BOX FOR DOOR
SERVICE POLE. SEE SHEET 1. ACTUAL LOCATION OF ALL FIRE ALARM SYSTEM DEVICES SHALL BE
MECHANISM/BADGE READER SYSTEM.
E-002 FOR CONTINUATION. DETERMINED IN THE FIELD. ADJUST LOCATIONS TO AVOID CONFLICTS
2 SECURITY PANEL WITH UNIT HEATERS, HOT WATER PIPING, FANS VENTILATION INTAKE AND
2 DISCHARGE LOUVERS AND OTHER EQUIPMENT.
2. FOR EACH DUCT SMOKE DETECTOR AND FOR ANY DETECTOR (HEAT OR
COMBUSTIBLE GAS DETECTION SMOKE) THAT IS NOT VISIBLE OR READILY "ACCESSIBLE", PROVIDE A
1 ALARM HORN AND LIGHT REMOTE TEST STATION. TEST STATION TO BE LOCATED IN A CONVENIENT
J AND ACCESSIBLE LOCATION AND BE SUITABLE FOR THE AREA OF
INSTALLATION. PROVIDE CONDUIT AND WIRE AS REQUIRED BY
MANUFACTURER.
R DC 3. PROVIDE LAMINATED PLASTIC PLACARD WITH 2" WHITE LETTERS ON RED
WP WEATHERPROOF HORN/STROBE BACKGROUND, TO READ "FIRE ALARM. IF FLASHING CALL 911 TO REPORT
P FIRE NOTIFICATION DEVICE. SEE FIRE". MOUNT DIRECTLY BENEATH HORN/STROBE UNIT.
WP 4. FIRE ALARM SIGNALING APPLIANCES SHALL BE MOUNTED SUCH THAT

S
NOTE 3. PROVIDE PLACARD PER
SPECIFICATION SECTION 16721. THE ENTIRE LENS IS NOT LESS THAN 80 INCHES AND NOT GREATER THAN
95 INCHES ABOVE THE FINISHED FLOOR.
WP 5. ALL FIRE ALARM DEVICES SHALL MEET ADA REQUIREMENTS.
6. THE FIRE DETECTION SYSTEM SHALL BE INSTALLED IN ACCORDANCE
WITH NFPA-72.
7. ALL WIRING FOR THE FIRE DETECTION SYSTEM SHALL BE INSTALLED
WITHIN A DEDICATED CONDUIT.

SECURITY SYSTEM NOTES:


MAIN TELEPHONE EQUIPMENT
MOUNTING PANEL 1. PROVIDE COMPLETE FULLY FUNCTIONAL SECURITY SYSTEM IN
ACCORDANCE WITH THE CONTRACT DRAWINGS AND SPECIFICATIONS.
2. PROVIDE FLUSH DOOR CONTACTS WHERE SHOWN.
3. CARD READERS, CARD READER CONTROLLER, DOOR CONTACTS, AND
INTERIOR DOOR MOTION DETECTOR WILL BE PROVIDED AND INSTALLED
UNDER THIS CONTRACT. CONTRACTOR SHALL PROVIDE AND INSTALL
ALL CONDUIT AND CONDUCTOR , DEVICE BOXES AS REQUIRED FOR
INSTALLATION AND TERMINATION. DOORS WILL BE "PREPARED" TO
2 RECEIVE ELECTRIC STRIKES AND DOOR CONTACTS.
4. ALL DOORS WILL BE OPENED ON FIRE FROM SECURE SIDE USING
1 PANIC HARDWARE ON DOORS.

J
CR
P R DC FIRE ALARM CONTROL PANEL
(FACP) AND BATTERY CABINETS
P

TWO RJ-21X JACKS MOUNTED IN THE MAIN FACP


XP OR IMMEDIATELY ADJACENT TO THE PANEL

AREA CLASSIFICATION NOTE

XP REQUIREMENTS FOR ELECTRICAL WORK AND

P
MATERIALS VARIES FOR EACH ROOM OR AREA.
REFER TO THE TABLE ON SHEET E-101 FOR
ROOM/AREA CLASSIFICATIONS
2
DC

1 J
XP
R

SECURITY SYMBOL LEGEND


SYMBOL DESCRIPTION MTG HT

S J J JUNCTION BOX-CEILING MTD./WALL MTD.

XP CR
CARD READER

R DOOR RELEASE (MOTION SENSOR LOCATED ON SECURE SIDE OF DOOR)


W

P
DC SECURITY DOOR CONTACTS
R DC

J S
1 WP
WP
2

COMBUSTIBLE GAS DETECTION


ALARM HORN AND LIGHT

FIRE ALARM, INTRUSION AND TELEPHONE SYSTEM


PLAN
SCALE: 1/4" = 1'-0"

SCALE: MRW ONONDAGA COUNTY DEPARTMENT OF WATER ENVIRONMENT PROTECTION File Number
In charge of
2 0 2 4
2 6 8 10 006.64
LOWER HARBOR BROOK CSO STORAGE FACILITY
1/4" = 1'-0" JEC
Designed by
UTILITIES BUILDING - FIRE ALARM, INTRUSION Date

THIS DRAWING WAS PREPARED AT THE SCALE INDICATED IN THE


2
1
08/11
04/11
AS BID
ISSUED FOR APPROVAL
MRW
MRW
Drawn by
JEC
SYRACUSE, NEW YORK AND TELEPHONE SYSTEM PLAN
08/11 E-104
TITLE BLOCK. INACCURACIES IN THE STATED SCALE MAY BE
INTRODUCED WHEN DRAWINGS ARE REPRODUCED BY ANY
NO. DATE REVISION INT. MRW
Checked by
MEANS. USE THE GRAPHIC SCALE BAR IN THE TITLE BLOCK TO NO ALTERATIONS PERMITTED HEREON EXCEPT AS PROVIDED UNDER SECTION 7209
DETERMINE THE ACTUAL SCALE OF THIS DRAWING. SUBDIVISION 2 OF THE NEW YORK STATE EDUCATION LAW ELECTRICAL
PUMP CABLE PROVIDED BY
PUMP MANUFACTURER
P-7 D
P-1B TANK DEWATERING
THE EQUIPMENT FOR THE CHOPPER PUMP PUMP NO.1 (M-200A)
AND DEWATERING PUMPS SHALL BE FREE P-11B
TANK DEWATERING
STANDING, SEE NON-METALLIC MOUNTUING
PUMP NO.2 (M-200B)
PANELS DETAIL SHEET E-307

DISCONNECT SWITCH (TYPICAL) GENERAL NOTES:


SEE NON-METALLIC MOUNTING
PANELS DETAIL SHEET E-307 AE-211C (H2S) 1. IT IS THE CONTRACTORS RESPONSIBILITY TO COORDINATE AND
AE-211B (LEL) SCHEDULE ALL WORK WITH THE OWNER, ENGINEER AND OTHER
SUBMERSIBLE PRESSURE CONTRACTORS.
TRANSMITTER/TRANSDUCER. AE-211A (O2)
2. CONDUIT ROUTINGS SHOWN ARE SCHEMATIC ONLY, CONTRACTOR
SEE MOUNTING DETAIL SHALL ROUTE CONDUIT BASED ON ACTUAL FIELD CONDITIONS AND IN
SHEET I-201 COORDINATION WITH ALL OTHER EQUIPMENT BEING INSTALLED
UNDER THIS CONTRACT.
C 3. WHERE TRENCHING FOR ELECTRICAL IS REQUIRED, CONTRACTOR
SHALL VERIFY EXISTENCE OF UNDERGROUND OBSTRUCTIONS PRIOR
LE-200 TO EXCAVATION.
4. CONTRACTOR SHALL FIELD VERIFY ALL LENGTHS AND DIMENSIONS
LSL-200 NOT SPECIFICALLY CALLED OUT ON THE DRAWINGS OR OTHERWISE
NOTED.
LSL-201
5. ALL SPLICES IN UNDERGROUND CONDUCTORS (I.E. JUNCTION BOXES)
C-200 SHALL BE SEALED WITH 3M SCOTCHCAST.

WET WELL
CHOPPER
PUMP (M-201)
AREA CLASSIFICATION NOTE
B REQUIREMENTS FOR ELECTRICAL WORK AND
MATERIALS VARIES FOR EACH ROOM OR AREA.
REFER TO THE TABLE ON SHEET E-101 FOR
ROOM/AREA CLASSIFICATIONS

AE-210C (H2S)
AE-210B (LEL)

AE-210A (O2)

CIRCULAR TANK
FLUSHING SYSTEM

A
SEE SHEET I-201 FOR
MOUNTING DETAIL SEE SHEET I-201 FOR
CONDUIT AND WIRING
REQUIREMENTS
LE-205
START/STOP PUSHBUTTON
LS-205A CONTROL STATION FOR THE
CIRCULAR TANK FLUSHING
SYSTEM
C-205A AE-212C (H2S)

AE-212B (LEL)
C-205
AE-212A (O2)
SUMP PUMP
DISCONNECT SWITCHES

UP TO SUMP PUMP CONTROL


PANEL LOCATED IN MECHANICAL 5
ROOM
P-18B
AE-214C (H2S)
AE-214B (LEL)
SEE SHEET I-201 FOR
CONDUIT AND WIRING
REQUIREMENTS DC
AE-214A (O2)
LE-202
LS-205B

CIRCULAR TANK FLUSHING


SYSTEM CONTROL PANEL
LP1-36
SUMP PUMP CONTROL
SEE SHEET I-201 FOR PANEL
CONDUIT AND WIRING C-207
REQUIREMENTS (TYPICAL)

GAS MONITOR TRANSMITTERS/INDICATORS


(AIT-210, AIT-211, AIT-212 & AIT-213) MOUNTED
4 ADJACENT TO DOOR. (FOR GAS MONITORS
LOCATED IN STORAGE TANK AREA)
AE-213C (H2S)
AE-213B (LEL) C-205C
AE-213A (O2) HS-003 (EMERGENCY CALL)
LOCATED ADJACENT TO WATERTIGHT DOOR
AT ELEV. 327'-0". SEE I-201 FOR ADDITIONAL
C-008 DETAIL.
1 MOUNT INSTRUMENTS P-18A
ADJACENT TO ROOF
HATCH. SEE MOUNTING FLEX CONNECTION TO
PUMP (TYPICAL)
3
DETAIL SHEET I-201
2
C-205B

STORAGE TANK POWER PLAN


SCALE: 3/32" = 1'-0"

SCALE: MRW ONONDAGA COUNTY DEPARTMENT OF WATER ENVIRONMENT PROTECTION File Number
In charge of
8 0 8 16 24 006.64
LOWER HARBOR BROOK CSO STORAGE FACILITY
3/32"=1'-0" JEC
Designed by
STORAGE TANK - POWER PLAN Date

THIS DRAWING WAS PREPARED AT THE SCALE INDICATED IN THE


2
1
08/11
04/11
AS BID
ISSUED FOR APPROVAL
MRW
MRW
Drawn by
JEC
SYRACUSE, NEW YORK
08/11 E-201
TITLE BLOCK. INACCURACIES IN THE STATED SCALE MAY BE
INTRODUCED WHEN DRAWINGS ARE REPRODUCED BY ANY
NO. DATE REVISION INT. MRW
Checked by
MEANS. USE THE GRAPHIC SCALE BAR IN THE TITLE BLOCK TO NO ALTERATIONS PERMITTED HEREON EXCEPT AS PROVIDED UNDER SECTION 7209
DETERMINE THE ACTUAL SCALE OF THIS DRAWING. SUBDIVISION 2 OF THE NEW YORK STATE EDUCATION LAW ELECTRICAL
ODOR CONTROL
BLOWER VESSEL OCV-2
BL-2
HEAT TRACE POWER CONNECTION BOX,
SEE HEAT TRACE DETAILS ON SHEET E-
D
DAMPER #4/0 BARE COPPER GROUND CABLE
310 (TYPICAL FOR ODOR CONTROL
D-2 CONNECT TO BUILDING STEEL
VESSEL OCV-1). SEE SHEETS H-202 AND (TYPICAL FOR 5 PLACES)
LP2-9 H-203 FOR PIPE SIZE, LENGTH AND #4/0 BARE COPPER GROUND
LOCATION. CABLE, 2'-6" BELOW FINISHED
GRADE (TYPICAL)
GENERAL NOTES:
1. IT IS THE CONTRACTORS RESPONSIBILITY TO COORDINATE AND
ODOR CONTROL SCHEDULE ALL WORK WITH THE OWNER, ENGINEER AND OTHER
VESSEL OCV-1 CONTRACTORS.
P-12B
C-005 2. CONDUIT ROUTINGS SHOWN ARE SCHEMATIC ONLY, CONTRACTOR
BLOWER P-12A J P-12 SHALL ROUTE CONDUIT BASED ON ACTUAL FIELD CONDITIONS AND IN
BL-1
C-011 DC DC
COORDINATION WITH ALL OTHER EQUIPMENT BEING INSTALLED
UNDER THIS CONTRACT.
LP2-1 DC 3. WHERE TRENCHING FOR ELECTRICAL IS REQUIRED, CONTRACTOR
DAMPER 8'-0"x5/8" DIAMETER SHALL VERIFY EXISTENCE OF UNDERGROUND OBSTRUCTIONS PRIOR
DC
D-1 COPPER WELD GROUNDING
ROD (TYPICAL)
C 4.
TO EXCAVATION.
CONTRACTOR SHALL FIELD VERIFY ALL LENGTHS AND DIMENSIONS
LP2-9 DAVIT NOT SPECIFICALLY CALLED OUT ON THE DRAWINGS OR OTHERWISE
CRANE NOTED.
5. ALL SPLICES IN UNDERGROUND CONDUCTORS (I.E. JUNCTION BOXES)
P-3B SHALL BE SEALED WITH 3M SCOTCHCAST.

P-3A P-3
C-004
GROUND GRID CONNECTION TO
BLOWER MOTOR FRAME (TYPICAL
BLOWER CONTROL PANEL
FOR BLOWER BL-1 AND BL-2)
(TYPICAL FOR 2)

DISCONNECT SWITCH MOUNTED


ON NON-METALLIC MOUNTING PANEL
(TYPICAL). SEE DETAIL SHEET E-307
AREA CLASSIFICATION NOTE
B REQUIREMENTS FOR ELECTRICAL WORK AND
MATERIALS VARIES FOR EACH ROOM OR AREA.
P-5
REFER TO THE TABLE ON SHEET E-101 FOR
GFI LP2-7
SUPPLY FAN ROOM/AREA CLASSIFICATIONS
WP
SF-1
SUPPLY FAN
SF-3 P-4

P-13
EXHAUST FAN
EF-1
FOR CONTINUATION
SEE SHEET E-101
P-14

SUPPLY FAN
EXHAUST FAN
EF-2
DC SF-4 A

GRAVITY ROOF
VENTILATOR GRV-1
P-15
LP2-7
P-6

SUPPLY FAN
GFI
SF-2 ? WP
5

DC

PRE-4

LP1-14
DC FOR CONTINUATION
SEE SHEET E-101

DC

4
DOOR CONTACT (TYPICAL)
SEE SHEET I-201 FOR TYPICAL
INTRUSION ALARM DOOR SWITCHES
ELEMENTARY DIAGRAM AND INTRUSION

1 ALARM SCHEDULE.

ROOF ACCESS HATCH


(TYPICAL FOR 8)
3
2
STORAGE TANK ROOF POWER PLAN
SCALE: 3/32" = 1'-0"

SCALE: MRW ONONDAGA COUNTY DEPARTMENT OF WATER ENVIRONMENT PROTECTION File Number
In charge of
006.64
8 0 8 16 24 LOWER HARBOR BROOK CSO STORAGE FACILITY
3/32"=1'-0" JEC
Designed by
STORAGE TANK - ROOF POWER PLAN Date

THIS DRAWING WAS PREPARED AT THE SCALE INDICATED IN THE


2
1
08/11
04/11
AS BID
ISSUED FOR APPROVAL
MRW
MRW
Drawn by
JEC
SYRACUSE, NEW YORK
08/11 E-202
TITLE BLOCK. INACCURACIES IN THE STATED SCALE MAY BE
INTRODUCED WHEN DRAWINGS ARE REPRODUCED BY ANY
NO. DATE REVISION INT. MRW
Checked by
MEANS. USE THE GRAPHIC SCALE BAR IN THE TITLE BLOCK TO NO ALTERATIONS PERMITTED HEREON EXCEPT AS PROVIDED UNDER SECTION 7209
DETERMINE THE ACTUAL SCALE OF THIS DRAWING. SUBDIVISION 2 OF THE NEW YORK STATE EDUCATION LAW ELECTRICAL
D

TOPPING HIGH PT
T/ TANK
382' - 8" ROOF
EL. SECOND FLOOR PLAN
382' - 0"
T/ TANK ROOF EL.
382' - 0"
B/ ROOF EL.
381' - 0" 381' - 0"

FINISHED FLOOR
T/ CULVERT OPNG
378' - 6" EL. T/FLOOR
FIRST FIN.
T/ FIN.FLR.
PLAN
FLR.
XP2B
378' - 0" 378'
378'- -0"
0"

XP2 XP1
C
XP2 LP1-27
LP1-27
XP1
T/ CULVERT SLAB
373' - 6"
XP2
XP2B

WALKWAY EL. T/ WALKWAY


T/ WALKWAYEL. EL.
XP2 370' - 0" 370'
370'- -0"
0"
B/ OUTFALL
368' - 6"
XP2B T/ COLLAR BEAM
XP2

XP2B
XP2 XP2 B T/ DROP MAT
367' - 0"
366' - 0"
UP TO LIGHT FIXTURE AT
XP1 LANDING, SEE PLAN VIEW
THIS SHEET
T/ DIAPHRAGM WALL EL.
LP1-27 363' - 0"

XP2 XP2B T/ UPPER CONC. STRUT


360' - 0"
T/ STAIR LANDING-1 EL.
XP2 358' - 11"
T/ STAIR LANDING-A
358' - 4"

XP2B
A
XP2 XP2B XP2

P
C
A
F

T/ RAINWATER WALL EL.


350' - 0"

T/ STAIR LANDING-2 EL.


XP2 347' - 10"
XP2 T/ RAINWATER STORAGE SLAB
347' - 0" T/ STAIR LANDING-B
XP2B 346' - 8"

XP2B
LP1-27

XP1
5
XP2B
XP2 LP1-29
XP2
XP2
LP1-27
EX-XP
T/ LOWER CONC. STRUT
T/ STAIR LANDING-3
337' EL.
- 3"
DC 336' - 9"
XP2
C-208 EX-XP T/ STAIR LANDING-C
335' - 7"
XP2B XP2
XP2B

XP2 2 LP1-37
LP1-27
XP2 GENERAL LIGHTING NOTES:
E-203
XP2 1. PROVIDE CONDUIT SLEEVE FOR EXTERIOR LIGHTING AND DEVICES. Lower Tank Plan
XP1 DOWN TO STAIRWELL
2. VERIFY CLEARANCE REQUIREMENTS FOR ANY FIXTURE DIRECTLY 330' - 0"
LIGHTING SEE
TO XP1 TASK SECTION 2 THIS SHEET ABOVE EQUIPMENT.
LIGHTING 3. REFER TO PANELBOARD SCHEDULE ON DRAWING E-305.
XP2B FIXTURES 4. WALL MOUNTED EXIT SIGNS TO BE MOUNTED 8'-0" AFF AND CIRCUITED
4 5.
TO PANEL AS SCHEDULED. SEE PANEL SCHEDULE SHEET E-305.
NIGHT LIGHT CIRCUIT IS ON THE UN-SWITCHED CIRCUIT, WIRE THIS
HIGH PT. STRUCT. SLAB EL.
327' - 0"
CIRCUIT DIRECTLY TO THE CIRCUIT BREAKER ASSIGNED. T/ STORAGE SLAB
6. EMERGENCY LIGHT IS TO BE CIRCUITED TO THE HOT LEG OF THE 325' - 10"
CIRCUIT FEEDING THE LIGHTS IN THE SAME AREA.
7. LIGHT FIXTURE MOUNTING HEIGHTS ARE TO BE LISTED AS BOTTOM OF
FIXTURE.
8. INSTALL FIXTURES AT HEIGHT SHOWN ON TABLE, SHEET E-102 UNLESS
1 A SPECIFIC MOUNTING HEIGHT IS CALLED OUT ON PLAN DRAWINGS.
9. INSTALL FIXTURES IN LOCATIONS AS SHOWN, AS NOTED OR AS CLOSE
3 AS POSSIBLE TO THESE LOCATIONS. WHEN ADJUSTMENTS TO AVOID
INTERFERENCE ARE REQUIRED, FIXTURES SHALL BE INSTALLED LEVEL
AND PLUMB.
2 10. CLEAN EACH FIXTURE AT THE TIME OF SUBSTANTIAL COMPLETION.
11. REPLACE AT THE TIME OF SUBSTANTIAL COMPLETION ANY LAMPS THAT
ARE OUT, REPLACEMENT LAMPS SHALL NOT COME FROM SPARE LAMPS
BEING PROVIDED. SECTION 1 2
12. OPERATE EACH FIXTURE AFTER INSTALLATION AND CONNECTION.
INSPECT FOR AND REPAIR ALL IMPROPER CONNECTIONS AND
1/4" = 1'-0" E-203

STORAGE TANK LIGHTING PLAN 13.


OPERATION.
INSTALL EXIT SIGNS IN THE LOCATIONS AS INDICATED ON THE
SCALE: 3/32" = 1'-0" DRAWINGS.
14. INSTALL EXIT SIGNS IMMEDIATELY ABOVE THE EXITS SO THEY ARE
VISIBLE FROM THE DIRECTION OF TRAVEL TO THE EXIT.

SCALE: MRW ONONDAGA COUNTY DEPARTMENT OF WATER ENVIRONMENT PROTECTION File Number
8 0 8 16 24 In charge of
3/32"=1'-0" 006.64
LOWER HARBOR BROOK CSO STORAGE FACILITY
2 0 2 4 6 8 10
JEC
Designed by
1/4"=1'-0"
STORAGE TANK - LIGHTING PLAN AND SECTION Date

THIS DRAWING WAS PREPARED AT THE SCALE INDICATED IN THE


2
1
08/11
04/11
AS BID
ISSUED FOR APPROVAL
MRW
MRW
Drawn by
JEC
SYRACUSE, NEW YORK
08/11 E-203
TITLE BLOCK. INACCURACIES IN THE STATED SCALE MAY BE
INTRODUCED WHEN DRAWINGS ARE REPRODUCED BY ANY
NO. DATE REVISION INT. MRW
Checked by
MEANS. USE THE GRAPHIC SCALE BAR IN THE TITLE BLOCK TO NO ALTERATIONS PERMITTED HEREON EXCEPT AS PROVIDED UNDER SECTION 7209
DETERMINE THE ACTUAL SCALE OF THIS DRAWING. SUBDIVISION 2 OF THE NEW YORK STATE EDUCATION LAW ELECTRICAL
D

FIRE ALARM SYSTEM NOTES:


1. ACTUAL LOCATION OF ALL FIRE ALARM SYSTEM DEVICES SHALL BE
DETERMINED IN THE FIELD. ADJUST LOCATIONS TO AVOID CONFLICTS
WITH UNIT HEATERS, HOT WATER PIPING, FANS VENTILATION INTAKE AND
DISCHARGE LOUVERS AND OTHER EQUIPMENT.
2. FOR EACH DUCT SMOKE DETECTOR AND FOR ANY DETECTOR (HEAT OR
SMOKE) THAT IS NOT VISIBLE OR READILY "ACCESSIBLE", PROVIDE A
REMOTE TEST STATION. TEST STATION TO BE LOCATED IN A CONVENIENT
AND ACCESSIBLE LOCATION AND BE SUITABLE FOR THE AREA OF
INSTALLATION. PROVIDE CONDUIT AND WIRE AS REQUIRED BY
MANUFACTURER.
3. PROVIDE LAMINATED PLASTIC PLACARD WITH 2" WHITE LETTERS ON RED
XP C BACKGROUND, TO READ "FIRE ALARM. IF FLASHING CALL 911 TO REPORT
FIRE". MOUNT DIRECTLY BENEATH HORN/STROBE UNIT.
4. FIRE ALARM SIGNALING APPLIANCES SHALL BE MOUNTED SUCH THAT
XP THE ENTIRE LENS IS NOT LESS THAN 80 INCHES AND NOT GREATER THAN
95 INCHES ABOVE THE FINISHED FLOOR.
5. ALL FIRE ALARM DEVICES SHALL MEET ADA REQUIREMENTS.
6. THE FIRE DETECTION SYSTEM SHALL BE INSTALLED IN ACCORDANCE
WITH NFPA-72.
7. ALL WIRING FOR THE FIRE DETECTION SYSTEM SHALL BE INSTALLED
XP WITHIN A DEDICATED CONDUIT.

XP

XP
B

XP

XP

XP

XP
HEAT DETECTOR
(TYPICAL)
A

P
C
A
F

XP

XP

XP
XP
5

XP XP

XP

AREA CLASSIFICATION NOTE


REQUIREMENTS FOR ELECTRICAL WORK AND
MATERIALS VARIES FOR EACH ROOM OR AREA.
XP REFER TO THE TABLE ON SHEET E-101 FOR
ROOM/AREA CLASSIFICATIONS

XP XP

1
3
2
STORAGE TANK FIRE ALARM PLAN
SCALE: 3/32" = 1'-0"

SCALE: MRW ONONDAGA COUNTY DEPARTMENT OF WATER ENVIRONMENT PROTECTION File Number
In charge of
8 0 8 16 24 006.64
LOWER HARBOR BROOK CSO STORAGE FACILITY
3/32"=1'-0" JEC
Designed by
STORAGE TANK - FIRE ALARM AND INTRUSION Date

THIS DRAWING WAS PREPARED AT THE SCALE INDICATED IN THE


2
1
08/11
04/11
AS BID
ISSUED FOR APPROVAL
MRW
MRW
Drawn by
JEC
SYRACUSE, NEW YORK PLAN
08/11 E-204
TITLE BLOCK. INACCURACIES IN THE STATED SCALE MAY BE
INTRODUCED WHEN DRAWINGS ARE REPRODUCED BY ANY
NO. DATE REVISION INT. MRW
Checked by
MEANS. USE THE GRAPHIC SCALE BAR IN THE TITLE BLOCK TO NO ALTERATIONS PERMITTED HEREON EXCEPT AS PROVIDED UNDER SECTION 7209
DETERMINE THE ACTUAL SCALE OF THIS DRAWING. SUBDIVISION 2 OF THE NEW YORK STATE EDUCATION LAW ELECTRICAL
PRIMARY CABLE BY UTILITY, CONDUIT
PROVIDED AND INSTALLED UNDER THIS
CONTRACT, CONDUCTORS BY UTILITY, SEE
SHEET E-002 FOR UTILITY POLE LOCATION

1250 KVA 480/277V


TRANSFORMER AND PAD
BY UTILITY

SERVICE
TRANSFORMER

TRANSFORMER (T-A)
1000 KVA
13.2 KV PRIMARY
480/277V SECONDARY

1600A SERVICE
DISCONNECT

UTILITY METERING,
COORDINATE WITH
UTILITY
MF-A TRANSFORMER SECONDARY
CONDUIT AND WIRE UNDER N1A N2A N3A N4A N5A N6A
THIS CONTRACT

MCC-N N2E N3E N5E N6E

N2G N4G

N3I N5I N6I


1600AT
3000AF
1600 AMP BUS

POWER N2M N3M N4M N5M N6M


METER

60 500 225 225 40 40 40 225 225 40 70 70 20 20 20 20


N4Q N5Q
150 600 250 250 150 150 150 250 250 150 150 150 150 250 250 250
3 N2S

SIZE 2 SIZE 2 SIZE 2 SIZE 2 SIZE 2 SIZE 2 N4U N5U


N3V
N2W

PORTABLE GENERATOR P-3 P-4 P-5 P-6 P-12 P-22 P-23 P-24
(NOT PART OF CONTRACT) P-13 P-14 P-15 P-18
TVSS

GENERATOR MOTOR CONTROL CENTER MCC-N ELEVATION


NOT TO SCALE

P-2
GENERATOR
DISCONNECT
125 125 15 15 15 125 125 15 25 25
3 P-18B

P-2A ODOR ODOR EXHAUST SUPPLY SUPPLY ODOR ODOR EXHAUST SUPPLY SUPPLY P-18A SLUICE SLUICE SLUICE
CONTROL CONTROL FAN AIR FAN AIR FAN CONTROL CONTROL FAN AIR FAN AIR FAN GATE GATE GATE
BLOWER BLOWER EF-1 SF-1 SF-2 BLOWER BLOWER EF-2 SF-3 SF-4 SUG-102 SUG-101 SUG-103
MOBILE
GENERATOR BL-1 (FUTURE) BL-2 (FUTURE)
CONNECTION BLOWER CONTROL
MANUAL TRANSFER BLOWER CONTROL SUMP PUMP
BOX PANEL 1 1
SWITCH MTS-1 PANEL CONTROL
600 AMP, 3 POLE PANEL E1A E2A E3A
480/277V OPEN SUMP
P-2B PUMPS
TRANSITION
MCC-E
E2E E3E
SPACE
600 AMP BUS
500AT
3 600AF
E2I E3I

E1K
60 125 70 20 20 20 125 125 20 20 20 20
150 150 150 150 150 150 150 150 150 150 150 150 E1M E2M E3M

SIZE 2 SIZE 1
E2Q E3Q

E2U E3U

P-1 P-11
P-7 P-10
HARMONIC HARMONIC P-16 P-17 P-20
TVSS
FILTER FILTER
(T-1) TRANSFORMER
P-1A 75 KVA 480V P-11A
PRIMARY 120/208
SECONDARY
P-8 P-9 P-19
VFD VFD
MOTOR CONTROL CENTER MCC-E ELEVATION
P-10A
P-1B P-11B NOT TO SCALE
25

PANEL- EUH-2 EUH-3 GATE SPARE


CHOPPER BOARD 5KW 5KW OPERATOR (TYP. FOR 3)
PUMP LP1 UNIT UNIT
HEATER HEATER
64 64
ECH-1 P-10B
EUH-1 HEATING
TANK ELECTRIC TANK
5KW COIL
DEWATERING CABINET DEWATERING
UNIT EDH-1
PUMP HEATER PANEL- PUMP
HEATER 7.5 KW
NO.1 3.3 KW BOARD NO.2
LP2

ONE-LINE DIAGRAM
NOT TO SCALE

SCALE: MRW ONONDAGA COUNTY DEPARTMENT OF WATER ENVIRONMENT PROTECTION File Number
In charge of
006.64
NOT TO SCALE JEC
LOWER HARBOR BROOK CSO STORAGE FACILITY
Designed by
3 9/19/11 ADDENDUM NO. 1 MRW
MOTOR CONTROL CENTER ONE-LINE DIAGRAM Date

THIS DRAWING WAS PREPARED AT THE SCALE INDICATED IN THE


2
1
08/11
04/11
AS BID
ISSUED FOR APPROVAL
MRW
MRW
Drawn by
JEC
SYRACUSE, NEW YORK
08/11 E-301
TITLE BLOCK. INACCURACIES IN THE STATED SCALE MAY BE
INTRODUCED WHEN DRAWINGS ARE REPRODUCED BY ANY
NO. DATE REVISION INT. MRW
Checked by
MEANS. USE THE GRAPHIC SCALE BAR IN THE TITLE BLOCK TO NO ALTERATIONS PERMITTED HEREON EXCEPT AS PROVIDED UNDER SECTION 7209
DETERMINE THE ACTUAL SCALE OF THIS DRAWING. SUBDIVISION 2 OF THE NEW YORK STATE EDUCATION LAW ELECTRICAL
WALL MOUNTED NEXT
M OL T1
TO VFD ENCLOSURE
HARMONIC L1
FILTER OL T2
L1 U T1 CHOPPER
480V,3ɸ L2 M
L1 PUMP
60HZ OL T3
L2 V T2 SUPPLY
3 PHASE INVERTER L3
480V,3ɸ L2 M
DUTY MOTOR
60HZ L3 W T3
SUPPLY L3 G

G
480/120 PRIMARY
50 VA EXTRA
TERMINAL IN STARTER
CAPACITY 120V
DISCONNECT (TYPICAL)
SECONDARY
480V PRIMARY INTERLOCK
50 VA EXTRA
DISCONNECT CAPACITY
INTERLOCK 120V SECONDARY CONTROL STATION
"CS" AT MCC
OFF
53 W HAND AUTO
SPEED SPEED CR1 CR2 CR3 OL
55 W MOTOR STARTER
CONTROL FEEDBACK M
X00 CONTACTOR
CR3 CR4 REMOTE
12 AUTO START

OFF
HAND AUTO
00X
XOO
PLC CONTACT FROM SCADA
M CLOSES TO RUN MOTOR
OUTPUT
18 G RUNNING

OOX RUN
01 02 CR1 ETM ELAPSED TIME METER
CR1
RUN/FAULT M
STATUS TO PUMP MOTOR
FAULT SCADA I/O PROTECTION RELAY RUN STATUS TO
01 03 CR2
MODULE SCADA I/O MODULE
CR2 RESET
RESET
LIQUID LEVEL
WINDING TEMP. SW.'S 400 
SWITCH

+
CR1
G RUNNING
800 

ETM ELAPSED TIME METER


SUBMERSIBLE PUMP MOTOR

PUMP MOTOR MCC-1


CR3
PROTECTION RELAY LEAKAGE &
OVERTEMP 3/4"C w/2-#16 TSP, SPEED CONTROL R LEAKAGE
RESET STATUS TO AND SPEED FEEDBACK
CR4 LEAKAGE
RESET SCADA I/O
LIQUID LEVEL MODULE VARIABLE LEAKAGE
WINDING TEMP. SW.'S 400  { CR1
SWITCH FREQUENCY SHUTDOWN RELAY
TO SCADA SYSTEM
DRIVE
+

MAIN CONTROL PANEL (10 SEC)


(VFD)
R WINDING OVER-TEMPERATURE
800  ELECTRIC SEE
ROOM NOTE 3/4"C w/14-#14, IN-AUTO MODE,
- (101) 1 START/STOP, RUN STATUS, FAULT STATUS, CR2 WINDING OVER-TEMPERATURE
UNCLASSIFIED MOISTURE ALARM, TEMPERATURE ALARM SHUTDOWN RELAY
SUBMERSIBLE PUMP MOTOR WINDING
OVER-TEMPERATURE
1-1/2"C w/3-#2, 1-#6GRD
(PUMP POWER)
R LEAKAGE STORAGE TANK
CLASS I, DIVISION 1, GROUP D 3/4"C w/16-#14 (MOISTURE/TEMPERATURE, GROUND FAULT
LEAKAGE HAZARDOUS AREA GROUND FAULT
LEAKAGE DISC AUX, HOA, IN LOCAL TO PLC, RELAY
RELAY POWER
CR3 SHUTDOWN 5 SPARES)
RELAY GF
(10 SEC)
WINDING OVER- CR3
R
TEMPERATURE
WINDING OVER- SEAL OFF DS CR3
CR4 TEMPERATURE FITTING XP
3/4"C w/2-#14 (DISC. AUX) A GROUND FAULT
SHUTDOWN (TYPICAL)
WINDING RELAY
OVER-TEMPERATURE JUNCTION BOX, PROVIDE
WITH TERMINAL BLOCKS
3/4"C w/5-#14 TO GROUND FAULT
RELAY RESET CONTACTS

JB CS HOA
GROUND FAULT GROUND FAULT
RELAY RELAY POWER XP XP

CHOPPER PUMP CONTROL ELEMENTARY


PUMP MANUFACTURER/SUPPLIER
PROVIDED CABLE ASSEMBLY, WITH NOT TO SCALE
CONDUCTORS FOR PUMP POWER, AND
STRAIN RELIEF MOISTURE/TEMPERATURE SENSOR
GF BUSHING
CR5 SUBMERSIBLE PUMP MOTOR WITH
INTEGRAL MOTOR WINDING THERMAL
64 PROTECTORS AND MOISTURE SENSOR.
CR5
A GROUND FAULT MPMR

NOTE:
TO GROUND FAULT
RELAY RESET CONTACTS 1. MONITORING RELAY FOR TEMPERATURE/MOISTURE SENSOR SHALL BE
PROVIDED BY PUMP MANUFACTURER/SUPPLIER. THE RELAY SHALL BE
PROVIDED TO THE VFD MANUFACTURER FOR INSTALLATION AT THE
FACTORY. THE ELECTRICAL CONTRACTOR SHALL COORDINATE THE
TRANSFER OF THE RELAY WITH THE GENERAL CONTRACTOR.

SCHEMATIC
OOX
H-O-A IN "AUTO" TO SCADA
I/O MODULE
TANK DEWATERING PUMP NO.1 CONTROL ELEMENTARY TANK DEWATERING PUMP NO.1 DIAGRAM
NOT TO SCALE NOT TO SCALE
(TYPICAL FOR PUMP NO. 2)
(TYPICAL FOR TANK DEWATERING PUMP NO.2)

SCALE: MRW ONONDAGA COUNTY DEPARTMENT OF WATER ENVIRONMENT PROTECTION File Number
In charge of
006.64
NOT TO SCALE JEC
LOWER HARBOR BROOK CSO STORAGE FACILITY
Designed by
ELEMENTARY DIAGRAMS Date

THIS DRAWING WAS PREPARED AT THE SCALE INDICATED IN THE


2
1
08/11
04/11
AS BID
ISSUED FOR APPROVAL
MRW
MRW
Drawn by
JEC
SYRACUSE, NEW YORK
08/11 E-302
TITLE BLOCK. INACCURACIES IN THE STATED SCALE MAY BE
INTRODUCED WHEN DRAWINGS ARE REPRODUCED BY ANY
NO. DATE REVISION INT. MRW
Checked by
MEANS. USE THE GRAPHIC SCALE BAR IN THE TITLE BLOCK TO NO ALTERATIONS PERMITTED HEREON EXCEPT AS PROVIDED UNDER SECTION 7209
DETERMINE THE ACTUAL SCALE OF THIS DRAWING. SUBDIVISION 2 OF THE NEW YORK STATE EDUCATION LAW ELECTRICAL
M OL M OL
T1 T1
L1 L1
480V,3ɸ T2 T2
L2 M MOTOR 480V,3ɸ L2 M MOTOR
60HZ 60HZ
SUPPLY T3 SUPPLY T3
L3 L3

G G

480V PRIMARY 480V PRIMARY


DISCONNECT 50 VA EXTRA CAPACITY TERMINAL IN STARTER 50 VA EXTRA CAPACITY TERMINAL IN STARTER
DISCONNECT
INTERLOCK 120V SECONDARY (TYPICAL) 120V SECONDARY (TYPICAL)
INTERLOCK

FIRE ALARM FIRE ALARM


DISABLE OFF DISABLE
FROM FACP HAND AUTO OL FROM FACP START STOP OL
MOTOR MOTOR
M M
STARTER COIL STARTER COIL
X00
REMOTE
AUTO START M
R RUNNING M

CONTACT FROM SCADA I/O RUN/FAULT STATUS


MODULE CLOSES TO RUN ELAPSED FAULT TO SCADA I/O MODULE
MOTOR ETM
00X TIME METER

G OFF
00X H-O-A IN "AUTO"
TO SCADA I/O MODULE
M
ANTI CONDENSATION HEATER

M
R RUNNING M

RUN/FAULT STATUS
SUPPLY FAN SF-3 CONTROL ELEMENTARY
ELAPSED FAULT TO SCADA I/O MODULE NOT TO SCALE
ETM
TIME METER TYPICAL FOR SUPPLY FAN SF-4, EF-1 AND EF-2

G OFF

M IN MCC-N IN BLOWER CONTROL


PANEL
ANTI CONDENSATION HEATER

M OL
T1
L1
2"C w3-#4/0 T2
1-#2 GRD TO 480V,3ɸ L2 M MOTOR
SUPPLY FAN SF-1 CONTROL ELEMENTARY 3/4"C w/4-#14
(FIRE ALARM
MCC-N 60HZ
SUPPLY T3
NOT TO SCALE DISABLE) L3
TYPICAL FOR SUPPLY FAN SF-2
G
2"C w/3-#4/0, 3/4"C w/10-#14
1-#2 GRD TO FACP JB (BL-2 FAULT STATUS,
MCC-N SYSTEM START)
LP1-13

(120 VAC) LP2-5 LP2-4


L N FIRE ALARM 480V PRIMARY
(120V, 1 PHASE) (120V, 1 PHASE) DISABLE 50 VA EXTRA CAPACITY TERMINAL IN STARTER
DISCONNECT
FROM FACP INTERLOCK 120V SECONDARY (TYPICAL)
MANUAL MOTOR PRE-1
STARTING SWITCH MOTOR ODOR CONTROL 3/4"C w/2-#12, ODOR CONTROL 3/4"C w/2-#12,
CR 3/4"C w/10-#14 BLOWER 1-#12 GRD BLOWER 1-#12 GRD
(BL-1 FAULT STATUS,
1/25 PANEL NO.1 PANEL NO.2
SYSTEM START)
START/STOP OL
3/4"C w/2-#14 3/4"C w/4-#14, 3/4"C w/2-#14 3/4"C w/4-#14, MOTOR
OFF M
(START/STOP) (RUN IND, FAIL IND) (START/STOP) (RUN IND, FAIL IND) STARTER COIL
HAND AUTO
CR
X M SYSTEM START
R RUNNING FROM SCADA
COOLING ODOR ODOR M SYSTEM
T'STAT CONTROL CONTROL
X BLOWER BLOWER
LOUVER L-2 BL-1 BL-1 ELAPSED
ACTUATOR ETM
STARTER STARTER TIME METER
CR
IN BLOWER IN BLOWER
PANEL NO.1 PANEL NO.2 OL FAULT STATUS
2"C w/3-#4/0, 2"C w/3-#4/0, R FAULT FAULT TO SCADA SYSTEM
1-#2GRD 1-#2GRD
PRE-1 CONTROL ELEMENTARY
NOT TO SCALE
2"C w/3-#4/0, 2"C w/3-#4/0, G OFF
DS DS
1-#2GRD 1-#2GRD
M
SEAL OFF SEAL OFF ANTI CONDENSATION HEATER
LP1-14

(120 VAC)
L N

ODOR CONTROL BLOWER BL-1 CONTROL ELEMENTARY


MANUAL MOTOR PRE-2 NOT TO SCALE
STARTING SWITCH MOTOR 125 125
TYPICAL FOR ODOR CONTROL BLOWER BL-2
1/20 ODOR CONTROL ODOR CONTROL
BLOWER BL-1 BLOWER BL-2

PRE-2 CONTROL ELEMENTARY ODOR CONTROL BLOWERS BL-1, AND BL-2 SCHEMATIC
NOT TO SCALE NOT TO SCALE
TYPICAL FOR PRE-3 (LP1-13) AND PRE-4 (LP1-14)

SCALE: MRW ONONDAGA COUNTY DEPARTMENT OF WATER ENVIRONMENT PROTECTION File Number
In charge of
006.64
NOT TO SCALE JEC
LOWER HARBOR BROOK CSO STORAGE FACILITY
Designed by
ELEMENTARY DIAGRAMS Date

THIS DRAWING WAS PREPARED AT THE SCALE INDICATED IN THE


2
1
08/11
04/11
AS BID
ISSUED FOR APPROVAL
MRW
MRW
Drawn by
JEC
SYRACUSE, NEW YORK
08/11 E-303
TITLE BLOCK. INACCURACIES IN THE STATED SCALE MAY BE
INTRODUCED WHEN DRAWINGS ARE REPRODUCED BY ANY
NO. DATE REVISION INT. MRW
Checked by
MEANS. USE THE GRAPHIC SCALE BAR IN THE TITLE BLOCK TO NO ALTERATIONS PERMITTED HEREON EXCEPT AS PROVIDED UNDER SECTION 7209
DETERMINE THE ACTUAL SCALE OF THIS DRAWING. SUBDIVISION 2 OF THE NEW YORK STATE EDUCATION LAW ELECTRICAL
3/4"C w/2-#16 (TYPICAL FOR
SMOKE DETECTOR ALL SIGNALING LINE CIRCUITS)
MOUNTED ABOVE FACP
IN HALLWAY 3/4"C w/2-#14 (TYPICAL FOR ALL NOTIFICATION
APPLIANCE CIRCUITS)

UTILITIES BUILDING
STORAGE 1
WP XXXX
WALL
S

203

3/4"C w/4-#14 (FACP


P P P
IN ALARM MODE,
TROUBLE MODE) OFFICE DATA 2
XXXX 1

PBx
WALL
P DATA
3/4"C w2-#12,
3 ELECTRICAL ROOM
1-#12 GRD XXXX

2
FIRE ALARM
CONTROL PANEL
LOCATED IN
HALLWAY X 2
STORAGE TANK AREA
CLASS 1, DIVISION 1, GROUP D AREA
TO NEC DEDICATED
EARTH GROUND
VESTIBULE
S S X XXXX
1

3/4"C w/#10 GRD


NOTE:
INCOMING TELEPHONE SERVICE FROM THE UTILITY POLE
1 3/4"C w/1-2 PR TELEPHONE CABLE
TO TELEPHONE MOUNTING PANEL FURNISHED AND INSTALLED
P BY THE TELEPHONE UTILITY. THE DUCTBANK CONDUITS AND
2 3/4"C w/2-2 PR TELEPHONE CABLE
SERVICE RISER PROVIDED AND INSTALLED UNDER THIS
CONTRACT.
3 3/4"C w/4-2 PR TELEPHONE CABLE

CABLE FURNISHED
TELEPHONE RISER DIAGRAM
BY FACP SUPPLIER SEALOFFS ONLY REQUIRED NOT TO SCALE
RJ-31X RJ-31X CONDUITS EXIT AND ENTER
HAZARDOUS AREAS (TYPICAL)

3/4"C w/1-4 PR
TO TELEPHONE
FIRE ALARM SYSTEM NOTES:
TELEPHONE CABLE
TERMINATION BOARD 1. REFER TO SPECIFICATION SECTION 16721 FOR ADDITIONAL SUBMITTAL,
(TWO SEPARATE TELEPHONE LINES) DEVICE, CONDUIT, WIRING AND INSTALLATION REQUIREMENTS.
2. ALL SYSTEMS SHALL BE A "CLASS A" TYPE SYSTEM.
3. DESIGN RATING OF HEAT DETECTORS IS 40'-0" BEFORE DERATING IS
REQUIRED.
4. ALL STROBES SHALL BE RATED A MINIMUM OF 15 CANDELAS UNLESS CHOPPER PUMP
OTHERWISE NOTED. MOTOR TO SCADA SYSTEM
5. ENCLOSURE AND BOXES SHALL BE COLORED RED. STARTER IN MAIN CONTROL PANEL
6. CONDUIT SHALL BE IDENTIFIED BY A LABEL READING "FIRE" EVERY 10 FEET MCC-E
AND ON EACH SIDE OF WALLS OR FLOORS. ELECTRIC
ROOM 3/4"C w/14-#14, IN-AUTO MODE,
(101) START/STOP, RUN STATUS, FAULT STATUS,
FIRE ALARM SYSTEM RISER DIAGRAM UNCLASSIFIED MOISTURE ALARM, TEMPERATURE ALARM

NOT TO SCALE
3/4"C w/3-#8, 1-#10GRD
(PUMP POWER)
STORAGE TANK
CLASS I, DIVISION 1, GROUP D 3/4"C w/16-#14 (MOISTURE/TEMPERATURE,
HAZARDOUS AREA DISC AUX, HOA, IN LOCAL TO PLC,
COAX CABLE
SCADA 5 SPARES)
460/3 PHASE SYSTEM

3/4"C w/3-#12,
BILL OF MATERIALS 1-#12 GRD 3/4"C w/12-#14 (RUN INDICATION,
GE SECURITY 19 INCH TRU-VISION LCD MONITOR HIGH WATER LEVEL, FLOOD SEAL OFF DS
(1) #GEL-19DV ALARM, COMMON FAIL) FITTING XP
(TYPICAL) 3/4"C w/2-#14 (DISC. AUX)
GE SECURITY TRU-VISION DVR 10 4-CHANNEL DIGITAL VIDEO RECORDER MONITOR SUMP PUMP
DIGITAL VIDEO 120V
(1) #TVR-1004-500 CONTROL
GE SECURITY TRU-VISION 540 TVL CAMERAS RECORDER JUNCTION BOX, PROVIDE
PANEL IN
(3) #TVP-12C-E w/TVP-ESB MECHANICAL WITH TERMINAL BLOCKS
ROOM MECHANICAL ROOM 3/4"C w/5-#14
UNCLASSIFIED
120V
JB CS HOA
XP XP

2"C w/MANUFACTURERS STORAGE AREA STAIRWELL


CABLE CLASS I, DIVISION 1, GROUP D PUMP MANUFACTURER/SUPPLIER
HAZARDOUS AREA PROVIDED CABLE ASSEMBLY, WITH
C-301 C-302 C-303 CONDUCTORS FOR PUMP POWER, AND
STRAIN RELIEF MOISTURE/TEMPERATURE SENSOR
DS DS JB 3/4"C w/10-#14 BUSHING
NOTES: XP XP
1. COORDINATE THE EXACT LOCATION OF THE EQUIPMENT SUBMERSIBLE PUMP MOTOR WITH
LP2-6 LP2-6 LP2-6 WITH THE OWNER. INTEGRAL MOTOR WINDING THERMAL
STRAIN RELIEF BUSHING MANUFACTURERS 25 PROTECTORS AND MOISTURE SENSOR.
(120V) (120V) (120V) 2. PROVIDE A MINIMUM OF FOUR HOURS TRAINING FOR
CABLE
OWNERS PERSONNEL.
3. EQUIPMENT SPECIFIED IS GE SECURITY OR AS MPMR
APPROVED BY OWNER.
FLOOD LEVEL FLOAT
NOTE:
HIGH LEVEL FLOAT 1. MONITORING RELAY FOR TEMPERATURE/MOISTURE SENSOR SHALL BE PROVIDED BY
PUMP MANUFACTURER/SUPPLIER. THE RELAY SHALL BE PROVIDED TO THE MCC
1 1 LAG PUMP START FLOAT MANUFACTURER FOR INSTALLATION AT THE FACTORY. THE ELECTRICAL
CAMERA @ CAMERA @ CAMERA @ LEAD PUMP START FLOAT CONTRACTOR SHALL COORDINATE THE TRANSFER OF THE RELAY WITH THE
ENTRANCE JUNCTION FLAP GATE MPMR MPMR GENERAL CONTRACTOR.
PUMP STOP FLOAT
CHAMBER STRUCTURE
SUMP SUMP
PUMP PUMP SCHEMATIC
MOTOR MOTOR
CCTV RISER DIAGRAM
CHOPPER PUMP DIAGRAM
NOT TO SCALE STAIRWELL SUMP PUMP SCHEMATIC NOT TO SCALE
NOT TO SCALE

SCALE: MRW ONONDAGA COUNTY DEPARTMENT OF WATER ENVIRONMENT PROTECTION File Number
In charge of
006.64
NOT TO SCALE JEC
LOWER HARBOR BROOK CSO STORAGE FACILITY
Designed by
FIRE, SECURITY & TELEPHONE SCHEMATICS Date

THIS DRAWING WAS PREPARED AT THE SCALE INDICATED IN THE


2
1
08/11
04/11
AS BID
ISSUED FOR APPROVAL
MRW
MRW
Drawn by
JEC
SYRACUSE, NEW YORK
08/11 E-304
TITLE BLOCK. INACCURACIES IN THE STATED SCALE MAY BE
INTRODUCED WHEN DRAWINGS ARE REPRODUCED BY ANY
NO. DATE REVISION INT. MRW
Checked by
MEANS. USE THE GRAPHIC SCALE BAR IN THE TITLE BLOCK TO NO ALTERATIONS PERMITTED HEREON EXCEPT AS PROVIDED UNDER SECTION 7209
DETERMINE THE ACTUAL SCALE OF THIS DRAWING. SUBDIVISION 2 OF THE NEW YORK STATE EDUCATION LAW ELECTRICAL
EQUIPMENT IN MOTOR CONTROL CENTER MCC-N
Branch Panel: LP1 CIRCUIT BREAKER STARTER FIELD MOUNTED DEVICES SEE ELEMENTARY
COMP. EQUIP EQUIPMENT DOOR MOUNTED
Location: ELECTRIC 101 Volts: 120/208 Wye A.I.C. Rating: LOAD OR SCHEMATIC
NO. NO. DESCRIPTION TRIP FRAME SIZE TYPE ACCESSORIES BY ELECTRICAL BY OTHERS DIAGRAM ON SHEET
Supply From: T-1 Phases: 3 Mains Type:
N1A MCB-N MAIN CIRCUIT BREAKER FOR -- 1600AT 3000AF -- -- CBDH, NP -- -- 100%
Mounting: Surface Wires: 4 Mains Rating: 225 A
MAIN FEEDER MF-A RATED CB
Enclosure: Type 1 MCB Rating: 225 A
N2A PM POWER METER- (FEEDER MF-A) -- -- -- -- -- NP --
-- --
N2E TVSS TRANSIENT VOLTAGE SURGE SUPPRESSOR -- 60 150 -- -- CBDH, NP -- -- --

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT N2G BL-1 ODOR CONTROL BLOWER 125 HP 225 250 - -- CBDH, NP, DS -- E-302
1 ELECTRIC ROOM 101 RECEPTACLES 20 A 1 360 VA 540 VA 1 20 A OFFICE 107 RECEPTACLES 2 RUN IND, FAIL IND
3 ELECTRIC ROOM 101 LIGHTING 20 A 1 384 VA 128 VA 1 20 A HALL 102, BATH 106 RECEPTACLES 4 N2M -- ODOR CONTROL BLOWER (FUTURE) -- 225 250 -- -- -- -- -- --
5 MECH. RM 105, HALL 102, VEST. 103 LIGHTING 20 A 1 256 VA 192 VA 1 20 A OFFICE 107, BATH 106 LIGHTING 6
7 EXTERIOR LIGHTS 20 A 1 0 VA 0 VA 1 20 A MECHANICAL ROOM RECEPTACLES 8 N2S EF-1 EXHAUST FAN EF-1 15 HP 40 150AF 2 -- CBDH, NP, DS -- E-303
9 EBH-1 20 A 2 500 VA 600 VA 2 20 A PTAC-1 10 RUN IND, FAIL IND
11 -- -- -- 500 VA 600 VA -- -- -- 12
N3A SF-1 SUPPLY AIR FAN 15 HP 40 250AF 2 -- CBDH, NP, DS, CS -- E-303
13 PRE-1 AND PRE-3 20 A 1 120 VA 600 VA 1 20 A PRE-2 AND PRE-4 14 RUN IND, FAIL IND
15 SUPPLY FAN SF-5 20 A 1 300 VA 420 VA 1 20 A CENTER FLUSH CONTROL PANEL 16
N3E SF-2 SUPPLY AIR FAN 15 HP 40 250AF 2 -- CBDH, NP, DS, CS -- E-303
17 FIRE ALARM CONTROL PANEL 20 A 1 600 VA 120 VA 1 15 A LEVEL TRANSMITTER LIT-203, LIT-204 18
RUN IND, FAIL IND
19 BATTERY CABINET 20 A 1 200 VA 360 VA 1 20 A SCADA SYSTEM ENCLOSURE 20
N3I - SPARE - - - 2 -- CBDH, NP
21 LEVEL TRANS. LIT-200, LIT-201, LIT-202 15 A 1 180 VA 2000 3 25 A ELECTRIC WATER HEATER 22
23 GFI RECEPTACLE @ JUNCTION CHAMBER 20 A 1 180 VA 2000 -- -- -- 24
N3M MTS-1 MANUAL TRANSFER SWITCH -- 300 400AF -- -- NP -- -- --
25 DAMPER D-1 20 A 1 120 VA 2000 -- -- -- 26
27 STORAGE TANK LIGHTS 20 A 1 960 VA 80 VA 1 15 A FLOW TRANSMITTER FIT-200 28
29 STORAGE TANK LIGHTS 20 A 1 896 VA 490 VA 1 20 A EXIT LIGHTS 30 N4A BL-2 ODOR CONTROL BLOWER 125 HP 225 250 -- -- DS -- E-302
31 STORAGE TANK TASK LIGHTING 20 A 1 875 VA 700 VA 1 20 A STORAGE TANK ROOF TASK LIGHTING 32
33 MOBILE GENERATOR CONNECTION BOX 20 A 1 200 VA 0 VA 1 20 A SPARE 34 N4G -- ODOR CONTROL BLOWER (FUTURE) -- 225 250 -- -- -- -- -- --
35 SPARE 20 A 1 0 VA 80 VA 1 20 A EMERGENCY CALL PUSHBUTTON 36
37 STAIR 104 & STORAGE TANK STAIRWELL 20 A 1 64 VA 0 VA 1 20 A Spare 38 N4M EF-2 EXHAUST FAN EF-2 15 HP 40 150AF 2 -- CBDH, NP, DS -- E-303
RUN IND, FAIL IND
39 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 40
41 Spare 20 A 1 0 VA 0 VA 1 20 A Spare 42 N4Q SF-3 SUPPLY AIR FAN 25 HP 70 150AF 2 -- CBDH, NP, DS -- E-303
Total Load: 5939 VA 5752 VA 5914 VA RUN IND, FAIL IND

Total Amps: 49 A 48 A 49 A N4U - SPARE - - - 2 -- CBDH, NP,


RUN IND, FAIL IND
N5A SF-4 SUPPLY AIR FAN 25 HP 70 150AF 2 -- CBDH, NP, DS -- E-303
RUN IND, FAIL IND

N5E -- SUMP PUMP CONTROL PANEL 2-1HP 20 150AF -- -- CBDH, NP DS -- --


PUMPS RUN IND

Branch Panel: LP2 N5I-


N5U
- SPARE - - - 1 -- CBDH, NP

Location: ELECTRIC 101 Volts: 120/208 Wye A.I.C. Rating:


N6A SUG-1 JUNCTION CHAMBER SLUICE GATE 5 HP 20 150AF - -- CBDH, NP, DS --
Supply From: Phases: 3 Mains Type:
RUN IND, FAIL IND -
Mounting: Surface Wires: 4 Mains Rating: 100 A
Enclosure: Type 1 MCB Rating: 100 A N6E SUG-2 JUNCTION CHAMBER SLUICE GATE 5 HP 20 150AF - -- CBDH, NP, DS -- -
RUN IND, FAIL IND

N6I SUG-3 JUNCTION CHAMBER SLUICE GATE 5 HP 20 150AF - -- CBDH, NP, DS -- -


RUN IND, FAIL IND

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT N6M - SPACE
1 DAVIT CRANE 20 A 1 300 VA 175 VA 1 20 A FLAP VALVE STRUCTURE LIGHTING 2
3 SITE LIGHTING 20 A 1 525 VA 540 VA 1 20 A ODOR CONTROL BLOWER PANEL NO.2 4
5 ODOR CONTROL BLOWER PANEL NO.1 20 A 1 540 VA 405 VA 1 20 A SITE SECURITY CAMERAS 6 EQUIPMENT IN MOTOR CONTROL CENTER MCC-E
7 STORAGE TANK RECEPTACLES 20 A 1 360 VA 135 VA 1 20 A SECURITY GATE CARD READER 8
E1A - SPACE - - - -- -- - - -- --
9 OCV-1 & OCV-2 2" DRAIN PIPING HEAT TRACE 20 A 1 200 VA 10
11 12
13 14 E1K TVSS TRANSIENT VOLTAGE SURGE SUPPRESSOR - 60 150AF -- -- CBDH, NP - -- --
15 16
17 18 E1M MCB-E MAIN CIRCUIT BREAKER - 300 400AF -- -- CBDH, NP - -- --
19 20 500 600AF
21 22 E2A -- TANK DEWATERING PUMP 64 HP 125 150 VFD -- CBDH, NP, DS, CS -- E-302
23 24 NO.1 RUN IND, FAIL IND
25 26 E2E -- CHOPPER PUMP 25 HP 70 150 2 FVNR CBDH, NP, DS, CS -- --
27 28 RUN IND, FAIL IND
29 30 E2I EUH-1 UNIT HEATER 5 KW 20 150AF -- -- DS -- --
CBDH, NP
31 32
33 34
E2M ECH-1 ELECTRIC CABINET HEATER 3.3 KW 20 150AF -- -- CBDH, NP DS -- --
35 36
37 38
E2Q EDH-1 HEATING COIL 7.5 KW 20 150AF -- -- CBDH, NP DS -- --
39 40
41 42
E2U - SPARE - 20 150AF 1 FVNR CBDH, NP - -- --
Total Load: 970 VA 1265 VA 945 VA
Total Amps: 8A 11 A 8A
E3A -- TANK DEWATERING 64 HP 125 150 VFD -- CBDH, NP, DS, CS -- E-302
PUMP NO.2 RUN IND, FAIL IND

E3E EUH-2 ELECTRIC UNIT HEATER 5 KW 20 150AF -- -- CBDH, NP DS -- --


PANELBOARD GENERAL NOTES:
1. FOR THREE PHASE CIRCUITS - PROVIDE 3/4"C w/3-#12, 1-#12G FOR 20 AMP E3I EUH-3 ELECTRIC UNIT HEATER 5 KW 20 150AF -- -- CBDH, NP DS -- --
CIRCUITS SERVING EQUIPMENT WITHIN 60' OF PANELBOARD, UNLESS
OTHERWISE NOTED. INCREASE WIRE AND CONDUIT SIZES IN ACCORDANCE
WITH SPECIFICATION SECTIONS 16110, 16120, AND THE NEC FOR LONGER E3M -- ENTRANCE GATE OPERATOR 1HP 20 150AF -- -- - - -- --
CIRCUITS OR CIRCUITS MORE THAN 20 AMPS.
2. FOR SINGLE PHASE CIRCUITS - PROVIDE 3/4"C w2-#12, 1-#12 GRD FOR 20
E3Q - - SPARE - - - 1 -- CBDH, NP - -- --
AMP CIRCUITS SERVING EQUIPMENT WITHIN 60' OF PANELBOARD, UNLESS E3U
OTHERWISE NOTED. INCREASE WIRE AND CONDUIT SIZE IN ACCORDANCE
WITH SPECIFICATION SECTIONS 16120, 16110, AND NEC FOR LONGER
CIRCUITS OR CIRCUITS MORE THAN 20 AMPS.
3. ALL RECEPTACLE CIRCUITS SHALL BE POWERED THROUGH A GFCI CIRCUIT
BREAKER , EXCEPT AS FOLLOWS:
LEGEND
A. WHEN THE DISTANCE TO THE FIRST RECEPTACLE IS OVER 50' IN
LENGTH, USE A STANDARD CIRCUIT BREAKER AND PROVIDE A CBDH - CIRCUIT BREAKER DISCONNECT HANDLE
FEED THROUGH GFCI TYPE RECEPTACLE. CS - CONTROL STATION
B. ALL RECEPTACLES MOUNTED IN LIGHT POLES OR ON HANDRAIL DS - DISCONNECT SWITCH
SHALL BE GFCI TYPE. FAIL IND - FAIL INDICATING LIGHT
C. PROVIDE GFCI RECEPTACLES AT ALL LOCATIONS WHERE NP - NAMEPLATE
RECEPTACLES ARE MORE THAN 50' APART. RUN IND - RUN INDICATING LIGHT
D. PROVIDE GFCI RECEPTACLES FOR ALL SINGLE PHASE CORD
CONNECTED, SUBMERSIBLE PUMP, MIXERS, ETC.
4. FOR HEAT TRACE CIRCUITS PROVIDE GFCI, 30mA CIRCUIT BREAKERS
(ADDENDUM NO. 1)

SCALE: MRW ONONDAGA COUNTY DEPARTMENT OF WATER ENVIRONMENT PROTECTION File Number
In charge of
006.64
NOT TO SCALE JEC
LOWER HARBOR BROOK CSO STORAGE FACILITY
Designed by
SCHEDULES Date

THIS DRAWING WAS PREPARED AT THE SCALE INDICATED IN THE


2
1
08/11
04/11
AS BID
ISSUED FOR APPROVAL
MRW
MRW
Drawn by
JEC
SYRACUSE, NEW YORK
08/11 E-305
TITLE BLOCK. INACCURACIES IN THE STATED SCALE MAY BE
INTRODUCED WHEN DRAWINGS ARE REPRODUCED BY ANY
NO. DATE REVISION INT. MRW
Checked by
MEANS. USE THE GRAPHIC SCALE BAR IN THE TITLE BLOCK TO NO ALTERATIONS PERMITTED HEREON EXCEPT AS PROVIDED UNDER SECTION 7209
DETERMINE THE ACTUAL SCALE OF THIS DRAWING. SUBDIVISION 2 OF THE NEW YORK STATE EDUCATION LAW ELECTRICAL
POWER CONDUCTOR AND CONDUIT SCHEDULE CONTROL CONDUCTOR AND CONDUIT SCHEDULE
CONDUIT CONDUCTORS
DESIGNATION FROM TO REMARKS CONDUIT CONDUCTORS
SIZE QTY/SIZE DESIGNATION FROM TO REMARKS
SIZE QTY/SIZE

PRIMARY PAD MOUNTED 3(4")


PF-1 PULLWIRE PRIMARY CONDUCTORS BY UTILITY MOTOR CONTROL CENTER SCADA SYSTEM MAIN CONTROL
SERVICE POLE TRANSFORMER 1 SPARE C-001 2" 90-#14 INCLUDES SPARES
MCC-1 PANEL
INCOMING MOTOR CONTROL CENTER 5-500 MCM PER PHASE
MF-A 5(4") - MOTOR CONTROL CENTER SCADA SYSTEM MAIN CONTROL
UTILITY TRANSFORMER "A" MAIN CIRCUIT BREAKER 5-#4/0 GRD C-002 2" 10-#16 TSP INCLUDES SPARES
MCC-1 PANEL
MOTOR CONTROL CENTER TANK DEWATERING PUMP NO.1 3-#2
P-1 1 1/2" - SCADA SYSTEM MAIN CONTROL ETHERNET HUB
MCC-E LINE REACTOR #6 GRD C-003 3/4" 1-CAT 6 CABLE -
PANEL SCADA SYSTEM OFFICE
TANK DEWATERING PUMP NO.1 TANK DEWATERING PUMP NO.1 3-#2
P-1A 1 1/2" - SCADA SYSTEM MAIN CONTROL ODOR CONTROL PANEL
LINE REACTOR VFD #6 GRD C-004 3/4" 1-CAT 6 CABLE -
PANEL BLOWER BL-1
TANK DEWATERING PUMP NO.1 TANK DEWATERING 3-#2
P-1B 1 1/2" - SCADA SYSTEM MAIN CONTROL ODOR CONTROL PANEL
VFD PUMP NO.1 #6 GRD, 2-#14 C-005 3/4" 1-CAT 6 CABLE -
PANEL BLOWER BL-2
MOTOR CONTROL CENTER MANUAL TRANSFER SWITCH 2-#250 MCM PER PHASE
P-2 2(3") - SCADA SYSTEM MAIN CONTROL CIRCULAR TANK FLUSHING SYSTEM
MCC-N MTS-1 2-#2 GRD C-006 3/4" 1-CAT 6 CABLE -
PANEL CONTROL PANEL
MANUAL TRANSFER SWITCH MOBILE GENERATOR 2-#250 MCM PER PHASE
P-2A 2(3") - SCADA SYSTEM MAIN CONTROL GAS MONITOR TRANSMITTER/
MTS-1 CONNECTION BOX 2-#2 GRD C-007 3/4" 1-CAT 6 CABLE -
PANEL INDICATOR (AIT-214) VESTIBULE 103
MANUAL TRANSFER SWITCH MOTOR CONTROL CENTER 2-#250 MCM PER PHASE
P-2B 2(3") 3 - SCADA SYSTEM MAIN CONTROL EMERGENCY CALL
MTS-1 MCC-E 2-#2 GRD C-008 3/4" 2-#14
PANEL STATION
MOTOR CONTROL CENTER ODOR CONTROL BLOWER BL-1 3-#4/0
P-3 2" - ELECTRIC ROOM ENTRANCE GATE
MCC-N CONTROL PANEL #2 GRD C-009 1" PULLWIRE STUB-UP 6" AFF AND CAP
(NORTH WALL) OPERATOR
ODOR CONTROL BLOWER BL-1 ODOR CONTROL BLOWER 3-#4/0
P-3A 2" - FIRE ALARM MOTOR CONTROL CENTER
CONTROL PANEL MOTOR BL-1 #2 GRD, 2-#14 C-010 3/4" 2-#14 FIRE ALARM DISABLE ALARM
CONTROL PANEL MCC-1
ODOR CONTROL BLOWER BL-1 DAMPER 2-#12
P-3B 3/4" FIRE ALARM ODOR CONTROL PANELS FIRE ALARM DISABLE ALARM
CONTROL PANEL D-1 1-#12 GRD C-011 3/4" 4-#14
CONTROL PANEL BLOWER BL-1 & BL-2 2 CONDUCTORS TO EACH BLOWER PANEL
MOTOR CONTROL CENTER EXHAUST FAN 3-#8
P-4 3/4" -
MCC-N EF-1 1-#10 GRD, 2-#14
MOTOR CONTROL CENTER SUPPLY AIR FAN 3-#8
P-5 3/4" - SCADA SYSTEM MAIN CONTROL SLUICE GATE ACTUATOR
MCC-N SF-1 1-#10 GRD, 2-#14 C-101 3/4" 10-#14
PANEL SUG-101
MOTOR CONTROL CENTER SUPPLY AIR FAN 3-#8
P-6 3/4" - SCADA SYSTEM MAIN CONTROL SLUICE GATE ACTUATOR
MCC-N SF-2 1-#10 GRD, 2-#14 C-102 3/4" 10-#14
PANEL SUG-102
MOTOR CONTROL CENTER CHOPPER 3-#4
P-7 1" - SCADA SYSTEM MAIN CONTROL SLUICE GATE ACTUATOR
MCC-E PUMP 1-#8 GRD, 2-#14 C-103 3/4" 10-#14
PANEL SUG-103
MOTOR CONTROL CENTER EUH-1 UNIT HEATER 3-#12
P-8 3/4" - SCADA SYSTEM MAIN CONTROL LSH-100 LEVEL SWITCH HIGH
MCC-E 5 KW 1-#12 GRD C-104 3/4" 2-#14
PANEL AT JUNCTION CHAMBER
MOTOR CONTROL CENTER ECH-1 ELECTRIC CABINET HEATER 3-#12
P-9 3/4" - SCADA SYSTEM MAIN CONTROL LSH-101 LEVEL SWITCH HIGH
MCC-E 3.3 KW 1-#12 GRD C-105 3/4" 2-#14
PANEL AT JUNCTION CHAMBER
MOTOR CONTROL CENTER TRANSFORMER T-1 3-#1
P-10 1 1/2" -
MCC-E 75 KVA 1-#6 GRD
TRANSFORMER T-1 PANELBOARD 4-#4/0
P-10A 2 1/2" - SCADA SYSTEM MAIN CONTROL WET WELL LEVEL SWITCH
75 KVA LP1 1-#4 GRD C-200 3/4" 4-#14 SEE P&ID SHEET I-101
PANEL LOW LSL-200, LSL-201
PANELBOARD PANELBOARD 4-#2
P-10B 1 1/4" - CIRCULAR TANK FLUSHING SYSTEM SUBMERSIBLE LEVEL TRANSDUCER
LP1 LP2 1-#8 GRD C-205 3/4" MANUFACTURERS CABLE SEE P&ID SHEET I-101
CONTROL PANEL LE-205
MOTOR CONTROL CENTER TANK DEWATERING PUMP NO.2 3-#2
P-11 1 1/2" - CIRCULAR TANK FLUSHING SYSTEM LS-205A
MCC-E LINE REACTOR #6 GRD C-205A 3/4" 4-#14 SEE P&ID SHEET I-101
CONTROL PANEL HIGH AND LOW LEVEL SWITCHES
TANK DEWATERING PUMP NO.2 TANK DEWATERING PUMP NO.2 3-#2
P-11A 1 1/2" - LS-205B CIRCULAR TANK FLUSHING SYSTEM
LINE REACTOR VFD #6 GRD C-205B 3/4" 2-#14 SEE P&ID SHEET I-101
RAINWATER STORAGE TANK CONTROL PANEL
TANK DEWATERING PUMP NO.2 TANK DEWATERING 3-#2
P-11B 1 1/2" - CIRCULAR TANK FLUSHING SYSTEM START/STOP CONTROL
VFD PUMP NO.2 #6 GRD, 2-#14 C-205C 3/4" 2-#14 SEE P&ID SHEET I-101
CONTROL PANEL STATION @ CATWALK DOOR
MOTOR CONTROL CENTER ODOR CONTROL BLOWER BL-2 3-#4/0
P-12 2" SCADA SYSTEM MAIN CONTROL SUMP PUMP INCLUDES SPARES,
MCC-N CONTROL PANEL #2 GRD C-206 3/4" 12-#14
PANEL CONTROL PANEL SEE P&ID SHEET I-101
ODOR CONTROL BLOWER BL-2 ODOR CONTROL BLOWER 3-#4/0
P-12A 2" - SCADA SYSTEM MAIN CONTROL UPPER LEVEL TANK DOOR
CONTROL PANEL MOTOR BL-2 #2 GRD, 2-#14 C-207 3/4" 6-#14 INCLUDES SPARES
PANEL LIMIT SWITCH AT CATWALK
ODOR CONTROL BLOWER BL-2 DAMPER 2-#12
P-12B 3/4" SCADA SYSTEM MAIN CONTROL LOWER LEVEL TANK DOOR
CONTROL PANEL D-2 1-#12 GRD C-208 3/4" 6-#14 INCLUDES SPARES
PANEL LIMIT SWITCH
MOTOR CONTROL CENTER EXHAUST FAN 3-#8
P-13 3/4" -
MCC-N EF-2 1-#10 GRD,2-#14
MOTOR CONTROL CENTER SUPPLY AIR FAN 3-#4
P-14 1" - SCADA SYSTEM MAIN CONTROL LIMIT SWITCHES AT
MCC-N SF-3 1-#8 GRD, 2-#14 C-300 3/4" 8-#14 SEE P&ID SHEET I-101
PANEL FLAP VALVE STRUCTURE
MOTOR CONTROL CENTER SUPPLY AIR FAN 3-#4
P-15 1" - SECURITY SYSTEM SECURITY CAMERA AT
MCC-N SF-4 1-#8 GRD, 2-#14 C-301 3/4" COAX CABLE SEE SHEETS E-304 & E-309
MULTIPLEXER ENTRANCE GATE
MOTOR CONTROL CENTER EUH-2 UNIT HEATER 3-#12
P-16 3/4" - SECURITY SYSTEM SECURITY CAMERA AT
MCC-E 5 KW 1-#12 GRD C-302 3/4" COAX CABLE SEE SHEETS E-304 & E-309
MULTIPLEXER JUNCTION CHAMBER
MOTOR CONTROL CENTER EUH-3 UNIT HEATER 3-#12
P-17 3/4" - SECURITY SYSTEM SECURITY CAMERA AT
MCC-E 5 KW 1-#12 GRD C-303 3/4" COAX CABLE SEE SHEETS E-304 & E-309
MULTIPLEXER FLAP GATE STRUCTURE
MOTOR CONTROL CENTER SUMP PUMP 3-#12
P-18 3/4" -
MCC-N CONTROL PANEL 1-#12 GRD
SUMP PUMP SUMP PUMP 3-#12
P-18A 3/4" -
CONTROL PANEL NO.1 1-#12 GRD
SUMP PUMP SUMP PUMP 3-#12
P-18B 3/4" -
CONTROL PANEL NO.2 1-#12 GRD
MOTOR CONTROL CENTER HEATING COIL EDH-1 3-#12
P-19 3/4" -
MCC-E 7.5 KW 1-#12 GRD
MOTOR CONTROL CENTER ENTRANCE GATE 3-#12
P-20 3/4" -
MCC-N OPERATOR 1-#12 GRD
ELECTRIC ROOM ENTRANCE GATE
P-21
(NORTH WALL) OPERATOR
1" PULLWIRE STUB-UP 6" AFF AND CAP NOTES:
MOTOR CONTROL CENTER SLUICE GATE 1. WHERE PRACTICAL CONTRACTOR MAY COMBINE CIRCUITS INTO ONE CONDUIT. WHEN DOING SO
P-22 1" PULLWIRE -
MCC-N SUG-102 CONTRACTOR IS RESPONSIBLE FOR DE-RATING CONDUCTORS AND CONDUIT FILL REQUIREMENTS IN
MOTOR CONTROL CENTER SLUICE GATE ACCORDANCE WITH ALL APPLICABLE CODES OF THE NATIONAL ELECTRICAL CODE (NEC).
P-23 1" PULLWIRE - 2. THE MAXIMUM PULLING TENSION FOR CONDUCTORS OR CABLES SHALL NOT EXCEED THE MAXIMUM
MCC-N SUG-101
RECOMMENDED MANUFACTURER PULLING TENSION. WHEN PULLING CABLES WHICH EXCEED 300 FEET
MOTOR CONTROL CENTER SLUICE GATE
P-24 1" PULLWIRE - IN LENGTH WITH A MECHANICAL PULLING DEVICE, THE CONTRACTOR SHALL SUBMIT CABLE PULLING
MCC-N SUG-103 CALCULATIONS TO THE OWNER FOR APPROVAL PRIOR TO STARTING OF THE PULL. NO
CALCULATIONS ARE REQUIRED IF PULLED BY HAND (MANPOWER ONLY).
3. NO WIRE OR CABLE SHALL BE PULLED UNTIL AFTER THE CONDUIT SYSTEM HAS BEEN COMPLETELY
INCOMING PRIMARY MAIN TELEPHONE EQUIPMENT AND THOROUGHLY SWABBED OF ALL FOREIGN MATERIAL. WHEN PULLING WIRES OR CABLES INTO
T-1 2" PULLWIRE - CONDUITS, ONLY AN APPROVED INERT PULLING COMPOUND MAY BE USED.
SERVICE POLE MOUNTING PANEL

SCALE: MRW ONONDAGA COUNTY DEPARTMENT OF WATER ENVIRONMENT PROTECTION File Number
In charge of
006.64
NOT TO SCALE JEC
LOWER HARBOR BROOK CSO STORAGE FACILITY
Designed by
3 9/19/11 ADDENDUM NO. 1 MRW
CONDUIT SCHEDULES Date

THIS DRAWING WAS PREPARED AT THE SCALE INDICATED IN THE


2
1
08/11
04/11
AS BID
ISSUED FOR APPROVAL
MRW
MRW
Drawn by
JEC
SYRACUSE, NEW YORK
08/11 E-306
TITLE BLOCK. INACCURACIES IN THE STATED SCALE MAY BE
INTRODUCED WHEN DRAWINGS ARE REPRODUCED BY ANY
NO. DATE REVISION INT. MRW
Checked by
MEANS. USE THE GRAPHIC SCALE BAR IN THE TITLE BLOCK TO NO ALTERATIONS PERMITTED HEREON EXCEPT AS PROVIDED UNDER SECTION 7209
DETERMINE THE ACTUAL SCALE OF THIS DRAWING. SUBDIVISION 2 OF THE NEW YORK STATE EDUCATION LAW ELECTRICAL
5 HEAVY DUTY BACK-TO-BACK
FIBERGLASS OR GLASS FIBER-REINFORCED
2 POLYESTER ELECTRIC CHANNEL

4 ADDITIONAL ELECTRIC CHANNEL


SUPPORT BRACING AS REQUIRED WALL THICKNESS
TO PROVIDE FOR A RIGID MOUNTING
3/4" STAND. INTERIOR OR ACCESSIBLE WALL
7/16"
2" CONCRETE EQUIPMENT FIBERGLASS

2" MIN.
PAD MOUNTING PLATE
5/8" DIA. S.S. BOLTS STAINLESS STEEL AND NEOPRENE
(TYPICAL) MECHANICAL SEAL PYRO-PAK BY

6'-6" MAX.
4'-6" MIN.
THUNDERLINE CORP. OR EQUAL.
3 ANGLE

10" MIN.
1 5/8" S.S. THREADED COORDINATE SLEEVE SIZE AND

5" MIN.
ROD (TYP. OF 4) O.D. OF PIPE WITH MECHANICAL
1" SEAL MFG.
5/8" S.S. NUT
HEAVY DUTY FIBERGLASS OR
LEGEND GLASS FIBER-REINFORCED 1/4" STEEL SLEEVE: FOR FINISH
6"X6" POST
POLYESTER ELECTRIC CHANNEL BASE SEE SPECIFICATIONS, INSIDE
1 - COPPER GROUND BAR, 1/4"x4"x36", NEWTON INSTRUMENT CO. CAT. NO. 2100360010. 5/8" LEVELING/ 1" PROCESS PIPING AND PAINTING
HOLE CENTERS TO MATCH NEMA DOUBLE LUG CONFIGURATION. SPACING NUT TYP. SLEEVE PROVIDED BY MECHANICAL
2 - INSULATORS, NEWTON INSTRUMENT CAT. NO. 00306150810. MIN. 1" SPACE SEAL MANUFACTURER. FILL VOID
3 - 5/8" LOCKWASHERS, NEWTON INSTRUMENT CO. CAT. NO. 0030150810 WITH FIRE RATED NON-SHRINK
4 - WALL MOUNTING BRACKET, NEWTON INSTRUMENT CO. CAT. NO. 00030630400. 1" NON-SHRINK GROUT.
5 - 5/8-11x1"H.H.C.S. BOLTS, NEWTON INSTRUMENT CO. CAT. NO. 0030120110. GROUT FOR THREADED RODS PRE-MEASURED, GROUT
2 PART, SELF MIXING, CARTRIDGE TYPE EPOXY 6"
ADHESIVE, PARAMOUNT HVC BY MOLLY, EDCON EMBEDMENT TYPICAL CONDUIT
GROUND BAR DETAIL SYSTEM BY RAMSEY/REDHEAD OR EQUAL.
THROUGH FIRE RATED BLOCK WALL
NOT TO SCALE NOT TO SCALE
CONCRETE SLAB
GROUT FOR THREADED RODS PRE-MEASURED,
SIDE MOUNTED ON EQUIPMENT FREE STANDING 2 PART, SELF MIXING, CARTRIDGE TYPE EPOXY
ADHESIVE, PARAMOUNT HVC BY MOLLY, EDCON
GROUND CABLE TO PAD OR CONCRETE CURB SYSTEM BY RAMSEY/REDHEAD OR EQUAL
EQUIPMENT, ETC.
ITEMS LARGER THAN 4" X 4" SHALL BE INSTALLED ON A MOUNTING PLATE. TWO POSTS ARE
NON-METALLIC 1" PVC CONDUIT BEND REQUIRED FOR ENCLOSURES WIDER THAN 8". MOUNTING PLATES SHALL BE 1/4" TH.
BUSHING FIBERGLASS PLATE 2" GREATER ON EACH SIDE THAN DIMENSION OF ENCLOSURE(S). ROUND WALL THICKNESS
TOP OF FINISHED SLAB ALL CORNERS AND EDGES. EDGES SHALL BE COATED AND SMOOTHED TO REMOVE LOOSE
FIBERS. EQUIPMENT MOUNTING SHALL BE WITH S. S. FASTENERS. SINGLE POST MOUNTING INTERIOR OR
PLATES AND MULTIPLE POST MOUNTING PLATES SHALL BE SECURED TO POSTS VIA 3/8" DIA. ACCESSIBLE WALL
GROUND CABLE TO RUN IN S.S. FASTENERS. ALL S.S. FASTENERS SHALL BE TYPE 316.
SLAB (SIZE AS REQUIRED)
4"

FILL VOID WITH FIRE


STAINLESS STEEL & RATED NON-SHRINK
NEOPRENE MECHANICAL
TYPICAL NON-METALLIC MOUNTING PANELS SEAL PYRO-PAK BY
GROUT

NOT TO SCALE THUNDERLINE CORP. OR


TO GROUND BAR
EQUAL.

NON-METALLIC BUSHING CONDUIT CLAMP 1/2" DIA. GALV. STEEL RODS COORDINATE SLEEVE
NOTE: FASTENED OR ANCHORED TO SIZE & O.D. OF CONDUIT
GROUNDING CONDUCTOR SIZE SHALL BE AS STRUCTURE WITH MECHANICAL SEAL
PER THE SPECIFICATIONS AND THE NEC. MANUFACTURER 1/4"
DOUBLE CHANNEL FOR ALL
TYPICAL GROUND CABLE CONDUIT RUNS ABOVE LOWER 1/4" STEEL SLEEVE AND
WATERSTOP FOR FINISH. SEE
LEVEL
SLAB PENETRATION FLAT PLATE,
SPECIFICATIONS, INSIDE PROCESS
PIPING & PAINTING. SLEEVE
NOT TO SCALE CONDUIT (TYPICAL) PROVIDED BY MECHANICAL SEAL
LOCKWASHER,
AND NUT (TYPICAL) MANUFACTURER.
1/2 WALL THICKNESS
SINGLE CHANNEL FOR LOWER
RIGID STEEL CONDUIT (RSC)
LOCKWASHER, JAM NUT LEVEL OF CONDUIT OR SINGLE
AND LOCKNUT (TYPICAL) LAYER RUNS
DOUBLE LOCKNUT AND
GROUNDING BUSHINGS
NOTES: TYPICAL CONDUIT
BONDING CONDUCTOR,
1.
2.
CHANNEL MEMBERS SHALL BE 1 5/8"x1 5/8"x12 GA. MINIMUM.
CHANNEL SUPPORT SYSTEMS SHALL BE GALVANIZED, STAINLESS STEEL OR
THROUGH FIRE RATED CONCRETE WALL
SIZE TO MATCH EQUIPMENT PVC COATED AND SHALL CONFORM TO CONDUIT APPLICATIONS AND AREAS NOT TO SCALE
GROUNDING CONDUCTOR OF INSTALLATION, ALSO SEE SPECIFICATION SECTION 16191.
3. THE LOWEST POINT OF HORIZONTAL RUN SUPPORT SYSTEM SHALL BE 7'-0"
ABOVE FLOOR.

1'-2"
GROUND NON-METALLIC PROTECTIVE TYPICAL CHANNEL SUPPORTS PAINTED 20 Ga. BREAKMETAL -
ONE PIECE TOP, BACK AND SIDES PAINTED 20 Ga. BREAKMETAL -
BUS CONDUIT , 3/4" WITH NON-METALLIC ONE PIECE TOP, BACK & SIDES
BUSHING BOTH ENDS NOT TO SCALE
BADGE READER STATION

STRUCTURAL CEILING BADGE READER STATION


WELDED ALUMINUM OR SLAB PAINTED 20 Ga. BREAKMETAL -
ANGLE MOUNTING ONE PIECE FRONT
#4/0 AWG TO CONTROL PANEL OR PAINTED 20 Ga. BREAKMETAL
STAND
FLOOR GROUND BARS ONE PIECE FRONT
SLAB MCC GROUNDING DISCONNECT SWITCH PAINTED 20 Ga. BREAKMETAL -

4'-0"
JB OR CONDUIT BODY ONE PIECE BOTTOM

3'-7"
NOT TO SCALE TWO SIZES LARGER THAN UNISTRUT CHANNEL PAINTED 20 Ga. BREAKMETAL -
POWER CONDUIT, PROVIDE STEEL REINFORCING ANGLES ONE PIECE BOTTOM
REDUCERS AS REQUIRED DEVICE BOX UNISTRUT CHANNEL
w/CONTINUOUS FILLET WELDS
AT ALL JOINTS DASHED LINE INDICATES
SEALTITE TAP GROUND WIRE ANGLE FITTING
POWER CONDUIT CONDUIT INSIDE BOLLARD
FITTING TO CONDUIT
PAINTED 5"x5" SQ. TUBE STEEL
BOLLARD GROUT SOLID PAINTED 5"x5" SQ. TUBE STEEL
MOTOR BOLLARD (GROUT SOLID)
J.B. CONDUIT BODY
OR DEVICE BOX
GROUND FRAME FOR MOTORS
SEALTITE 10 HP AND LARGER

3'-0"
CONCRETE FOOTING
FLEXIBLE
CONDUIT
NOTES:
CONDUIT (6" MIN. RADIUS)
NON-METALLIC BUSHING CONDUIT IN SLAB CONDUIT IN SLAB 1. PROVIDED BY SECURITY ACCESS VENDOR UNDER
THIS CONTRACT.
CENTER LINE OF STEEL TUBING 2. CONCRETE BASE AND INSTALLATION BY

1'-0"
TO GROUND BARS NON-METALLIC BUSHING CONTRACT NO. XX.
NON-METALLIC 3. COORDINATE EXACT DIMENSIONS WITH BADGE
PROTECTIVE SLAB ENCASED OVERHEAD FEED READER REQUIREMENTS.
CONDUIT 9" 9"
NOTE: NOTE:
GROUNDING CONDUCTOR SIZE SHALL BE AS NO CONDUIT SHALL BE PLACED IN OR UNDER CONCRETE SLABS THAT ARE BELOW FRONT VIEW
PER THE SPECIFICATIONS AND THE NEC. GRADE. ALL CONDUIT IN BELOW GRADE AREAS SHALL BE INSTALLED EXPOSED.
SIDE VIEW
GROUNDING ELECTRIC MOTOR
NOT TO SCALE TYPICAL ELECTRICAL FEED GATE ACCESS PEDESTAL
NOT TO SCALE NOT TO SCALE

SCALE: MRW ONONDAGA COUNTY DEPARTMENT OF WATER ENVIRONMENT PROTECTION File Number
In charge of
006.64
NOT TO SCALE JEC
LOWER HARBOR BROOK CSO STORAGE FACILITY
Designed by
DETAILS Date

THIS DRAWING WAS PREPARED AT THE SCALE INDICATED IN THE


2
1
08/11
04/11
AS BID
ISSUED FOR APPROVAL
MRW
MRW
Drawn by
JEC
SYRACUSE, NEW YORK
08/11 E-307
TITLE BLOCK. INACCURACIES IN THE STATED SCALE MAY BE
INTRODUCED WHEN DRAWINGS ARE REPRODUCED BY ANY
NO. DATE REVISION INT. MRW
Checked by
MEANS. USE THE GRAPHIC SCALE BAR IN THE TITLE BLOCK TO NO ALTERATIONS PERMITTED HEREON EXCEPT AS PROVIDED UNDER SECTION 7209
DETERMINE THE ACTUAL SCALE OF THIS DRAWING. SUBDIVISION 2 OF THE NEW YORK STATE EDUCATION LAW ELECTRICAL
1. EMERGENCY LIGHTING POWER UNIT WITH REMOTE HEADS
1. LOW WATTAGE, HIGH INTENSITY DISCHARGE, AREA LIGHT. UL-924 LISTED

2. CEILING MOUNTED, CAST ALUMINUM BACK PLATE.


1. INDUSTRIAL FLUORESCENT LUMINAIRE, NOMINALLY 4-FEET
2. BATTERY - 12 VOLT, MAINTENANCE-FREE LEAD ACID TYPE,
1. EXIT SIGN. LONG.
WITH 1.5 HOUR CAPACITY.
3. ONE PIECE DIE-CAST ALUMINUM HOUSING
2. TOP BACK OR END MOUNT. 2. MOUNTING CEILING, SUSPENDED, OR WALL MOUNTED WITH
3. BATTERY CHARGER - MAINTAIN FULL-CHARGE STATE DURING
4. TEMPERED GLASS LENS.
45° STAINLESS STEEL ANGLE BRACKETS.
NORMAL CONDITIONS AND RECHARGE TO FULL CAPACITY WITHIN
12 HOURS. SELF TESTING/SELF DIAGNOSTIC SYSTEM 3. IMPACT-RESISTANT, THERMOPLASTIC HOUSING.
5. DARK BRONZE POLYESTER POWDER FINISH.
3. HEAVY GAUGE, DIE FORMED, COLD ROLLED STEEL
4. SIX INCH LETTERS HOUSING. WHITE BAKED ENAMEL FINISH, PAINT AFTER
4. ACCESSORIES: BRACKET SHELF; 14 GAUGE STEEL WITH
6. ALUMINUM REFLECTOR.
FABRICATION.
CORROSION RESISTANT UNDERCOAT AND BAKED ENAMEL
FINISH COAT. MOUNT SHELF 7'-0" AFF 5. SINGLE FACE
7. SUITABLE FOR OUTDOOR APPLICATION
4. REFLECTOR DIE EMBOSSED, SMOOTH EXTRUDED
GASKETED COVER. SINGLE REMOTE (DOUBLE FACE AS INDICATED ON CONTRACT DRAWINGS -2) APERTURES FOR MIN. 10% UPLIGHT.
5. HOUSING - NEMA 1 STEEL CABINET, DARK BROWN ENAMEL FINISH.
HEAD
6. UNIVERSAL CHEVRON ARROWS
8. ONE 100-WATT PULSE START
(EMX) 5. TWO 32 WATT, T-8, LAMPS PER LUMINAIRE. SEE
6. INDICATOR LIGHTS - INDICATE "AC ON" AND "MALFUNCTION".
NOTE 1
METAL HALIDE LAMP PER LUMINAIRE. 7. RED LED FACE
7. TEST SWITCH TO INDICATION BATTERY CONDITION. 6. TWO-LAMP RAPID START ELECTRONIC
9. BALLAST, 120 VOLTS, PULSE START. 8. DUAL VOLTAGE 120/277VOLT. BALLAST, 120 VOLTS. SEE NOTE 2.
8. INPUT VOLTAGE - 120 VOLTS, CORD AND PLUG CONNECTED
10. ACCESSORIES, IN-LINE FUSE, PHOTOCELL. 9. SELF CONTAINED EMERGENCY SEALED 7. BATTERY BALLAST-120 VOLT
9. REMOTE HEADS NICKEL-CADMIUM BATTERY BACKUP (AS SPECIFIED ON PLAN VIEWS)
POWER TO PROVIDE A MINIMUM OF
MANUFACTURERS: HAZARDOUS AREA - 12 VOLT, 28 WATT FIXTURE. LISTED FOR USE IN 90 MINUTES OF ILLUMINATION. 8. ACCESSORIES, PROVIDE 4-FOOT WIRE GUARD.
LUMARK CL SERIES CLASS I, DIV. 1, GROUP D AREAS. CAST ALUMINUM BODY SOLID STATE BATTERY CHARGING CIRCUIT
HUBBEL UCO2 SERIES WITH PYREX LENS, ANGLED REFLECTORS ON ALL. WITH SELF DIAGNOSTIC AND TEST SWITCH. MANUFACTURERS:
OR APPROVED EQUAL
BATTERY LITHONIA: AF SERIES
PACK DAY-BRITE: 1F SERIES
MANUFACTURERS: MANUFACTURERS:
LITHONIA: LQM SERIES COLUMBIA: KL SERIES
BATTERY PACK: DUAL LITE - AS SERIES I, OR EQUAL
McPHILBEN DAY-BRITE: CXX SERIES LIGHTOLIER: TU SERIES
REMOTE HEAD: HAZARDOUS AREA DUAL LITE MODEL REX-1CD, OR EQUAL
LUMINAIRE 'E' SPECIFICATION OR APPROVED EQUAL OR APPROVED EQUAL
NOT TO SCALE

LUMINAIRE 'EMX' SPECIFICATION LUMINAIRE 'EX' SPECIFICATION LUMINAIRE 'C' SPECIFICATION


NOTES: NOT TO SCALE NOT TO SCALE NOT TO SCALE
1. T8 FLUORESCENT LAMPS WILL BE SELECTED FROM LISTED
HIGH-PERFORMANCE T8 SYSTEMS WITH CRI>84 AS FOUND AT
THE CONSORTIUM FOR ENERGY EFFICIENCY (CEE). 1. FLUORESCENT LUMINAIRE, NOMINALLY 4-FEET 1. HAZARDOUS LOCATION SELF-LUMINOUS EXIT SIGN 1. HID LUMINAIRE TESTED AND CERTIFIED FOR HAZARDOUS
2. T8 FLUORESCENT BALLASTS WILL BE SELECTED FROM LISTED
LONG. LOCATIONS.
NEMA PREMINUM R HIGH-PERFORMANCE T8 SYSTEMS AS FOUND
AT THE CONSORTIUM FOR ENERGY EFFICIENCY (CEE). 2. SURFACE MOUNTED OR CEILING MOUNTED.
2. WALL MOUNTED. 2. MOUNTING: PENDANT, CEILING, WALL AND STANCHION.
3. COMPLETELY SEALED HOUSING. WALL BRACKET: 90° ANGLE BRACKETS, STANCHION
3. HEAVY GAUGE, DIE FORMED, COLD ROLLED MOUNTED: 25° BRACKET.
TYPE XP1 FIXTURE, SEE SHEET E-203 STEEL HOUSING.
FOR LOCATIONS 4. SIX INCH LETTERS WITH UNIVERSAL CHEVRON.
SLIP FITTER BY
LUMINAIRE
3. DIE CAST COPPER FREE ALUMINUM ALLOY HOUSING.
4. ACRYLIC PRISMATIC LENS.
MANUFACTURER 5. SINGLE FACE
PROVIDE 2" TO 1-1/4" 5. WHITE BAKED ENAMEL REFLECTOR WITH UP
(DOUBLE FACE AS INDICATED 4. PRE STRESSED GLASS, PRISMATIC BOTTOM GLOBE.
REDUCING COUPLING TO LIGHT. ON CONTRACT DRAWINGS -2)
ATTACH LUMINAIRE TO 5. FIBERGLASS REINFORCED POLYESTER REFLECTOR.
POLE 7. TWO 32 WATT, T-8 LAMPS PER LUMINAIRE. 6. ALUMINUM ANODIZED FRAME.
SEE NOTE 1. 6. CLASSIFICATION, LISTED FOR CLASS I, DIVISION 1,
7. STENCIL FACEPLATE GROUP D.
8. RAPID START BALLAST,
SET SCHEDULE 80 2" 120 VOLTS. SEE NOTE 2
GALVANIZED STEEL 8. LISTED FOR CLASS 1, DIVISION 1, 7. LAMP, 175 WATT METAL HALIDE
SCREWS
90° LUMINAIRE POLE GROUP D.
9. BATTERY BALLAST-120 VOLT 8. BALLAST, TYPE AND SIZE TO MATCH SPECIFIED LAMP,
APART (AS SPECIFIED ON PLAN VIEWS).
9. TRITIUM FILLED GLASS TUBES LOCATE IN HOUSING. 120 VOLT, SINGLE PHASE.
20 YEAR LUMINOUS LIFE.
9. ACCESSORIES, GLOBE WIRE GUARD, QUARTZ AUX. (ONLY
AS SHOWN ON LUMINAIRE TYPES AND MOUNTING HEIGHT TABLE

MANUFACTURERS: 10. SELF CONTAINED NO POWER CONNECTION, ON LUMINAIRES W/ 'QTZ' ON PLAN), ANGLED REFLECTOR
LITHONIA: WP SERIES COMPLETELY SEALED LAMP COMPARTMENT (ONLY ON LUMINAIRES W/ 'AR' ON PLAN) DOME
LIGHTOLIER: LWBU SERIES REFLECTOR (ONLY ON LUMINAIRES W/ 'R' ON PLAN).
OR EQUAL MANUFACTURERS:
MULE LIGHTING: EGX SERIES MANUFACTURERS:
EMERGI-LITE: SLX SERIES COOPER CROUSE-HINDS - SERIES EVM
OR APPROVED EQUAL RIG-A-LITE - SERIES SXP
APPLETON ELECTRIC - CODE MASTER 2 SERIES
OR APPROVED EQUAL
LUMINAIRE 'A' SPECIFICATION LUMINAIRE 'EX-XP' SPECIFICATION
NOT TO SCALE NOT TO SCALE

SS LUMINAIRE 'XP1' SPECIFICATION


3" TALL SS PIPE U-BOLTS 1. FLUORESCENT LUMINAIRE TESTED AND CERTIFIED FOR NOT TO SCALE
HAZARDOUS LOCATIONS.
1/4" DIAMETER WEEP HOLE
1. LOW WATTAGE, HIGH INTENSITY DISCHARGE, NON-CUTOFF 1. LOW WATTAGE, LED, CUTOFF AREA LIGHT.
5/8" S.S. THREADED
2. MOUNTING: CEILING. SUSPENDED, OR WALL MOUNTED AREA LIGHT.
ROD (TYP. OF 4)
3/8" "T" WITH WALL BRACKET. 2. POLE MOUNTED, CAST ALUMINUM WITH GASKET SEALS.
5/8" S.S. NUT SET FLEX FITTING 2. WALL MOUNTED, CAST ALUMINUM BACK PLATE.
SCREW 3. COPPER FREE ALUMINUM ALLOY HOUSING WITH EPOXY 3. DIE-CAST ALUMINUM HOSING WITH INTEGRAL COOLING
1/4"THICK
6" x 6" x 1/2" FINISH. 3. DARK BRONZE BAKED POLYESTER POWDER FINISH. RIBS, DARK BRONZE BAKED POLYESTER POWDER FINISH.
S.S. POST BASE
1"
TYP. 4. HEAT AND IMPACT RESISTANT GLASS TUBES. 4. ONE PIECE, POLYCARBONATE FRONT HOUSING WITH 4. CLEAR FLAT TEMPERED GLASS LENS
CLEAR, U.V. STABILIZED, PRISMATIC REFRACTOR. IN HINGED FRAME WITH LATCH.
5. REFLECTORS EASILY REMOVED FOR CLEANING
USING SCREW DRIVER. 5. POLISHED ALUMINUM REFLECTOR. 5. LED ARRAY TO ACHIEVE
TYPE III DISTRIBUTION.
1/4" S.S. PLATE 6. CLASSIFICATION, LISTED FOR CLASS I, 6. SUITABLE FOR OUTDOOR APPLICATION.
DIVISION 1, GROUP D. 6. SUITABLE FOR OUTDOOR APPLICATION
5/8" S.S. NUT 6" MIN 7. ONE 175-WATT, METAL HALIDE GASKETED COVER.
7. TWO 32 WATT T8 FLUORESCENT LAMPS LAMP PER LUMINAIRE.
SEE NOTE 1 7. MINIMUM 120 LED CONFIGURATION, REPLACEABLE.
STEEL GRATING
8. ENERGY SAVING CLASS P BALLASTS 120 VOLT 8. BALLAST, 120 VOLTS PULSE START.
FULLY 8. DRIVER, 277 VOLTS.
SINGLE PHASE, EQUIPPED WITH AN AUTOMATIC
WELDED 9. ACCESSORIES, IN-LINE FUSE MOUNTING POLE
BASE THERMALLY-ACTIVATED PROTECTIVE DEVICE.
SQUARE, STRAIGHT 18-FOOT ALUMINUM
SEE NOTE 2. INTEGRAL PHOTOCELL. 9. ACCESSORIES: INLINE FUSE,
POLE WITH DARK BRONZE BAKED
PHOTO CELL
9. BATTERY BALLAST - 120 VOLT (AS SPECIFIED ON PLANS) MANUFACTURERS: POWDERCOAT FINISH, HAND HOLE, AND
POLE BASE DETAIL CAST ALUMINUM ANCHOR BASE.
LITHONIA: TWP SERIES MANUFACTURERS:
MANUFACTURERS: HUBBLE: PVL SERIES KIM LIGHTING: WP9LE SERIES
APPLETON - EFU SERIES GE: WALLLIGHTER 175 SERIES POLE MANUFACTURERS:
GARDCO: GULWING SERIES
COOPER CROUSE-HINDS - SERIES EVFDR OR APPROVED EQUAL KIM LIGHTING: PSA SERIES
OR APPROVED EQUAL
OR APPROVED EQUAL GARDCO: SSA4 SERIES
OR APPROVED EQUAL
PLAN VIEW
LUMINAIRE 'EXP2' SPECIFICATION
LUMINAIRE STANCHION MOUNTING DETAIL NOT TO SCALE LUMINAIRE 'S7' SPECIFICATION LUMINAIRE 'PM1' SPECIFICATION
NOT TO SCALE NOT TO SCALE
NOT TO SCALE

SCALE: MRW ONONDAGA COUNTY DEPARTMENT OF WATER ENVIRONMENT PROTECTION File Number
In charge of
006.64
NOT TO SCALE JEC
LOWER HARBOR BROOK CSO STORAGE FACILITY
Designed by
DETAILS Date

THIS DRAWING WAS PREPARED AT THE SCALE INDICATED IN THE


2
1
08/11
04/11
AS BID
ISSUED FOR APPROVAL
MRW
MRW
Drawn by
JEC
SYRACUSE, NEW YORK
08/11 E-308
TITLE BLOCK. INACCURACIES IN THE STATED SCALE MAY BE
INTRODUCED WHEN DRAWINGS ARE REPRODUCED BY ANY
NO. DATE REVISION INT. MRW
Checked by
MEANS. USE THE GRAPHIC SCALE BAR IN THE TITLE BLOCK TO NO ALTERATIONS PERMITTED HEREON EXCEPT AS PROVIDED UNDER SECTION 7209
DETERMINE THE ACTUAL SCALE OF THIS DRAWING. SUBDIVISION 2 OF THE NEW YORK STATE EDUCATION LAW ELECTRICAL
BASE COVER

"PM1" TYPE FIXTURE,


SEE DETAIL SHEET E-308.

45.
00°
600A
300A, 480 VAC, 3 PHASE, 4 WIRE
SERVICE ENTRANCE RATED, TYPE 3R
LONGITUDINAL TERMINATION ENCLOSURE (GREEN
REFERENCE LINE. POWDER COAT FINISH), CABINET AS
ORIENT PARALLEL MANUFACTURED BY EASTER-OWENS
TO CURB/PAVEMENT MODEL NO. LTE-001-300-UT OR
OR WALKWAY APPROVED EQUAL.
48"
BOLT CIRCLE SECURITY CAMERA
DIAMETER MOUNTING ARM POLE TO BE MODIFIED FOR CAMERA TERMINAL STRIP
MOUNTED 12" BELOW FIXTURES.
PROVIDE HANDHOLE AT CAMERA LOCATION.
CAMERA BRACKET PROVIDED BY CAMERA
SECURITY MANUFACTURER. PROVISIONS FOR MOUNTING
CAMERA CAMERA BRACKET BY POLE MANUFACTURER

BASE COVER
24" DIAMETER CONCRETE BASE
ANCHOR BOLT SEE DETAIL THIS SHEET
PROJECTION
PROVIDE DOUBLE NUTS 60"
AND WASHERS
18"
GROUT MUST BE PACKED UNDER
POLE BASE TO INSURE FULL CONTACT REFER TO SITE PLANS
LEVELING NUT WITH FOOTING AND PREVENT LOOSENING FOR FINAL GRADE
AND WASHER OF LEVELING NUTS.
PVC J-BOX w/TAMPER
PROVIDE A CHANNEL THROUGH RESISTANT SCREWS 1/4"x4" COPPER
THE GROUT FOR DRAINAGE CARLON #HS11B7 GROUND BAR
FROM THE POLE INTERIOR ANCHOR BOLT (QUANTITY, SIZE
& SPACING PER POLE
REQUIREMENTS
POWER AND LIGHTING CIRCUIT CONDUIT 30"
LOCATE BOXES ON BACK SIDE (REFER TO CONTRACT DRAWINGS) 3/4"C w/2-#12, #12G TO POWER

XXXXXXXXXXXXXXXXXXXXXX
OF POLE, AWAY FROM VEHICLE PANEL LP1 (SEE POWER PLAN 6-4" CHASE NIPPLES
TRAFFIC

XXXXXXXXXXXXXXXXXXXXXXXX
E-101 AND PANEL SCHEDULE w/PVC CAPS

XXXXXXXXXXXXX
E-305 FOR CIRCUIT DESIGNATION
X #6 BARE STRANDED COPPER GROUND 1"C w/8-#14 TO MANUAL
SECURITY COMMUNICATION TRANSFER SWITCH
XX

XX
XX
WIRE. PROVIDE GROUND BUSHINGS FOR
AND POWER CONDUITS EACH METALLIC CONDUIT AND TERMINATE
TYPICAL POLE
XX

XX
XX

(REFER TO SHEET E-306 FOR

X X XX X X X X
GROUND WIRING @ BUSHINGS, POLE

X XX X X

X XX XX

XX
XX
BASE ANCHOR DETAILS
XX
CONDUIT AND CONDUCTOR XX

XXXX
GROUNDING LUGS, AND CONNECT TO
XX

MOBILE GENERATOR CONNECTION BOX DETAIL

XXXXXXXXXXXXXXXX
XX
XX

XX
XX
XX
SIZE AND QUANTITIES) X
XX
CIRCUIT GROUND.

X X X X X X X XXX XX X
XXXXXXXXXXXXXXXX

XX X X X X X X X X X X X X XX
XX XX X
X

XXXXX

XXXXXXXX
XX

XX XXX X XX X X XX
XX XX

XXXXXXXXXXXXXXXX
X
XX
XX
XX
NOT TO SCALE
X
X
XX
X

XX
X
XX
THE CONDUIT RUNS UNDER
XX
XX
10'-0"x3/4" DIAMETER COPPER WELD
XX
XX

XXX
XX
XX
THE CURB OF PAVEMENT
XX
XX
GROUNDING ROD

XXXX

X XX X
XX
XX
X
3/8" SAWCUT
XX X

XXXX
VERTICAL REINFORCING
TIES
PAVEMENT EDGE

APPROVED BACKFILL
MATERIAL
4" DIAMETER CORE FINISHED GRADE
OR TYPICAL SITE LIGHT FIXTURE & 24" DIA. POLE BASE DETAIL DUCTBANK
2"x4" CUTOUT
NOT TO SCALE MARKING TAPE

3" MINIMUM
(TYPICAL FOR ALL POLE BASES WITH SECURITY CAMERA JUNCTION BOX)
TOP VIEW
30" MINIMUM 3" MINIMUM
#4/0 GROUND CABLE
12"
CONCRETE

SAWCUT CURB TOP OR PAVEMENT EDGE AT


3/8" WIDE BY 1/4" DEEP TO SHOW WHERE THE
CONDUIT RUNS UNDER THE CURB OR PAVEMENT CURB DETAIL IS SHOWN BY SAWCUT
THE DASHED LINES RUN THE 3/8"
CONDUIT UNDER THE CURB LOOP EMBEDDING SEALER HOLD DOWN
FILL WITH LOOP EMBEDDING SEALER
1'-0" MAX
SIDEWALK
TIE VERTICAL #5 REBAR #5 REBAR CONTINUOUS
LOOP WIRE HOLD DOWN NOTE: TO HORIZONTAL #5 (TYPICAL 4 SIDES)
4" 6" TO 12" SHOULDER
USE SHORT (1"TYPICAL) PIECE OF FLEXIBLE REBAR, (TYPICAL 4
CURB NEOPRENE RUBBER OR ROUND FOAM SEALING PLACES)

2-1/2" MAX

1-1/2" MIN
STRIPS AT 2'-0" CENTERS TO HOLD LOOP
3" WIRES IN PLACE UNTIL SEALER SETS. DO NOT
USE SOLID OBJECTS TO HOLD WIRES DOWN.
CONDUIT (TYPICAL)

PAVEMENT
2'-0" DESIRABLE

1'-6" MINIMUM

NUMBER OF WIRES AS
REQUIRED BY MANUFACTURER
2" MINIMUM
SEPARATION (TYPICAL)

TWIST 2 TURNS
USE INSULATING BUSHING, SEAL THE
END OF THE CONDUIT AND THE HOLE 30° TO 60°
PER FOOT MIN SAWCUT CROSS SECTION IN CONCRETE OR ASPHALT BASE AND INTERMEDIATE
THROUGH THE PAVEMENT TO PREVENT TYPICAL NOT TO SCALE SPACERS 4'-0" ON CENTER
LOOP EMBEDDING SEALER FROM ENTERING.

1-1/2" MINIMUM HOLE DRAIN TO PULLBOX 3" MINIMUM (TYPICAL)


BELOW GATE OPERATOR
1" MINIMUM DIAMETER METAL STEEL
CONDUIT, ZINC COATED FLEXIBLE
LIQUID-TIGHT STEEL CONDUIT OR CHIP OUT CORNERS
RIGID PLASTIC CONDUIT.
3" MINIMUM
1 1/2" MINIMUM (TYPICAL)
SIDE VIEW
2" MINIMUM
SEPARATION (TYPICAL)
LOOP LEAD IN AT PAVEMENT EDGE SAWCUT KERF DETAIL AT CORNERS
NOT TO SCALE NOT TO SCALE MASONRY LEVELING #5 REBAR (TYPICAL
BLOCKS AT BASE
SPACERS TYPICAL DUCT BANK 2 PER SECTION)

NOT TO SCALE

(ADDENDUM NO. 1)
SCALE: MRW ONONDAGA COUNTY DEPARTMENT OF WATER ENVIRONMENT PROTECTION File Number
In charge of
006.64
NOT TO SCALE JEC
LOWER HARBOR BROOK CSO STORAGE FACILITY
Designed by
DETAILS Date

THIS DRAWING WAS PREPARED AT THE SCALE INDICATED IN THE


2
1
08/11
04/11
AS BID
ISSUED FOR APPROVAL
MRW
MRW
Drawn by
JEC
SYRACUSE, NEW YORK
08/11 E-309
TITLE BLOCK. INACCURACIES IN THE STATED SCALE MAY BE
INTRODUCED WHEN DRAWINGS ARE REPRODUCED BY ANY
NO. DATE REVISION INT. MRW
Checked by
MEANS. USE THE GRAPHIC SCALE BAR IN THE TITLE BLOCK TO NO ALTERATIONS PERMITTED HEREON EXCEPT AS PROVIDED UNDER SECTION 7209
DETERMINE THE ACTUAL SCALE OF THIS DRAWING. SUBDIVISION 2 OF THE NEW YORK STATE EDUCATION LAW ELECTRICAL
24" CAST IRON FRAME AND LID WITH
A.A.S.H.T.O. HS-20-44 DESIGN RATING
WITH "ELECTRIC" CAST IN COVER
4"x4" PRESSURE
TREATED LUMBER .) 38
IN " (M
" ( M IN
38 .)

3" TYP.
20A, GFI RECEPTACLE
6" BOX SHOWN w/WEATHERPROOF ENCLOSURE ELECTRIC
SINGLE GANG NON-METALLIC,

6"
WITH COVER OFF
GROUND ROD (FOR CLARITY) SUITABLE FOR WET LOCATIONS
3/4"x8'-0" (TYPICAL FOR 2) WHEN RECEPTACLE IS IN USE, RACO CAST IRON
CAT. NO. 5061-0 OR EQUAL FRAME

12"
4"
GROUND GRID #2/0 CU
REINFORCING BARE SOFT DRAWN -
19 STRAND

'30"

'24"
CONCRETE SLAB
82"

12" 12" FINISHED GRADE


CONCRETE FOUNDATION
TO TELCO GROUND
A A (IF AVAILABLE)

15"
12"
6"

EXTRA 3'
ABOVE WATERPROOF BETWEEN

8"
CONCRETE SECTIONS AND ON
FRONT ACCESS PRIMARY SECONDARY OUTER SURFACE
EXTRA 3'

'30"
12" 8" 25" 12" ABOVE
"C" TYPE COMPRESSION CONCRETE
CONNECTOR (TYPICAL) SEE SITE PLAN
83"
SHEET E-002 FOR

'48"
CONDUIT ROUTING
PLAN #5@12" MAXIMUM SPACING

24"
ON CENTER EACH WAY
MID-DEPTH

20"
10"

30" (MIN.)
CONNECT GROUND ROD
REBAR DIAGRAM TO GROUND GRID WITH
CONCRETE SLAB
GROUND CLAMPS (TYPICAL)
3/4" CHAMFER GROUND 1" GROUT ALL CONDUIT
ENTRY LOCATIONS
4"

10"
CLAMP FINISHED GRADE
TRANSFORMER GROUNDING DETAIL RECEPTACLE DETAIL WATERTIGHT
10"

NOT TO SCALE
NOT TO SCALE GROUND ROD
2" FLOOR OPENING
SAND
12"

GRAVEL 4"x10" KNOCKOUTS


(4 WALLS)

SECTION A-A PRECAST ELECTRIC PULLBOX DETAIL (EMH-1)


NOT TO SCALE

TRANSFORMER PAD DETAIL


NOT TO SCALE
NOTES:
SERVICE POLE BY UTILITY
1. ALL WORK SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF NATIONAL (SEE PLAN FOR LOCATION)
GRID STANDARDS. LOCATION OF UTILITY RACK
2. PRIOR TO INSTALLING THE TRANSFORMER PAD, CONTRACTOR SHALL CONSULT UTILITY FOR EXACT
COORDINATE ACTUAL LOCATION OF PAD WITH NATIONAL GRID. LOCATION.

#2 AWG BARE COPPER


GROUND WIRE AND GROUND
CLAMP. PROVIDE SUFFICIENT PRIMARY CONDUCTORS (BY
NEMA 4X T-STAT WITH 120 VAC BRANCH LENGTH TO EXTEND 36"
INTERNAL ADJUSTMENT CIRCUIT GFCI BREAKER 120 VOLT CIRCUIT UTILITY) UNDER THIS CONTRACT
IN CONDUIT BEYOND RACK ABOVE. PROVIDE PULLWIRE.

REFER TO TYPICAL GROUND CLAMP


HEAT TRACE
CONNECTION DETAIL
(TYPICAL) INSULATED GROUNDING
BUSHINGS

NEMA 4X ENCLOSURE CARRIER PIPE CONDUIT T-1 w/PULLWIRE


T-STAT CAPILLARY GROUND CLAMP
(TYPICAL) FOR TELEPHONE. EXTEND CONDUIT BY THIS CONTRACT
TO 8'-0" ABOVE GRADE. CAP CONSULT UTILITY FOR EXACT
CABLE GROUND CONDUIT w/BUSHING.
CAPILLARY LOCATION ON POLE
BRAID MANUFACTURERS
BULB (TYPICAL) 10'-0"
BRAID TERMINATION FITTING SPARE HEAT ON-LINE HEAT
TRACE CABLE TRACE CABLE
PIPE INSULATION AND
CAP SPARE CONDUITS
COVER PER
12" ABOVE GRADE (TYPICAL) PIPE STRAP @ 30" INTERVALS
SPECIFICATIONS

PIPE TO BE LOCATE CONDUIT ON POLE


HEAT TRACED AWAY FROM TRAFFIC
45° 45°

42" MIN. 30"


PIPE INSULATION MIN
PER SPECIFICATION RADIUS

FIBERGLASS TAPE HEAT TRACE CABLE


(TYPICAL) (SELF-LIMITING) HEAT TRACE CABLE NOTES:
PIPE STRAP (TYPICAL) 1. INSTALLATION SHALL BE IN PF-1
ACCORDANCE WITH LATEST EDITION (SEE PLAN)
PIPE TO BE TRACED OF UTILITY STANDARDS.
(REFER TO CONTRACT
TELEPHONE SERVICE
DRAWINGS)
LATERAL T-1 (SEE PLAN)

TYPICAL HEAT TRACE INSTALLATION DETAIL TYPICAL HORIZONTAL PIPING HEAT TRACE DETAIL
NOT TO SCALE NOT TO SCALE
INCOMING PRIMARY SERVICE POLE DETAIL
NOT TO SCALE

SCALE: MRW ONONDAGA COUNTY DEPARTMENT OF WATER ENVIRONMENT PROTECTION File Number
In charge of
006.64
NOT TO SCALE JEC
LOWER HARBOR BROOK CSO STORAGE FACILITY
Designed by
DETAILS Date

THIS DRAWING WAS PREPARED AT THE SCALE INDICATED IN THE


2
1
08/11
04/11
AS BID
ISSUED FOR APPROVAL
MRW
MRW
Drawn by
JEC
SYRACUSE, NEW YORK
08/11 E-310
TITLE BLOCK. INACCURACIES IN THE STATED SCALE MAY BE
INTRODUCED WHEN DRAWINGS ARE REPRODUCED BY ANY
NO. DATE REVISION INT. MRW
Checked by
MEANS. USE THE GRAPHIC SCALE BAR IN THE TITLE BLOCK TO NO ALTERATIONS PERMITTED HEREON EXCEPT AS PROVIDED UNDER SECTION 7209
DETERMINE THE ACTUAL SCALE OF THIS DRAWING. SUBDIVISION 2 OF THE NEW YORK STATE EDUCATION LAW ELECTRICAL
ABBREVIATIONS
ABBREVIATIONS SYMBOLS
A G Q
DUCT TEMPERATURE EXISTING TO REMAIN
@ AT Ga GAGE OR GAUGE QTY QUANTITY EXISTING TO REMAIN THERMOMETER
A
A/C
AIR
AIR CONDITIONING
GAL
GV
GALLON(S)
GATE VALVE R EXISTING TO BE REMOVED
T
SENSOR EXISTING TO BE REMOVED

NEW WORK
ACC AIR-COOLED CONDENSER GHWR GLYCOL/HOT WATER RETURN PRESSURE GAGE W/COCK
ACFM ACTUAL CUBIC FEET PER MINUTE GHWS GLYCOL/HOT WATER SUPPLY RAD RADIUS DUCT HUMIDITY SENSOR
DIRECTION OF FLOW
GLV GLOBE VALVE REF REFERENCE H
AD ACCESS DOOR NEW WORK
ADD'L GPH GALLONS PER HOUR REINF REINFORCE CONCENTRIC REDUCER
ADDITIONAL
AFF ABOVE FINISHED FLOOR GPM GALLONS PER MINUTE REQ'D REQUIRED AIR VENT W/COCK
GUH-( ) GAS UNIT HEATER-( ) REV REVISION SUPPLY AIR UP DUCT SMOKE DETECTOR ECCENTRIC REDUCER
AFM AIR FLOW METER
SDT
AHU
ALUM
AIR HANDLING UNIT
ALUMINUM
H RL
RM
REFRIGERANT LIQUID
ROOM
SUPPLY AIR DOWN DUCT PRESSURE CLASS
ELBOW - UP
ELBOW - DOWN ORIFICE PLATE
APD AIR PRESSURE DROP RPM REVOLUTIONS PER MINUTE
HCP HOT WATER CIRCULATING PUMP RR RETURN REGISTER DESIGNATION - OMIT BOTTOM TAKE-OFF
APPD APPROVED
HD HEAD RS REFRIGERANT SUCTION EXHAUST OR RETURN IF DUCT MATERIALS PRESSURE/TEMPERATURE PLUG
APPROX APPROXIMATE TOP TAKE-OFF
HHL HUMIDITY HIGH LIMIT RTU REMOTE TERMINAL UNIT - AIR UP AND CONSTRUCTION
ARCH ARCHITECTURAL
HORIZ HORIZONTAL ROOF TOP UNIT SCHEDULE IS USED
ARV AIR RELEASE VALVE EXHAUST OR RETURN
ASPH
AUTO
ASPHALT
AUTOMATIC
HP
HP-( )
HORSE POWER OR HIGH POINT
HEAT PUMP-( ) S AIR DOWN
SP

SECURITY PENETRATION
GATE VALVE

HVAC
AUX AUXILIARY HPCOND HIGH PRESSURE CONDENSATE GLOBE VALVE
HPST HIGH PRESSURE STEAM SA SUPPLY AIR ROUND DUCT UP
AVG AVERAGE
SCFM STANDARD CUBIC FEET PER MINUTE
B
HPWR HEAT PUMP WATER RETURN
EQUIPMENT DESIGNATION
OED OPEN END DUCT W/
HPWS HEAT PUMP WATER SUPPLY SD STORM DRAIN OR SMOKE DAMPER CHECK VALVE
ROUND DUCT DOWN 1/2"x1/2" WIRE MESH
HR HOUR SECT SECTION
SF SQUARE FOOT SCREEN CLOSURE AHU-1
B OR BOT BOTTOM HRC HEAT RECOVERY COIL BALANCING VALVE
SH OR SHT SHEET RECTANGULAR DUCT SIZE AD
BBD BOILER BLOW DOWN HT HEIGHT 24x36
HTHWR HIGH TEMPERATURE HOT SIM SIMILAR (FIRST FIGURE-SIDE SHOWN) AUTOMATIC DAMPER
BBH BASE BOARD HEATER SUFFIX LETTER (FOR DISTINCTION OF
SP STATIC PRESSURE OR STOP BALL VALVE
BD BALANCE DAMPER WATER RETURN SIMILAR ITEMS, IF NEEDED)
BDD BACK DRAFT DAMPER HTHWS HIGH TEMPERATURE HOT SPEC SPECIFICATION BD
SQ SQUARE DIRECTION OF FLOW BALANCING DAMPER ANGLE GATE VALVE EQUIPMENT PROCESS SEQUENCE NUMBER
BFF BELOW FINISHED FLOOR WATER SUPPLY
BLDG BUILDING HW HOT WATER SS STAINLESS STEEL
EQUIPMENT TYPE OR FUNCTION
BOD BOTTOM OF DUCT HWR HOT WATER RETURN STD STANDARD UP DN DUCT INCLINED RISE BDD
BTU BRITISH THERMAL UNITS HWS HOT WATER SUPPLY STL STEEL OR DROP IN BACK DRAFT DAMPER
STOR STORAGE RELIEF OR SAFETY VALVE
BTUH BRITISH THERMAL UNITS PER HOUR HX HEAT EXCHANGER DIRECTION OF FLOW

C I STRUCT
SUSP CLG
STRUCTURAL
SUSPENDED CEILING
SD
SMOKE DAMPER WITH
MISCELLANEOUS
90° ELBOW WITH S
SV SOLENOID VALVE ACCESS DOOR
C/C CENTER TO CENTER SOLENOID VALVE
T
I/A INSTRUMENT AIR TURNING VANES EXISTING PIPING
CAV COMBINATION AIR VALVE FD
ID INSIDE DIAMETER FIRE DAMPER WITH
CD CONTROL DAMPER NEW PIPING
IN INCH OR INCHES T
CFM CUBIC FEET PER MINUTE ACCESS DOOR
TSTAT THERMOSTAT 45°ELBOW (NO VANES) THERMAL EXPANSION VALVE
CFS CUBIC FEET PER SECOND INSUL INSULATION OR INSULATED TEMPERATURE
TEMP FSD COMBINATION FIRE &
CHWR
CHWS
CHILLED WATER RETURN
CHILLED WATER SUPPLY L TG
TOD
TRANSFER GRILLE
TOP OF DUCT SUPPLY OR RETURN
SMOKE DAMPER WITH
ACCESS DOOR
PLUG VALVE OR
FLOW DIRECTION
CI CAST IRON TOP TOP OF PIPE
LAB LABORATORY BRANCH CONNECTION BUTTERFLY VALVE
CL CENTERLINE TEMPERATURE SWITCH
LAT LEAVING AIR TEMPERATURE TS
CLG CEILING TIGHT SHUTOFF DAMPER
TSD
CLR
CO
CLEAR
CLEAN OUT
LAV
LBS
LAVATORY
POUNDS TSP
TYP
TOTAL STATIC PRESSURE
TYPICAL SUPPLY BRANCH WITH
EQUIPMENT 2-WAY CONTROL VALVE PIPE CONTINUES
LF LINEAR FEET S
U
COL COLUMN SPIN COLLAR CONNECTION
CONC CONCRETE LPCOND LOW PRESSURE CONDENSATE DIRECTION OF PITCH
CONST CONSTRUCTION LPG LIQUID PROPANE GAS 3-WAY VALVE
SUPPLY AIR DIFFUSER (SD)
CONT CONTINUE OR CONTINUOUS LPST LOW PRESSURE STEAM UH-( ) UNIT HEATER-( )
COORD COORDINATE LRR LINEAR RETURN REGISTER UON UNLESS OTHERWISE NOTED DIFFUSER (D) UNION
LSR LINEAR SUPPLY REGISTER
CORR
CPD
CS
CORRIDOR
CONDENSATE PUMP DISCHARGE
CARBON STEEL
LS
LV
LIMIT SWITCH
LOUVER
V TYPE
CFM
RETURN AIR GRILLE (RG)
STRAINER

CTR CENTER LWT LEAVING WATER TEMPERATURE V VENT OR VOLTS EXHAUST OR RETURN
STRAINER W/BLOW-OFF
M
A
VAC VOLTS ALTERNATING CURRENT REGISTER (R) ACCESS DOOR
D
D & CAP
VAV VARIABLE AIR VOLUME TYPE GRILLE (G)
VD VOLUME DAMPER
MAT'L MATERIAL CFM LINEAR DIFFUSER (LSD)
DEG DEGREE VERT VERTICAL
MAX MAXIMUM FLOAT AND THERMOSTATIC
DA DOUBLE ACTING OR VFD VARIABLE FREQUENCY DRIVE AD FLEX DUCT
MBH THOUSAND BTU PER HOUR TRAP
DB
DAMPING ACTUATOR
DRY BULB (TEMPERATURE) MECH
MFR
MECHANICAL
MANUFACTURER
W ACCESS DOOR
BUCKET TRAP
DI DUCTILE IRON
DIA DIAMETER MIN MINIMUM W/O WITHOUT
FLEXIBLE CONNECTION VARIABLE AIR VOLUME BOXES (VAV)
DRAWING NOTE:
DIM DIMENSION MISC MISCELLANEOUS W/ WITH FLOW SENSOR
DISCH DISCHARGE MPCOND MEDIUM PRESSURE CONDENSATION WB WET BULB (TEMPERATURE)
DN DOWN MPST MEDIUM PRESSURE STEAM AFS SIGHT GLASS
WLD WELD OR WELDED LOUVER (LV)
DP DIFFERENTIAL PRESSURE MUA MAKE UP AIR AIR FLOW STATION THIS DRAWING CONTAINS SYMBOLS AND ABBREVIATIONS
MUAU MAKE UP AIR UNIT Wt WEIGHT
DWG DRAWING PIPE GUIDE WHICH MAY NOT BE USED FOR THIS PROJECT.
MUW MAKE UP WATER
E N ACTUATORS FLEXIBLE DUCTWORK
POWERED ROOF EXHAUSTER (PRE)
GRAVITY ROOF VENTILATOR (GRV) PIPE ANCHOR

EAT ENTERING AIR TEMPERATURE MANUAL OPERATOR


NFPA NATIONAL FIRE PROTECTION FLEXIBLE CONNECTOR
EHC-( ) ELECTRIC HEATING COIL-( ) ASSOCIATION NON-RISING STEM 20X12 SG1
SUPPLY GRILLE, SIDE OF DUCT EXHAUST FAN (EF)
EL ELEVATION NIC NOT IN CONTRACT
LEVER 100 CFM (INDICATE SIZE, TYPE AND AIRFLOW) EXPANSION JOINT
ELEC ELECTRIC OR ELECTRICAL No or # NUMBER
EQUIP EQUIPMENT NTS NOT TO SCALE
ERH ELECTRIC REHEAT COIL
O 20X12 RG1 FM
S SOLENOID OPERATOR RETURN GRILLE, SIDE OF DUCT CABINET UNIT HEATER FLOW METER
ESH ELECTRIC STEAM HUMIDIFIER (INDICATE SIZE, TYPE AND AIRFLOW)
100 CFM AT FLOOR (CUH)
ESP EXTERNAL STATIC PRESSURE DIAPHRAGM OPERATOR
EUH-( ) ELECTRIC UNIT HEATER-( ) O/C ON CENTER
UNIT HEATERS (EUH / UH)
EWF ELECTRIC WALL FIN OA OUTSIDE AIR M
EWT ENTERING WATER TEMPERATURE OBD OPPOSED BLADE DAMPER MOTOR OPERATOR
DUCT SECTION
EXH EXHAUST OD OUTSIDE DIAMETER BASEBOARD HEATER (BB)
P
EXIST OR EX EXISTING ODP OPEN-DRIP PROOF PNEUMATIC MOTOR OPERATOR
M MOTOR
F OPNG OPENING

P
PRESSURE OPERATOR

T THERMOSTAT
F&T
FE
FLOAT & THERMOSTATIC
FLOOR DRAIN OR FIRE DAMPER P PRESSURE
CONTROLS TC TEMPERATURE CONTROLLER
FL FLOOR PW PLANT WATER
SP STATIC PRESSURE SENSOR
FLV FLAP VALVE PNL PANEL RADIAL BLOWER
POC POINT OF CONNECT
FOB FLAT ON BOTTOM T THERMOSTAT
PP POLYPROPYLENE
FOR FUEL OIL RETURN
PRE-( ) POWERED ROOF EXHAUSTER
FOT FLAT ON TOP H HUMIDISTAT IN-LINE PUMP
PRV PRESSURE REDUCING VALVE
FPM FEET PER MINUTE PS PRESSURE SWITCH
FPS FEED PER SECOND TS TEMPERATURE SENSOR
PG PROPANE GAS
FRP FIBERGLASS REINFORCED PLASTIC
PSF POUNDS PER SQUARE FOOT HS HUMIDITY SENSOR
FS FLOW SWITCH
PSI POUNDS PER SQUARE INCH
FT FOOT OR FEET
PSIG POUNDS PER SQUARE INCH GAGE
PTFE POLYTETRAFLUOROETHYLENE
PV PLUG VALVE
PWE-( ) POWERED WALL EXHAUSTER
PWR PROCESS WATER RETURN

SCALE: LJC ONONDAGA COUNTY DEPARTMENT OF WATER ENVIRONMENT PROTECTION File Number
In charge of
006.64
NOT TO SCALE SWM
LOWER HARBOR BROOK CSO STORAGE FACILITY
Designed by Date
2 08/11 AS BID LJC
Drawn by
KJL SYMBOLS AND ABBREVIATIONS 08/11 H-001
THIS DRAWING WAS PREPARED AT THE SCALE INDICATED IN THE 1 04/11 ISSUED FOR APPROVAL LJC
TITLE BLOCK. INACCURACIES IN THE STATED SCALE MAY BE
SYRACUSE, NEW YORK
INTRODUCED WHEN DRAWINGS ARE REPRODUCED BY ANY
NO. DATE REVISION INT. GBC
Checked by
MEANS. USE THE GRAPHIC SCALE BAR IN THE TITLE BLOCK TO NO ALTERATIONS PERMITTED HEREON EXCEPT AS PROVIDED UNDER SECTION 7209
DETERMINE THE ACTUAL SCALE OF THIS DRAWING. SUBDIVISION 2 OF THE NEW YORK STATE EDUCATION LAW HVAC
A

LOUVER LV-2
300 CFM

M
D-2

EUH-1

ELECTRIC
101

30X24 SUPPLY AIR DUCT

5 16"x8 " BACKDRAFT


DAMPER (BDD)

EUH-3
VESTIBULE
HALL
STAIR 103
SR-1 SR-1
102 ECH-1
104 100 CFM 100 CFM

10"x6"
SR-1
75 CFM 10"x6"
EUH-2
10"x8"
MECHANICAL
105 FC
OFFICE
107
SF-5 FC
14"x12"
10'-3" AFF. BATH
CLASS 1, ELECTRIC
DIVISION 1 DUCT HEATER 106
GROUP D EDH-1
HAZARDOUS EBH-1 PTAC-1
FILTER BOX 24"x24"
AREA
DAMPER D-1
M

LOUVER L-1
275 CFM

1
H-102

FLOOR PLAN
SCALE: 1/4" = 1'-0"

SCALE: LJC ONONDAGA COUNTY DEPARTMENT OF WATER ENVIRONMENT PROTECTION File Number
In charge of
2 0 2 4
2 6 8 10 006.64
LOWER HARBOR BROOK CSO STORAGE FACILITY
1/4" = 1'-0" GBC
Designed by Date
2 08/11 AS BID LJC
Drawn by
KJL UTILITIES BUILDING - BELOW ROOF PLAN 08/11 H-101
THIS DRAWING WAS PREPARED AT THE SCALE INDICATED IN THE 1 04/11 ISSUED FOR APPROVAL LJC
TITLE BLOCK. INACCURACIES IN THE STATED SCALE MAY BE
SYRACUSE, NEW YORK
INTRODUCED WHEN DRAWINGS ARE REPRODUCED BY ANY
NO. DATE REVISION INT. SWM
Checked by
MEANS. USE THE GRAPHIC SCALE BAR IN THE TITLE BLOCK TO NO ALTERATIONS PERMITTED HEREON EXCEPT AS PROVIDED UNDER SECTION 7209
DETERMINE THE ACTUAL SCALE OF THIS DRAWING. SUBDIVISION 2 OF THE NEW YORK STATE EDUCATION LAW HVAC
12"x14" SUPPLY FAN 8"x10"
BOD 10'-3" SF-5
AFF 10"x6" 16"x8" BACKDRAFT DAMPER MOUNTED
LOUVER L-1 IN WALL SET TO OPEN AT VESTIBULE
275 CFM PRESSURE +0.1" W.C.

FC FC

6x10 SA DUCT SR-1


TO HALL 102 100 CFM
VESTIBULE
ELECTRIC HEATING
COIL EDH-1 103

DAMPER D-1 24"x24"

FILTER BOX

MECHANICAL
105

SECTION 1
3/4" = 1'-0" H-101

SCALE: LJC ONONDAGA COUNTY DEPARTMENT OF WATER ENVIRONMENT PROTECTION File Number
In charge of
1 0 1 2 3 006.64
LOWER HARBOR BROOK CSO STORAGE FACILITY
3/4" = 1'-0" GBC
Designed by Date
2 08/11 AS BID LJC
Drawn by
KJL UTILITIES BUILDING - SECTION 08/11 H-102
THIS DRAWING WAS PREPARED AT THE SCALE INDICATED IN THE 1 04/11 ISSUED FOR APPROVAL LJC
TITLE BLOCK. INACCURACIES IN THE STATED SCALE MAY BE
SYRACUSE, NEW YORK
INTRODUCED WHEN DRAWINGS ARE REPRODUCED BY ANY
NO. DATE REVISION INT. SWM
Checked by
MEANS. USE THE GRAPHIC SCALE BAR IN THE TITLE BLOCK TO NO ALTERATIONS PERMITTED HEREON EXCEPT AS PROVIDED UNDER SECTION 7209
DETERMINE THE ACTUAL SCALE OF THIS DRAWING. SUBDIVISION 2 OF THE NEW YORK STATE EDUCATION LAW HVAC
NOTES:
FUTURE ODOR 1. TOP OF TANK ELEVATION 382'-8" .
CONTROL UNITS
2. INSTALL ALL ODOR CONTROL DUCTWORK ON TANK ROOF AT BOTTOM OF
DUCT ELEVATION 384.8 AFF. ALL TRANSITIONS SHALL BE FLAT ON
BOTTOM (FOB).

ODOR CONTROL
VESSEL OC-2
D
BLOWER
BL-2

ODOR CONTROL
VESSEL OC-1

1
H-203 BLOWER 40"x30" 40"x30"
C
BL-1
40"x24" 40"x36"

30"x24" FOB 40"x40"


96"x48 FOB SA
EXHAUST FOB

FOB
B
20"x20" DOWN

1 2 TYP.x6

SF-3 H-204 EF-1 SF-1


H-204 30,000 30,000 30,000
CFM CFM CFM

3
RIS
E
EF-2
30,000
64"x48"
DOWN
H-204 GRAVITY ROOF
VENTILATOR
A
CFM GRV-1
40"x40"
DOWN
(TYP.x2)

96"x48
EXHAUST FOB SF-4
30,000
40"x40" CFM
DOWN
96"x48 (TYP.x2) PRE-1
SF-2 30"x24"
30,000 EXHAUST
CFM

20"x20" DOWN 5
TYP.x6
FOB
FOB FOB PRE-3
FOB PRE-2
40"x40" FOB
SA

40"x36" 40"x24"

40"x30" 40"x30"
PRE-4 12x12 SA TO
500 CFM STAIRWELL

1
3
2

PLAN
SCALE: 1/16" = 1'-0"

SCALE: LJC ONONDAGA COUNTY DEPARTMENT OF WATER ENVIRONMENT PROTECTION File Number
In charge of
006.64
1/16" = 1'-0"
0 8' 16' 32'
Designed by
GBC STORAGE TANK & UTILITIES BUILDING - ROOF
LOWER HARBOR BROOK CSO STORAGE FACILITY

Date
2 08/11 AS BID LJC
Drawn by
KJL PLAN 08/11 H-201
THIS DRAWING WAS PREPARED AT THE SCALE INDICATED IN THE 1 04/11 ISSUED FOR APPROVAL LJC
TITLE BLOCK. INACCURACIES IN THE STATED SCALE MAY BE
SYRACUSE, NEW YORK
INTRODUCED WHEN DRAWINGS ARE REPRODUCED BY ANY
NO. DATE REVISION INT. SWM
Checked by
MEANS. USE THE GRAPHIC SCALE BAR IN THE TITLE BLOCK TO NO ALTERATIONS PERMITTED HEREON EXCEPT AS PROVIDED UNDER SECTION 7209
DETERMINE THE ACTUAL SCALE OF THIS DRAWING. SUBDIVISION 2 OF THE NEW YORK STATE EDUCATION LAW HVAC
NOTE:
FUTURE ODOR
CONTROL UNIT 1. 2" STAINLESS STEEL DRAIN ROUTE BELOW GRADE AT EDGE OF
CONCRETE PAD. PROVIDE 24" TRAP BELOW GRADE HEAT TRACE
AND INSULATE ABOVE-GRADE PIPING & CONTINUE TO 4'-0" BELOW
GRADE. ROUTE TO SANITARY MANHOLE MH-1 INVERT ELEVATION 373.50'
(REFER TO DRAWING G-103 & G-104) PROVIDE 1/2" BALL VALVE AND
COMPRESSED AIR CONNECTION AT TOP OF VERTICAL FOR BLOWING
OUT TRAP.

FUTURE ODOR
CONTROL UNIT

POTENTIAL FUTURE
EXPANSION
(NOT IN CONTRACT)

BLOWER
BL-2

48" DIA. DISCHARGE


TYPICAL

ODOR CONTROL
BLANK OFF END VESSEL OC-2 2" TANK DRAIN
OF DUCT SEE NOTE 1

INV. EL. 373.50


(TYP.x2)

MH-1
D-4
80"x48" EXHAUST
DUCT CONCRETE PAD
(BY CONTRACT 4A)
BLOWER
BL-1 MANHOLE

INLET
DAMPER
(TYP.)
96"x48" EXHAUST
2" TANK DRAIN SEE NOTE 1
DUCT
ODOR CONTROL
VESSEL OC-1

D-3

1
40"x40" 30"x50" INLET BOX BLOWER CONTROL
H-203 (TYP.) (TYP.) (TYP.) PANEL (TYP.)

ENLARGED PLAN
SCALE: 1/4" = 1'-0"
SCALE: LJC ONONDAGA COUNTY DEPARTMENT OF WATER ENVIRONMENT PROTECTION File Number
In charge of
006.64
2 0 2 4
2 6 8 10 LOWER HARBOR BROOK CSO STORAGE FACILITY
SWM
1/4" = 1'-0" Designed by Date
2 08/11 AS BID LJC
Drawn by
KJL ODOR CONTROL SYSTEM ENLARGED PLAN 08/11 H-202
THIS DRAWING WAS PREPARED AT THE SCALE INDICATED IN THE 1 04/11 ISSUED FOR APPROVAL LJC
TITLE BLOCK. INACCURACIES IN THE STATED SCALE MAY BE
SYRACUSE, NEW YORK
INTRODUCED WHEN DRAWINGS ARE REPRODUCED BY ANY
NO. DATE REVISION INT. GBC
Checked by
MEANS. USE THE GRAPHIC SCALE BAR IN THE TITLE BLOCK TO NO ALTERATIONS PERMITTED HEREON EXCEPT AS PROVIDED UNDER SECTION 7209
DETERMINE THE ACTUAL SCALE OF THIS DRAWING. SUBDIVISION 2 OF THE NEW YORK STATE EDUCATION LAW HVAC
STACK SEE DETAIL
ON SHEET H-302

48" DIA
DISCHARGE
DUCT

FLANGED CONNECTION
(NOTE 2)

ODOR CONTROL
VESSEL
BLOWER DISCHARGE
DUCT (NOTE 1)
OC-1

DISCHARGE FLEXIBLE
INLET DAMPER CONNECTION
96"x48 " EXHAUST D-3
DUCT
INLET FLEXIBLE
CONNECTION

2" STAINLESS STEEL


DRAIN VALVE

BLOWER BL-1 1/2" AIR RELIEF


VALVE

CONCRETE PAD TANK WALL

EXHAUST DUCT SUPPORT


SEE DETAIL ON SHEET
H-302

BLOWER INLET BOX SUPPORT (NOTE 3)

2" DRAIN TO
MANHOLE MH-1

NOTES:
1. DISCHARGE DUCT SHALL EXPAND AT 5-DEGREE ANGLE ON TOP AND SIDES (FOB). DISCHARGE DUCT AND FITTINGS SHALL BE RATED +20" W.C..

2. MATCH SIZE AND LOCATION OF ODOR CONTROL VESSEL INLET TO BLOWER DISCHARGE DUCT. SECTION 1 1
1/2" = 1'-0" H-201
3. SUPPORT DISCHARGE DUCT FROM CONCRETE PAD, INDEPENDENT OF BLOWER BASE.

SCALE: LJC ONONDAGA COUNTY DEPARTMENT OF WATER ENVIRONMENT PROTECTION File Number
In charge of
1 0 1 2 3 4 5 006.64
LOWER HARBOR BROOK CSO STORAGE FACILITY
1/2" = 1'-0" SWM
Designed by Date
2 08/11 AS BID LJC
Drawn by
KJL ODOR CONTROL SYSTEM SECTION 08/11 H-203
THIS DRAWING WAS PREPARED AT THE SCALE INDICATED IN THE 1 04/11 ISSUED FOR APPROVAL LJC
TITLE BLOCK. INACCURACIES IN THE STATED SCALE MAY BE
SYRACUSE, NEW YORK
INTRODUCED WHEN DRAWINGS ARE REPRODUCED BY ANY
NO. DATE REVISION INT. GBC
Checked by
MEANS. USE THE GRAPHIC SCALE BAR IN THE TITLE BLOCK TO NO ALTERATIONS PERMITTED HEREON EXCEPT AS PROVIDED UNDER SECTION 7209
DETERMINE THE ACTUAL SCALE OF THIS DRAWING. SUBDIVISION 2 OF THE NEW YORK STATE EDUCATION LAW HVAC
B

BOD 384'-8"

EXHAUST 30,000 CFM 40"x40" 48"x96" EXHAUST


FAN EF-2 EXHAUST DUCT 384'-8"
DUCT
96"x48 EXHAUST TO ODOR 96"x48
ELECTRICAL CONTROL VESSELS
PANEL BOD 379'-0"

2' - 8"
STORAGE
TANK
ROOF

6' - 2"
2' - 8"
WALKWAY

TANK WALL

1' - 8"
SECURITY
BARS

40"x40" EXHAUST 40"x40" EXHAUST


DUCT THROUGH 30,000 CFM 30,000 CFM DUCT THROUGH
ROOF ROOF

SECTION 3 2 SECTION 2 1
1/4" = 1'-0" H-201 1/4" = 1'-0" H-201

POWERED ROOF
EXHAUSTER
PRE-2

POWERED ROOF
EXHAUSTER
PRE-4

SUPPLY AIR FAN


SF-4

12"x12" SA
GRAVITY ROOF
VENTILATOR
20"x30" SA
GRV-1

20"x20" SUPPORT
(TYP.)

12"x12" SA
4' - 0"

36"x30

5,000 CFM 5,000 CFM


24"x24"

30,000 CFM

24"x24" EXHAUST DUCT DOWN


TO EL 327'10. PROVIDE 24"x24"
RETURN GRILLE AT INTAKE
OPENING

SECTION 4 3
1/4" = 1'-0" H-201

SCALE: LJC ONONDAGA COUNTY DEPARTMENT OF WATER ENVIRONMENT PROTECTION File Number
In charge of
2 0 2 4
2 6 8 10 006.64
LOWER HARBOR BROOK CSO STORAGE FACILITY
1/4" = 1'-0" SWM
Designed by Date
2 08/11 AS BID LJC
Drawn by
KJL STORAGE TANK SECTIONS 08/11 H-204
THIS DRAWING WAS PREPARED AT THE SCALE INDICATED IN THE 1 04/11 ISSUED FOR APPROVAL LJC
TITLE BLOCK. INACCURACIES IN THE STATED SCALE MAY BE
SYRACUSE, NEW YORK
INTRODUCED WHEN DRAWINGS ARE REPRODUCED BY ANY
NO. DATE REVISION INT. GBC
Checked by
MEANS. USE THE GRAPHIC SCALE BAR IN THE TITLE BLOCK TO NO ALTERATIONS PERMITTED HEREON EXCEPT AS PROVIDED UNDER SECTION 7209
DETERMINE THE ACTUAL SCALE OF THIS DRAWING. SUBDIVISION 2 OF THE NEW YORK STATE EDUCATION LAW HVAC
ELECTRIC UNIT HEATER (EUH) SCHEDULE BLOWER (BL) SCHEDULE
FAN ELECTRICAL DESIGN BASIS
MOUNTING S.P.
NO. LOCATION KW VOLTS/PHASE REMARKS NO. SERVES WHEEL REMARKS
HEIGHT
CFM DIAMETER RPM BHP HP RPM VOLTS/PHASE MANUFACTURER MODEL NO.
(WC)
EUH-1 ELECTRIC 101 5.0 480/3 9'-0" 1 NEW YORK
BL-1 ODOR CONTROL 30,000 13" 48" 1250 80 125 1800 480/3 FE 482 HP 1 -12
BLOWER
EUH-2 MECHANICAL 105 5.0 480/3 9'-0" 1
NEW YORK
BL-2 ODOR CONTROL 30,000 13" 48" 1250 80 125 1800 480/3 FE 482 HP 1 - 12
BLOWER
EUH-3 STAIR 104 5.0 480/3 9'-0" 1,2

REMARKS:
REMARKS:
1. ARRANGEMENT 1.
1. INSTALL WITH HORIZONTAL DISCHARGE. 2. UNITARY BASE
2. SUITABLE FOR CLASS I, DIVISION I, GROUP D ATOMSPHERE. 3. BELT GUARD WITH TACHOMETER OPENING AND PLUG.
4. SHAFT AND BEARING GUARD WITH EXTENDED BEARING LUBRICATION FITTING.
5. FLUSH - BOLTED CLEANOUT DOOR
6. DRAIN WITH DRAIN PLUG.
7. FLANGED OUTLET WITH COMPANION FLANGE.
8. FLANGED INLET WITH COMPANION FLANGE.
ELECTRIC DUCT HEATER (EDH) SCHEDULE 9. OUTLET DAMPER.
10.SUITABLE FOR OUTDOOR INSTALLATION.
11.AMCA TYPE A SPARK RESISTANT CONSTRUTION.
12.SUITABLE FOR CLASS I, DIVISION I, GROUP D ATMOSPHERE.
MINIMUM HEATING
NO. LOCATION CAPACITY VOLTS/PHASE REMARKS
(KW)

POWERED ROOF EXHAUSTER (PRE) SCHEDULE


EDH-1 MECHANICAL 105 7.5 480/3 1

REMARKS:
1. PROVIDE COMPLETE CONTROLS PER SPECIFICATIONS. FAN MOTOR ROOF
NO. LOCATION AIR FLOW (CFM) S.P. (WC) OPENING MANUFACTURER/ MODEL REMARKS
HP VOLTS/PHASE SIZES

PRE-1 ELECTRIC 101 300 0.25 1/25 120/1 13.5 X 13.5 COOK/ACEB - 100C210DM -

ELECTRIC CABINET HEATER (ECH) SCHEDULE PRE-2 STAIR 104 100 0.25 1/20 120/1 13.5 X 13.5 COOK/ACED - 70C15DL 1

PRE-3 BATH 106 75 0.125 1/25 120/1 13.5 X 13.5 COOK/ACED - 70C10DM -
NO. LOCATION MIN HEATING CAPACITY VOLT/PHASE DESIGN BASIS
(KW) STORAGE TANK - STAIRWELL 500 0.25 1/6 120/1 13.5 X 13.5 COOK/ACEB - 100C2B 1
PRE-4
ECH-1 HALL 102 3.3 480/3 TRANE UHEC-3
REMARKS:
1. SUITABLE FOR CLASS I, DIVISION I, GROUP D ATMOSPHERE.

PACKAGED TERMINAL AIR CONDITIONER (PTAC) SCHEDULE SUPPLY FAN (SF) SCHEDULE
FAN MOTOR
SUPPLY MINIMUM MAXIMUM NO. LOCATION AIR FLOW (CFM) S.P. (WC) MANUFACTURER/ MODEL REMARKS
NOMINAL
NO. LOCATION EER HEATING VOLTS/PHASE COOLING MOCP REMARKS HP VOLTS/PHASE
COOLING BTUH
(CFM) CAPACITY (BTU) AMPS
SF-1 STORAGE TANK 30,000 1.00 15 480/3 GREENHECK 49-BISW 1,2
PTAC-1 OFFICE 107 9,000 11.2 220 11,600 208/1 3.9 20 1
SF-2 STORAGE TANK 30,000 1.00 15 480/3 GREENHECK 49-BISW 1,2
REMARKS:
SF-3 STORAGE TANK 30,000 3.50 25 480/3 GREENHECK 49-BISW 1
1. DESIGN DATA BASED ON FRIEDRICH MODEL PDE9K.
SF-4 STORAGE TANK 30,000 3.50 25 480/3 GREENHECK 49-BISW 1

SF-5 MECHANICAL 105 275 0.5 1/12 120/1 GREENHECK SQ-85-D -


ELECTRIC BASEBOARD HEATER (EBH) SCHEDULE REMARKS:

MINIMUM HEATING MAXIMUM 1. SUITABLE FOR CLASS I, DIVISION I, GROUP D ATMOSPHERE.


NO. LOCATION CAPACITY VOLTS/PHASE MOUNTING 2. PROVIDE WITH MANUALLY OPERATED DISCHARGE DAMPER.
(KW) HEIGHT

EBH-1 BATH 106 1 208/1 FLOOR


EXHAUST FAN (EF) SCHEDULE
FAN MOTOR
NO. LOCATION AIR FLOW (CFM) S.P. (WC) MANUFACTURER/ MODEL REMARKS
HP VOLTS/PHASE
REGISTERS, DIFFUSERS, GRILLES (SR) EF-1 STORAGE TANK 30,000 1.00 15 480/3 GREENHECK 49-BISW 1

DIMENSION EF-2 STORAGE TANK 30,000 1.00 15 480/3 GREENHECK 49-BISW 1


AIR FLOW NOISE MAX. PRESURE
NO. DUTY MODEL DESIGN BASIS REMARKS
WIDTH HEIGHT RANGE(CFM) CRITERIA (NC) DROP (IN.WC)
REMARKS:

SR-1 SUPPLY 10" 6" 80-250 25 0.08 TITUS MODEL 50F 1 1. SUITABLE FOR CLASS I, DIVISION I, GROUP D ATMOSPHERE.

REMARKS:

1. SEE DRAWING H-101 FOR DUCTWORK AND REGISTER CONNECTION SIZE DAMPER (D) SCHEDULE
DIMENSION DAMPER ACTUATOR
NO. LOCATION QUANTITY TYPE DUTY INTERLOCK WITH MODEL

LOUVER (LV) SCHEDULE WIDTH HEIGHT TYPE OPEN CLOSE REMARKS

D-1 LOUVER L-1 1 24" 24" STANDARD INTAKE ELECT. POWER SPRING SF-5 GREENHECK MODEL VCD -
DIMENSION MIN.
FREE AREA D-2 LOUVER L-2 1 24" 24" INSULATED INTAKE ELECT. POWER SPRING PRE-1 GREENHECK MODEL ICD -
NO. LOCATION DUTY MODEL
WIDTH HEIGHT (SF)
D-3 BL-1 1 66" 37" ALUMINUM ISOLATION ELECT. POWER SPRING BL-1 GREENHECK MODEL VCD 1
L-1 MECHANICAL 105 24" 24" 1.00 INTAKE GREENHECK MODEL ESD-435
D-4 BL-2 1 66" 37" ALUMINUM ISOLATION ELECT. POWER SPRING BL-1 GREENHECK MODEL ICD 1
L-2 ELECTRIC 101 24" 24" 1.00 INTAKE GREENHECK MODEL ESD-435
REMARKS:

1. DIMENSIONS ARE APPROXIMATE. COORDINATE WITH BLOWER INLET BOX.

SCALE: LJC ONONDAGA COUNTY DEPARTMENT OF WATER ENVIRONMENT PROTECTION File Number
In charge of
006.64
NOT TO SCALE SWM
LOWER HARBOR BROOK CSO STORAGE FACILITY
Designed by Date
2 08/11 AS BID LJC
Drawn by
KJL SCHEDULES 08/11 H-301
THIS DRAWING WAS PREPARED AT THE SCALE INDICATED IN THE 1 04/11 ISSUED FOR APPROVAL LJC
TITLE BLOCK. INACCURACIES IN THE STATED SCALE MAY BE
SYRACUSE, NEW YORK
INTRODUCED WHEN DRAWINGS ARE REPRODUCED BY ANY
NO. DATE REVISION INT. GBC
Checked by
MEANS. USE THE GRAPHIC SCALE BAR IN THE TITLE BLOCK TO NO ALTERATIONS PERMITTED HEREON EXCEPT AS PROVIDED UNDER SECTION 7209
DETERMINE THE ACTUAL SCALE OF THIS DRAWING. SUBDIVISION 2 OF THE NEW YORK STATE EDUCATION LAW HVAC
4'-0"

DUCT WIDTH
+ 12"

EXHAUST DUCT

2" WIDE HEAVY GAUGE ALUMINUM


STRAP BOLTED TO CHANNEL

48" DIA VESSEL DISCHARGE

8' - 0"
6" HOT-DIPPED GALVANIZED
HOT-DIPPED GALVANIZED STEEL C6x8 (NOTE2)
3" DIA. STD. PIPE STANCHION
1/2" SPACERS (TYP.x2) (NOTE 1)
BETWEEN STACK AND
VESSEL OUTLETS
(NOTE 1)
8" DIA CONCRETE
PIER (TYP.x2)
(TYP)
1" SPACER AT BASE OF TOP OF 3/16
STACK VESSEL

1' - 0"
GRADE ELEVATION
VARIES

VESSEL

MINIMUM
4' - 0"
NOTES:
1. FASTEN STACK TO VESSEL DISCHARGE.

2. "D" = VESSEL DISCHARGE OUTSIDE DIAMETER +1". APPROXIMATELY 50".


FIELD VERIFY.
NOTES:
3. STACK SHALL BE CONSTRUCTED OF FRP.
1. VARY PIPE LENGTH AS REQUIRED FOR LOCATION AND GRADE CONDITIONS.
4. STACK SHALL BE PAINTED SKY BLUE.
2. CHANNEL SHALL BE MOUNTED LEVEL, WITH BACK UP.

3. POWDER COAT HOT-DIPPED GALVANIZED COMPONENTS PAINT WHITE.

ODOR CONTROL VESSEL


DISCHARGE DUCT PIPE
EXHAUST DUCT AT GRADE
SUPPORT DETAIL
SCALE: 1/2" = 1'-0"
SUPPORT DETAIL
SCALE: 1/2" = 1'-0"

DUCT WIDTH
+ 12"

ALUMINUM DUCT DAMPER EXHAUST DUCT


(NOTE 2) TOP (SF-1 & SF-2 ONLY)

TOPPING 2" WIDE HEAVY GAUGE ALUMINUM


SECURITY BARS (DEPTH VARIES) STRAP BOLTED TO CHANNEL
(NOTE 3)

TOP OF POUR POUR STOP


STOP (NOTE 1)

TOP OF PRECAST PLANK


CONCRETE TOPPING 382.00
THICKNESS VARIES 6" GALVANIZED STEEL 6" HOT-DIPPED GALVANIZED
(2" TO 8") STEEL C6x8 (NOTE2)
1' - 0"

TOP OF PRECAST HOT-DIPPED GALVANIZED 2" DIA. STD. PIPE STANCHION

2' - 8"
PLANK (TYP) (TYP. OF 2) (NOTE 1)
1/8"
PAIR OF ANCHORS
(NOTE 1)

NOTES:

1. PROVIDE CONCRETE POUR STOP CONSTRUCTED FROM 3/16" STAINLESS STEEL PLATE WELDED
ALL AROUND. FASTEN TO PRECAST PLANK WITH 1/4" DIA. DROP-IN ANCHORS WITH 7/8" MIN.
EMBEDMENT INTO SOLID SUBSTRATE OF HOLLOWCORE PLANK (3 PAIRS PER SIDE MIN.). PROVIDE
WITH WATER STOP. POUR STOP SHALL EXTEND 1'- 0" ABOVE PRECAST PLANK.
NOTES:
2. FABRICATE DUCT TO SLIP OVER POUR STOP. FASTEN DUCT TO POUR STOP. PROVIDE GASKET
AND CAULKING FOR WATERTIGHT SEAL.
1. VARY PIPE LENGTH AS REQUIRED FOR LOCATION AND GRADE CONDITIONS.
3. FASTEN SECURITY BARS TO POUR STOP WITH STAINLESS STEEL SCREWS AT 8" MAX. SPACING.
2. CHANNEL SHALL BE MOUNTED LEVEL, WITH BACK UP.
DUCT PENETRATION 3. WELD STANCHION TO PLATE. FASTEN PLATE TO CONCRETE WITH (4) 3/8" DIA. 3" L ANCHOR BOLTS.
THROUGH TANK ROOF 4. POWDER COAT HOT-DIPPED GALVANIZED COMPONENTS PAINT WHITE.
DETAIL
SCALE: 1/2" = 1'-0"
EXHAUST DUCT ON TANK
SUPPORT DETAIL
SCALE: 1/2" = 1'-0"

SCALE: LJC ONONDAGA COUNTY DEPARTMENT OF WATER ENVIRONMENT PROTECTION File Number
In charge of
1 0 1 2 3 4 5 006.64
LOWER HARBOR BROOK CSO STORAGE FACILITY
1/2" = 1'-0" SWM
Designed by Date
2 08/11 AS BID LJC
Drawn by
KJL DETAILS 08/11 H-302
THIS DRAWING WAS PREPARED AT THE SCALE INDICATED IN THE 1 04/11 ISSUED FOR APPROVAL LJC
TITLE BLOCK. INACCURACIES IN THE STATED SCALE MAY BE
SYRACUSE, NEW YORK
INTRODUCED WHEN DRAWINGS ARE REPRODUCED BY ANY
NO. DATE REVISION INT. GBC
Checked by
MEANS. USE THE GRAPHIC SCALE BAR IN THE TITLE BLOCK TO NO ALTERATIONS PERMITTED HEREON EXCEPT AS PROVIDED UNDER SECTION 7209
DETERMINE THE ACTUAL SCALE OF THIS DRAWING. SUBDIVISION 2 OF THE NEW YORK STATE EDUCATION LAW HVAC
PLC SYSTEM PLC SYSTEM

COMMON ALARM COMMON ALARM

START/STOP BL-1 FAIL BL-2 FAIL START/STOP


BL-1 IN REMOTE BL-2 IN REMOTE

FIRE ALARM
FIRE ALARM

BLOWER BL-1 BLOWER BL-2


LOCAL CONTROL STATION LOCAL CONTROL STATION
VENTILATION
FAILURE ALARM VENTILATION
FAILURE ALARM

OPEN RUN FAIL WATER OPEN RUN FAIL WATER


DETECT DETECT

O O
120V/1PHASE H R H R
120V/1PHASE
CLOSED CLOSED

ODOR ODOR
CONTROL CONTROL
DAMPER BLOWER/STATUS VESSEL DAMPER BLOWER/STATUS VESSEL
D-3 BL-1 OC-1 D-4 BL-2 OC-2

FAN
OPEN/CLOSE START/STOP STATUS
EXH

LS M LS STARTER

ODOR
CONTROL
VESSEL
OC-2

DAMPER BLOWER
D-4 BL-2

STATUS

FAN START/STOP

OPEN/CLOSE EXH

LS M LS STARTER

ODOR
CONTROL
VESSEL
OC-1

DAMPER BLOWER
D-3 BL-1

EXHAUST FROM STORAGE TANK WATER


DETECTOR
(TYP,)

SCALE: LJC ONONDAGA COUNTY DEPARTMENT OF WATER ENVIRONMENT PROTECTION File Number
In charge of
006.64
NOT TO SCALE SWM
LOWER HARBOR BROOK CSO STORAGE FACILITY
Designed by Date
2 08/11 AS BID LJC
Drawn by
KJL BLOWER CONTROL DIAGRAM 08/11 H-303
THIS DRAWING WAS PREPARED AT THE SCALE INDICATED IN THE 1 04/11 ISSUED FOR APPROVAL LJC
TITLE BLOCK. INACCURACIES IN THE STATED SCALE MAY BE
SYRACUSE, NEW YORK
INTRODUCED WHEN DRAWINGS ARE REPRODUCED BY ANY
NO. DATE REVISION INT. GBC
Checked by
MEANS. USE THE GRAPHIC SCALE BAR IN THE TITLE BLOCK TO NO ALTERATIONS PERMITTED HEREON EXCEPT AS PROVIDED UNDER SECTION 7209
DETERMINE THE ACTUAL SCALE OF THIS DRAWING. SUBDIVISION 2 OF THE NEW YORK STATE EDUCATION LAW HVAC
ABBREVIATIONS SYMBOLS

A F Q PIPING VALVES EQUIPMENT PLUMBING EQUIPMENT


DESIGNATION
@ AT FD FLOOR DRAIN BUTTERFLY VALVE
PIPING
AAV AUTOMATIC AIR VENT FDC FIRE DEPARTMENT CONNECTION EMERGENCY EYEWASH/SHOWER
QTY. QUANTITY
ABS ACRYLONITRILE BUTADIENE STYRENE FL. FLOOR
ADD'L
AFF
ADDITIONAL
ABOVE FINISHED FLOOR
FLV
FM
FLAP VALVE
FLOW METER
R FLANGED JOINT CHECK VALVE
WATER METER
EWH-5A
M
ALUM ALUMINUM FS FLOW SWITCH WELDED JOINT BALL VALVE
RA RETURN AIR SUFFIX LETTER (FOR DISTINCTION OF
ANSI AMERICAN NATIONAL STANDARDS FT. FOOT OR FEET
RAD. RADIUS SIMILAR ITEMS, IF NEEDED)

APPD.
INSTITUTE
APPROVED
G RD
RED.
ROOF DRAIN
REDUCE(R)
MECHANICAL JOINT GLOBE VALVE BACKFLOW PREVENTER EQUIPMENT PROCESS SEQUENCE NUMBER

APPROX APPROXIMATE Gal GALLON(S) REF. REFERENCE EQUIPMENT TYPE OR FUNCTION


ARCH ARCHITECTURAL REINF. REINFORCE SLEEVE-TYPE GATE VALVE
GV GATE VALVE MECHANICAL COUPLING HOSE BIBB
ASPH ASPHALT GLV REQ'D REQUIRED
ASTM AMERICAN SOCIETY FOR GLOBE VALVE
GPH REV. REVISION
TESTING AND MATERIALS GALLONS PER HOUR RM. ROOM ELBOW UP COCK VALVE BFP BACKFLOW PREVENTER
GPM GALLONS PER MINUTE
AUTO AUTOMATIC RPM REVOLUTIONS PER MINUTE FLOOR DRAIN EWH ELECTRIC WATER HEATER
AUX
AV
AUXILIARY
ACID VENT H RPZ REDUCED PRESSURE ZONE BACKFLOW
PREVENTER
ELBOW DOWN NEEDLE VALVE EWS
P
EYEWASH SHOWER
PLUMBING FIXTURE

S
AVG AVERAGE
HB HOSE BIBB 90° ELBOW IN PLANE WATER HEATER
AVV AIR/VACUUM VALVE KNIFE GATE VALVE
HD. HEAD
AW ACID WASTE
HDPE HIGH DENSITY POLYETHYLENE
AWS AMERICAN WELDING SOCIETY
HORIZ. HORIZONTAL SAN. SANITARY 45° ELBOW IN PLANE BALANCING VALVE
AWWA AMERICAN WATER WORKS ASSOCIATION HOSE REEL
HP HORSE POWER OR HIGH POINT SCH. SCHEDULE

B HR.
HT.
HOUR
HEIGHT
SD
SECT.
STORM DRAIN OR SMOKE DAMPER
SECTION TEE UP
DIAPHRAGM VALVE

B&S BELL & SPIGOT HV HOSE VALVE SF SQUARE FOOT IN-LINE PUMP
B. OR BOT. BOTTOM HW HOT WATER PINCH VALVE
SFD SIGHT FLOW DRAIN
B&B BELL & BELL
I SH. OR SHT. SHEET TEE DOWN

MISCELLANEOUS
B&F BELL & FLANGE PLUG VALVE
SIM. SIMILAR
BAV BALL VALVE
ID INSIDE DIAMETER SOLV. WLD. SOLVENT WELDED SUMP PUMP
BF BLIND FLANGE
SPEC. SPECIFICATION TEE IN PLANE
BFF BELOW FINISHED FLOOR IN. INCH OR INCHES PRESSURE REDUCING
SQ. SQUARE
BFP BACKFLOW PREVENTER INSUL. INSULATION OR INSULATED VALVE
SS STAINLESS STEEL EXISTING PIPING
BFV BUTTERFLY VALVE INV. INVERT STD. STANDARD
BACK PRESSURE
L
B BASE LINE
STL. STEEL VALVE
BLDG BUILDING NEW PIPING
STOR. STORAGE CROSS
Bm BEAM
BOP BOTTOM OF PIPE STRUCT STRUCTURAL
LAB. LABORATORY
SUSP. CLG. SUSPENDED CEILING ANGLE VALVE
BPS BOOSTER PUMPING STATION LAV. LAVATORY SV SOLENOID VALVE
BSMT BASEMENT LBS POUNDS LATERAL WYE IN PLANE FLOW DIRECTION
OR
BW BUTT WELD LINEAR FEET ANGLE GATE VALVE
T
LF

C LG.
LS
LENGTH OR LONG
LIMIT SWITCH

C/C CENTER TO CENTER M TSTAT


TEMP.
THERMOSTAT
TEMPERATURE
CONCENTRIC REDUCER ANGLE GLOBE VALVE
MISCELLANEOUS SYMBOLS PIPE CONTINUES
CA COMPRESSED AIR
MATERIAL TOP TOP OF PIPE S
CaO CALCIUM OXIDE (LIME) MAT'L ECCENTRIC REDUCER 3 WAY VALVE
MAXIMUM TS TEMPERATURE SWITCH DIRECTION OF PITCH
CHEM CHEMICAL MAX PRESSURE GAUGE
MECHANICAL TW TEMPERED WATER
CI CAST IRON MECH.
CISP CAST IRON SOIL PIPE TYP. TYPICAL SEDIMENT TRAP
MFR. MANUFACTURER 3 WAY BALL VALVE
CL
CLG
CENTERLINE
CEILING
MIN.
MISC.
MINIMUM
MISCELLANEOUS
U CALIBRATION
P POINT OF CONNECTION
CLR CLEAR CAP 3 WAY GLOBE VALVE PIPE STAND
MTD. MOUNTED
CMP CORRUGATED METAL PIPE
MTL. METAL UON UNLESS OTHERWISE NOTED
CMU CONCRETE MASONRY UNIT
CO CLEAN OUT
N UNION
PRESSURE RELIEF VALVE
COL
CONC
COLUMN
CONCRETE NFPA NATIONAL FIRE PROTECTION ASSOCIATION
V A AIR VENT AUTO
CONST CONSTRUCTION NIC NOT IN CONTRACT STRAINER
CONT CONTINUE OF CONTINUOUS NMPC NIAGARA MOHAWK POWER CORPORATION V VENT OR VOLTS MUD VALVE
CONT'D CONTINUED No. or # NUMBER VAC VOLTS ALTERNATING CURRENT AIR VENT MANUAL
CONTR CONTRACT OR CONTRACTOR NRS NON-RISING STEM VERT. VERTICAL HOSE CONNECTION
COORD COORDINATE FC
NSF NATIONAL SANITATION FOUNDATION FLUSHING CONNECTION
CORR
CPVC
CORRIDOR
CHLORINATED POLYVINYL CHLORIDE NTS
NYSDEC
NOT TO SCALE
NEW YORK STATE DEPARTMENT OF
W QUICK CONNECTION ST
DRAWING NOTE:
THIS DRAWING CONTAINS SYMBOLS AND ABBREVIATIONS
CS CARBON STEEL SAMPLE TAP
ENVIRONMENTAL CONSERVATION
CTR CENTER WHICH MAY NOT BE USED FOR THIS PROJECT.
NYSDOH NEW YORK STATE DEPARTMENT OF HEALTH W/O WITHOUT
CV CHECK VALVE
NYSDOT NEW YORK STATE DEPARTMENT OF W/ WITH
CW COLD WATER OR CLOCKWISE
TRANSPORTATION WC WATER CLOSET OR WATER COLUMN

D NYTEL NEW YORK TELEPHONE COMPANY WH WATER HEATER


NaClO SODIUM HYPOCHLORITE WHA WATER HAMMER ARRESTER
PLUMBING SPECIALTIES
DEG
D
DEGREE
DRAIN (ALL TYPES) (SPECIFY)
O WLD.
Wt.
WELD OR WELDED
WEIGHT
WTP WATER TREATMENT PLANT
DCW DOMESTIC COLD WATER O/C ON CENTER HB HOSE BIBB
WWTP WASTE WATER TREATMENT PLANT FLOOR DRAIN
DF DRINKING FOUNTAIN OD OUTSIDE DIAMETER
DHW DOMESTIC HOT WATER OPNG. OPENING
DI DUCTILE IRON OS&Y OUTSIDE SCREW & YOKE BACKFLOW VALVE
DECKPLATE
DIA. DIAMETER OSHA OCCUPATIONAL SAFETY AND HEALTH
DIM DIMENSION ADMINISTRATION CLEANOUT
DN DOWN RPZ BACKFLOW VALVE
TRAP (PLAN)
P
DPCO DECK PLATE CLEANOUT
DWG DRAWING

E P
PE
PRESSURE
POLYETHYLENE OR PLAIN END
TRAP (SIDE)
FLEX CONNECTION

Ea EACH PW PLANT WATER DPCO


HARNESSED COUPLING
EBH ELECTRIC BASEBOARD HEATER PNL. PANEL
ECV ELECTRIC CHECK VALVE POC POINT OF CONNECT CLEANOUT, DPCO
EFF EFFLUENT OR EFFICIENCY POT. W. POTABLE WATER FLOAT VALVE
EL ELEVATION PP POLYPROPYLENE
ELEC ELECTRIC OR ELECTRICAL PRV PRESSURE REDUCING VALVE
CO CLEANOUT, PLUG CORPORATION STOP
ELL ELBOW PS PRESSURE SWITCH
EQ EQUAL PSF POUNDS PER SQUARE FOOT
EQUIP EQUIPMENT PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE INCH GAGE CLEANOUT, WALL DRAIN VALVE
EWC ELECTRIC WATER COOLER
PTFE POLYTETRAFLUOROETHYLENE
EXIST OR EX EXISTING
PV PLUG VALVE
PVC POLYVINYL CHLORIDE HB DRAIN

NON-FREEZE WALL HYDRANT

SCALE: LJC ONONDAGA COUNTY DEPARTMENT OF WATER ENVIRONMENT PROTECTION File Number
In charge of
006.64
NOT TO SCALE BC
LOWER HARBOR BROOK CSO STORAGE FACILITY
Designed by Date

THIS DRAWING WAS PREPARED AT THE SCALE INDICATED IN THE


2
1
08/11
4/11
AS BID
ISSUED FOR APPROVAL
LJC
LJC
Drawn by
KJL SYMBOLS AND ABBREVIATIONS 08/11 P-001
TITLE BLOCK. INACCURACIES IN THE STATED SCALE MAY BE
SYRACUSE, NEW YORK
INTRODUCED WHEN DRAWINGS ARE REPRODUCED BY ANY
NO. DATE REVISION INT. GBC
Checked by
MEANS. USE THE GRAPHIC SCALE BAR IN THE TITLE BLOCK TO NO ALTERATIONS PERMITTED HEREON EXCEPT AS PROVIDED UNDER SECTION 7209
DETERMINE THE ACTUAL SCALE OF THIS DRAWING. SUBDIVISION 2 OF THE NEW YORK STATE EDUCATION LAW PLUMBING
A

NOTE:
1. ALL FLOOR DRAIN SHALL HAVE TRAPS AND TRAP PRIMERS. SEE DETAIL ON SHEET P-301.

2. FINISHED FLOOR ELEVATION 378.00.

3. FURNISH AND INSTALL 36"x36" CORNER BASE WITH DOUBLE THRESHOLD. BASE SHALL BE
ONE PIECE, "WHITE" MOLDED FIBERGLASS W/ SLIP RESISTANT SURFACE. INTEGRAL MOLDED
DRAIN WITH SEAL FOR CONNECTION TO 2" SCH. 40 PVC DWV SANITARY DRAIN
PIPE - REMOVABLE STRAINER. SHALL MEET ANSI SPECIFICATION Z97.1. UNIT TO BE MODEL
3636DTM AS MAUNFACTURED BY E.L. MUSTEE & SONS INC. OR EQUAL.

4. FURNISH AND INSTALL SHOWER ENCLOSURE AS SHOWN ON PLAN. ENCLOSURE SHALL BE


DOUBLE-THRESHOLD STYLE WITH ALUMINUM FRAME AND CLEAR TEMPERED SAFETY GLASS
ELECTRIC PANEL. CONTINUOUS PULL HANDLE WITH MAGNETIC SEAL.. OUT OF PLUMB CONDITION UP TO
1" CAN BE ADJUSTED. SHALL MEET ANSI SPECIFICATION Z97.1. UNIT TO BE STYLEMATE MODEL
101 36.202 AS MANUFACTURED BY E.L. MUSTEE & SONS, INC. OR EQUAL.

4" SECONDARY DRAIN


DOWNSPOUT NOZZLE 16"
ABOVE GRADE PROVIDE

5 SPLASH BLOCK AT GRADE

VESTIBILE
4" UP TO 108 4" UP TO HALL
5 STAIR ROOF
DRAIN
SECONDARY
ROOF DRAIN 102
P-103 104 CO S
4" ST

CO

4" STORM DRAIN

S
2" VENT UP 6

2" VENT
3" VENT THROUGH

4" ST
ROOF WCO P-103
4" TYPE "C"
FLOOR
DRAIN MECHANICAL 4" SANITARY DRAIN
LV-1 INV. EL. 370.42
105 SS-1 BATH SEE SHEET G-103
FOR CONTINUATION
S 106 S
4" SAN 4" SAN
DPCO

STORM DRAIN 4" TYPE "C" OFFICE


DOWN W/ CO S FLOOR DRAIN 5' - 0"
4" ST WC-1 107
CO LIMIT OF
3" VENT UP PLUMBING
THROUGH SH-1 4" TYPE "A" TRADE
4" STORM DRAIN SEE CHECK VALVE ROOF FLOOR DRAIN
SHEET P-201 FOR
CONTINUATION

6" PLANT WATER SEE 4" BACKFLOW 4" TYPE "C" 2" BACKFLOW SHOWER 2" SHOWER
SHEET P-201 FOR PREVENTER FLOOR DRAIN PREVENTER SEE NOTES DRAIN
CONTINUATION DRAIN W/ MESH DRAIN 3&4
ON OUTLET

FLOOR PLAN
SCALE: 1/4" = 1'-0"

SCALE: LJC ONONDAGA COUNTY DEPARTMENT OF WATER ENVIRONMENT PROTECTION File Number
In charge of
2 0 2 4
2 6 8 10 006.64
LOWER HARBOR BROOK CSO STORAGE FACILITY
1/4" = 1'-0" GBC
Designed by Date

THIS DRAWING WAS PREPARED AT THE SCALE INDICATED IN THE


2
1
08/11
4/11
AS BID
ISSUED FOR APPROVAL
LJC
LJC
Drawn by
KJL UTILITIES BUILDING DRAINAGE PIPING PLAN 08/11 P-101
TITLE BLOCK. INACCURACIES IN THE STATED SCALE MAY BE
SYRACUSE, NEW YORK
INTRODUCED WHEN DRAWINGS ARE REPRODUCED BY ANY
NO. DATE REVISION INT. GBC
Checked by
MEANS. USE THE GRAPHIC SCALE BAR IN THE TITLE BLOCK TO NO ALTERATIONS PERMITTED HEREON EXCEPT AS PROVIDED UNDER SECTION 7209
DETERMINE THE ACTUAL SCALE OF THIS DRAWING. SUBDIVISION 2 OF THE NEW YORK STATE EDUCATION LAW PLUMBING
A

NOTE:
1. FINISHED FLOOR ELEVATIONS 378.00.

2. SHOWER TRIM SHALL CONSIST OF A PRESSURE BALANCING VALVE WITH


INTEGRAL VOLUME CONTROL AND MAXIMUM TEMPERATURE LIMIT STOP.
UNIT SHALL BE A WALL/HAND SHOWER WITH FLEXIBLE METAL HOSE, WALL
CONNECTION AND FLANGE, AND SLIDE BAR FOR HAND SHOWER
MOUNTING. SHOWER TRIM SHALL BE "TEMPTROL" MODEL S-96-300B-24 AS
MANUFACTURED BY SYMMONS INDUSTRIES, INC. OR EQUAL.

ELECTRIC
101

3" PLANT WATER SEE 5


SHEET P-201 FOR
CONTINUATION

STAIR VESTIBULE HALL


104 103 102

4
MECHANICAL P-103
1/2" HYDRAULIC TUBING 6" STAINLESS 6" DUCTILE IRON
TO FLUSING TANK SEE STEEL 105
SHEET P-201 FOR
CONTINUATION OFFICE
(2) 1/2" PVC COATED 1 1/2" PRZ WATER SS-1
304 SS HYDRAULIC BACKFLOW HEATER
107
TUBING 6" AFF. LV-1
PREVENTER EWH-1

6" PRZ WC-1


6" PRESSURE BACKFLOW 8" FULL
REDUCING PORT SHUT
BATH
PREVENTER
VALVE OFF VALVE 106
2

1' - 0"
P-103
SH-1

1' - 10"
6" PLANT WATER TO 6" PLANT EXPANSION SHOWER

5' - 0"

5' - 0"
STORAGE TANK SEE WATER LIMIT OF TANK SEE NOTE 2
SHEET P-201 FOR SHUT-OFF PLUMBING
CONTINUATION 3 TRADE
6" PLANT WATER TO 8" INCOMING WATER SUPPLY SEE
P-103 HYDRANT SEE SHEET SHEET G-103 FOR CONTINUATION
G-103 FOR
CONTINUATION

1
P-103

FLOOR PLAN
SCALE: 1/4" = 1'-0"

SCALE: LJC ONONDAGA COUNTY DEPARTMENT OF WATER ENVIRONMENT PROTECTION File Number
In charge of
2 0 2 4
2 6 8 10 006.64
LOWER HARBOR BROOK CSO STORAGE FACILITY
1/4" = 1'-0" GBC
Designed by Date

THIS DRAWING WAS PREPARED AT THE SCALE INDICATED IN THE


2
1
08/11
4/11
AS BID
ISSUED FOR APPROVAL
LJC
LJC
Drawn by
KJL UTILITIES BUILDING WATER PIPING PLAN 08/11 P-102
TITLE BLOCK. INACCURACIES IN THE STATED SCALE MAY BE
SYRACUSE, NEW YORK
INTRODUCED WHEN DRAWINGS ARE REPRODUCED BY ANY
NO. DATE REVISION INT. GBC
Checked by
MEANS. USE THE GRAPHIC SCALE BAR IN THE TITLE BLOCK TO NO ALTERATIONS PERMITTED HEREON EXCEPT AS PROVIDED UNDER SECTION 7209
DETERMINE THE ACTUAL SCALE OF THIS DRAWING. SUBDIVISION 2 OF THE NEW YORK STATE EDUCATION LAW PLUMBING
4" STORM DRAIN TO
STORAGE TANK

EL. 389.33
1 1/2" DCW

PRESSURE
GAGE

1 1/2" PRV 6" RPZ PRESSURE


BFP REDUCING
EXPANSION TANK 1 1/2" RPZ VALVE 4" STORM DRAIN TO
BFP P P STORAGE TANK
6" PLANT WATER
1 1/2" FULL
WATER HEATER SHU-OFF VALVE
PORT BALL VALVE
EWH-1 P P
8" FULL-PORT
SHUT OFF
GATE VALVE
FINISHED FLOOR DI SS 1 1/2" PRZ
EL. 378.00 BACKFLOW
PREVENTER

6" PRZ BACKFLOW


PREVENTER
6" STRAINER 2" BFP
DRAIN 6" PLANT WATER
TO STORAGE
TANK
EL. 381.00
8" FULL PORT
4" CHECK SHUT OFF VALVE
6" PLANT WATER 4" STORM
8" INCOMING 4" BFP DRAIN 6" PLANT WATER (2) 1/2" HYDRAULIC VALVE
(PW) TO STORAGE DRAIN
TANK CLEANOUT WATER TO OUTSIDE TO HYDRANT SEE TUBING LINES TO
SHEET G-103 FOR FLUSHING

5' - 0"
0' - 3"
CONTINUATION SYSTEM 4" BACKFLOW
4" STORM DRAIN PREVENTER
TO STORAGE TANK DRAIN

3' - 0"
EL. 378.50 SECTION 2 2
EL. 377.83 (2) HYDRAULIC LINES 1/4" = 1'-0" P-102
FINISHED FLOOR
TO STORAGE TANK EL. 378.00
FLUSHING SYSTEM

5' - 0"

LIMIT OF
PLUMBING
TRADE

370' - 0"
STAIRWAY LANDING

SECTION 1 1
1/2" = 1'-0" P-102

SECTION 3 3
1/2" = 1'-0" P-102

SECONDARY
ROOF DRAIN
4" ROOF 4" SECONDARY
DRAIN ROOF DRAIN

CLEANOUT
EXPANSION
S TANK

4" ROOF
LEADER
4" STORM 3/4" DHW 3/4" DCW
4" STORM
TO STORAGE
TO OUTSIDE
TANK

SERVICE SINK
SS-1 ELECTRIC
WATER
CLEANOUT HEATER
EWH-1
FINISHED OVERFLOW CLEANOUT
FLOOR DOWNSPOUT NOZZLE TYPE "B"
378.00 FINISHED
FLOOR
2' - 6"

FLOOR
DRAIN
1' - 6"

EL. 378.00

SECTION 5 5 SECTION 4 4
SECTION 6 6 1/4" = 1'-0" P-101 1/2" = 1'-0" P-102
1/4" = 1'-0" P-101

SCALE: LJC ONONDAGA COUNTY DEPARTMENT OF WATER ENVIRONMENT PROTECTION File Number
2 0 2 4
2 6 8 10 In charge of
006.64
1/4" = 1'-0" LOWER HARBOR BROOK CSO STORAGE FACILITY
GBC
1 0 1 2 3 4 5 Designed by Date
SECTIONS
1/2" = 1'-0"

THIS DRAWING WAS PREPARED AT THE SCALE INDICATED IN THE


2
1
08/11
4/11
AS BID
ISSUED FOR APPROVAL
LJC
LJC
Drawn by
KJL
SYRACUSE, NEW YORK
08/11 P-103
TITLE BLOCK. INACCURACIES IN THE STATED SCALE MAY BE
INTRODUCED WHEN DRAWINGS ARE REPRODUCED BY ANY
NO. DATE REVISION INT. GBC
Checked by
MEANS. USE THE GRAPHIC SCALE BAR IN THE TITLE BLOCK TO NO ALTERATIONS PERMITTED HEREON EXCEPT AS PROVIDED UNDER SECTION 7209
DETERMINE THE ACTUAL SCALE OF THIS DRAWING. SUBDIVISION 2 OF THE NEW YORK STATE EDUCATION LAW PLUMBING
D

NOTES:
1. 4" STORM DRAIN FROM UTILITIES BUILDING SEE SHEET P-101
FOR CONTINUATION

2. 6" PLANT WATER FROM UTILITIES BUILDING SEE SHEET P-102


FOR CONTINUATION.

3" MONITOR C

3
P-203
3" PW

4" ROOF DRAIN


CLEANOUT
1 3" MONITOR B
P-203
S 2
T
6" S P-203
6" UP TO
ROOF
DRAIN

T
6" S
S
3" PW

S
INV. EL.
380'.00"

6" S
4" PW A

T
6" UP TO 3" MONITOR
ROOF
DRAIN
(2) 1/2" HYDRAILIC
TUBING DOWN TO
EL. 331.00

3" MONITOR
6" UP TO
(2) 1/2" ROOF
HYDRAILIC DRAIN
TUBING

S
T
6" S
3" PW

6" UP TO T
6" S
ROOF
S
DRAIN
4" PW (2) 1/2" 5
HYDRAILIC
3" MONITOR TUBING
3" PW
TYP. BOTH
SIDES

6" S
T
(2) 1/2" HYDRAULIC
2 TUBING TO FLUSING
SYSTEM @ EL. 380.00

P-202 3" PW 6" STORM DRAIN 4" STORM


EL. 377'.4"

SEE NOTES 1 & 2.

3" PW
6" PLANT WATER
CO

2" PLANT WATER TO


1 HOSE VLAVE

P-202
4
6" PLANT 4" PLANT WATER TO STORAGE
WATER AT TANK FILL SHUT-OFF AT EL. 374'.0"
EL. 378'.9"

1 4" STORM DRAIN TO


STORAGE TANK AT
EL. 378'.0"
3
3
4" STORM DRAIN
2 4" PLANT WATER TO
P-202
DOWN TO EL. 377'.0" STORAGE TANK AT
EL. 379'.6"

PLAN
SCALE: 3/32" = 1'-0"

SCALE: LJC ONONDAGA COUNTY DEPARTMENT OF WATER ENVIRONMENT PROTECTION File Number
In charge of
8 0 8 16 24 006.64
LOWER HARBOR BROOK CSO STORAGE FACILITY
3/32" = 1'-0"
GBC
Designed by Date

THIS DRAWING WAS PREPARED AT THE SCALE INDICATED IN THE


2
1
08/11
4/11
AS BID
ISSUED FOR APPROVAL
LJC
LJC
Drawn by
KJL STORAGE TANK BELOW ROOF PLAN 08/11 P-201
TITLE BLOCK. INACCURACIES IN THE STATED SCALE MAY BE
SYRACUSE, NEW YORK
INTRODUCED WHEN DRAWINGS ARE REPRODUCED BY ANY
NO. DATE REVISION INT. GBC
Checked by
MEANS. USE THE GRAPHIC SCALE BAR IN THE TITLE BLOCK TO NO ALTERATIONS PERMITTED HEREON EXCEPT AS PROVIDED UNDER SECTION 7209
DETERMINE THE ACTUAL SCALE OF THIS DRAWING. SUBDIVISION 2 OF THE NEW YORK STATE EDUCATION LAW PLUMBING
3 4

PLANT WATER 2" PLANT WATER TO


HIGH POINT RELIEF HOSE VALVE IN
VALVE STAIRWELL

PLANT WATER (2) 1/2" HYDRAULIC


HIGH POINT VACUUM TUBING TO
RELIEF VALVE STORAGE TANK

4" PLANT WATER TO


STORAGE TANK AT
EL. 379'.6"

6" PLANT WATER AT 4" STORM DRAIN TO


EL. 378'.9" STORAGE TANK AT (2) 1/2" HYDRAULIC
EL. 378'.0" TUBING FROM
CONTROL PANEL TO
377'-0" FLUSHING SYSTEM
4" SHUT-OFF VALVE FOR
STORAGE TANK FILL 4" SHUT-OFF VALVE
4" STORM DRAIN 6" STORM DRAIN STORM DRAIN 4" PLANT WATER TANK FILL FOR STORAGE TANK
FROM UTILITY FROM STORAGE CLEANOUT CENTERLINE EL. 379'-4" FILL
BUILDING TANK CENTERLINE
376'-10". EL. 377'-10"
2" PLANT WATER DOWN
TO HOSE VALVE AT
4" PLANT WATER EL. 330;-0"

2' - 6"

SECTION 12 3
1/4" = 1'-0"

SECTION 7 1
1/4" = 1'-0" P-201

1 2 3 4

6" ROOF DRAIN 6" ROOF DRAIN


(2) 1/2" HYDRAULIC TUBING
FROM CONTROL PANEL

S 4" PW S
3" PW
6" ST 6" ST

3" MONITOR
6" ROOF DRAIN TO 3" MONITOR
RAIN WATER
STORAGE TANK

3" SHUT-OFF
BALL VALVE (TYP.)

WALKWAY
3/4" DRAIN VALVE
EL. 370.00
(TYP.)

SECTION 8 2
1/4" = 1'-0" P-201

SCALE: LJC ONONDAGA COUNTY DEPARTMENT OF WATER ENVIRONMENT PROTECTION File Number
In charge of
2 0 2 4
2 6 8 10 006.64
LOWER HARBOR BROOK CSO STORAGE FACILITY
1/4" = 1'-0"
GBC
Designed by Date

THIS DRAWING WAS PREPARED AT THE SCALE INDICATED IN THE


2
1
08/11
4/11
AS BID
ISSUED FOR APPROVAL
LJC
LJC
Drawn by
KJL STORAGE TANK SECTIONS 08/11 P-202
TITLE BLOCK. INACCURACIES IN THE STATED SCALE MAY BE
SYRACUSE, NEW YORK
INTRODUCED WHEN DRAWINGS ARE REPRODUCED BY ANY
NO. DATE REVISION INT. GBC
Checked by
MEANS. USE THE GRAPHIC SCALE BAR IN THE TITLE BLOCK TO NO ALTERATIONS PERMITTED HEREON EXCEPT AS PROVIDED UNDER SECTION 7209
DETERMINE THE ACTUAL SCALE OF THIS DRAWING. SUBDIVISION 2 OF THE NEW YORK STATE EDUCATION LAW PLUMBING
C B A

3" PLANT WATER 6" STORM DRAIN TO 4" STORM WATER TO


RAIN WATER STORAGE RAIN WATER STORAGE
6" STORM DRAIN 6" BRANCH FROM (2) 1/2" HYDRAULIC 6" BRANCH FROM
TANK TANK
CLEANOUT ABOVE STORM DRAIN TUBING FROM STORM DRAIN
WALKWAY CONTROL PANEL 4" PLANT WATER TO
RAIN WATER STORAGE
TANK

6" STORM DRAIN 3" MONITOR


EL. 377'-0"

WALKWAY
EL. 370.00

(2) 1/2" HYDRAULIC TUBING


DOWN TO FLUSING SYSTEM
AT EL. 331.00

SECTION 9 1
1/4" = 1'-0" P-201

10' - 0"

MAX.

WATER HAMMER ARRESTER


TYPICAL AT ALL MONITOR
LOCATIONS

3" PLANT WATER


PIPE SUPPORT EL. 378'-0"
TYPICAL

3" PLANT WATER


TO MONITOR
6" PLANT WATER
EL. 378'-0"

3" MONITOR 3" PLANT WATER


3" MONITOR

3/4" BALL VALVE W/ HOSE


SUPPORT PIPING ON CONNECTION (TYP.)
STRUCTURAL TUBING

3" SHUT-OFF BALL


3' - 6"

VALVE (TYP.)

3/4" DRAIN BALL VALVE


(TYP.)

3/4" DRAIN BALL VALVE


(TYP.)

14' - 6"

SECTION 11 3 SECTION 10 2
1/2" = 1'-0" P-201 1/2" = 1'-0" P-201

SCALE: 2 0 2 4
2 6 8 10 LJC ONONDAGA COUNTY DEPARTMENT OF WATER ENVIRONMENT PROTECTION File Number
In charge of
1/4" = 1'-0" 006.64
LOWER HARBOR BROOK CSO STORAGE FACILITY
1 0 1 2 3 4 5
GBC
Designed by Date
1/2" = 1'-0"

THIS DRAWING WAS PREPARED AT THE SCALE INDICATED IN THE


2
1
08/11
4/11
AS BID
ISSUED FOR APPROVAL
LJC
LJC
Drawn by
KJL STORAGE TANK SECTIONS 08/11 P-203
TITLE BLOCK. INACCURACIES IN THE STATED SCALE MAY BE
SYRACUSE, NEW YORK
INTRODUCED WHEN DRAWINGS ARE REPRODUCED BY ANY
NO. DATE REVISION INT. GBC
Checked by
MEANS. USE THE GRAPHIC SCALE BAR IN THE TITLE BLOCK TO NO ALTERATIONS PERMITTED HEREON EXCEPT AS PROVIDED UNDER SECTION 7209
DETERMINE THE ACTUAL SCALE OF THIS DRAWING. SUBDIVISION 2 OF THE NEW YORK STATE EDUCATION LAW PLUMBING
PIPE
PLUMBING FIXTURE SCHEDULE
1 1/2" MAXIMUM
DOMESTIC WATER OR
NON-POTABLE WATER
SERVICE VALVE FIXTURE NAME DESCRIPTION DCW DHW TW VENT SANITARY REMARKS
FOR FINISH, SEE LINK SEAL TYPE (1/2" BALL VALVE)
SPECIFICATIONS, PENETRATION SEAL
INSIDE PROCESS ASSEMBLY W/ S.S. WC-1 WATER CLOSET 1" - - 2" 3" WALL HUNG
PIPING AND PAINTING BOLTS AND NUTS
TRAP PRIMER LV-1 LAVATORY 1/2" 1/2" - 1 1/4" 1 1/4" WALL HUNG
VALVE
3" SS-1 SERVICE SINK 3/4" 3/4" 1 1/2" 3" FLOOR MOUNTED
FINISHED FLOOR -
DISTRIBUTION UNIT
SH-1 SHOWER 1/2" 1/2" - 1 1/4" 2" SHOWER ENCLOSURE
THICKNESS

1/2 FLOOR
FLOOR

THICKNESS
DRAIN SUPPLY LINE
MIN. 1/2" TO EACH
FLOOR DRAIN TRAP
PRIMER CONNECTION
1/4" LUGS
WELDED TO SLEEVE
SCH. 40 SLEEVE
ELECTRIC WATER HEATER (EWH) SCHEDULE
HEATING INFORMATION
TANK CAPACITY
NO. LOCATION
(GALLONS) INPUT RATING VOLTAGE PHASE SET TEMPERATURE
FLOOR DRAIN TRAP PRIMER UNIT DETAIL
EWH-1 MECHANICAL ROOM 105 30 6 kW 208 3 105 DEG. F
COORDINATE SLEEVE NOT TO SCALE
SIZE & O.D. OF
PIPE WITH NOTE:
MECHANICAL SEAL
MFG. 1. TRAP PRIMING SYSTEM AUTOMATICALLY PRIMES UP TO FOUR FLOOR DRAINS.

FLOOR SLEEVE DETAIL 2. TRAP PRIMER VALVE AND DISTRIBUTION UNIT AS MANUFACTURERED BY
PRECISION PRODUCTS OR EQUAL.
NOT TO SCALE

FOR CONCRETE APPLICATIONS,


USE UNIVERSAL CONCRETE
INSERT OR UNISTRUT CHANNEL.
FOR STEEL BEAM APPLICATION,
USE BEAM ATTACHMENT,
GRINNEL FIGURE 292 OR EQUAL

PACK WITH FIBERGLASS


AND SEAL BOTH SIDES HANGER ROD HANGER ROD 1-#4x3'-0"

INSULATION ESCUTCHEON
PLATES (BOTH
SIDES WHERE
CLEVIS HANGER CLEVIS HANGER
EXPOSED)

SEE ROD ATTACHMENT DIA. AS ROD FOR


STEEL PLATE EXIST CONC USE
SLEEVE ANCHOR
SAME
PIPE INSULATION

(4)-3/8" DIA. GALV. ROD SIZED FOR LOAD AND


ASTM A36 SPACING
ADHESIVE ANCHORS
REFER TO PLANS W/ 3 1/2" EMBEDMENT
PIPE WALL SLEEVE, SET SLEEVE
FOR PIPE SIZES UNINSULATED PIPE REFER
IN WALL AND ANCHOR
TO PLANS FOR PIPE SIZES
DURING WALL CONSTRUCTION

PIPE SHIELD
BLOCK WALL

INSULATED PIPING UNINSULATED PIPING


PIPE HANGING CONCRETE ATTACHMENT DETAILS
NOT TO SCALE
PIPE SLEEVE THRU INTERIOR WALL DETAIL
NOT TO SCALE
PIPE HANGERS DETAILS NOTES:

NOT TO SCALE 1. TOTAL LOADING SHALL NOT EXCEED MANUFACTURER'S


RECOMMENDED LOADING.
DETAIL NOTES:

1. THIS DETAIL IS FOR ABOVE GRADE PENETRATION INTO


BUILDING THROUGH BLOCK WALLS INTO DRY AREA.

2. REFER TO STRUCTURAL DRAWING FOR LOCATION AND


DIMENSIONS.

SCALE: LJC ONONDAGA COUNTY DEPARTMENT OF WATER ENVIRONMENT PROTECTION File Number
In charge of
006.64
NOT TO SCALE GBC
LOWER HARBOR BROOK CSO STORAGE FACILITY
Designed by Date

THIS DRAWING WAS PREPARED AT THE SCALE INDICATED IN THE


2
1
08/11
4/11
AS BID
ISSUED FOR APPROVAL
LJC
LJC
Drawn by
KJL SCHEDULES & DETAILS 08/11 P-301
TITLE BLOCK. INACCURACIES IN THE STATED SCALE MAY BE
SYRACUSE, NEW YORK
INTRODUCED WHEN DRAWINGS ARE REPRODUCED BY ANY
NO. DATE REVISION INT. GBC
Checked by
MEANS. USE THE GRAPHIC SCALE BAR IN THE TITLE BLOCK TO NO ALTERATIONS PERMITTED HEREON EXCEPT AS PROVIDED UNDER SECTION 7209
DETERMINE THE ACTUAL SCALE OF THIS DRAWING. SUBDIVISION 2 OF THE NEW YORK STATE EDUCATION LAW PLUMBING
WATER
HAMMER
ARRESTER

3" MONITOR

4" PLANT
WATER (PW)

WATER WATER
HAMMER HAMMER
ARRESTER ARRESTER
3" MONITOR

3" MONITOR

4" PLANT
WATER (PW)

WATER
HAMMER
3" MONITOR ARRESTER
3" MONITOR

4" PLANT
WATER (PW)

3" PLANT
WATER (PW) 3" PLANT
WATER (PW)

1 1/2" DOMESTIC COLD


WATER (DCW)

1 1/2" PRESSURE REDUCING


VALVE SET @ 50 PSIG 4" PLANT WATER 4" PLANT
TO RAIN WATER WATER (PW) 3" PLANT
1 1/2" BACKFLOW STORAGE TANK WATER (PW)
PREVENTER

1" (DCW) WATER HAMMER


ARRESTERS
1 1/2" FULL PORT
BALL VALVE
1" (DHW)

1 1/4" 3/4" (DCW) & 3/4" (DHW)


(DCW) TO SERVICE SINK SS-1 2" PLANT
4" PLANT WATER (PW) DOWN
8" FULL PORT WATER (PW) TO HOSE VALVE
GATE VALVE
1/2" (DCW) & 1/2" (DHW) 6" SHUT-OFF VALVE
TO LAVATORY LV-1 6" PLANT
EXPANSION WATER (PW) 6" PRESSURE REDUCING VALVE SET @ 65 PSIG
TANK

HIGH POINT 6" RPZ BACKFLOW PREVENTER


1" (DHW) TO VACUUM RELIEF
WATER HEATER VALVE 1 1/2" PRESSURE REDUCING
PROVIDE UNION &
SHUT-OFF VAVLE 4" SHUT-OFF 1 1/2" RPZ BACKFLOW PREVENTER
1/2" (DCW) & 1/2" (DHW) VALVE
1 1/4" (DCW) TO SHOWER VALVE SH-1
8" INCOMING WATER SEE ENLARGED
SERVICE WATER HEATER 4" CHECK
VIEW THIS SHEET
PROVIDE UNION & VALVE
FOR CONTINUATION
SHUT-OFF VAVLE

6" PLANT 8" SHUT-OFF


WATER (PW) VALVE
TO HYDRANT

WATER HEATER EWH-1 1" (DCW) TO


WATER CLOSET
WC-1
4" BFP DRAIN TO
WATER PIPING SCHEMATIC SPLASHBLOCK
SCALE: AT GRADE
8" INCOMING
WATER
ENLARGED VIEW SERVICE
SCALE:

SCALE: LJC ONONDAGA COUNTY DEPARTMENT OF WATER ENVIRONMENT PROTECTION File Number
In charge of
006.64
NOT TO SCALE GBC
LOWER HARBOR BROOK CSO STORAGE FACILITY
Designed by Date

THIS DRAWING WAS PREPARED AT THE SCALE INDICATED IN THE


2
1
08/11
4/11
AS BID
ISSUED FOR APPROVAL
LJC
LJC
Drawn by
KJL WATER PIPING SCHEMATIC 08/11 P-302
TITLE BLOCK. INACCURACIES IN THE STATED SCALE MAY BE
SYRACUSE, NEW YORK
INTRODUCED WHEN DRAWINGS ARE REPRODUCED BY ANY
NO. DATE REVISION INT. GBC
Checked by
MEANS. USE THE GRAPHIC SCALE BAR IN THE TITLE BLOCK TO NO ALTERATIONS PERMITTED HEREON EXCEPT AS PROVIDED UNDER SECTION 7209
DETERMINE THE ACTUAL SCALE OF THIS DRAWING. SUBDIVISION 2 OF THE NEW YORK STATE EDUCATION LAW PLUMBING