Beruflich Dokumente
Kultur Dokumente
a r t i c l e i n f o a b s t r a c t
Article history: This study presents a potential approach for reducing the propane (R290) charge required in air condi-
Received 11 May 2018 tioners (ACs) by introducing micro bare-tube heat exchangers as the condenser and evaporator. A the-
Revised 23 January 2019
oretical model is developed to predict the performance of a split AC unit, and the unit is tested in an
Accepted 24 February 2019
experiment. The split AC unit is tested under the ISO 5151:2017 standard capacity rating test condition
Available online 28 February 2019
in a psychrometric room (outdoor conditions: 35 °C dry bulb/24 °C wet bulb; indoor conditions: 27 °C
Keywords: dry bulb/19 °C wet bulb). The compressor input electricity power is 928 W with 62-W condenser fan
R290 propane power and 82-W evaporator fan power. The test cooling capacity is 3645 W with a system coefficient of
Micro bare tube heat exchanger performance of 3.40. The stainless steel micro-tube heat exchanger has a 0.58-mm outer diameter and
Air conditioner 0.38-mm inner diameter. Owing to the use of micro bare tubes, the optimal propane charge is 248±5 g,
Heat pump which follows the EN378-1:2016 regulation. The use of micro bare-tube heat exchangers in a split AC unit
could be a potential approach to reducing the R290 charge required in ACs and heat pumps.
© 2019 Elsevier Ltd and IIR. All rights reserved.
Une approche potentielle pour réduire la charge de R290 dans les climatiseurs et
les pompes à chaleur
Mots-clés: Propane R290; Échangeur de chaleur à micro-tube nu; Conditionneur d’air; Pompe à chaleur
https://doi.org/10.1016/j.ijrefrig.2019.02.030
0140-7007/© 2019 Elsevier Ltd and IIR. All rights reserved.
48 W. Zhou and Z. Gan / International Journal of Refrigeration 101 (2019) 47–55
Table 2
Micro bare-tube geometry.
Symbols Parameters
L (mm) 480
w (mm) 200
H (mm) 15
Dis (mm) 1.64
Dout (mm) 0.58
Din (m) 0.38
N (-) 122
Symbols Parameters where qevap represents the cooling capacity of the propane in the
−6
evaporator. h4 and h1 are the specific enthalpy of propane at the
3
Vcmp (m ) 21.4 × 10
ω (rpm) 2860
evaporator inlet and outlet, respectively.
V˙ evap (m3 /h) 708 Fig. 2 shows the pressure–enthalpy diagram of the R290 vapor
Pdis (MPa) 1.87 compression cycle. The propane hermetic motor compressor in-
Psuc (MPa) 0.57 creases the pressure and temperature of the superheated propane
V˙ cnd (m3 /h) 2676
to 1.87 MPa and 67.7 °C, which corresponds to the process from
Rated Wc (W) 3170/3200 ± 3%
Rated Wcmp (W) 965/985 ± 3% state 1 to state 2 in Fig. 2. The high-temperature and high-pressure
Rated COP 3.34 vapor enters into the micro bare-tube condenser with a drastic
decrease in temperature and condenses into a high-pressure sub-
cooled liquid (state 3 in Fig. 2). The high-pressure liquid then
order to predict the system behavior, the thermodynamic model passes through a capillary tube with a large pressure drop to 0.57
is developed in Engineering Equation Solver (EES) software (Klein, MPa (state 4). This low-pressure vapor and liquid mixture flows
2018). Table 1 presents the basic system geometry and operation into another micro bare-tube evaporator and absorbs the heat from
parameters. the room while providing sufficient cooling. The superheated low-
The model is built in EES with the following equations. The temperature vapor (state 1) is sucked into the compressor inlet and
propane compression process is labeled in Fig. 1 from state 1 compressed into high-pressure vapor, which ends one vapor com-
to state 2. The mass flow rate of propane can be expressed as pression cycle. The evaporator is maintained at standard summer
follows: indoor air conditions with an electricity heater adding heat to the
room in order to facilitate the measurement of the room sensible
ω · ηv · Vcmp
m˙ = (1) load. The model of the basic vapor compression cycle is built to
60 · v simulate the behavior of the system. In Fig. 2, the calculated cool-
ω is the rotational speed of the compressor, and Vcmp is the com- ing capacity is 3719 W with a compression power of 922 W from
pressor compression volume, both of which are shown in Table 1. the model. From the point of view of heat transfer, the designed
v is the specific volume of the propane gas at the compressor in- heat exchangers are required to meet the condenser load and evap-
take, which is state 1 in Fig. 1. ηv is the volumetric efficiency of orator cooling capacity to improve the system efficiency. The heat
the compressor. The volumetric efficiency for the 1.3-HP AC com- exchanger design is the key to improving the system performance.
pressor is assumed to be 70% as a rough estimate. Using the above Owing to the stringent propane charge limit as per the EN 378-
equation, the mass flow rate of propane in the compressor can be 1:2016 standard, micro bare-tube heat exchangers with stainless
determined. By ignoring the heat transfer from the compressor to steel tubes of inner diameter of 0.38 mm are installed as the con-
the surroundings, the compression power provided by the com- denser and evaporator. The tiny micro tubes require much less
pressor can be calculated using the following equation: propane in the heat exchangers as compared to traditional fin-tube
heat exchangers. The configuration of one micro bare-tube heat ex-
Wcmp = m˙ (h2 − h1 ) (2)
changer unit is shown in Fig. 3. The micro bare tubes are welded
where Wcmp is the compression power. The heat transfer occurring inside D-shape connectors as indicated in the enlarged area in
in the condenser is the heating capacity. This heating energy may Fig. 3. There are N = 122 columns in the w width direction and
be dissipated to the surroundings or used as the heat pump. The 5–6 rows in the H height direction. Table 2 lists the detailed pa-
energy balance at the condenser may be represented by the fol- rameters of the condenser and evaporator installed in the AC unit.
lowing equation: The length of the one-piece heat exchanger is L = 480 mm, with a
width of 200 mm, and 15 mm height. The pitch distance between
qcnd + m˙ (h2 − h3 ) = 0 (3)
each tube is 1.64 mm. The effective number of transfer units (NTU)
where qcnd is the rate of energy transfer from the refrigerant in method is adopted to simulate the ideal performance of the micro
the condenser. h2 and h3 are the specific enthalpy of propane at bare-tube condenser and evaporator.
50 W. Zhou and Z. Gan / International Journal of Refrigeration 101 (2019) 47–55
7 R290 7
10 1x10
368.4 K
3 2
316.2 K
P [Pa]
6 6
10 1x10
4
1
271.4 K
0.4 0.6
0.2 0.8
233 K
5 5
10 1x10
0.0 2.0x105 4.0x105 6.0x105
h [J/kg]
Fig. 2. P–h diagram of vapor compression cycle with R290 as refrigerant.
The condensers and evaporators with micro bare tubes are de- viscosity of the air. The Nusselt number NuD is determined from
signed using the effective-NTU method. Several assumptions are Zukauskas correlation, which is shown below (Zukauskas, 1972):
made to simplify the problem: 0.36 Pr 1/4
N uD = 0.92 · 0.8 · ReD 0.4 Pr (6)
1. The evaporation and condensation process are not modeled in Prs
detail. There are five or six rows of micro bare tubes in the flow direc-
2. Owing to the low wall thickness of the stainless steel tube, its tion and the calculated outside air Reynold number is 145, there-
thermal resistance is neglected. fore, the Zukauskas correlation is adopted to determine the average
Nusselt number. Pr is the Prandtl number evaluated at the arith-
The air-side thermal resistance is modeled according to the air
metic mean of the air inlet and outlet temperatures, Prs is the
flow across the bare tube. The Reynolds number is determined as
Prandtl number evaluated at the tube wall surface temperature.
follows:
The thermal resistance Rout of the air side is given by the following
ReD = ρair · u˙ air · Dout /μair (5) equation:
Rout = 1/λout /Aout (7)
where ReD is the Reynolds number outside the micro bare tube.
ρ air is the air density, u˙ air is the velocity of the air, and Dout is λout is the heat transfer coefficient outside the bare tube, and
the outer diameter of the bare tube. μair represents the dynamic Aout is the total outside area of the bare tube. On neglecting the
W. Zhou and Z. Gan / International Journal of Refrigeration 101 (2019) 47–55 51
8000
4000
7000
3500
6000 3000
D out = 0.98 mm
D out = 0.38 mm
5000 2500
D out = 0.78 mm
D out = 0.58 mm
4000 2000 D out = 0.58 mm
D out = 0.78 mm
1000
2000 40 60 80 100 120 140 160
40 60 80 100 120 140 160
Number of tubes in each column (-)
Number of tubes in each column (-)
Fig. 5. Evaporator cooling capacity for various numbers of tube columns.
Fig. 4. Heat rejection from condenser for various numbers of tube columns.
thermal resistance of the stainless steel tube, the thermal resis- larger-diameter heat exchanger is smaller than that of the smaller-
tance inside the micro bare tube can also be calculated as follows: diameter heat exchanger. Moreover, a large outer diameter implies
a large void volume, and therefore, the required propane charge
1
Rin = (8) will also be greater. Fig. 5 illustrates the evaporator performance
Ltot · π · (Dout − 2 · th ) · λin for various numbers of tubes in each heat exchanger column. The
where Ltot is the total tube length, th is the stainless steel tube cooling capacity increases from 1500 W to 40 0 0 W when the num-
wall thickness, and λin is the propane heat transfer coefficient. ber of tubes increases from 50 to 150. The calculated cooling ca-
The Reynolds number inside the micro bare tube is approximately pacity of 3200 W is close to the rated cooling capacity Rated Wc ,
161, and therefore, the Nusselt number for a laminar, hydro- which is specified as 3170 W in the compressor manual. However,
dynamically, and thermally fully developed flow in a circular tube a cooling power of 3719 W is obtained on using the previously pre-
can be determined using the following equation while assuming a sented thermodynamic model. This discrepancy can be attributed
uniform wall temperature (Kays, 1993), to the inaccuracy of the effectiveness-NTU method in predicting
the performance of heat exchangers involving a phase change, such
λin Din
N uin = = 3.66 (9) as in the case of condensers or evaporators. This discrepancy could
kin also be caused by other uncertainties such as sub-cooling and de-
The number of heat transfer units can be calculated as follows: superheating. Moreover, the micro bare-tube condenser and evap-
orator are new types of heat exchangers. The detailed heat-transfer
1 phenomenon that occurs in the micro bare-tube heat exchanger is
NT U = (10)
(Rout + Rin )cair m˙ air required to be further explored.
The heat exchanger effectiveness is as follows: Based on Fig. 4, a condenser with 122 columns of tubes per
row is fabricated and tested in the experiment. As shown in Fig. 5,
ε = 1 − exp[−NT U ] (11) an evaporator with 90 columns of micro bare tubes per row can
provide sufficient cooling. However, it is easy to fabricate the heat
The maximum heat transfer rate can be determined as follows:
exchanger with 122 columns per row in the case of both the con-
denser and evaporator. Moreover, there is always some discrepancy
q˙ max = m˙ air · Cair (TR,in − Tair,in ) (12)
between the theoretical calculation and the experimental results,
Furthermore, the heat transfer rate is and therefore, the oversized evaporator with 122 columns of tubes
per row is adopted in the experiment. The condenser has (col-
q˙ = q˙ max · ε (13)
umn × row × piece) 122 × 6 × 3 = 2196 micro bare tubes, while the
The condenser and evaporator design is shown in this paper evaporator has 122 × 5 × 3= 1830 micro bare tubes.
as an example. Figs. 4 and 5 show the micro bare-tube heat ex- The propane charge for the condenser and evaporator is esti-
changer performance for various numbers of micro bare tubes and mated based on the micro bare-tube heat-exchanger infrared im-
tube outer diameters. age, which is shown in Fig. 7. The color bar in the infrared image
Fig. 4 indicates that the condenser heat rejection rate increases indicates the temperature in Celsius. The inlet of the propane va-
significantly from 2750 W to 7250 W when the number of heat ex- por is on the top left and the outlet of the propane liquid is at the
changer columns is increased from 50 to 150. For the same number bottom right in the image. The saturated propane vapor and liquid
of micro bare-tube columns, the large-diameter micro bare-tube temperature at 1.87 MPa is 56.6 °C, therefore, the vapor propane
heat exchanger dissipates more heat to the surroundings. For in- condensed into saturated liquid immediately at the entrance of the
stance, as shown in Fig. 4, with 122 columns of tubes, the 0.98-mm condenser as shown in Fig. 7. Thus, the amount of the propane
outer diameter heat exchanger delivers a heating capacity of al- in the condenser is calculated by multiplying the saturated liq-
most 6500 W while the 0.58-mm one only rejects 5800 W of heat. uid density with the void volume of the condenser; this should
The larger-diameter heat exchanger has a larger heat-transfer area provide a rough estimation of propane quickly in the condenser
such that it transfers a greater amount of energy. However, the during the operation. A similar method is used to calculate the
tube column number is limited by the heat exchanger size. For a propane charge required in the evaporator as well. Fig. 6 shows the
heat exchanger of given dimensions, 122 0.58-mm-diameter tubes condenser and evaporator liquid propane with micro bare tubes
can be fit in each row, while only 80 0.98-mm-diameter tubes of various outer diameters and various numbers of columns. In
can be fit in each row. Thus, the total heat transfer area of the Fig. 6(a), when the column number is maintained at 122, the 0.58-
52 W. Zhou and Z. Gan / International Journal of Refrigeration 101 (2019) 47–55
0.25 0.25
Propane liquid mass in condenser (kg)
0.2 0.2
0.15 0.15
0.1 0.1
D out = 0.58 mm D out = 0.58 (mm)
0.05 0.05
0 0
40 50 60 70 80 90 100 110 120 130 140 150 160 40 50 60 70 80 90 100 110 120 130 140 150 160
Number of tubes in each column (-) Number of tubes in each column (-)
(a) (b)
Fig. 6. Propane liquid in condenser (a) and evaporator (b) with micro bare tubes of various outer diameters.
Fig. 8. AC unit with micro bare tube heat exchanger (left condenser, right evaporator).
Table 3
Experimental testing results (20-V evaporator fan voltage).
Min 12.4 67.9 38.1 8.9 34.6 40.6 43.0 43.0 39.9 37.3 26.9 14.0
Max 12.5 68 38.2 9.3 34.7 40.7 43.1 43.1 40.0 37.4 26.9 14.1
Ave. 12.4 67.9 38.2 9.0 34.7 40.6 43.0 43.1 39.9 37.4 26.9 14.0
Table 4
Experimental testing results (24-V evaporator fan voltage).
Min 14.3 69.3 38.0 10.2 34.6 40.8 43.4 43.5 39.8 37.2 26.8 15.1 2787.8 809.6 3613.4
Max 14.4 69.5 38.1 10.3 34.8 40.9 43.5 43.6 40.0 37.3 27.0 15.2 2842.7 848.7 3668.6
Ave. 14.3 69.4 38.1 10.2 34.7 40.9 43.5 43.6 39.9 37.3 26.9 15.2 2814.0 831.6 3645.6
Table 5
Cooling performance comparison between model and experiment.
Model Experiment (20-V fan) Discrepancy with model Experiment (24-V fan) Discrepancy with model
The total AC unit COP at this condition is 3.40 with a 24-V performance. Moreover, the micro bare-tube heat exchanger has a
evaporator fan input and 3.44 with a 20-V evaporator fan voltage. better Hinterland-relation between surface–area-to-volume ratios.
The cooling capacity calculated using the thermodynamic model is In the experiment, the propane charge in the system is 248±5 g.
3719 W with a compression power of 922 W. The modeled COP The micro bare-tube system propane charge follows the EN378-
is 4.0, which is close to the measured COP of 3.93 without the 1:2016 regulation. Therefore, this R290 AC unit with a 248±5-g
fan power. The discrepancy in the COP between the model predic- propane charge and with micro bare tubes as a condenser and
tion and experimental result is 1.75%. The model does not take into evaporator could be a good approach to reducing the propane
consideration the condensation of water on the evaporator surface; charge in ACs and heat pumps.
this could cause the above-mentioned discrepancy. Table 6 shows the comparison of the propane charge for vari-
Table 5 shows the comparison of the measured cooling capacity ous ACs and heat pumps from previous studies and this work. The
with the thermodynamic model prediction. The measured cooling proposed split AC unit has air to propane type heat exchangers as
power values are 3645 W and 3516 W for an 81-W and a 51-W fan condensers and evaporators which is similar to Park (2009), Zhou
power input, respectively. The calculated cooling power from the (2010) and Padalkar (2014) air conditioner systems. Notice that the
theoretical thermodynamic model is 3719 W. The cooling capacity system in this research are not exactly the same as the systems
measured in the experiment is within 5% of the model, and the reported by other researchers in Table 6, such as, different cool-
COP comparison is within 15%. The evaporator cooling capacity ing/heating capacities, different oil types and different oil charge
determined by the effectiveness-NTU method is 3200 W, which is etc. In order to simplify the propane charge comparison, the charge
less than that of the measurement data. This is caused by the high per kilo-watts capacity is listed in the table. As shown in the table,
heat-transfer performance of the new micro bare-tube heat ex- the micro bare-tube split AC can reduce 56.1%, 61.2% and 2.7% less
changers. The propane inside the micro channel provides a larger propane charge per kilo-watts cooling capacity comparing to the
heat transfer coefficient owing to the instant and high-efficiency previous studies. The first two rows in Table 6 indicate the propane
boiling process inside such micro bare tubes. There are 1830 charge/capacity increases, which is caused by adopting different
micro bare tubes installed as evaporators such that the air-side type of condensers or evaporators. Fernando (2004) used the
surface area is 435% greater than that of the copper tube heat liquid-to-propane micro channel heat exchanger as a condenser
exchangers of 9.52-mm outer diameter and 10-m length (assume and evaporator and obtained 5 kW of heating capacity with a
no fins). Therefore, the air-side thermal resistance is enhanced by charge/capacity of 40 g/kW propane in the experiment. Corberan
the increased outside surface area. In addition, the wall thickness (2008) used the plate and frame heat exchanger cooling system
of the stainless steel tube is 0.1 mm, which provides a rela- and achieved a cooling capacity of 14 kW with a 550-g propane
tively low thermal resistance. This results in a high heat transfer charge. The micro channel plate heat exchangers could use water
W. Zhou and Z. Gan / International Journal of Refrigeration 101 (2019) 47–55 55
Table 6
Comparison of the propane charge between previous literatures and this research.
Researcher Heat exchanger type Cooling/heating capacity Charge (g) Charge/Capacity (g/kW) Charge/capacity savings by this work
or other liquids to transfer heat with the propane refrigerant. Air also thank the staff of Jinstong Tech, Inc., Shouren Yu, Xianliang
is not suitable for this type of heat exchanger because of the large Han, and Wenlong Zhao, for their useful work done. Their useful
pressure drop across the small channels. The micro bare-tube heat input and good experimental skills provided a great help in this
exchanger could also be used in a liquid-to-liquid heat transfer research.
scenario and provides good performance. The micro bare-tube
condenser and evaporator split AC unit could be a potential ap- References
proach to reducing the required propane charge while avoiding a
BSEN378, 2016. The British Standard Institution BS EN 378.
degradation in the performance of residential ACs and heat pumps. Choudhari, C.S., Sapali, S.N., 2017. Performance investigation of natural refriger-
ant R290 as a substitute to R22 in refrigeration systems. Energy Procedia 109,
4. Conclusion and discussion 346–352.
Corberan, J.M., Martinez, I.O., Gonzalvez, J., 2008. Charge optimisation study of re-
versiable water to water propane heat pump. Int. J. Refrig. 31, 716–726.
The micro bare-tube heat exchanger could be used in an R290 Fernando, P., Palm, B., Lundqvist, P., Granryd, E., 2004. Propane Heat Pump with Low
AC and heat pump system because of its high heat transfer perfor- Refrigerant Charge: Design and Laboratory Tests.
He, G., Liu, F., Cai, D., Jiang, J., 2016. Experimental investigation on flow boiling heat
mance, small size, and low required charge. The reported R290 AC
transfer performance of a new near azeotropic refrigerant mixture R290/R32 in
unit could achieve a COP of 3.40 with a cooling power of 3645 W. horizontal tubes. Int. J. Heat Mass Transf. 102, 561–573.
The system propane charge is 248±5 g, which follows the EN378- Huang, L., Aute, V., Radermacher, R., 2014. A model for air-to-refrigerant microchan-
nel condensers with variable tube and fin geometries. Int. J. Refrig. 40, 269–281.
1:2016 regulation. Therefore, the use of the micro bare-tube AC
Jin, S., Wang, X., Ma, X., Wang, Q., 2017. Study on the performance of small tube
unit could potentially be an approach to reducing the required diameter R290 fin-tube evaporator. Procedia Eng. 205, 1578–1583.
propane charge in ACs and heat pumps, which could also poten- Kays, W.M., Crawford, M.E., 1993. Convective Heat and Mass Transfer. McGraw-Hill,
tially be used in the AC and heat pump field in the future. New York.
Klein, S., 2018. EES: Engineering Equation Solver. F-Chart Software, Madison, WI.
The use of the new micro bare-tube heat exchangers as a con- Lampugnani, G., Z., M., 1996. R290 as a substitute of R502 and R22 in commercial
denser and evaporator also poses some problems, such as the un- refrigeration and air conditioning. In: Proceedings of the International Compres-
even distribution of the liquid and gas in the evaporator and con- sor Engineering Conference, pp. 1087–1094.
Mohanraj, M., Jayaraj, S., Muraleedharan, C., Chandrasekar, P., 2009. Experimental
denser, and the required improvement in the fan performance and investigation of R290/R600a mixture as an alternative to R134a in a domestic
efficiency for both the condenser and evaporator. Therefore, fur- refrigerator. Int. J. Therm. Sci. 48, 1036–1042.
ther study is required to understand the characteristics of the mi- Padalkar, A.S., Mali, K.V., Devotta, S., 2014. Simulated and experimental performance
of split packaged air conditioner using refrigerant HC-290 as a substitute for
cro bare tube R290 AC and heat pump units in depth. HCFC-22. Appl. Therm. Eng. 62, 277–284.
Park, K.-J., Jung, D., 2009. Performance of heat pumps charged with R170/R290 mix-
ture. Appl. Energy 86, 2598–2603.
Acknowledgments Zukauskas, A., 1972. Heat transfer from tubes in cross-flow. Adv. Heat Transf. 8,
93–160.
Zhou, G, Zhang, Y., 2010. Performance of a split-type air conditioner matched with
This research is sponsored by the National Natural Science coiled adiabatic capillary tubes using HCFC22 and HC290. Appl. Energy 87,
Foundation of China (Grant No. 51806191) and the 63rd post- 1522–1528.
doctor foundation of China (Grant No. 2018M632458). The authors