Bay Controller SIPROTEC 6MD86

Properties

Properties – SIPROTEC 6MD86


1
Brief description Bay controller for medium-voltage and
1.1 high- to extra-high-voltage switchgear with
integrated operation and extensive protec-
1.2 tion functions. Powerful automation, simple
configuration with DIGSI 5.
1.3 Inputs and outputs • 6 predefined standard variants with up to
8 current transformers and
1.4 8 voltage transformers,
11 to 75 binary inputs,
1.5 9 to 41 binary outputs or
Hardware flexibility • flexibly adjusted and expandable I/O
quantity structure within the scope of the
1.6 SIPROTEC 5 modular system. The device
can be expanded into the second tier if a
1.7 large number of inputs and outputs are
needed. For example, 240 (and more)
1.8 binary inputs are possible with the IO230
(see Section Hardware).
1.9 Housing width 1/3 × 19" to 2/1 × 19"

2 • Integrated bay controller with versatile protection functions


2.1 for applications from medium to extra high voltage
• Control of up to 20 switching devices
2.2 • Synchrocheck, switchgear interlocking system and protection
Fig. 2.9 / 4 Bay controller SIPROTEC 6MD86 (1/3 device with 1/6
functions related to the switching device, such as circuit-
2.3 breaker tripping signal and automatic reclosing
expansion module and operation panel for key-operated
switch)
2.4 • Integrated electrical Ethernet port J for DIGSI
as selective protection equipment for overhead lines and cables
• IEC 61850 (Reporting) via integrated port J
with single- and multi-ended infeeds. The device supports all
• Up to 4 pluggable communication modules usable for different SIPROTEC 5 system characteristics. It enables future-oriented
and redundant protocols (IEC 61850, IEC 60870-5-103, system solutions with high investment security and low operat-
IEC 60870-5-104, DNP3 (serial+TCP), Modbus RTU Slave) ing costs.
• Ethernet redundancy protocols PRP and HSR
Functions
2.5 • Cyber Security in accordance with NERC CIP and BDEW
whitepaper Table 2.9 / 3 on page 2.9 / 8 shows all functions that are available
• Powerful automation with CFC (Continuous Function Chart) in the 6MD86. Basically, all functions can be configured freely
with DIGSI 5. For the application of some of the functions, you
• Optional overcurrent protection for all voltage levels with require the appropriate number of free function points within
3-pole tripping the device. The function point calculator in the online configura-
• Also used in switchgear with breaker-and-a-half scheme tor provides support in determining the required number of
2.6 • Selective protection of overhead lines and cables with function points for your device.
single- and multi-ended infeeds for use with protection data
Application templates
2.7 communication
• Overcurrent protection also configurable as backup Application templates are available in DIGSI for standard
2.8 function applications. They comprise all basic configurations and default
settings. Table 2.9 / 3 on page 2.9 / 8 shows the functional scope
• Secure serial protection data communication, also over great
2.9 distances and all available physical media (fiber-optic cable,
and the function point requirement for the application templates
described. The following application templates are available:
2.10 2-wire connections and communication networks)
• Measurement of operational values SIPROTEC 6MD86 standard double busbar
3 • Synchrophasor measured values and IEEE C37.118 protocol • Double-busbar feeder with switchgear interlocking system
integrated (PMU)
3.1 • Synchrocheck for circuit-breaker
• Powerful fault recording
• Switching sequence for automatic busbar transfer precon-
3.2 • Auxiliary functions for simple tests and commissioning. figured (tripped by function key).

3.3 Applications
The bay controller SPROTEC 6MD86 is a universal protection,
3.4 control and automation device on the basis of the SIPROTEC
3.5 5 system. It is especially designed for the protection of lines
and therefore it is optimally suitable for reserve or emergency
3.6 protection for the line protection devices. Due to its high flex-
ibility in using of protection data communication it is suitable
3.7
2.9 / 6 SIPROTEC 5 – Devices · Protection, Automation and Monitoring · Siemens SIPROTEC 5.01 · Edition 2
Bay Controller SIPROTEC 6MD86
Application examples

SIPROTEC 6MD86 breaker-and-a-half type 1 SIPROTEC 6MD86 breaker-and-a-half type 2


1
• Control of a breaker-and-a-half diameter (3 circuit-breakers, • Control of a part of breaker-and-a-half diameter
14 disconnectors) • Supports concepts with several bay controllers per bay 1.1
• Synchrocheck for the three circuit-breakers with dynamic • Circuit-breaker failure protection and automatic reclosing.
measuring point changeover. 1.2
1.3
1.4
1.5
1.6
QB1 QB2
1.7


)* 9,BSK )* &LUFXLWEUHDNHU4$ 1.8
QA1 MP I-3ph  V-1ph 
V4
V-1ph 1 V-3ph
1.9
V-3ph 
I-3ph 50BF
QB9 I1  2
I2 MP 
I3 I-3ph 1 2SHUDWLRQDOPHDVXUHG
Display,
2.1
I4 YDOXHV Ctrl
Commu- BI
(QHUJ\PHWHUHG CB 2.2
nication, BO
YDOXHV
V1 CFC
V2
MP 2.3

Fig_5_7_Visio-Bsp-Application-2-us.pdf
V-3ph 1 &)&
V3 )* 'LVFRQQHFWRU4% 6ZLWFKLQJVHTXHQFH
IRUEXVEDUWUDQVIHU
2.4
/LQH Ctrl

Dco BI
BO

)* )XQFWLRQJURXS  6\QFKURFKHFNV\QFKURQL]LQJIXQFWLRQ 2.5


03 0HDVXULQJSRLQW %) &LUFXLWEUHDNHUIDLOXUHSURWHFWLRQ
4$ &% &LUFXLWEUHDNHU  2YHUYROWDJHSURWHFWLRQ
4% 'FR 'LVFRQQHFWRU  $XWRPDWLFUHFORVLQJ
%, %LQDU\LQSXW  )UHTXHQF\SURWHFWLRQ
%2 %LQDU\RXWSXW  3RZHUSURWHFWLRQ
&WUO &RQWURO
&)& &RQWLQXRXV)XQFWLRQ&KDUW
2.6

Fig. 2.9 / 5 Application example: Bay controller 6MD86 for double busbar with protection functions 2.7
2.8
2.9
2.10
3
3.1
3.2
3.3
3.4
3.5
3.6
3.7
SIPROTEC 5 – Devices · Protection, Automation and Monitoring · Siemens SIPROTEC 5.01 · Edition 2 2.9 / 7
Bay Controller SIPROTEC 6MD86
Functions, application templates

1 Application templates

1.1

Available in 6MD86

and-a half type 1

and-a half type 2


6MD86 standard

6MD86 breaker-

6MD86 breaker-
1.2

double busbar
1.3
1.4
ANSI Functions Abbr.
1.5 25 Synchrocheck, synchronizing function Sync Q Q Q Q
50BF Circuit-breaker failure protection CBFP Q Q
1.6 79 Automatic reclosing AR Q Q
PMU Synchrophasor measurement PMU Q
1.7 Operational measured values, standard Q Q Q Q

1.8 Measured values, extended: Min, Max, Avg Q


Switching-statistic counters Q Q Q Q
1.9 CFC standard Q Q Q Q
CFC arithmetic Q
2 CFC switching sequences Q Q
Control for 4 switching devices Q Q Q Q
2.1 Control for more than 4 switching devices Q Q Q

2.2 Protection interface Q


50/51 Overcurrent protection, phases I>, IP> Q
2.3 50N/51N Overcurrent protection, ground IN>, INP Q
50HS High speed instantaneous overcurrent protection I>>> Q
2.4 59 Overvoltage protection, 3-phase V> Q
59 Overvoltage protection, positive-sequence system V1> Q
59N Overvoltage protection, zero-sequence system V0> Q
27 Undervoltage protection, 3-phase V< Q
27 Undervoltage protection, positive-sequence system V1< Q
81O Overfrequency protection f> Q
2.5 81U Underfrequency protection f< Q
Inrush-current detection Q
Monitoring and supervision Q Q Q Q
46 Negative-sequence system overcurrent protection I2>, I2/I1> Q
49 Thermal overload protection θ, I2t Q
External trip initiation Q
74TC Trip-circuit supervision TCS Q
2.6
Function points 0 0 75
The configuration and function points for your application can be ascertained in the
2.7 SIPROTEC 5 order configurator under: www.siemens.com/siprotec

2.8 Table 2.9 / 3 SIPROTEC 6MD86 – Functions and application templates

2.9
2.10
3
3.1
3.2
3.3
3.4
3.5
3.6
3.7
2.9 / 8 SIPROTEC 5 – Devices · Protection, Automation and Monitoring · Siemens SIPROTEC 5.01 · Edition 2