OTIS Maintenance Manual No.

JESIOTIS-0002
09/06/2020
Consol (LCB2 LMCB GDCB) Rev1.0

Contents
1. Symbol...................................................................................................................................................................... 2
2. Consol (SVT) ............................................................................................................................................................. 4
2-1. Favorite menu ................................................................................................................................................... 4
2-2. Calls (M111) ...................................................................................................................................................... 5
2-3. Input (M112) ................................................................................................................................................. 7
2-4. Output (M113) .............................................................................................................................................. 7
2-5. Event (M121) ................................................................................................................................................ 8
2-6. Event code (M121) ........................................................................................................................................ 9
Revision report ........................................................................................................................................................... 13

Copyright (C) japan elevator service indonesia all rights reserved 1


OTIS Maintenance Manual No.JESIOTIS-0002
09/06/2020
Consol (LCB2 LMCB GDCB) Rev1.0

1. Symbol
Symbol Contents Symbol Contents
1BFS 1st Buffer Switch CDLD Car Door Lock Device
1LS down slowdown Limit Switch CEIB Communication and Encoder Interface Board
1LV 1st door zone switch CFL Car Fluorescence Light
1PES 1st Pit Emergency Stop switch CGIB Communication Gateway modem Isolation Board
1PMS Pit Maintenance Socket 1 CGMPB Communication Gateway Modem Processor Board
2BFS 2nd Buffer Switch 2 CGS Car Gate Solenoid
2LS up slowdown Limit Switch CHCS Cancel Hall Call Switch
2LV 2nd door zone switch CHF Current Harmonic Filter
2nd OCB Overload Circuit Breaker 2 CHT separate Car and Hall call door Times
2PES 2nd Pit Emergency Stop switch CKS Car Block Switch
6LS Limit Switch CLD Central opening Landing Door
7LS down final Limit Switch CLF_TC Fluorescent Car Light Travelling Cable
8LS up final Limit Switch CNV Converter
ACB Automatic Circuit Breaker CPI Car Position Indicator
ACD4-MR Asia Controller and Drive - Machine Room CTTL Car Tell Tale Light
ADO Advanced Door Opening CWS Counterweight Safety switch
AGS Auxiliary Gate Switch D Diode
AGSR Auxiliary Gate Switch Relay DBR Drive Brake Resistor
ALB Alarm Button DBS electrical recall switch
ANS Anti-Nuisance Car call DCB Door Close Button
APD Anti-Pollution Device DCL Down Collective Operation
ARD Automatic Return Device DCP Delayed Car Protection
ARED Automatic Rescue Emergency Device DCSS Door Control Subsystem
ARO Automatic Rescue Operation DDB electrical recall Down Direction Button
ARO BOX Automatic Rescue Operation Box DDO Disable Door Operation
AT120 A T120 door operator DDOS Disable Door Operation Switch
ATK Attendant service Key switch DDP Delayed Drive Protection
ATT Attendant service operation DDSR Disable Door Switch Relay
ATTD Attendant Down start button DE Door motor Encoder
ATTU Attendant Up start button DEEC Disable EEC
B Brake DEECR Disable EEC Relay
BAT Battery DFC Door Full Closed contact
BCB Battery Control Board DHB Door Hold Button
BCPC Brake Control and Power Conditioning DHBL Door Hold Button Light
BCR Brake Control Relay DIB Down Inspection Button
BDS Brake Drop Soft. DIS Door zone limit switch down
BFS oil Buffer Switch DM Door Motor
BID Belt Inspection Device DOB Door Open Button
BR Brake Relay DOBF DOB Faster response
BRB Brake Release Button DOL Door Open Limit switch
BRK Brake DOLR Door Open Limit Relay
BRM Brake Module DRV Drive
BS Brake Switch DS Door Switch
BSM Basement Service DTG Digital Tacho Generator
BUZ Buzzer DTP Door Time Protection
BV Brake Varistor DW Door Watch contact
BY Brake relay DXT-1 Extra Door lime (lobby and parking)
C2L 2 Cars to Lobby DZI Door Zone Indicator
CAP Capacity E&I PANEL Emergency and Inspection Panel
CB Circuit Breaker ECB Emergency Car Battery
CBM Car Button Mechanical ECL Emergency Car Light
CBn Car button n ECU Emergency Car Light Unit (for light, alarm bell, intercom)
CBS Car Sound Button EEC top of car Emergency Exit Contact
CBT Two Car operating panels EFO Emergency Fireman Operation
CCBL Car Call to Bottom Landing EFO Emergency Fireman Operation Monitoring
CCM Car Chime Monitoring
CCTL Car Call to Top Landing EFOR Emergency Fireman Operation Relay
CDD Car Door Detector EFS Emergency Fireman Service

Copyright (C) japan elevator service indonesia all rights reserved 2


OTIS Maintenance Manual No.JESIOTIS-0002
09/06/2020
Consol (LCB2 LMCB GDCB) Rev1.0

Symbol Contents Symbol Contents


EIS Socket in E&I panel MRO Manual Rescue Operation
EPFL Extended Power supply For Link NBCOP Number of COP
EQO Earthquake Operation NBENT Number of Entrance
EQR Earthquake Relay NDG Nudging
EQS Earthquake Sensor NOR/DIAG Normal/Diagnosis
ERO Electrical Recall Operation NSB Non Stop Button
RS Emergency Stop switch OCB Overload Circuit Breaker
ESR Emergency Stop Relay OCB-AUX Overload Circuit Breaker Auxiliary Contacts
ESS Emergency Stop Switch OLD Overload Device
F Fuse OS Over speed Switch
F1/2/6/8C Circuit breaker 1/2/6/8 OSU Upper Over speed Switch
F1L Fuse OVF 0CR OTIS VF drive
FAN Fan OVFR1A-40 OTIS VF Regen drive
FCL Full Collective Operation OVFR2B-40 OTIS VF Regen drive
FDP Faulty Door Protection PCS1/2 outlet Socket on Car
FS Fan Switch PDB Power Dri11e Board
FSK circuit breaker PES Pit Emergency Stop switch
FSS Fireman Service Switch PIT Pit
GCS Counterweight Governor Switch PKS Parking Switch
GDCB Global Drive Control Board PL Pit Lighting
GECB Global Elevator Control Board PLS Pit Lighting Switch
GRP Group PRS Position Reference System
GS Gate Switch PS outlet socket in hoistway
GSR Gate Switch Relay R Resistor
GTC Governor Tension Contact RALB Rear Alarm Button
HBM Hall Buttons Mechanical RCB Rear Car Button
HDI Hall Direction Indicator RCPI Rear Car Position Indicator
HIB integrated Hall Indicator Board RDCB Rear Door Close Button
HPI Hall Position indicator(16-seg) RDHB Rear Door Hold Button
HRS Handrail Switch RDHBL Rear Door Hold Button Light
HTTL Hall Tell Tale Lights RDOB Rear Door Open Button
HVIB High Voltage Interface Board R-ENC Rescue-Encoder
ICU Intercommunication Unit RF Rectifier
INS Inspection RLEV Relive lin g
INV Invert or RPS Replacing Protection Switch
IPS Intercom Power Supply RRD Remote Resetting Device
ISC Independent Service RS Remote Station
ISS Independent Service Switch RTD Remoter Trigger Device
J BOX Junction Box RTDOS Rear Top of car Door Operating Switch
LC Light Curtain RTES Rear Top of Car Emergency Stop button
LCD Liquid Crystal Display SCS Slack Cable Switch
LDLB Landing Door Lock Bypass SGS Safety Gate Shoe
LIH Hoistway Light Sin/Cos Sine/Cosine Encoder
LIHR Hoistway Light Relay Encoder
LIHS-C Hoistway Light Switch-Controller SL Short Landing distance
LIHS-P Hoistway Light Switch-Pit SLS Inspection Limit Switch
LNS Load Non Stop SOM Switch Over Module
LR Fan/Light Relay SOR Switch Over Relay
LRD Light Ray Device SOS Safety Over speed Switch
LS Limit Switch SPB Service Panel Board
LT C Line Terminator SPBC Service Panel Board with CAN
LT H Line Terminator SSR Solid State Relay
LW Load Weighing SVT Service Tool
LWB Load Weighing Board SW main contactor
LW-S Load Weighting Switch TB Terminal Block
MCB Motion Control Board TBE Terminal Block
MES Machine room Emergency Stop switch TC Trip Counter
MO Motor TCBC Traction control board CAN

Copyright (C) japan elevator service indonesia all rights reserved 3


OTIS Maintenance Manual No.JESIOTIS-0002
09/06/2020
Consol (LCB2 LMCB GDCB) Rev1.0

Symbol Contents Symbol Contents


TCI Top of Car Inspection UHBn Up hall button
TCIB Top of Car Inspection Button UIB Up Inspection Button
TCL Top of Car Light UIS Door zone limit switch up
TDOS Top of Car Door Operating Switch VR Voltage Regulator
TES Top of car Emergency Stop button W/ With
THB Thermal contact W/O Without
TIB Top of car Inspection direction Buttons XDS Aux. door switch
TIMER Time relay XDSn Rear Landing Door Switch
TOCL Top of Car inspection Light XEFO aux Emergency Fireman Operation
TOCLS Top of Car inspection Light Switch XGS aux. car Gate Switch
TRF Transformer Z Zener
TRIC Trip Counter
UCM Unintended Car Mo11ement
UCMR Unintended Car Mo11ement Relay
UDB Electrical recall up direction button
UDLS Up/Down Final Limit Switch

2. Consol (SVT)
Used for error information, call registration, setup, etc.

エラー情報や呼び登録、セットアップ等に使用する。

2-1. Favorite menu

・Calls (M111) ・Input (M112) ・Output (M113)


・Event (M121) ・RSL-TEST (M124) ・RSL (M132)

Start from “Module” and proceed to the desired command.


“Module”からスタートし、目的のコマンドまで進める。

For example, if you want to see "Input",


例えば、” Input “を見たい場合、

Module → 1: System → 1: Status → 2: Input

Copyright (C) japan elevator service indonesia all rights reserved 4


OTIS Maintenance Manual No.JESIOTIS-0002
09/06/2020
Consol (LCB2 LMCB GDCB) Rev1.0

2-2. Calls (M111)

1 A Lift Number
2 - Direction ‐:Stop;U:Up;D:Down;
**:Position lost;
3 00 Position
00‐31:Floor position;
4 IDL Operation
5 ST Drive status
6 ][ Front door ] [:CLOSE;[ ]:OPEN;
<>:Opening;><: Closing;
7 ][ Rear door
DDO:Door off
8 Message System lock failure information

Operation
IDL Idol CHC Landing call cut ANS Light load
ATT Attendant mode PKS Parking LNS Full load
EFS Fire operation DHB Door hold OLD Over load
ISC Independent mode INS Inspection

Drive status
IDL Idol CHC Landing call cut ANS Light load
ATT Attendant mode PKS Parking LNS Full load
EFS Fire operation DHB Door hold OLD Over load
ISC Independent mode INS Inspection

Message
Learn Run ! Calibration DBSS fault Drive is not ready
DBP - Fault ! Door bypass fault SE - Fault ! Host thermal failure
TCI - Lock ! Inspection activation lock start DCS! DCS Run not running
LS - Fault Limit switch fault RLV - Count! Re-leveling times exceeded
1LS + 2LS ON ! 1LS+2LS On (same time) Drive Fault Drive failure
Adr – Check ! Address detection Speed Check Speed feedback failure

Copyright (C) japan elevator service indonesia all rights reserved 5


OTIS Maintenance Manual No.JESIOTIS-0002
09/06/2020
Consol (LCB2 LMCB GDCB) Rev1.0

C : Car call
U : Hall call (Up)
1 C Call status
D : Hall call (Down)
E : Emergency power supply running call
2 Destination floor 0-31
3 U00 Up call (Hall) 0-31
4 D00 Down call (Hall) 0-31
A:Light load <100kg
D:Normal
5 A Load status
F:Full load >80%
O:Over load >110%
Lift number and 1C‐4C Normal power No1~4
6 1C
power status 1E‐4E Emergency power No1~4

Enter the M111 menu. The first line shows the software status. The second line controls the elevator call
system. You can monitor up and down calls, number of commands, load, elevator number in service, and
power supply.Press GOON or SHIFT GOBACK: to realize cyclic switching between C-U-DE.
Number key: Input the target floor
SHIFT ENTER: Cancel input

M111 メニューに入ります。最初の行はソフトウェアのステータスを表示します。2 番目の行はエレベータコールシステムを制御します。


アップとダウンコール、コマンドの数、負荷、稼働中のエレベータ番号、および電源を監視できます。
GOON または SHIFT GOBACK:を押して、C-U-DE 間の循環切り替えを実現します。
数値キー:ターゲットフロアの入力
SHIFT ENTER:入力をキャンセル

M111

Button "5"
Shift (Blue Button) +"ENTER"

moving to floor

Copyright (C) japan elevator service indonesia all rights reserved 6


OTIS Maintenance Manual No.JESIOTIS-0002
09/06/2020
Consol (LCB2 LMCB GDCB) Rev1.0

2-3. Input (M112)

When you enter the M112 menu, the input signal is displayed. System input: Upper case indicates that a signal is
being input; Lowercase letters indicate that the signal has no input. Display the next page with GO ON or GO BACK.

M112 メニューに入ると、入力信号が表示されます。システム入力:大文字は信号が入力されていることを示し、小文字は、信号に入力がない
ことを示します。GOON または GOBACK で次ページを表示。

2-4. Output (M113)

When you enter the M113menu, the output signal is displayed. System input: Upper case indicates that a signal is
being output; Lowercase letters indicate that the signal has no output. Display the next page with GO ON or GO
BACK.

M113 メニューに入ると、出力信号が表示されます。システム入力:大文字は信号が出力されていることを示し、小文字は、信号に出力がない
ことを示します。GOON または GOBACK で次ページを表示。

Copyright (C) japan elevator service indonesia all rights reserved 7


OTIS Maintenance Manual No.JESIOTIS-0002
09/06/2020
Consol (LCB2 LMCB GDCB) Rev1.0

2-5. Event (M121)

You can check the fault error history with M121.

M121 でエラーを確認できる。

Display Contents Remarks


0204 TCI/ERO on The fault code and fault name See table below
c003 The number of occurrences of this fault Record 999 times
t00020 The fault elapsed time Record 99999 minutes
P** The fault was last sent floor Between floors 00-31

Clear event (M121 Shift+2)

Press 1 to confirm

Press 2 to confirm + Enter

Copyright (C) japan elevator service indonesia all rights reserved 8


OTIS Maintenance Manual No.JESIOTIS-0002
09/06/2020
Consol (LCB2 LMCB GDCB) Rev1.0

2-6. Event code (M121)

I Information
W Warning
F Fault

Event code Type Contents Remarks


total runs The number of runs after the last power-on -
minutes on Running time after the last power-on (unit: minutes) -
Operating System
0000 Task Timing W -
0001 S/W Reset W GECB monitoring circuit triggers, software restarts -
0002 Illegal Int W Illegal interrupt -
0003 CanTxFull W CAN cannot send information -
0004 CanBusOff W CAN communication restart -
0006 StackCheck F Stack error, restart -
0007 SCN Error F Incorrect software -
0008 TimerSync F The internal software timer is not refreshed -
0009 Task Fail F Software operation error -
0010 McbCommErr F Inverter CAN communication error -
0011 SpbCommErr W SPB communication error -
0012 Power On I Control board power on -
0013 Event Fail W -
0014 PowerOffOn I Instant power outage -
0016 S/W Restart W Unknown reset -
0017 Trace Error F Event tracking buffer error -
0019 MissedLvInt F LV1 and LV2 signals are not obtained -
Operational Control Sub System
0100 OpMode NAV F OCSS is unavailable due to inverter fault, and this fault -
will also appear during reset operation after
maintenance
0101 EPO shutd. W Cannot run due to EPO NU (017)
NUSD (018)
NUSG (019)
0102 OpMode DTC W The door cannot be completely closed within DCL (694)
the specified time (DCL, DFC or DW signal RDCL (695)
error) DOOR, REAR
DTC-T
0103 OpMode DTO F The door cannot be fully opened within the DOL (000)
specified time (DOL signal error) RDOL (544)
DOOR, REAR
DTO-T

Copyright (C) japan elevator service indonesia all rights reserved 9


OTIS Maintenance Manual No.JESIOTIS-0002
09/06/2020
Consol (LCB2 LMCB GDCB) Rev1.0

Event code Type Contents Remarks


0104 OpMode DCP W The car cannot respond to the call (eg the DCP-T
door is manually opened)
0106 PDS active I PDD (784)
0107 DS bypass F Shield door lock circuit due to housekeeping service DDSRC (970)
0108 EEC bypass F Circuit for shielding safety windows due to DEMERC (971)
housekeeping services
0109 Stuck DCB F The door close button keeps moving DCB (003)
0110 Stuck RDCB F The back door closing button keeps moving RDCB (547)
Motion Control Sub System
0201 Correct.Run I Reset operation -
0202 /ES in FR W ES action when express train is running -
0203 /ES in SR W ES action during deceleration -
0204 TCI/ERO on I TCI or ERO action ERO-TYP
0205 SE-Fault F The car cannot start due to SE failure, -
check the door lock circuit
0210 /DZ in NST F DZ signal lost during parking DZ-TYP
0211 /DFC in FR W he door was opened while the express train was -
running
0212 /DFC in SR W The door was opened during deceleration -
0213 DrvPrepErr W -
0214 DrvStuckPtr W The inverter status has always been -
PrepareToRun
0215 DrvStuckRtr W The inverter status has always been -
ReadyToRun(NoAbl)
0216 DrvBrakeErr F The brake is not open -
0217 DrvCreepErr F Crawling time is too long -
0218 DrvShutdown F Inverter off -
0219 DrvStartErr F
0220 DrvService W -
0222 1TH-Fault W The DBR contact connected to ITH opens, the -
frequency converter closes and cools
0223 2TH-Fault F The contact connected to 2TH opens -
0224 DrvEndRun F Inverter cannot stop operation -
0225 110VAC dead F 110VAC power interruption for 5 seconds -
0228 1LS+2LS on F ILS and 2LS act simultaneously -
0230 RSL Adr Chk F The IO address is incorrect, it is not allowed to set to TCI(691)
00-0 and 01-0
0233 PowerSave I PDR-D
0235 ABL Abort W The function of opening the brake early is prohibited EN-ABL=1,
because the door has not been completely closed DRV-TYP=1
after 10 seconds of opening of the brake.
0237 /DW in FR W The hall door was opened during the express -
train operation

Copyright (C) japan elevator service indonesia all rights reserved 10


OTIS Maintenance Manual No.JESIOTIS-0002
09/06/2020
Consol (LCB2 LMCB GDCB) Rev1.0

Event code Type Contents Remarks


0238 /DW in SR W The hall door was opened during deceleration -
Door Control Sub System
0300 DBP: dfc_SE F During the door opening process or when the door is EN-RLV,
fully opened, the door lock circuit is found not to EN-ADO
operate.
0301 DCL in [ ] F (R) DCL acts when the door is in place DCL (694)
RDCL (695)
0302 DoorBridge F DW or DFC is high level during the last door opening -
and closing process, indicating that the safety circuit is
shorted or the door lock circuit is wrong.
0304 DOL:alw. on F DOL action when the door is fully closed. DOL (000)
This fault also occurs when the fuse that
supplies power to the door machine blows. .
The fault is not recorded within 40 seconds
after the system is started.
0306 Hwy Access F The hall door opens and the car door closes. -
0307 RDOL:alw.on F RDOL acts when the door is fully closed. RDOL(544)
This fault also occurs when the fuse that
supplies power to the door machine blows. .
The fault is not recorded within 40 seconds
after the system is started.
0308 DOOR sync F Double door synchronization failure -
0309 DOOR adr. F -
0310 FDOOR chk F Front door check error -
0311 RDOOR chk F Backdoor check error -
0312 FDOOR Tout F Front door communication timeout -
0313 RDOOR Tout F Backdoor communication timeout -
0314 GDS noPull F GDS relay does not pull in -
0315 GDS noDrop F GDS relay does not release -
0319 GSM Ferror F Front door GSM input error -
0320 GSM Rerror F Backdoor GSM input error -
Signaling Sub System
0400 RSL parity W Two identical station addresses on the same serial line -
0401 RSL sync W Remote serial communication synchronization -
error
0402 RSL reinit F RSL driver display failure -
0403 RSL Fail F RSL is not working -
0404 RSL Hrtbeat F RSL is not working -
0405 RSL Board F The remote communication board does not -
match
0406 Group RSL F Group control RSL failure -
Group
0500 RNG1 msg W -

Copyright (C) japan elevator service indonesia all rights reserved 11


OTIS Maintenance Manual No.JESIOTIS-0002
09/06/2020
Consol (LCB2 LMCB GDCB) Rev1.0

Event code Type Contents Remarks


0501 RNG1 time W Didn't receive the message to other elevator GROUP
0502 RNG1 sio W -
0503 RNG1 tx W Group control information cannot be sent -
0504 RNG1 rxOff W Communication reception error within -
specified time
0505 RNG1 reset W Reinitialize -
0506 DES offline F DES is not in the system -
0507 GCB offline F GCB is not in the system -
System
0600 SPB-Alert W The control board has detected SPB and SDI failures. -
Possible reasons for Ssk are:
Encoder failure
E2 memory failure on SPB
Battery failure
At the same time, press REB+DDO on SPB to locate the
cause of the fault
0601 SPB:TempHTS W Control board detected over temperature SPB-Temp
0602 LwssService W Weighing system request service -
0604 S/W Changed I SCN changes -
0605 Update S/W! F -
0606 SpbService W SPB request service -

Copyright (C) japan elevator service indonesia all rights reserved 12


OTIS Maintenance Manual No.JESIOTIS-0002
09/06/2020
Consol (LCB2 LMCB GDCB) Rev1.0

Revision report

Content Date Name


Revision Number
1 First edition 10/06/2020 Satoshi Sawada

Copyright (C) japan elevator service indonesia all rights reserved 13