SHORT CIRCUIT STRENGTH CALCULATION - BGR 270 MVA 1-PH GT

COIL SUPPORT

MECHANICAL FORCE IN WINDING

1 Maximum Axial Force to Clamping Structure during Short Circuit at the Maximum Tap

LV Winding 300 Tons


Resultant 300 Tons
HV Winding 50Tons (As Maximum Values of HV and
LV Windings occur at different
2 Mechanical Force / Coil Spacer instances)

Total No. of Spacers provided = 36

LV Winding Pml = 300000 = 8333.3 Kg


36
HV Winding Pmh = 50000 = 1388.8 Kg
36

3 Coil Clamping Force/ Coil Spacer at 10Kg/cm2

Wdg. Spacer
Wdg. Name Width(mm) Width(mm)
LV 136 50
HV 163 60

Coil Clamping Force/Coil Spacer = (Wdg. Width(mm) x Spacer Width(mm) x 10/100 ) Kg

LV Winding Pcl = 50 x 136 x 10/100 = 680 Kg

HV Winding Pch = 60 x 163 x 10/100 = 978 Kg

4 Total Clamping Force / Coil Spacer

LV Winding Ptl = Pml + Pcl = 9013.3 Kg

HV Winding Pth = Pmh + Pch = 2366.8 Kg

Coil Clamping Push Bolts (M 36 x 32 Nos. provided)

Effective Area of each Push Bolt = 817 mm2

LV Winding (1.2 Spacers/Bolt)

SigmaL = 9013.3 x 1.2 = 13.24 Kg/mm2


817 ( < 18 Kg/mm2 )

HV Winding (0.7 Spacers/Bolt)

SigmaH = 2366.8 x 0.7 = 2.03 Kg/mm2


817 ( < 18 Kg/mm2 )
STRENGTH OF UPPER CLAMP PLATE MADE OF DENSIFIED WOOD ( 50 t x 540W)

HV Winding Pth 2l =318 Pth


A B
A&B Spacer Supports
C Coil Clamping Push Bolt 50
2Pth l =159
C
Pth x l
Bending Moment Mhv = Pth x l
= 2366.8 x 159 A B
= 376.3 x 103 Kg-mm B M Diagram

Section Modulus Zhv = b x t2


6
= 540 x 502
6
= 225 x 103 mm3

Sigma hv = Mhv
Zhv
= 376.3 x 103
225 x 103

= 1.67 Kg/mm2

< 5 Kg/mm2 (Hitachi Standard)

LV Winding
Ptl 318 Ptl
A&B Spacer Supports A B
C&D Coil Clamping Push Bolt
50
Ptl 148 Ptl
85 C D l = 85

Bending Moment Mlv = Ptl x l


= 9013.3 x 85 C- D Ptl x l
= 766.14 x 103 Kg-mm

Section Modulus Zlv = b x t2 A B M Diagram B


6
= 540 x 502
6
= 225 x 103 mm3

Sigma lv = Mlv
Zlv
= 766.14 x 103
225 x 103

= 3.41 Kg/mm2

< 5 Kg/mm2 (Hitachi Standard)


CONCLUSION:

The maximum Axial Force occuring during the Short Circuit is 296 Tons at the

Maximum Tap position, as per the HITACHI Program for the Calculation of Dynamic Forces during

Short Circuit. The Calculation furnished above shows that the Densified Wood Clamp Plate of 50 t

provided on the top of the winding and the core clamping structure is rigid enough with sufficient margin

to withstand the Dynamic Axial Force of 300 Tons. Also it can be seen that the Coil Clamping Push

Bolts (M36 x 32 Nos.) are also having sufficient safety margins and will not yield / fail during

Short Circuit.