Two different TIE-INs

should have different


numbering. Please review.

Correct scale.

Please consider the following comments


about drawing details in order to improve
... DE FILTROS representation:
MULTIMEDIA. - Review alarm representation, as they
should be represented as: A±A2± .
- Replace in PI&Ds arrows VEOLIAs
number to ENEVAs PI&Ds number.
- Include all the arrows in instrument signals
to clarify to/from.
- In case of line intersection, interrupt
vertical lines.
- Adjust scale in all PI&Ds from lines and
signals (dashed, software, …).
- Existing piping and electrical signal should
POS/EME have different representation.
- Remove pumps scope of supply as it does
not add information. Otherwise please
represent line differently (not dashed).
- Try to represent lines the most straight
possible.
FGJ/LPE 06/03/20
A

Please correct scale.

See comments
above.
00GDN80 AP051/052/053/055/056

00GDN90 AP051/052/053/057/059

00GDN60 AP051/052/053/056/057
3/4" 3/4" 3/4"

Switch places.

See comments
above.

See comments
above.