Sie sind auf Seite 1von 15

ACI STRUCTURAL JOURNAL TECHNICAL PAPER

Title no. 97-S02

Seismic Load Tests on Interior and Exterior Beam-Column


Joints with Substandard Reinforcing Details
by Shigeru Hakuto, Robert Park, and Hitoshi Tanaka

Simulated seismic load tests on reinforced concrete one-way inte-


rior and exterior beam-column joints with substandard reinforcing
details typical of buildings constructed before the 1970s are
described. The interior beam-column joint cores lacked transverse
reinforcement and the longitudinal bars passing through the joint
core were poorly anchored. Some of the beam-column joint units
were also tested after retrofitting by jacketing with new reinforced
concrete. The limited ductility available from interior beam-column Fig. 1—Some mechanisms of postelasic deformation of
joints with the substandard details, the improved ductility available moment- resisting frames during earthquakes.
from the retrofitted joints, and a means of seismic assessment of inte-
rior beam-column joints without transverse reinforcement are
discussed. The exterior beam-column joint units contained very resisting frames.1-3 Hence, a beam sidesway mechanism, or
little transverse reinforcement in the members and in the joint core. at the very least a mixed sidesway mechanism (Fig. 1(c) and
In one beam-column joint unit the beam bar hooks were not bent (d)), which makes more moderate demands on column
into the joint core. That is, the hooks at the ends of the top bars plastic hinge rotation, is sought. The design procedures spec-
were bent up and the hooks at the ends of the bottom bars were ified in recent standards for detailing reinforcement in poten-
bent down. This anchorage detail was common in many older tial plastic hinge regions are also aimed at making certain that
buildings constructed before the 1970s. In the other beam-column
the transverse reinforcement is sufficient to ensure adequate
joint unit the hooks at the ends of the bars were bent into the joint
core as in current practice. The improvement in performance of the ductility and shear strength, taking into account the need to
joint with beam bars anchored according to current practice is confine the concrete and prevent longitudinal bars from
demonstrated. buckling, and to prevent the degradation of shear strength
during cyclic loading in the postelastic range.
Keywords: anchorage (structural); earthquake-resistant structures; flexural Damage caused by earthquakes through the years, including
strength; shear strength. the Hyogo-ken Nanbu earthquake in Kobe, Japan, in January
1995,4 indicated that some reinforced concrete buildings
INTRODUCTION designed prior to the mid-1970s may have serious structural
Substantial advances in the seismic design of reinforced deficiencies. These deficiencies are mainly a consequence of
concrete moment resisting frames have occurred internation- a lack of capacity design approach and/or poor detailing of
ally during the last 30 years. For example, in New Zealand, reinforcement. As a result, the available ductility of the struc-
a major step forward in seismic design standards occurred in ture during the cycles of lateral loading in the post-elastic
the late 1970s and early 1980s when capacity design and range imposed by a severe earthquake may be inadequate.
detailing procedures for adequate ductility were introduced A common seismic assessment procedure for existing rein-
into the standards. forced concrete structures is a checklist-type approach in which
the reinforcing details are compared with the requirements of
In capacity design, the designer chooses the most desirable
current concrete design standards. More realistic force-based
mechanism for the structure to achieve the required displace-
procedures suggested by Priestley and Calvi5 and Park6 consider
ment ductility factor in the post-elastic range during a major
the overall performance of the structure by determining the
earthquake, normally by flexural yielding occurring at
available lateral load strength and ductility of the critical post-
selected plastic hinge positions. All other regions of the
elastic mechanism of deformation of the structure. Priestley7 has
structure are then made adequately strong to ensure that the
also proposed a displacement-based procedure that gives an
post-elastic deformations occur only at the selected plastic
even better indication of the ductility required of structures.
hinge regions and that failures due to shear and loss of rein-
forcement anchorage are avoided. The capacity design These approaches5-7 require information on the ductility
procedure aims to ensure an appropriate balance of flexural available from structural elements and joints containing the
strength between the selected plastic hinge regions and other poorly detailed reinforcement that was typical of older
modes of failure. For example, columns can be vulnerable concrete structures. However, there is a scarcity of such
elements of moment-resisting frames. If a number of basic information. Also, retrofit techniques for such struc-
columns attain their flexural strength during severe earth- tures need further development.
quakes, a column sideway mechanism, such as that shown in
Fig. 1(b), can form, leading to very high ductility demands at ACI Structural Journal, V. 97, No. 1, January-February 2000.
Received March 31, 1998, and reviewed under Institute publication policies. Copy-
the plastic hinges. The result may be catastrophic soft story right © 2000, American Concrete Institute. All rights reserved, including the making
failures. New Zealand and U. S. standards use the concept of of copies unless permission is obtained from the copyright proprietors. Pertinent discus-
sion will be published in the November-December 2000 ACI Structural Journal if
ensuring strong column-weak beam behavior for moment- received by July 1, 2000.

ACI Structural Journal/January-February 2000 11


Shigeru Hakuto is a research engineer in the Structural Laboratory of the Architectural
Research Department of the Technological Research Center of the Tokyu Construction
Co., Sagamihara, Japan. He received his PhD from the Department of Civil Engi-
neering of the University of Canterbury, New Zealand, in 1995.

ACI Honorary Member Robert Park is Professor of Civil Engineering and Deputy
Vice-Chancellor at the University of Canterbury. He was corecipient of ACI’s
Raymond C. Reese Structural Research Award in 1984 and 1989. His research interests
include seismic behavior of concrete structures.

Hitoshi Tanaka is an associate professor in the Department of Architecture and Civil


Engineering at Toyohashi University of Technology, Toyohashi, Japan. He received
his PhD in civil engineering from the University of Canterbury.

This paper reports the results of simulated seismic load


tests on some poorly detailed reinforced concrete interior
and exterior beam-column joints, typical of pre-1970s
designed moment-resisting frames in New Zealand. Test
results from interior beam-column joints retrofitted by jack-
eting with new reinforced concrete are also reported. The
results may be seen reported in more detail elsewhere.8

RESEARCH SIGNIFICANCE
Designers are being confronted more with the task of
assessing the seismic risk of existing reinforced concrete
structures, and the retrofit, where necessary, of those struc-
tures. There is a lack of comprehensive experimental evidence
of the behavior of structures with poor reinforcement details,
typical of those designed before the mid-1970s, when
subjected to severe seismic actions. This paper reports the
results of some seismic load tests on interior and exterior
beam-column joints of older structures in which the anchorage
conditions of longitudinal bars in the joint and the amount of
transverse reinforcement in the joint do not satisfy the require-
ments of current codes. The results of the tests provide further
information for use in the assessment of the performance of
older structures when responding to severe earthquakes. Tests
on interior beam-column joints retrofitted by jacketing with Fig. 2—Typical details of reinforced concrete moment-
new reinforced concrete are also reported. A method of retro- resisting frame designed in New Zealand in late 1950s. (Note:
fitting by increasing the section size of the column to limit the 1 ft = 0.305 m; 1 in. = 25.4 mm.)
joint shear stress is proposed.
ASSESSMENT OF INTERIOR BEAM-COLUMN
JOINTS
TYPICAL EARLY-REINFORCED CONCRETE General
MOMENT-RESISTING FRAME INVESTIGATED As shown in Fig. 2, it will often be found in the case of
An existing seven-story reinforced concrete building that interior joints of older frames that longitudinal beam bars of
was designed and built in New Zealand in the late 1950s was relatively large diameter pass through interior columns of
considered. Typical details of the reinforcement of the frame relatively small depth. This will result in high bond stresses
are shown in Fig. 2. As with many building structures designed and some bar slip during seismic loading. NZS 3101:19952
to codes created prior to the mid-1970s, the reinforcement is and ACI 318-953 both require the column depth to bar diam-
adequate for gravity and wind loads, but some of the details of eter ratio to be large enough for the bond stress to be suffi-
the reinforcement are inadequate for earthquake forces if ciently small to prevent significant bar slip. If significant slip
ductile behavior is required. Assessment of the building does occur, the bar will be in tension through the joint core
studied showed that when compared with the current code and the compression reinforcement in the beam on one side
requirements for ductile frames,2,3 some of the columns have of the column may actually be in tension, with a resulting
inadequate longitudinal reinforcement to ensure strong loss in beam flexural strength and ductility. Also, the stiffness
column-weak beam behavior and inadequate transverse rein- of the frame will be reduced significantly.
forcement for shear strength and ductility, and that the beams Probably the greatest uncertainty when assessing the
have inadequate transverse reinforcement for shear resistance seismic performance of reinforced concrete frames is the
and some have lap splices in the bottom longitudinal reinforce- likely behavior of beam-column joints with limited transverse
ment in potential plastic hinge regions. Also, the beam-column reinforcement in the joint core. Most framed structures
joints have no transverse reinforcement for shear and confine- designed before 1970 did not include any transverse reinforce-
ment, and the longitudinal reinforcement passing through or ment in the joint core. Very limited testing has been conducted
terminating in the joints is poorly anchored. At the exterior on such joints to determine their shear strength and whether
beam-column joints, the longitudinal beam bars are anchored buckling of longitudinal column bars occurs there. Shear
by bending the hooks out of the joint cores, which does not failure of beam-column joint cores without transverse rein-
meet the current NZS 3101:19952 and ACI 318-95.3 forcement is due to extensive diagonal tension cracking that

12 ACI Structural Journal/January-February 2000


Fig. 3—Interior beam-column joint subjected to seismic loading.

may eventually lead to diagonal compression failure in the If the total bond force U becomes zero as a result of bond
joint core. The prevention of premature buckling of column deterioration in the joint core due to poor bond conditions
bars requires adequate ties. and bond degradation during cyclic loading in a major
earthquake, then from Eq. (4)
Joint shear force and shear resistance
Cs2 = –T1 (5)
Figure 3(a) shows the forces acting on the joint core as a
result of the actions of the beams and columns.
Eq. (5) implies that the top bars are in tension along the
The horizontal shear force acting on the joint core is whole length of the joint core and are anchored in the left-
hand beam. Substituting Eq. (5) into Eq. (2) gives
V jh = C s2 + C c2 + T 1 – V c′ (1)
Cc2 = T1 + T2 (6)
For equilibrium of forces in the left-hand beam at the face of
the column Then substituting Eq. (5) and (6) into Eq. (1) gives

Cs2 + Cc2 = T2 (2) V jh = – T 1 + T 1 + T 2 + T 1 – V c′ = T 1 + T 2 – V c′ (7)

Substituting Eq. (2) into Eq. (1) gives Eq. (3) and (7) are identical. Hence, the total horizontal shear
force acting on the joint core is unchanged by deterioration
V jh = T 1 + T 2 – V c′ (3) of bond along the longitudinal beam bars in the joint core,
although the manner of application is changed.
Now Eq. (1) assumes that the resistance provided by total Mechanisms of shear resistance that provide means of trans-
bond force U along the top bars in the joint core is sufficient ferring the beam and column forces across the joint core after
to anchor the bars in the joint core (Fig. 3(b)). That is, diagonal tension cracking are shown in Fig. 3(c) and (d).9 When
the bond forces tend to zero, it is evident that the majority of the
U = Cs2 + T1 (4) shear will be transferred across the joint core by the diagonal

ACI Structural Journal/January-February 2000 13


compression strut mechanism, and hence, diagonal tension to assume that the shear strength is reached at the stage of
cracking is less likely if bond deterioration occurs at an early initial diagonal tension cracking of the joint core. If the
stage of loading. tensile strength of the joint concrete is assumed to be k√f c′ ,
It should also be noted that T1 = Mb1/jd1 and T2 = Mb2/jd2 where k is an empirically determined constant, then from Eq.
where Mb1 and Mb2 are the beam moments at the face of the (15), the nominal horizontal joint shear stress at first diag-
joint core, and jd1 and jd2 are the lever arms between the onal cracking is given by
tensile forces and the centroids of the compressive forces, at
the right- and left-hand sides of the joint, respectively. N
Hence, Eq. (3) can also be written as v jh = k f c′ 1 + ----------------------- (16)
b j h c k f c′
M b1 M b2
- + --------- – V c′
V jn = -------- (8) As expected, Eq. (16) shows that the presence of axial
jd 1 jd 2 compression in the column will delay the appearance of
diagonal tension cracking.
Joint principal stresses The previously explained diagonal tension criteria for joint
The nominal horizontal shear stress at the mid-depth of the core failure may be too conservative, however, since the joint
joint core can be written as core may be capable of transferring significantly higher shear
forces after diagonal tension cracking by means of the diagonal
vjh = Vjh /bjhc (9) compression strut mechanism shown in Fig. 3(c).
In that case, joint failure of the joint core will finally occur
where as a result of diagonal compression failure. That is, crushing
bj = effective width of the joint core; and of the diagonal compression strut will occur when the
hc = depth of the column. compressive strength of the strut is sufficiently weakened by
NZS 3101:19952 defines bj as either the smaller of diagonal tension strains and by the repeated opening and
closing of diagonal tension cracks in alternating directions.
b j = b c or ( b w + 0.5h c ) when b c ≥ b w (10) The stage of diagonal compression failure is best estimated
by determining the value of vjh when a limiting diagonal
b j = b w or ( b c + 0.5h c ) when b c ≤ b w (11) compressive stress is reached. After diagonal tension cracking
initiates, however, the stress distribution in the joint core
where becomes much more complex, and the previously explained
bc = width of column; simple Mohr’s circle approach is inadequate for determining
bw = width of beam web; and the diagonal compression stress corresponding to a given vjh
hc = depth of column. and fa. Note that if fa is very large, diagonal compression
The nominal axial compressive stress on the column at the failure by crushing of the diagonal compression strut could
mid-depth of the joint core can be written as also occur before the vjh at first diagonal cracking is reached.
The most simple failure criterion for an interior beam-
fa = N/bjhc (12)
column joint without shear reinforcement would appear to be
where a diagonal compression failure criteria. This approach is
N = axial compressive load on column. recognized by NZS 3101:1995,2 which specifies that, to
The stresses vjh and fa are both nominal values since they avoid diagonal compression failure in beam-column joints,
are not uniform over the horizontal plane at the mid-depth vjh should not exceed 0.2fc′.
of the joint core. In this investigation, a series of simulated seismic load
Nevertheless, a measure of the principal tensile and tests were conducted on one-way interior beam-column
compressive stresses at the mid-depth of the joint core, as joints, most of which had no transverse reinforcement in the
found from Mohr’s circle, is given by joint core. The results of these tests and of some other inves-
tigators’ tests were studied to determine whether the previ-
ously explained simple procedure of limiting vjh was valid.
–f f 2
p = ------a- ±  ---a + v jh
2
(13)
2  2 ASSESSMENT OF EXTERIOR BEAM-COLUMN
JOINTS
where compressive stresses are taken as negative. The internal forces acting on a reinforced concrete exterior
The principal tensile stress then is beam-column joint during seismic loading are shown in Fig. 4.
After diagonal tension cracking in the joint core, the beam
–f f 2 and column forces are transferred across the joint core mainly
p t = ------a- +  ---a + v jh
2
(14)
2  2 by a diagonal compression strut. It is evident that the current
practice of bending the hooks at the ends of the longitudinal
from which beam reinforcement into the joint core permits the diagonal
compression strut to bear effectively against the hooks, since
f the bearing stresses at the bend in the bar act in the direction
v jh = p t 1 + ---a- (15) of the strut.
pt In the case of older frames, constructed before the 1970s
in New Zealand and some other countries, it was common to
Failure criteria for joint anchor the longitudinal beam bars at exterior beam-column
One approach for the assessment of the shear strength of joints by bending the hooks out of the joint core. This old
interior beam-column joints without shear reinforcement is detail does not provide the best configuration to enable the

14 ACI Structural Journal/January-February 2000


Fig. 5—Main mechanisms of joint shear resistance of
Units O6 and O7.

lateral load-carrying capacity when diagonal cracking first


occurs. Diagonal tension is important because tension strains
Fig. 4—Exterior beam-column joint subjected to seismic at right angles to the concrete diagonal compression strut
loading. will weaken the compressive strength of the strut. Diagonal
compression failure, which occurs when a limiting joint
tensile bar force at the bend in the bar to be transferred to the shear stress k2 fc′ is reached, would appear to be a more
diagonal compression strut.9 appropriate failure criterion.
The situation is illustrated in Fig. 5, where Fig. 5(a) shows
the currently specified bar anchorage detail and Fig. 5(b) INTERIOR BEAM-COLUMN JOINT TEST UNITS
shows the old detail. In Fig. 5(a), the bearing stresses at the Test units
bend act in terms of strut and tie model considerations, and Six one-way interior beam-column joint units were
the diagonal compression strut effectively engages the beam constructed and tested. Figures 6 through 12 show the
reinforcement. The detail of Fig. 5(b) does not provide an dimensions of the units and the details of the reinforcement.
effective node point at the top of the diagonal compression
strut unless a considerable quantity of column hoops exists Details of as-built units
above the joint core to equilibrate the horizontal component Figure 6 shows the reinforcement details of the three full-
of force of the compression strut, as shown in Fig. 5(c). scale as-built units constructed. These units were identical to
The New Zealand concrete design standard NZS the interior beam-column joints shown in Fig. 2, except that
3101:19952 and ACI building code, ACI 318-95,3 both deformed bars were used as longitudinal reinforcement,
require that the hooks be bent into the joint core so that the whereas plain round bars would have been used in the proto-
bearing stresses at the inside of the bend are in the direction type structure. It is to be noted that reinforced concrete build-
of and at the end of the diagonal compression strut. ings constructed in New Zealand before the mid-1960s
NZS 3101:1995 and ACI 318-95 also specify quantities of contain plain round longitudinal reinforcement that would
transverse reinforcement required in the joint core for shear lead to poorer bond conditions. Also, although the frames of
reinforcement and confinement. In addition, NZS 3101:1995 the existing structure were two-way, the units tested did not
specifies that the nominal horizontal joint shear stress for all contain beams at right angles to the direction of lateral
joints shall not exceed 0.2fc′ . ACI 318-95 specifies that loading.
nominal horizontal joint shear stress for joints with a beam The longitudinal reinforcement in the columns and beams
entering on only one face of the joint shall not exceed 12√fc′ of the as-built units was from deformed bars with a measured
psi (1.0√fc′ MPa). For fc′ = 30 MPa (4300 psi), this ACI yield strength of fy = 325 MPa (47,100 psi). The transverse
limiting shear stress is 0.18fc′ , which is close to the New reinforcement was from plain round bar with a measured
Zealand limiting value for all joints. yield strength of fyt = 339 MPa (49,200 psi).
The nominal horizontal joint shear stress is given by The normalweight concrete of the as-built units at the
stage of testing had a compressive cylinder strength fc′ of 41
vjh = Vjh/Aj (17) MPa (5950 psi). The units were cast in the horizontal plane.
As shown in Fig. 6, no shear reinforcement was present in
where the beam-column joint core. The ratio of the theoretical flex-
Vjh = joint horizontal shear force defined as shown in ural strength of the column when the axial load was zero to
Fig. 4; and that of the beam was 0.69, calculated using the measured
Aj = effective area of the joint, as defined in the stan- material properties and a strength reduction factor of unity.
dards.2,3 Hence, plastic hinges were expected to form in the columns
For many cases of older buildings, Aj = Ag where Ag = gross during the test. The ratio of beam bar diameter to column
area of the column. depth was db/hc = 24/300 = 1/12.5, which did not satisfy the
The matter of whether the limiting value of vjh should be requirements of NZS 3101:19952 for ductile frames.
expressed as k1√fc′ as in ACI 318 or k2 fc′ as in the New
Zealand standard, where k1 and k2 are empirical constants, is Details of Units O1, R1, R2, and R3
of interest. The use of k1√fc′ is a diagonal tension criterion, One of the as-built units, Unit O1, was tested under simulated
since the tensile strength of the concrete is a function of √fc′ . seismic loading, and then the damaged specimen was retro-
The joint, however, does not necessarily reach its maximum fitted by jacketing the beams, columns and joint with new

ACI Structural Journal/January-February 2000 15


Fig. 6—Dimensions and reinforcement details of as-built
Unit O1. (Note: All dimensions are in mm. 1 mm = 0.039 in.) Fig. 8—Dimensions and reinforcement details of retrofitted
Units R1 and R2. (Note: All dimensions in mm. 1 mm =
0.039 in.)

Fig. 7—Reinforcement cage of as-built Unit O1.


Fig. 9—Reinforcement cage of jacket of Unit R1.
reinforced concrete to become Unit R1, as shown in Fig. 8 and
9. The longitudinal reinforcement in the column jackets was
from deformed bars with a measured yield strength of fy = Another as-built unit, not previously damaged, was retro-
462 MPa (67,000 psi), while those in the beam jackets were fitted in the same manner as Unit R1 to become Unit R2,
deformed bars with a measured yield strength of fy = 330 MPa except that hoops were not placed in the joint core of Unit R2
(43,800 psi). The transverse reinforcement in both the (Fig. 8).
column and beam jackets was from deformed bars with The other nondamaged as-built unit was retrofitted by
measured yield strengths of fyt = 302 and 330 MPa (43,800 jacketing the columns only, to become Unit R3 (Fig. 10 and
and 47,900 psi), respectively. Plain round bars with a 11). The longitudinal and transverse reinforcement in the
column jackets of Unit R3 were deformed bars with a
measured yield strength of fyt = 436 MPa (63,200 psi) were
measured yield strength of fy = 308 MPa (44,700 psi) and fyt
used for the horizontal joint core shear reinforcement in the
= 358 MPa (51,900 psi), respectively.
jacket, as illustrated in Fig. 8.
The normal weight concrete used for the jackets of the
The new joint core hoops consisted of two U-shaped beams and columns of Units R1, R2, and R3 had a compres-
segments of ties. After placing those segments through holes sive cylinder strength of 54, 61, and 42 MPa, (7830, 8850,
drilled horizontally in the beams, both segments were and 6090 psi), respectively, at the time of testing. The jackets
welded in place to form closed hoops. The reinforcement in were cast with the units in the vertical position. Before
the beams, columns, and joint core met the requirements of placing the concrete jackets, the surface of the concrete of
NZS 3101:1995,2 except that in the columns the horizontal the as-built units was lightly roughened, and in the case of
spacing of the tied longitudinal bars in the jacket exceeded the previously damaged Unit O1, all loose concrete was
the code permitted maximum spacing of 200 mm (7.9 in.). removed. The cover concrete of top beam face of the as-built

16 ACI Structural Journal/January-February 2000


Fig. 12—Dimensions and reinforcement details of Units O4
and O5. (Note: All dimensions are in mm. 1 mm = 0.039 in.)

Fig. 10—Dimensions and reinforcement details of retrofitted


(7690 and 4790 psi), respectively, at the time of testing the
Unit R3. (Note: All dimensions in mm. 1 mm = 0.039 in.)
units. The longitudinal reinforcement had measured yield
strengths of 308 MPa (44,700 psi) for the 24 mm (0.94 in.)
diameter bars, 321 MPa (46,500 psi) for the 28 mm (1.10 in.)
diameter bars, and 306 MPa (44,400 psi) for the 32 mm (1.26
in.) diameter bars. The measured yield strength of the trans-
verse reinforcement used in both the columns and beams was
398 MPa (57,700 psi).

EXTERIOR BEAM-COLUMN JOINT TEST UNITS


Test units
Figures 13 and 14 show the reinforcement details of the
two one-way exterior beam-column joint units that were
tested, Units O6 and O7.

Details of Units O6 and O7


Unit O7 was a full-scale replica of the exterior beam-
column joint of an existing reinforced concrete frame
constructed in New Zealand in the 1950s, in which the hooks
at the ends of the beam longitudinal bars were bent out of the
Fig. 11—Reinforcement cage of jacket of Unit R3. joint core. Unit O6 was identical to Unit O7 except that the
hooks at the ends of the beam longitudinal bars were bent
units of Units R1 and R2 was chipped off to place the new into the joint core.
transverse reinforcement in the beam jackets. For both units, deformed longitudinal reinforcement was
The retrofitting of the beams, columns, and joints by used rather than the plain round longitudinal reinforcement
concrete jacketing was found to be very labor intensive. that was typically used in New Zealand in the 1950s. Also,
although the frames of the existing structure were two-way,
Details of Units O4 and O5 the units tested did not contain beams at right angles to the
Units O4 and O5 had bigger column sections than the as- direction of lateral loading.
built Unit O1 and were tested to investigate different The 90 degree hooks at the ends of longitudinal beam bars
anchorage conditions for the longitudinal beam bars in the of Unit O6 had a straight extension at the tail of the hooks of
joint. Units O4 and O5 were identical except for the diame- length 12db as is required by NZS 3101:1995,2 where db is
ters of the longitudinal beam bars passing through the beam- the bar diameter. For Unit 07, the 90 degree hooks at the ends
column joint. These units were designed to form plastic of the longitudinal beam bars had a straight extension at the
hinges in the beams during the test. The ratio of beam bar tail of the hooks of 4db , as was required by the New Zealand
diameter to column depth was db/hc = 1/25 for Unit O4 and standard in the 1950s. A plastic hinge was expected to occur
1/18.8 for Unit O5. As shown in Fig. 12, Units O4 and O5 in the beam during seismic loading, and hence, the anchorage
lacked shear reinforcement in the joint core. details for the beam longitudinal reinforcement should ideally
The normal weight concrete used for Units O4 and O5 had be able to sustain several cycles of yielding of that reinforce-
measured compressive cylinder strengths of 53 and 33 MPa ment. Units O6 and O7, however, contained only small quan-

ACI Structural Journal/January-February 2000 17


Fig. 15—Loading frame used to apply simulated seismic
loading to units. (Note: All dimensions in mm. 1 mm =
0.039 in.)

Fig. 13—Dimensions and reinforcement details of Units O6


and O7. (Note: All dimensions are in mm. 1 mm = 0.039 in.)

Fig. 16—Test setup for exterior beam-column joint used.


(Note: All dimensions in mm. 1 mm = 0.039 in.)

METHOD OF LOADING
The beam-column joint units were subjected to simulated
seismic loading using the loading system shown in Fig. 15
for interior test units and Fig. 16 for the exterior test units,
respectively. The ends of the members of the subassemblage
coincided with the midspan and midheight points of the
building frame investigated. Cyclic horizontal loading was
applied to the top end of the columns of the test units using a
double acting hydraulic jack. For Unit O1, which was
expected to develop plastic hinges in the columns, the pinned
connection at the bottom of the column was modified so that
the column was held against lateral displacement there, but
the column was allowed to rotate and elongate. The ends of
the beams were connected by pin-ended steel members to the
reaction floor, so that the ends of the beams were free to
rotate and to translate horizontally but not vertically. To
simulate the negative moment in the beams at the column
faces due to gravity loading, the end of the bottom column of
the as-built unit was lifted up, before the cyclic horizontal
Fig. 14—Reinforcement in exterior beam-column joint units: loading was applied, by an appropriate amount using a center
(a) Unit O6; and (b) Unit O7. hole jack.
No axial load was applied to the columns during the tests
(N = 0), since axial compressive load applied across the joint
tities of shear reinforcement in the joint core, beam, and core would make conditions in the joint core more favorable.
columns, as in the prototype building shown in Fig. 2. In all tests, two cycles of horizontal loading to ±0.5Hi and
The normalweight concrete used for Units O6 and O7 had ±0.75Hi were initially applied, where Hi is the lateral load at
measured compressive cylinder strengths of 34 and 31 MPa the top of the column associated with the theoretical flexural
(4930 and 4500 psi), respectively, at the time of testing the strength being reached at the critical sections of the beams or
units. The measured yield strength of the longitudinal rein- columns, whichever is least, calculated using the conven-
forcement was 308 MPa (44,700 psi) and of the transverse tional compressive stress block for the concrete with an
reinforcement was 398 MPa (57,710 psi). extreme fiber concrete compressive strain of 0.003 and the

18 ACI Structural Journal/January-February 2000


Fig. 17—Horizontal column force versus horizontal Fig. 19—Horizontal column force versus horizontal
displacement at top of column relationship for as-built displacement at top of column relationship for retrofitted
Unit O1. (1 kN = 0.225 kips; 1 mm = 0.039 in.) Unit R1 (original specimen was damaged before retro-
fitted). (Note: 1 kN = 0.225 kips; 1 mm = 0.039 in.)

values and taking into account shear deformations of the


members9 and the shear deformation of the joint core. It was
assumed that the shear deformation of the joint core contrib-
uted 20% of the total displacement, as has been found previ-
ously.10 During the loading cycles, bond splitting cracks
occurred along the longitudinal beam reinforcement in the
joint core, and diagonal tension cracking developed in the
joint core (Fig. 18). As shown in Fig. 17, the flexural strength
of the columns was barely reached. The deformations due to
shear and bond slip in the joint core became very significant,
and pinching and severe degradation of stiffness were
observed in the hysteresis loops.

Units R1, R2, and R3


Fig. 18—Observed cracking of as-built Unit O1 at first Figures 19 and 20 show the measured hysteresis loops for
load cycle to 2% story drift. horizontal column force versus horizontal displacement at
the top of the column for the retrofitted Units R1 and R2. The
increase in stiffness, strength, and ductility of the retrofitted
measured material strengths, and assuming a strength reduc- units can be observed by comparing Fig. 17 with Fig. 19 and
tion factor of unity. The yield displacements Δy for all test 20. The measured hysteresis loops for Unit R1, which was
units were calculated by extrapolating the measured hori- damaged before retrofitting, demonstrated stable and ductile
zontal displacement at 0.75Hi , linearly to Hi. The applied response with plastic hinges forming in the beams, although
cyclic loading in the inelastic range was displacement some pinching was observed. Units R1 and R2 reached their
controlled. The test units were subjected to two cycles of theoretical strengths based on the theoretical flexural
loading to μ of ±1, ±2, ±4, ±6, and ±8, as far as possible, where strengths of the retrofitted beams, calculated using the
μ is the displacement ductility factor defined as Δ/Δy , where Δ measured material strengths and assuming a strength reduc-
is the horizontal displacement at the top of the test unit. tion factor of unity. Only a little reduction in strength was
evident up to the end of testing. The hysteresis loops shown
TEST RESULTS OF INTERIOR BEAM-COLUMN in Fig. 20 for Unit R2, which was not previously damaged,
JOINT TEST UNITS are quite similar to those observed for Unit R1, although
Unit O1 diagonal cracks had developed in the joint core earlier for
The measured hysteresis loops for horizontal column force Unit R1 than for Unit R2 due to the previous damage to the
versus horizontal displacement at the top of column, and the as-built Unit O1. This suggests that the previous damage to
crack pattern at a story drift of 2%, for Unit O1 are shown in the as-built unit had little effect on the response of the unit
Fig. 17 and 18. Also shown in Fig. 17 is the theoretical hori- when retrofitted. Although diagonal tension cracks devel-
zontal load strength of the unit Hi , based on the flexural oped in the jacket of the joint core of the retrofitted Unit R2,
strengths of the columns, calculated using the methods of this cracking evidently had no detrimental effect on the
NZS 31012 and ACI 318-953 using the measured material seismic performance of the unit, in spite of the fact that hori-
strengths and assuming a strength reduction factor φ of 1.0. zontal shear reinforcement was not placed in the jacket of the
In addition, the theoretical stiffness of the beam-column unit joint core. This is mainly due to the reduction in the hori-
is shown, calculated assuming an effective moment of inertia zontal shear stress in the joint core as a result of the enlarge-
of the beams and columns of 0.5 of the gross (uncracked) ment of the column area.

ACI Structural Journal/January-February 2000 19


Fig. 20—Horizontal column force versus horizontal Fig. 22—Observed cracking of retrofitted Unit R3 at end of
displacement at top of column relationship for retrofitted test at second load cycle to μ = –8.
Unit R2 (original specimen was not damaged before retro-
fitted). (Note: 1 kN = 0.225 kips; 1 mm = 0.039 in.)

Fig. 23—Horizontal column force versus horizontal displace-


Fig. 21—Horizontal column force versus horizontal ment at top of column relationship for Unit O4. (Note: 1 kN =
displacement at top of column relationship for retrofitted 0.225 kips; 1 mm = 0.039 in.)
Unit R3 (original specimen was not damaged before retro-
fitted). (Note: 1 kN = 0.225 kips; 1 mm = 0.039 in.) the first loading cycle to a displacement ductility factor of 4.
The test was temporarily terminated after that loading cycle,
Figures 21 and 22 show the measured hysteresis loops for and the beams were retrofitted using external vertical stir-
horizontal column force versus horizontal displacement at the rups that were tightened by nuts on threaded portions to
top of the column, and the final crack pattern, for Unit R3, apply vertical clamping forces to the beams (Fig. 25 and 26).
which was not damaged before retrofitting the columns alone. The units were then retested to obtain further information
As can be seen in Fig. 22, after plastic hinging developed in about the seismic behavior of the joints. In Fig. 23 and 24,
the beams at the critical regions, the diagonal tension cracks the response before beam retrofit is shown by dotted lines,
extended and opened wide in the beams during negative and that after beam retrofit by solid lines. Also shown are the
moment, causing beam shear failure at a storey drift of theoretical horizontal load strengths Hi based on the flexural
approximately 0.7%. Figure 21 shows that the strength of Unit strength of the beams calculated using the measured material
R3 reduced significantly after a displacement ductility factor strengths and assuming a strength reduction factor of unity.
of 4 was reached, which was the stage of initiation of the beam Figures 25 and 26 show the observed cracking of Units O4
shear failure. The strength of the beams then degraded rapidly and O5 at the end of the tests.
as the displacement ductility factor imposed on the test spec- For Unit O4, after diagonal tension cracking occurred in
imen increased, mainly due to the reduced shear carried by the the joint core, the flexural strengths of the beams were
concrete mechanisms, particularly by aggregate interlock. reached in the loading cycle to a displacement ductility
factor μ of 2, as shown in Fig. 23. In the loading cycle to μ
Units O4 and O5 of 6, the diagonal tension cracks in the joint core extended
The measured hysteresis loops for horizontal column force and widened in conjunction with bond splitting cracks along
versus horizontal displacement at the top of the column for the column corner bars, as seen in Fig. 25. Severe degrada-
Units O4 and O5 are shown in Fig. 23 and 24, respectively. tion of strength and pinching were observed in the hysteresis
For both units, shear failure of the beams commenced during loops at this stage.

20 ACI Structural Journal/January-February 2000


Fig. 26—Observed cracking of Unit O5 at end of test at
Fig. 24—Horizontal column force versus horizontal displace- second load cycle to μ = –8.
ment at top of column relationship for Unit O5. (Note: 1 kN =
0.225 kips; 1 mm = 0.039 in.)

Fig. 27—Horizontal column force versus horizontal


displacement at top of column relationship measured for
Unit O6. (Note: 1 kN = 0.225 kips; 1 mm = 0.039 in.)
Fig. 25—Observed cracking of Unit O4 at end of test at
second load cycle to μ = –8.

For Unit O5, the measured hysteresis loops for horizontal


column force versus horizontal displacement at the top of the
column, shown in Fig. 24, and the observed cracking, shown
in Fig. 26, are quite similar to those for Unit O4, in spite of
the fact that the bond conditions along the beam bars passing
through the joint core were more severe for Unit O5 due to
the larger beam bar diameter-to-column depth ratio used.
Nevertheless, the degradation of strength was a little more
severe in the case of Unit O5, which can be attributed to the
smaller concrete compressive strength measured for Unit O5
as well as to the higher bond stresses.

TEST RESULTS OF EXTERIOR BEAM-COLUMN


JOINT TEST UNITS Fig. 28—Horizontal column force versus horizontal
Figures 27 and 28 show the measured hysteresis loops for displacement at top of column relationship measured for
the horizontal force applied to the top of the column versus Unit O7. (Note: 1 kN = 0.225 kips; 1 mm = 0.039 in.)
the horizontal displacement at the top of column for Units
O6 and O7, respectively. The observed cracking of the two
units near the end of testing is shown in Fig. 29. The core, demonstrated stable and ductile response with the
measured stiffness of the units compared with the calculated plastic hinge forming in the beam, although negligible shear
initial stiffness after cracking is shown in Fig. 27 and 28. reinforcement was present in the joint core and the quantity
of column hoops and beam stirrups was small (Fig. 27). The
Units O6 and O7 theoretical flexural strength of the beam was reached during
The measured hysteresis loops for Unit O6, in which the the test. The measured stiffness in the elastic range after
hooks at the ends of the beam bars were bent into the joint cracking was generally lower than calculated.

ACI Structural Journal/January-February 2000 21


loading. The joint core of Unit O7 failed in shear shortly after
the development of diagonal tension cracking there.

DISCUSSION OF TEST RESULTS


Units O1, R1, R2, and R3
The test on Unit O1 confirmed that the performance of the
interior beam-column joint region of the as-built frame
would be poor in a major earthquake, mainly due to the lack
of transverse reinforcement and to the inadequate anchorage
of longitudinal beam bars in the joint core. The maximum
horizontal nominal joint shear stress calculated was 0.095fc′ ,
which can also be expressed as 0.61√fc′ MPa (7.32√fc′ psi).
The diameter of longitudinal beam bar to column depth ratio
was 1/12.5. The joint showed significant diagonal tension
cracking (Fig. 18), and the degradation of stiffness shown in
Fig. 17 was due to that cracking in the joint and to bond slip
of the longitudinal beam bars through the joint.
The ratio of the theoretical flexural strength of the column,
when the axial load was zero, to that of the beam was 0.69
for Unit O1, and hence, plastic hinges were expected to form
in the columns during the test. The columns, however, did
not reach their theoretical flexural strength in one direction
of loading because shear failure of the joint core occurred.
The increase in flexibility of the unit due to bond slip and
(a) shear deformations became very large.
For Units R1 and R2, which were retrofitted by jacketing
the beams and columns, the maximum horizontal nominal
shear stress in the enlarged joint calculated from Vjh/Ag were
0.29√fc′ * and 0.27√fc′ * MPa (3.5√fc′ * and 3.2√fc′ * psi),
respectively, where fc′ * is the weighted average compressive
cylinder strength of the two concretes (existing and added)
of the joint core. This joint shear stress was evidently low
enough not to result in joint shear failure, since the joints of
Units R1 and R2 behaved satisfactorily, and almost simi-
larly, with ductile plastic hinge behavior in the beams in spite
of the fact that Unit R2 had no joint core hoops.
For Unit R3, which was retrofitted by jacketing the
column only, the maximum horizontal nominal shear stress
in the enlarged joint, calculated from Vjh/Ag , was 0.23√fc′ *
MPa (2.8√fc′ * psi), where fc′ * is the weighted average
compressive strength of the two concretes of the joint. The
joint behavior was satisfactory despite the absence of joint
core hoops, but the unit did not behave in a ductile manner
because shear failure of the beams occurred. The shear rein-
forcement in the beam was nominal, capable of carrying by
truss action, assuming 45 degree diagonal tension cracks,
less than 20% of the shear force at the flexural strength of the
beam. Shear failure in the beams occurred when, with beam
negative moment, the maximum nominal shear stress in the
beams reached approximately 0.18√fc′ MPa (2.2√fc′ psi). With
beam positive moment, the maximum nominal shear stress in
(b) the beams was approximately 0.11√fc′ MPa (1.3√fc′ psi) and
shear failure for that direction of shear force did not occur.
Fig. 29—Observed cracking of units near end of testing at The success of retrofitting the joint cores of Units R2 and
displacement ductility factor of 8: (a) Unit O6; and (b) Unit O7. R3 by increasing the column section and not placing hoops
around the longitudinal column bars in the joint core should
The measured hysteresis loops obtained for Unit O7, in be treated with caution. The axial compressive load on the
which the beam bar hooks were not bent into the joint core (the columns during the tests was zero. With an axial compres-
ends of the beam bar hooks of the top bars were bent up and sive load present, buckling of the longitudinal column bars
the ends of the beam bar hooks of the bottom bars were bent in the concrete jacket surrounding the joint core would have
down) were quite different from those observed for Unit O6 been more likely. Hence, some hoops should always be
(Fig. 27 and 28). The measured stiffness in the elastic range placed in the jacket of the joint core around the longitudinal
after cracking was generally lower than calculated. The flex- column bars. NZS 3101:19952 requires such hoop sets in the
ural strength of the beam was not reached in either direction of joint core to have a vertical spacing not exceeding 10 times

22 ACI Structural Journal/January-February 2000


the diameter of the longitudinal column bar or 200 mm concrete.11,12 When the joint shear stress is large, and trans-
(7.9 in.), whichever is least. verse reinforcement is not present in the joint core, signifi-
cant diagonal tension cracking in both directions will occur
Units O4 and O5 in the joint core. Note that Fig. 3(b) shows only the diagonal
For Units O4 and O5, the maximum nominal horizontal tension cracking in one direction. Under reversed cyclic
joint shear stresses were 0.47√fc′ and 0.61√fc′ MPa (5.6√fc′ loading in the inelastic range, as a consequence of earth-
and 7.35√fc′ psi), respectively. The test results from Units O4 quake forces, these diagonal tension cracks will become
and O5 indicated that, after the plastic hinges had developed large, and disintegration of the concrete will begin because
in the beams, the performance of the interior beam-column of the repeated opening and closing of the cracks along
joints deteriorated due to extensive diagonal tension cracking which shear sliding movements occur. This will be associ-
in the joint core. However, for such interior joints without ated with a drastic volumetric increase of the joint core
shear reinforcement in the joint core, where the beam bar concrete unless adequate confinement is provided (Fig. 25
diameter to column depth ratio ranged from 1/25 to 1/18.8, the and 26). These phenomena will reduce the diagonal
seismic behavior was not significantly affected by the bond compressive strength of the concrete of the joint core.
conditions along the beam bars passing through the joint. Hence, it is evident that after diagonal tension cracking of
The db /hc ratio of 25 for Unit O4 satisfied the bond the core of interior beam-column joints without shear rein-
requirements of NZS 3101:1995,2 but the db /hc ratio of 18.8 forcement, the eventual failure of the joint core will gener-
of Unit O5 did not. Although bar slip commenced at a lower ally occur as a result of compression failure of the diagonal
displacement ductility factor for Unit O5, the horizontal compression strut. That failure may occur at a seismic force
column load versus horizontal displacement hysteresis loops higher than required to cause diagonal tension cracking of
for the two units were almost identical for displacements up the joint core, as is observed from the test results of the six
to a displacement ductility factor of 6. units shown in Fig. 17, 19, 20, 21, 23, and 24. Diagonal
compression failure will occur regardless of the degree of
Units O6 and O7 bond deterioration along the bars passing through the joint
For Unit O6, the maximum nominal horizontal joint shear core. If the bond is poor, the diagonal compression strut
stress vjh , given by Eq. (17) with Aj = Ag and with Vjh calculated mechanism will transfer the joint shear since the truss mech-
as shown in Fig. 4, was 0.053fc′ , which evidently was not high anism will not function (Fig. 3(d)) without bond forces. If the
enough to cause joint shear failure. This maximum value of vjh bond is good, the truss mechanism cannot transfer the joint
can also be expressed as 0.31√fc′ MPa (3.7√fc′ psi). Only a very shear without shear reinforcement in the joint core, and the
small reduction in strength was measured during the loading diagonal tension cracking in the joint core will lead to the
cycles up to a displacement ductility factor μ of 10. In the final joint shear being carried mainly by the diagonal compression
stages of testing, shear failure occurred in the beam (Fig. 29(a)). strut mechanism. Bond forces will be transferred to the diag-
At the stage of beam shear failure, the maximum nominal shear onal compression strut over the width of the compression
stress in the beam was 0.14√fc′ MPa (1.7√fc′ psi). zone at the end of the strut.
For Unit O7, the maximum horizontal joint shear stress vjh To obtain the nominal joint shear stress at the stage of joint
was 0.045f c′ for one direction of lateral loading and failure, the test results of a number of other investigators
0.038fc′ for the other direction of lateral loading. These two
were analyzed. Figure 30 plots the relationship between the
maximum values of vjh can also be expressed as 0.25√fc′ and
maximum nominal horizontal joint shear stress vjh and the
0.21√fc′ MPa (3.0√fc′ and 2.5√fc′ psi), respectively. The
concrete compressive cylinder strength fc′ , obtained from the
maximum nominal shear stress reached in the beam was
test results of six interior beam-column joint units without
0.10√fc′ MPa (1.2√fc′ psi), which was not great enough to
joint shear reinforcement, as tested by Hanson and Conner,13
cause shear failure of the beam during the test.
Bessho et al.,14 Blaikie,15 Pessiki et al.,16 and Kawachi et
The diagonal tension cracks in the joint core widened during
al.17 The nominal horizontal joint shear stress was defined
the test and connected to the bond splitting cracks along the
by Eq. (9). The six units analyzed covered a wide range of
column outer bars as shown in Fig. 29(b). It is evident from
concrete strengths. The maximum nominal horizontal joint
Fig. 29(b), and schematically in Fig. 5(b) for one direction of
shear stresses of all the units analyzed were reached before
loading, that the diagonal compression strut in the joint core
did not effectively engage the beam hook, but rather pushed the theoretical flexural strengths of the beams were attained,
against the longitudinal column reinforcing steel, resulting in except for the unit of Hanson and Conner.13 Although the
a wide splitting crack along that column reinforcement. Had available test data is quite limited, the maximum nominal
the column hoops above and below the joint core been more horizontal joint shear stress was found to increase almost in
adequate, it is possible that the diagonal compression strut direct proportion to the compressive cylinder strength of
could have been equilibrated by engaging the column hoops concrete (Fig. 30). This indicates that for these test units, the
outside the depth of the beam, as shown schematically in Fig. maximum nominal horizontal joint shear stress was strongly
5(c) for one direction of bending moment. The quantity of related to the stage of diagonal compression failure of the
column hoops, however, was very small. joint core concrete. Based on this limited test data, the
A full analysis of the test results may be seen elsewhere.8 following equation can be used to give the lower bound for
the test results.
SHEAR STRENGTH OF INTERIOR BEAM-COLUMN
JOINTS WITHOUT SHEAR REINFORCEMENT v jh = 0.17f c′ (18)
Joint shear strength when governed by diagonal
compression failure For designers, it may be more convenient to express the
The presence of diagonal tensile strains in the joint core maximum nominal horizontal joint shear stress in terms of
will reduce the diagonal compressive strength of the √fc′ . In such a case, Eq. (18) can be replaced by the following

ACI Structural Journal/January-February 2000 23


Fig. 30—Measured relationship between joint horizontal Fig. 32—Model for degradation of available vjh/f c′ with
shear stress vjh and concrete compressive strength f c′ . (Note: imposed displacement ductility factor μ.
1 MPa = 145 psi.)

Fig. 31—Measured relationship between vjh/f c′ and Fig. 33—Model for degradation of available k = vjh/√f c′
displacement ductility factor μ. with imposed curvature ductility factor φu/φy.

more conservative equation for when the concrete compressive Based on the previously explained test data, a model
strength is greater than 30 MPa (4350 psi) (Fig. 30). shown in Fig. 32 is proposed for the shear strength degradation
of interior beam-column joints without shear reinforcement.
v jn = 1.0 f c′ MPa (12 f c′ psi) (19) The test data is shown by solid circles and linear interpolation
was used between the test data. The proposed model is based
on the results from beam-column joint specimens tested
Degradation of joint shear strength without axial load acting on the columns. The effect of axial
Of particular interest is the deterioration of the shear load on the column on the degradation of the joint strength
strength of beam-column joints under cyclic forces. The needs to be investigated in future research.
diagonal tension cracking of the joint core in alternative Designers have become accustomed to specifying shear
directions during seismic loading will reduce the diagonal strength in terms of √fc′ rather than fc′ . Figure 33 shows a
compressive strength of the concrete. Therefore, the joint shear strength degradation model proposed by Park6 for the
shear strength may degrade as the displacement ductility assessment of interior beam-column joints of one-way
factor imposed cyclically on the structure increases. frames. The available joint horizontal shear stress vjh is spec-
Figure 31 plots the relationship between the ratio of the ified in terms of √fc′ in Fig. 33, and the imposed ductility is
nominal horizontal joint shear stress to the concrete defined in terms of the curvature ductility factor φu/φy in the
compressive cylinder strength vjh /fc′ and the displacement beam plastic hinges at the faces of the column.
ductility factor μ obtained for the units tested in this study
and for Blaikie’s unit.15 The seismic behavior of these units CONCLUSIONS
without shear reinforcement can be classified as follows. At 1. The test results indicate that the seismic performance of
a joint shear stress vjh of approximately 0.17fc′ , joint shear typical interior beam-column joints of pre-1970s designed
failure initiated at a displacement ductility factor μ of 1, reinforced concrete moment-resisting frames without trans-
followed by rapid strength degradation as shown in Fig. 31. verse reinforcement in the beam-column joint cores would
When the joint shear stress vjh was in the range 0.11fc′ to be poor in a severe earthquake if the nominal horizontal joint
0.07fc′ , joint shear failure initiated during the loading to μ of shear stress exceeds approximately 0.17fc′ ;
4 or 6, and the joint strength degraded moderately. When the 2. If the frame responds in the post-elastic range, the avail-
joint shear stress vjh, was less than 0.05fc′ , the joint did not able shear strength of interior beam-column joint cores
fail up to a displacement ductility factor μ of at least 8, and without transverse reinforcement decreases with an increase
the joint behavior did not affect the ductility of the adjacent in the imposed ductility of the adjacent beam plastic hinge
members in which flexural plastic hinges had developed. regions. At an imposed displacement ductility factor of 6 for

24 ACI Structural Journal/January-February 2000


the interior beam-column joint units tested, failure of the db = diameter of longitudinal bar in beam
joint core occurred if the nominal horizontal joint shear f c′ = concrete compressive cylinder strength
fy = yield strength of longitudinal reinforcing steel
stress exceeded approximately 0.07fc′ ; fyt = yield strength of transverse reinforcing steel
3. The jacketing of beam-column joints with new rein- Hi = theoretical horizontal load strength of beam-column joint
forced concrete was identified as a useful technique for unit, calculated from flexural strength of members using
enhancing the stiffness, strength, and ductility of poorly measured material strengths and assuming strength reduc-
detailed as-built beam-column joint regions. The technique, tion factor φ of unity
jd1, jd2 = lever arm between tension steel force and resultant compres-
however, is very labor-intensive and the placement of the sive forces in Beams 1 and 2, respectively
new joint core hoops, passing through holes to be drilled in k = coefficient in joint shear strength equation
the existing beams, is difficult; N = axial compressive load on column
4. Based on the limited test data, it was found that, even T1, T2 = tensile forces in tension reinforcement in Beams 1 and 2,
when no joint core hoops are present in existing one-way inte- respectively
vjh = nominal horizontal shear stress in beam-column joint core
rior beam-column joints, no new joint core hoops are required
Vjh, Vjv = horizontal and vertical shear forces acting on beam-column
for shear reinforcement if the existing column is enlarged by joint core, respectively.
jacketing so that the horizontal nominal shear stress in the Vc′ = shear force acting in column at face of beam-column joint core
joint core is reduced to less than 0.07f c′ . This finding was for Δ = horizontal displacement
joints with no axial load on the columns. When axial compres- Δy = horizontal displacement at first yield
sive load is present on columns, a greater horizontal joint shear μ = Δ/Δy
φu = ultimate curvature
stress would be tolerable, but some joint core hoops would be φy = curvature at first yield
necessary to prevent column bar buckling;
5. A model for the available horizontal nominal shear stress in REFERENCES
a joint core versus the imposed curvature ductility factor at the 1. General Structural Design and Design Loadings for Buildings, NZS
plastic hinges in the beams adjacent to the joint core is proposed 4203:1992, Standards New Zealand, Wellington, 1992.
based on the above findings, which enables the shear strength of 2. The Design of Concrete Structures, NZS 3101:1995, Standards New
Zealand, Wellington, 1995.
interior beam-column joints of one-way frames without trans- 3. ACI Committee 318, “Building Code Requirements for Structural
verse reinforcement in the joint core to be assessed; Concrete (ACI 318-95) and Commentary,” American Concrete Institute,
6. The seismic performance of the one-way exterior beam- Farmington Hills, Mich., 369 pp.
column joints with very little transverse reinforcement in the 4. Park, R. et al., “The Hyogo-Ken Nanbu Earthquake (The Great
Hanshin Earthquake) of 17 January 1995. Report of the NZNSEE Recon-
beam-column joint core and adjacent members, and with naissance Team,” Bulletin of the New Zealand National Society for Earth-
moderate joint shear stresses, was significantly influenced quake Engineering, V. 28, No. 1, Mar. 1995, pp. 1-98.
by the directions in which the ends of the beam bar hooks in 5. Priestley, M. J. N., and Calvi, G. M., “Towards a Capacity Design
the joint core were bent. The performance under seismic Assessment Procedure for Reinforced Concrete Frames,” Earthquake
Spectra, V. 7, No. 3, 1991, pp. 415-437.
loading was significantly improved when the ends of the 6. Park, R., “A Static Force-Based Procedure for the Seismic Assess-
hooks of the top and bottom longitudinal beam bars were ment of Existing Reinforced Concrete Moment Resisting Frames,” Bulletin
bent into the joint core as in current practice. Exterior beam- of the New Zealand National Society for Earthquake Engineering, V. 30,
No. 3, Sept. 1997, pp. 213-226.
column joints of early frames in which the ends of the hooks 7. Priestley, M. J. N., “Displacement-Based Seismic Assessment of
of the beam bars were bent out of the joint core are likely to Existing Reinforced Concrete Buildings,” Bulletin of the New Zealand
behave unsatisfactorily during a severe earthquake; National Society for Earthquake Engineering, V. 29, No. 4, Dec. 1996,
7. The exterior beam-column joint tested in which the ends pp. 256-272.
8. Hakuto, S.; Park, R.; and Tanaka, H., “Retrofitting of Reinforced
of the hooks of the beam longitudinal bars were bent into the Concrete Moment-Resisting Frames,” Research Report 95-4, Department
joint core was able to withstand a nominal joint horizontal of Civil Engineering, University of Canterbury, New Zealand, 1995.
shear stress of 0.053fc′ when plastic hinging occurred in the 9. Park, R., and Paulay, T., Reinforced Concrete Structures, John Wiley,
New York, 1975.
beam. This nominal horizontal joint shear stress can also be 10. Cheung, P. C.; Paulay, T.; and Park, R., “Seismic Design of Rein-
expressed as 0.31√fc′ MPa (3.7√fc′ psi). Very little degrada- forced Concrete Beam-Column Joints with Floor Slab,” Research Report
tion of flexural and shear strength occurred up to an imposed 91-4, Department of Civil Engineering, University of Canterbury, New
displacement ductility factor of approximately 10; and Zealand, 1991.
11. Collins, M. P., and Mitchell, D., “Shear and Torsion Design of
8. The other exterior beam-column joint tested, which was Prestressed and Nonprestressed Concrete Beams,” Journal of the
identical except that the ends of the hooks of the beam longitu- Prestressed Concrete Institute, V. 25, No. 5, 1980, pp. 32-101.
dinal bars were bent out of the joint core, failed in shear when a 12. Stevens, N. B.; Uzumeri, S. M.; and Collins, M. P., “Reinforced
maximum nominal joint horizontal shear stress of 0.045fc′ was Concrete Subjected to Reversed Cyclic Shear—Experiments and Constitu-
tive Model,” ACI Structural Journal, V. 88, No. 2, 1991, pp. 135-146.
reached. This nominal horizontal joint shear stress can also be 13. Hanson, N. H., and Conner, H. W., “Tests of Reinforced Concrete
expressed as 0.25√fc′ MPa (3.0√fc′ psi). The flexural strength of Beam-Column Joints under Simulated Seismic Loading,” Portland Cement
the beam was not reached in either direction of loading. Association Research and Development, Bulletin RD 012, 1972, 11 pp.
14. Bessho, S.; Okamoto, K.; and Hatamoto, H., “Lateral Loading Behav-
iour of Reinforced Concrete Wide Beam to Column Subassemblages,” Trans-
ACKNOWLEDGMENTS actions of Architectural Institute of Japan, 1989, pp. 481-482. (in Japanese)
The financial assistance provided by the Earthquake Commission of New 15. Blaikie, E. L., “Behavior of Unreinforced and Lightly Reinforced
Zealand (Projects No. 91/15 and 93/102) is gratefully acknowledged. The Concrete Beam-Column Joints,” Proceedings of Pacific Concrete Confer-
Tokyu Construction Co. of Japan is also thanked for their financial support. ence, V. 1, Auckland, 1988, pp. 181-193.
16. Pessiki, S. P.; Conley, C. H.; Gergely, P.; and White, R. N., “Seismic
Behavior of Lightly Reinforced Concrete Column and Beam-Column Joint
NOTATION Details,” Technical Report NCEER 90-0014, National Center for Earth-
Ag = gross area of column quake Engineering Research, State University of New York at Buffalo,
bc = width of column N.Y., 1990.
bj = effective width of joint 17. Kawachi, T.; Jinno, Y.; Kadoriku, J.; and Kumagai, H., “An Experi-
bw = width of beam web mental Study on Behavior of Reinforced Concrete Interior Beam-Column
Cc1,Cc2 = compressive forces in concrete at faces of beam-column Joints Using High-Strength Materials,” Shimizu Technical Report, V. 55,
joint in Beams 1 and 2, respectively 1992, pp. 41-50. (in Japanese)

ACI Structural Journal/January-February 2000 25

Das könnte Ihnen auch gefallen