Beruflich Dokumente
Kultur Dokumente
AAAC - ASTM - B
All Aluminium Alloy Conductor
APPLICATION STANDARDS
AAAC is used as a bare overhead conductor for power ASTM B399, ASTM B231, TS IEC 1089, DIN 48201, BS 215,
transmission and distribution lines, on aerial circuits that UNE 21.018
require a larger mechanical resistance than AAC, and a better
corrosion resistance than ACSR. The sag characteristics and
the strength-to-weight ratio of AAAC is better than both
AAC / ACSR.
ISO/IEC
17025
Accredited
Testing
Laboratory
REGULATORY COMPLIANCE
This cable meets the requirements of the RoHS Directive 2011/65/EU. RoHS
compliance has been tested and confirmed by The Cable Lab® as meeting the
requirements of the BSI RoHS Trusted KitemarkTM.
RoHS Trusted
KITEMARK™
KM 634267
DIMENSIONS
ASTM Sizes
CODE SIZE STRANDING DIAMETER NOMINAL WEIGHT RATED RESISTANCE CURRENT SIZE ACSR WITH
KCM inches CROSS lbs/1000ft STRENGTH ohms/1000ft RATING EQUIV.DIAM.
SECTIONAL lbs Amps STRANDING
AREA Alt/Stl
Individual Total DC AC
sq ins
wires 20ºC 75ºC
AKRON 30.58 7 0.0661 0.198 0.024 28.7 1110 0.659 0.785 107 6 6\1
ALTON 48.69 7 0.0834 0.25 0.0382 45.7 1760 0.414 0.493 143 4 6\1
AMES 77.47 7 0.1052 0.316 0.0608 72.7 2800 0.26 0.31 191 2 6\1
AZUSA 123.3 7 0.1327 0.398 0.0968 115.7 4460 0.163 0.195 256 1/0 6\1
ANAHEIM 155.4 7 0.149 0.447 0.1221 145.9 5390 0.13 0.154 296 2/0 6\1
AMHERST 195.7 7 0.1672 0.502 0.1537 183.7 6790 0.103 0.1230 342 3/0 6\1
ALLIANCE 246.9 7 0.1878 0.563 0.1939 231.8 8560 0.0816 0.0973 395 4/0 6\1
BUTTE 312.8 19 0.1283 0.642 0.2456 293.6 11000 0.0644 0.0769 460 266.8 26\7
CANTON 394.5 19 0.1441 0.721 0.3098 370.3 13300 0.0511 0.061 532 336.4 26\7
CAIRO 465.4 19 0.1565 0.783 0.3655 436.9 15600 0.0433 0.0518 590 397.5 26\7
DARIEN 559.5 19 0.1716 0.858 0.4394 525.2 18800 0.036 0.0431 663 477 2617
ELGIN 652.4 19 0.1853 0.927 0.5124 612.4 21900 0.0309 0.0371 729 556.5 2617
FLINT 740.8 37 0.1415 0.991 0.5818 695.5 24400 0.0272 0.0327 790 636 26\7
GREELY 927.2 37 0.1583 1.108 0.7282 870.4 30500 0.0217 0.0263 908 795 26\7
1. Resistance is calculated using ASTM standard increments of stranding, and metal conductivity of 52.5% IACS. AC resistance at 60 Hz.
2. Current ratings are based on 75ºC conductor temperature, 250ºC ambient, 2 ft/s wind, 96/watts/sq.foot sun, 0.5 coefficients of emissivity and absorption.
ASTM Sizes
CONDUCTOR AREA NO. AND DIAMETER OVERALL DIAMETER LINEAR LB MAXIMUM DC
SIZE mm² OF WIRES CONDUCTOR WEIGHT STRENGTH RESISTANCE AT 20ºC
c mil lb ohm/km
inch mm inch mm kg/km daN
AKRON 30.58 15.5 7 1.679 5.04 42.7 503 2.16 2.57 107 13.3 6/1
ALTON 48.69 24.67 7 2.118 6.36 68 798 1.36 1.62 143 21.15 6/1
AMES 77.47 39.25 7 2.672 8.02 108.2 1270 0.853 1.02 191 33.63 6/1
AZUSA 123.3 62.48 7 3.371 10.11 172.2 2023 0.536 0.639 256 53.31 6/1
ANAHEIM 155.4 78.74 7 3.785 11.35 217.1 2445 0.425 0.509 296 67.44 6/1
AMHERST 195.7 99.16 7 4.247 12.74 273.3 3080 0.338 0.403 342 85.03 6/1
ALLIANCE 246.9 125.1 7 4.77 14.31 344.9 3883 0.268 0.319 395 107.22 6/1
BUTTE 312.8 158.5 19 3.259 16.29 436.9 4989 0.211 0.252 460 135.19 26/7
CANTON 394.5 199.9 19 3.66 18.3 551.1 6033 0.168 0.2 532 170.46 26/7
CAIRO 465.4 235.8 19 3.975 19.88 650 7076 0.142 0.17 590 201.42 26/7
DARIEN 559.5 283.5 19 4.359 21.79 781.5 8527 0.118 0.142 663 241.7 26/7
ELGIN 652.4 330.6 19 4.707 23.53 911.3 9934 0.101 0.122 729 281.98 26/7
FLINT 740.8 375.4 37 3.594 25.16 1035 11068 0.0892 0.107 790 322.27 26/7
GREELY 927.2 469.8 37 4.021 28.15 1295 13834 0.0713 0.0863 908 402.83 26/7
British Sizes
CODE N RATED STRENGTH1 LBS FORCE MAXIMUM DC RESISTANCE AT 20ºC2 CURRENT RATING3
kgF
ohms/km ohms/1000ft Temperate Tropical
Amps Amps
1. Rated strengths are calculated by ASTM methods and converted to metric units after rounding.
2. Resistance is calculated using ASTM standard increments of stranding, and metal conductivity of 52.5% IACS.
3. Current ratings are based on 50 Hz AC, 75ºC conductor temperature, and 0.61 m/s (2 ft/s) wind, 0.5 coefficients of emissivity and absorption,
Temperate rating - 250ºC ambient, 1000 watts/sq. meter sun, Tropical rating - 400ºC ambient, 1200 watts/sq. meter sun.
British Sizes
CODE NOMINAL EQUIVALENT Cu AREA STRANDING AND WIRE NOMINAL OVERALL TOTAL AREA WEIGHT1
AREA kg DIAMETER
mm2
mm2 inch2 mm inch mm2 inch2 mm2 inch2 mm2 lb/M ftt
- - 6.45 0.01 7/1.47 7/0.0574 4.41 0.174 11.7 0.01812 32.2 21.7
BOX - 9.68 0.015 7/1.85 7/0.0727 5.55 0.219 18.8 0.02908 51.7 34.7
ACACIA - 12.9 0.02 7/2.08 7/0.0822 6.24 0.246 23.9 0.03711 66.1 44.4
ALMOND 25 16.1 0.025 7/2.34 7/0.0921 7.02 0.276 30.1 0.04666 82.9 55.7
CEDA 30 19.4 0.03 7/2.54 7/1000 7.62 0.3 35.5 0.05498 97.8 65.7
- 40 22.6 0.035 7/2.77 7/1091 8.31 0.327 42.2 0.06543 116.4 78.2
FIR 50 25.8 0.04 7/2.95 70161 8.85 0.348 47.8 0.07415 131.8 88.6
HAZEL 100 32.3 0.05 7/3.30 7/0.1299 9.9 0.39 59.9 0.0928 165 110.9
PINE - 38.7 0.06 7/3.61 70422 10.83 0.426 71.7 0.1111 197.7 132.9
- - 45.2 0.07 7/3.91 7/1539 11.73 0.462 84.1 0.1303 231.6 155.6
WILLOW 150 48.4 0.075 7/4.04 7/1591 12.12 0.477 89.8 0.1392 247.5 166.3
- 175 51.6 0.08 7/4.19 7/1650 12.57 0.495 96.5 0.1490 266.2 178.9
- 300 58.1 0.09 7/4.45 7/0.1751 13.35 0.526 108.8 0.1686 299.8 201.5
OAK - 64.5 0.1 7/4.65 70831 13.95 0.549 118.9 0.1843 327.8 220.3
CODE NOMINAL EQUIVALENT Cu AREA STRANDING AND WIRE NOMINAL OVERALL TOTAL AREA WEIGHT1
AREA kg DIAMETER
mm2
mm2 inch2 mm inch mm2 inch2 mm2 inch2 mm2 lb/M ftt
- - 64.5 0.1 19/2.82 190111 14.1 0.555 118.8 0.1841 327.6 220.2
MULBERRY - 80.6 0.125 19/3.18 19/1253 15.9 0.626 151.1 0.2342 416.7 280
ASH - 96.8 0.15 19/3.48 19/1370 17.4 0.685 180.7 0.2801 498.1 334.8
ELM - 113 0.175 19/3.76 19/1481 18.8 0.74 211 0.3271 582.1 391.2
POPLAR - 129 0.2 37/2.87 37/1129 20.09 0.791 239 0.3705 658.8 442.7
- - 145 0.225 37/3.05 37/1202 21.35 0.841 270.8 0.4197 746.7 501.8
SYCAMORE - 161 0.25 37/3.23 37/0.1271 22.61 0.89 303 0.4697 834.9 561.1
UPAS - 194 0.3 37/3.53 37/1390 24.71 0.973 362.1 0.5613 998.6 671.1
- - 226 0.35 37/3.81 370500 26.47 1.05 421.8 0.6538 1163 781.5
YEW - 258 0.4 37/4.06 370600 28.42 1.119 479.9 0.7439 1323 889.2
French Sizes
CODE AREA NO. OF DIAMETER OVERALL TENSILE RATED MAXIMUM DC LINEAR ELASTICITY COEFFICIENT
mm2 WIRES OF WIRES DIAMETER OF STRENGTH STRENGTH OF RESISTANCE WEIGHT MODULUS* OF LINEAR EXPANSION
mm CONDUCTOR OF WIRE CONDUCTOR AT 20ºC kg/km hbar */oc
mm hbar daN km
German Sizes
CONDUCTOR SIZE ALLOY AREA NO. OF DIAMETER OVERALL DIAMETER LINEAR RATED MAXIMUM DC
mm2 mm2 WIRES mm OF CONDUCTOR WEIGHT STRENGTH RESISTANCE AT 20ºC
mm kg/km daN ohms/km
The information contained within this datasheet is for guidance only and is subject to change without notice or liability. All the information is provided in good faith and is
believed to be correct at the time of publication. When selecting cable accessories, please note that actual cable dimensions may vary due to manufacturing tolerances.