Sie sind auf Seite 1von 41

MC61C-nX

INSTRUCTION MANUAL
3 PHASE OVERCURRENT & EARTH FAULT RELAY WITH INSTANTANEOUS
HIGH SET FUNCTIONS AND COMMUNICATION FEATURE

L&T Electrical & Automation


Doc. No. 4D060236 Rev A.
CONTENT

CONTENT PAGE No.


1. Introduction 3

2. Features 3

3. Installation and Maintenance 11

4. User Interface 13

5. Technical Specification 19

6. Default Setting 23

7. Diagram 25

8. Secondary Current Injection Test 27

9. Memory Map 28

10. Product Ordering Information 40

11. Warranty 41

12. Disclaimer 41

-2-
INTRODUCTION AND FEATURES

1. INTRODUCTION

MC61C-nX is a numeric, non-directional 3 Phase Over current (OC) & Earth fault (EF) protection relay
model with instantaneous highset feature and RS-485 communication. It is suitable for Over current &
Earth fault protection schemes in LV, MV and HV power distribution system. It is also suitable for
application such as providing selective protection for overhead and underground feeders, AC
machines, transformer etc.

2. FEATURES

Screws for
locking
LED for TRIP module
indication

Graphical
LCD

RESET Button
Push buttons

Handle for
pulling the
Sealing
module
screws

-3-
FEATURES

FEATURES

n Graphical LCD & Push Buttons:

MC61C-nX series of relay has a graphical LCD interface to view the measurements, parameters
and settings. Four push buttons are provided for navigation and selection of parameters.

n Password protection:

Programming of relay settings is protected with user defined 4 digit numerical password. Default
password is “0000”. It is recommended to modify the password by going into programming mode
during installation. Refer page 14 for the procedure. Password protection is available through
RS-485 communication.

n Relay outputs:

MC61C-nX Relay has 5 output contacts. Relay output contact R5 is dedicated for Internal Relay
Failure (IRF)/Auxillary Fail and relay output contacts R1, R2, R3 and R4 can be programmed as per
Table - 1.

Output Configuration Can be programmed for Reset


Contacts

R1 1 N/O Protection Auto/Manual

R2 1 N/O Protection/Blocking Output Auto

R3 1 N/O Protection/Blocking Output/Breaker Auto


Open

R4 1 N/O Protection/Blocking Output/Breaker Auto


Close

Table -1

-4-
FEATURES

n
Measurement:

MC61C-nX relay has the capability to measure the following parameters:


1. Instantaneous Phase and Earth currents.
2. Starting current - When the feeder is switched ON, relay will record the initial current as
starting current.
3. Maximum current - Maximum instantaneous current during its operation till it is cleared
through programming mode.
All the measured parameters are RMS value.

n Trip counts:

Separate trip counts for OC and EF are available which rolls over after reaching 99999 and can be
reset to zero at any point of time.

n Trip Data:

Data of latest 15 OC and EF trips are recorded in memory. Trip data contains the following:
1. Fault current: CT secondary current of all Phases and Earth.
2. Date and Time stamp of relay trip.
3. Trip characteristics: IDMT curves or HS.

n LED indicators:

Four LEDs are provided for phase wise trip indication. LEDs blink during pick up and will glow
steady when trip has occurred. All LEDs start blinking during programming of parameters and
stop after programming is completed.
LED trip indications are cleared by pressing the RESET button.

-5-
FEATURES

n
Characteristic curve:

MC61C-nX relay model has wide range of IDMT (Inverse Definite Minimum Time) characteristics
curves and DTL (Definite Time Lag) options. Refer page 7 for Time-current characteristic curves.

> IDMT Curves:

1. Normal Inverse (NI) 1.3 seconds


2. Normal Inverse 3 seconds
3. Very Inverse (VI)
4. Extremely Inverse (EI)

Operating Time for IDMT Curves: Trip Time t(I) =

Where, I= Fault Current


Is = Setting Current
TMS =Time Multiplier setting

Pickup current = Set Current


Reset current = 0.93 times of Set current

Curve A a Standard

NI 1.3 0.0613 0.02 —

NI 3 0.1414 0.02 IEC60255-151

VI 13.5 1 IEC60255-151

EI 80 2 IEC60255-151

> DTL:

Definite time lag can be selected as 1s,10s,100s.


1. D1 corresponds to trip time delay of 1s.
2. D10 corresponds to trip time delay of 10s.
3. D100 corresponds to trip time delay of 100s.

n Instantaneous Trip (High set):

MC61C-nX has instantaneous Trip feature and can be assigned for any protection element.

Trip time < 55ms at 2Ihs

-6-
FEATURES

n
Time-Current Characteristics:

-7-
FEATURES

n
Reset Time:

Reset Time feature is used for intermittent faults. It works for DTL and IDMT curves.
Example: Let following be the settings in the relay.
Reset Time= 10s, Curve= D.10, OCLS = 2, Relay R1 selected for OCLS and Fault current: I>Is

Case Condition Working

Case 1 Fault current is present for 4s, Relay remembers the elapsed trip time of 4s.
absent for next 9s, then When the relay senses the fault again within the
reoccurs and continues. reset time period, it will trip after 6s (10-4).

Case 2 Fault current is present for 4s, Relay remembers the elapsed trip time of 4s.
absent for next 11s, then Since the fault is not present within the reset
reoccurs and continues. time period, relay will trip after 10s.

n
Dual rated CT:

CT rating of the Phase and Earth CT is field configurable as 1A or 5A without changing the
connections. CT rating can be changed in following combination,
1. P1E1
2. P5E1
3. P1E5
4. P5E5

n Diagnostics:

1. EEPROM and Real time clock (RTC) battery monitor: The protection element R5 is
dedicated for internal failure. In normal operation, R5 is in energized condition. When
relay detects any internal failure, output contact R5 will get de-energized and
corresponding failure is displayed.
Here internal failure corresponds to failure of EEPROM and RTC battery.
> The abnormality related to EEPROM will be displayed as 'EEPROM ERROR'. This error
is related to the corruption of memory contents. Default settings will be loaded once
this failure is detected.
> Low RTC battery voltage indication is displayed at the top right corner of the
LCD as 'LB'. Low RTC battery voltage can corrupt the real time clock.

2. Relay test: This feature is available in the ‘TEST’ option. Selection of this option will
energize and de-energize all the output contacts. This can used to check the working of
output contacts.

3. Display test: This feature is available in the ‘TEST’ option. With this option the operation
of graphical display can be checked.

-8-
FEATURES

n Serial Communication:

MC61C-nX has a RS-485 communication port on its rear panel. Settings and controls of the relay
is accessible through the port using MODBUS protocol.

n Blocking Function Logic:

Blocking Output (Starter) for Pilot wire co-ordination:

Blocking output is used for blocking the upstream relay. Blocking output energizes instantly [less
than or equal to 35 milliseconds] on occurrence of fault and de-energizes 70ms after elapse of
trip time delay. It is configurable for low set (Over current and Earth fault) and high set (Over
current and Earth fault) independently or for both.

Blocking Input (Digital Input D2) for Pilot wire co-ordination:

Blocking input is used to inhibit the trip function of upstream relay. Blocking output (Starter) of
downstream relay can be wired to Digital input D2 of upstream relay to inhibit the trip function.
It is configurable for functions of low set (Over current and Earth fault) and high set (Over
current and Earth fault) independently or for both.

n Digital Inputs:

D1: When Digital input D1 is active, it enables remote control of breaker (from the PC).

D2: It is used as blocking input for pilot wire co-ordination. (refer above blocking input
explanation) .

D3: Its condition will be read by the relay and transmitted to PC. Ideally, it can be used for
monitoring the breaker status.

n Breaker Operating Time (BOT):

Breaker operating time of downstream relay has to be set for blocking function logic in upstream
relay. Breaker operating time can be programmed from 10 msec to 250 msec.

Logic Explanation:

-9-
FEATURES

Blocking output (Starter) of downstream relay is wired to digital input D2 of upstream relay. On
fault, blocking output of downstream relay will activate the Blocking input (D2) of upstream
relay instantly (≤35 ms) and inhibit the Trip of upstream relay for duration of its trip time
delay+70ms. Once Digital input D2 gets deactivated and fault is not cleared by downstream
circuit breaker the upstream relay will initiate trip after set BOT.

Note: If Digital input D2 is activated continuously then upstream relay will initiate trip after its
trip time delay+2 times of set BOT of downstream relay.

n Breaker failure protection:

To achieve breaker failure protection, the blocking output of the downstream relay will be wired
to the blocking input of the upstream feeder relay.

Whenever fault is sensed by the downstream feeder relay it generates a blocking output signal in
the form of a contact. It will act as blocking input for the up-stream relay. The upstream relay
is blocked from initiating a tripping, for duration which is programmable in the upstream relay
with help of BOT.

It should be noted that the upstream relay will not be blocked permanently (till the blocking
input is removed). If fault is not cleared by down stream relay, due to its failure, the fault will
persist. To sense this condition, the down stream relay initiates a timer (BOT) to monitor the
breaker operation. If the breaker fails to clear the fault in this duration, the blocking output
signal, which is in energized condition, will be de-energized. Hence the upstream breaker, which
was blocked, will now instantaneously trip its breaker – thus clearing the fault at an upstream
level.

n Auto Doubling:

In transformer feeders, when breaker is switched ON, there will be a very high inrush current,
which may be greater than the high set value of the relay. This may lead to nuisance tripping by
the protection relay. To avoid nuisance trip of the feeder due to inrush current autodoubling is
provided. If the input current increases from 0A to 0.2In in 40msec then the over current high set
(OCHS) setting is auto doubled for next 20ms. After 60msec (40msec+20msec) initial set value
will be restored.

n Breaker Open/Close through remote connection:

Relay output contact R3 can be used for opening the breaker and relay output contact R4 can be
used for closing the breaker through RS-485 communication only.

Follow the below steps to open/close the breaker:

a) For opening the breaker relay output contact R3 has to be selected for breaker open manually
or through remote. Relay output contact R3 is energized for 250ms once the
command is received from PC.

b) For closing the breaker relay output contact R4 has to be selected for breaker close manually
or through remote. Relay output contact R4 is energized for 250ms once the command is received
from PC.
-10-
INSTALLATION AND MAINTAINENCE

3. INSTALLATION AND MAINTAINENCE


n
Preliminary checks:

Relay packing consists of


1. Relay
2. Mounting clamp
3. Instruction Manual
4. Test certificate

> Check the relay for any obvious damage, if found inform to nearest L & T office or dealer.
> Ensure that the units received are as per the requirement.
> Remove the protective cover from the terminal block by removing two screws.
> Connect suitable auxiliary supply between terminals 25 and 26.
> Switch ON the supply, all LEDs will blink once and the display indicates model number, software
version and CT rating. After this the relay will enter into normal operation mode.

Display and Output contacts can be checked manually. Refer “Diagnostic” section of the manual
regarding the procedure for testing the display and output contacts.

This completes the preliminary check. Disconnect the auxiliary supply and fix the protective covers
on terminal block.

n
Mounting and Wiring:

MC61C-nX is designed for flush mounting on the panel. Refer page 26 for panel cutout dimensions
and space required behind the panel. Fix the mounting clamps supplied, to the top and
bottom side of the relay. Insert the relay through the panel cutout and hold it firmly against the
panel. Tighten the screws on the mounting clamp. Wire the relay terminals as shown in the
wiring diagram (Refer page 25). Relay terminals are suitable for 2.5 mm.sq lugs. Ensure that the
protective cover is fixed on the terminal block with the help of two screws after completing the
wiring.

NOTE:
1. Ensure proper earth connection to the relay.
2. Please remove the relay from the panel during transportation.
3. During installation and uninstallation, ensure that supply to the relay is switched OFF. This is to
ensure the safety of the operating personnel.

-11-
INSTALLATION AND MAINTAINENCE

n
Handling Precautions:

In case of relay malfunction, the electronic module alone can be removed and replaced without
removing the complete relay assembly with its housing from the panel. Care has to be exercised
while handling the modules. The electronic components can be damaged by electrostatic discharge
while handling the module. Hence care has to be taken while handling the cards as mentioned
below:

1. Before removing the module ensure that you are at the same electrostatic potential as the
equipment by touching the same.
2. Handle the module by its front-plate, frame, or edges of the printed circuit board. Avoid
touching the electronic components, printed circuits and connectors.

n
Fault Detection & Repair:

Internal settings and components in the relay should not be altered. For repair, please contact
nearest L&T sales office.

n
Instructions for Draw-out & Plug-in:

Refer page 26 for relay Draw-out & Plug-in.

> Draw-out operation:

Rotate the four locking screws by 90 Degrees. Now the screws will be in unlocked position,
that is, the slots in the screws will be in horizontal position as shown in page 26. Hold the
handle by the fingers and pull out the module. The relay has CT shorting facility and hence
the CT secondary will be automatically in shorted condition when the module is plugged
out.

> Plug-in operation:

First ensure the four locking screws are in unlocked position, by verifying the screw driver mark
is in horizontal position. Position the module such that it gets engaged to the card guides in the
housing. Push the module into the connector. Push all four screws and rotate by 90 degree.
They will get locked to the housing.

WARNING

While plugging the module, if any of the Locking screws are in locked position (i.e. the
screwdriver mark in the screw is vertical), the module cannot be plugged fully. In such a
case, the CT shorting may not have opened. To avoid this problem, ensure the screws
are in unlocked position while pushing the module.

-12-
USER INTERFACE

4. USER INTERFACE

-13-
USER INTERFACE

USER INTERFACE
n
Menu Operations:

To enter into menu screen, press ENT key on default screen. Menus are divided mainly into
1. Edit Menu
2. View menu.

> View Menu :

Follow below steps to enter into View menu.

Step 1: Press ENT key on Default screen to enter into menu screen
Step 2: On menu screen Select 'View Menu' by UP/DN key and press ENT.
Step 3: Scroll through the options by UP/DN key and press ENT to select the desired option.

> Edit Menu :

Edit Menu is protected with password. Follow below steps to enter into Edit menu.

Step 1: Press ENT key on Default screen to enter into menu screen
Step 2: On menu screen select 'Edit Menu' by UP/DN key and press ENT.
Step 3: Press ENT key and then enter the numerical password by pressing 0-9 key, move to the
next space for entering the number using arrow key and press ENT.

NOTE:
Programming mode time out is 10s. After entering into programming mode if the relay is not
operated within 10s, it will exit from the programming mode.

n Password change:

Follow below steps for changing Password.

Step 1: Follow the steps given in 'Edit Menu'


Step 2: Select the 'Settings' menu by pressing DN/UP key and press ENT.
Step 3: Select the submenu 'Change Password' by pressing DN key and press ENT key to set
new password.
Step 4: Press ENT key and select the four numerical digits by pressing 0-9 key and arrow key
and press ENT. “Password changed successfully” message will be displayed.

NOTE:
1. Factory set password is “0000". It is preferable to change factory set password.
2. In case if password is forgotten then contact the nearest L&T area office to reset password.

-14-
USER INTERFACE

n
Parameter change:

Parameter submenu contains low set thresholds, IDMT curves, TMS ,high set thresholds,
time delay for highset, Reset time for over current and earth fault.

Follow the below steps for changing parameters.

Step 1: Follow the steps given in 'Edit Menu'


Step 2: Select the 'Settings' menu by pressing DN/UP key and press ENT.
Step 3: Select the submenu 'Parameters' and press ENT.
Step 4: Select the parameter by pressing DN/UP key in which changes have to be made and
press ENT key(LEDs start blinking) to change the threshold value, IDMT curves, TMS,
Reset time and CT ratios.
Step 5: Set the required values/curves by pressing UP/DN keys and press the ENT key (LEDs
stop blinking) to set the values/curves.

n
Configuring relay output contacts(R1,R2,R3,R4):

Relay Config submenu is for configuring output contacts for functions of over current low set,
over current high set, Earth fault low set, Earth fault high set, Over current starter,
Earth fault starter, Breaker open and close.
In this menu Starter function can be configured for Low set or High set or both, for over current and
earth fault separately. Also relay output R1 can be made as self reset or hand reset.

Follow below steps for configuring relay output contacts.

Step 1: Follow the given steps to enter into 'Edit Menu'


Step 2: Select the 'Settings' menu by pressing UP/DN key and press ENT.
Step 3: Select the submenu 'Relay config.' and press ENT.
Step 4: Select the functions by pressing DN/UP key for which the output contacts have to be
configured. Press ENT key(LEDs start blinking) to change or to select the output contacts.
Step 4: Select the required relay by pressing LT/RT keys and press the ENT key to select or
deselect output contacts.
Step 5: Press ESC key to configure the relays for other functions.

Follow below steps for configuring starter function (blocking output):

Step 1: Follow the steps 1 to 3 as mentioned above.


Step 2: If the output contact is to be configured as a starter function (blocking output) for
OC fault:
a) Select option STRTR (in OC TRIP screen) and press ENT.
b) Use LT/RT key and press ENT to select the required output contact and press ESC.
c) Use DN key to move to STARTER CONFIG screen.
d) Select option OC STR and press ENT. Use LT/RT key to select LS or HS or both and
press ENT to select or deselect LS or HS or both.
Now the output contact is configured for OC LS HS or OC LS or OC HS fault.

-15-
USER INTERFACE

EF fault:
a) Select option STRTR (in EF TRIP screen) and press ENT.
b) Use LT/RT key and press ENT to select the required output contact and press ESC.
c) Use DN key to move to STARTER CONFIG screen.
d) Select option EF STR and press ENT. Use LT/RT key to select LS or HS or both and
press ENT to select or deselect LS or HS or both.
Now the output contact is configured for EF LS HS or EF LS or EF HS fault.
NOTE:
1. Relay output contact R1 cannot be configured for starter function.
2. Output contacts which are configured for starter function cannot be selected for any other
protection function.

n Configuring relay output contacts for Breaker Open/Close :

Follow the below steps for configuring relay output contacts R3 for breaker open and relay
output contacts R4 for breaker close.

Step 1: Follow the steps given in 'Edit Menu'


Step 2: Select the 'Settings' menu by pressing DN/UP key and press ENT.
Step 3: Select the submenu 'Relay Config' and press ENT.
Step 3: Select ‘BRK O’ or ‘BRK C’ by pressing DN/UP key and press ENT(LEDs start blinking).
Step 4: Press ENT to select or deselect relay output contacts R3 or R4.

n Real Time Clock setting (RTC setting):

Follow the below steps for setting RTC.

Step 1: Follow the steps given in 'Edit Menu'


Step 2: Select the 'Settings' menu by pressing DN/UP key and press ENT.
Step 3: Select the submenu 'Relay Config' and press ENT.
Step 3: Select the parameter DATE and TIME by pressing DN/UP key in which changes have to be
made and press ENT key(LEDs start blinking).
Step 4: Select the day, month or year to be changed by using LT/RT key and press ENT.
Use UP/DN key to change. Follow same step for changing time.

n CT rating change:

CT rating of the relay is field configurable as 1A or 5A for both Phase and Earth CT without
changing the connections.

Follow below steps for changing the CT rating.

Step 1: Follow the steps given in 'Edit Menu'.


Step 2: Select the 'Settings' menu by pressing UP/DN key and press ENT.
Step 3: Select the submenu 'CT Rating' and press ENT.
Step 4: Press the ENT key (LEDs start blinking).
Step 5: Select the required CT Ratings by pressing DN/UP key and press ENT to select.
Step 6: Press ESC key to go back to previous menu.

-16-
USER INTERFACE

n Clearing Trip records and Maximum current value:

Follow below steps for clearing Trip records and Maximum current value.

Step 1: Follow the steps given in 'Edit Menu'.


Step 2: Select the 'Clear' menu by pressing UP/DN key and press ENT.
Step 3: Select the submenu 'Trip data' or ‘Maximum Current’ and press CLR key.
Step 4: Press ESC key to go back to previous menu.

n Blocking Input for Pilot wire co-ordination:

Follow the below steps for setting blocking functions.

Step 1:
Follow the steps given in 'Edit Menu'
Step 2:
Select the 'Settings' menu by pressing DN/UP key and press ENT.
Step 3:
Select the submenu 'Blocking Function' and press ENT.
Step Select blocking for OC or EF and press ENT(LEDs start blinking). Use LT/RT key to
3:
select LS or HS and press ENT(LEDs stop blinking) to select or deselect LS or HS
or both.
Step 4: Select BOT for entering the breaker operating time of downstream breaker and
press ENT. Use UP/DN key to change the BOT.

n Modbus settings:

Follow the below steps for setting node address, baud rate and parity.

Step 1:
Follow the steps given in 'Edit Menu'
Step 2:
Select the 'Settings' menu by pressing DN/UP key and press ENT.
Step 3:
Select the submenu 'Modbus settings' and press ENT.
Step Select the node addr, baud rate and parity by pressing DN/UP key in which changes
4:
have to be made and press ENT key(LEDs start blinking) to change.
Step 5: Set the required settings by pressing UP/DN keys and press the ENT key (LEDs
stop blinking) to set the values.

n Autodoubling settings:

Follow the below steps to make autodoubling ON or OFF.

Step 1: Follow the steps given in 'Edit Menu'.


Step 2: Select the 'Settings' menu by pressing DN/UP key and press ENT.
Step 3: Select the submenu 'Autodoubling' and press ENT.
Step 4: Press ENT key to set the Autodoubling ON or OFF.
Step 5: Use UP/DN key to select autodoubling ON or OFF and press ENT.

-17-
USER INTERFACE

n
View Settings:

In View menu, settings can be viewed.


In Settings menu, Parameters, Relay configuration, CT Ratings, Blocking Function, Modbus Settings
and Autodoubling status can be viewed.

Step 1: Follow the steps given in 'View Menu'.


Step 2: Select 'Settings' by pressing UP/DN key and press ENT key.
Step 3: Select the options which has to be to viewed.

n
View Trip records:

Latest 15 trip records with trip cause, date and time stamp can be viewed in Trip records.
Records will be updated First In, First Out basis.

Follow below steps for viewing Trip records.

Step 1: Follow the steps given in 'View Menu'.


Step 2: Select 'Trip Data' by pressing UP/DN key and press ENT key
Step 3: To see over current Trip records select 'OC Fault' by pressing UP/DN Key and press ENT key
to view trip records. By pressing UP/DN key 15 trip records can be viewed.
Step 4: To see Earth Fault Trip records select 'EF Fault' by pressing UP/DN Key and press ENT key
to view trip records. By pressing UP/DN key 15 trip records can be viewed.

n View Measurements:

In Measurement menu, Maximum Current, Starting Current and Instantaneous Current can be
viewed.

Follow the below steps to view measurements:

Step 1: Follow the steps given in 'View Menu'.


Step 2: Select 'Measurement' submenu by pressing UP/DN key and press ENT key
Step 3: Select the required measurements by pressing UP/DN Key and Press ENT key to view.
Step 4: Press ESC key to go back to previous menu.

NOTE:
1. Current value in default display and Instantaneous current displayed are the
external CT Primary current.
2. Starting current, Maximum current and the current value in trip data displayed are the
external CT Secondary current.

-18-
TECHNICAL SPECIFICATION

5. TECHNICAL SPECIFICATION
n
Rating:

Auxillary Power Supply Temperature

Supply Voltage range Tolerance Storage temperature -20˚C to 70˚C

24V to 240V AC/DC ±10% Operating temperature 0˚C to 60˚C

Power supply burden Weight

Type Value Weight(Approx.) 1.7kg

24V to 240V DC <3W Output contacts

24V to 240V AC <10VA Rated voltage 240V AC

Input Current (In) Rated current 5A

Parameter Value Rated breaking capacity 2000VA

CT rating (Field selectable) 1A or 5A

Frequency 50Hz ± 5%

Measurement Accuracy ±5% or ±5mA


whichever is
higher

Current circuit burden

Input current (In) Value

1A < 0.1VA

5A < 0.25VA

Overload capacity

Value Overload period

2In Continuous

20In 1second

-19-
TECHNICAL SPECIFICATION

n
Settings Range

A) Phase fault protection settings for IDMT curves and DTL (OCLS: Over current low set)

Setting Setting range Incremental step

Is 0.2 to 2.0 In 0.01

TMS 0.01 to 1.6 0.01

B) Phase fault protection settings for High set (OCHS: Over current high set)

Settings Setting range Incremental step

Is 0.2 to 40 In 0.1 or Disable

C) Earth Fault protection setting for IDMT and DTL (EFLS: Earth fault low set)

Settings Setting range Incremental step

Is 0.05 to 0.8 In 0.01

TMS 0.01 to 1.6 0.01

D) Earth Fault protection settings for High set (EFHS: Earth fault high set)

Settings Setting range Incremental step

Is 0.05 to 20 In 0.1 or Disable

E) Reset time

Settings Setting range Incremental step

T.RST 0.1s to 10s 0.1s or Disable

n Trip time variaton for Low set:


Type Variation Output contact operating time

IDMT/DTL ±5% <20ms


n
Trip time for High set:

Type Trip time Condition

Instantaneous < 55ms At 2 times of Ihs and above

-20-
TECHNICAL SPECIFICATION

n High set time delay:

Settings Setting range Incremental step

OCTD DSB,0.05,0.1 to 2sec 0.01


EFTD DSB,0.1 to 2sec 0.01

n Trip time for Starter (Blocking output):

Type Trip time Condition

Instantaneous < 35ms -----


n Breaker operating time:
Settings Setting range Incremental step

BOT 0.01 to 0.25sec 0.01


n MODBUS setting:
Settings Setting range Incremental step

Node Address 1 to 247 1

Baud Rate 2400, 4800, 9600 -----

Parity None, Even, Odd -----

n Standards applicable

Test name Standard Condition Level

Dielectric test IEC60255-27 Between any two 2.0 kV AC RMS for 1


independent circuit minute

Across NO contact 1.0 kV AC RMS for 1


minute

Impulse voltage IEC60255-27 Between any two 5kV peak, 1.2/50µs


independent circuit

Insulation resistance IEC60255-27 Insulation resistance > 1000 MΩ


between independent
circuit

Insulation resistance
between all circuits and
body

-21-
TECHNICAL SPECIFICATION

n
Standards applicable

Test name Standard Condition Level

Slow damped IEC60255-26 Differential Mode 1.0kV peak, 1MHz


oscillatory wave
Common Mode 2.5kV peak, 1MHz

Electrostatic Discharge IEC60255-26 Air Discharge 8kV

Contact Discharge 6kV

Electrical Fast IEC60255-26 In any circuit 4kV, 5kHz


Transient Zone A

Surge immunity EC60255-26 Differential mode 2kV, 1.2/50µs


Zone A

Radiation Susceptibility IEC60255-26 ---- 10V/m, 80MHz to 2.7GHz

Immunity to voltage IEC60255-26 ---- ----


variation, dips and
short interrupts on
power supply port

Radiated Radio IEC60255-26 30MHz to 230MHz 40dB (µV/m) at 10m


Frequency interference Quasi peak

230MHz to 1GHz 47dB (µV/m) at 10m


Quasi peak

Conducted Radio IEC60255-26 0.15MHz to 0.5MHz 79dB (µV) at Quasi peak


Frequency interference 66dB (µV) at average

0.5MHz to 30MHz 73dB (µV) at Quasi peak


60dB (µV) at average

Vibration test IEC60255-21-1 ------ Class-1

Shock test IEC60255-21-2 ------ Class-1

-22-
DEFAULT SETTING

6. DEFAULT SETTING

Parameter setting Relay configuration

OCLS 1 1 2 3 4
(Over Current Low Set)

OCHS 3 1 2 3 4
(Over Current High Set)

EFLS 0.2 1 2 3 4
(Earth Fault Low Set)

EFHS 2 1 2 3 4
(Earth Fault High Set)

OC Char NI3
(Over Current Characteristic Curve)

OC TMS 0.2
(Over Current Time Multiplier Setting)

EF Char NI3
(Earth Fault Characteristic Curve)

EF TMS 0.2
(Earth Fault Time Multiplier Setting)

T.RST DSB
(Reset time) (Disable)

PH.CTR 100
(Phase CT ratio)

E.CTR 100
(Earth CT ratio)

OCTD DSB
(Over current High set time dalay) (Disable)

EFTD DSB
(Earth fault high set time delay) (Disable)

RESET Self

CT RATING P5E5

-23-
DEFAULT SETTING

Parameter setting Relay configuration

OC - Blocking Input LS, HS

EF - Blocking Input LS,HS

BOT 0.05sec

Node addr 1

Baud rate 9600

Parity None

DBL OFF
(Auto doubling)

-24-
DIAGRAM

7. WIRING DIAGRAM

MC61C-nX FOR 3 WIRE SYSTEM

MC61C-nX FOR 4 WIRE SYSTEM

-25-
DIAGRAMS

DRAW OUT AND PLUG IN

DIMENSION AND MOUNTING DETAILS

a) All dimensions are in mm.

-26-
SECONDARY CURRENT INJECTION TEST

8. SECONDARY CURRENT INJECTION TEST

n Equipment: Single-phase secondary current injection kit.

n Connections:

Connect auxiliary supply between terminal 25 and 26 (as indicated in wiring diagram).
Connect terminals 7 and 8 for earth fault trip test.
Connect terminals 1, 2, 3, 4, 5 and 6 in series for over current trip test.
Connect terminals 1,2,3,4,5,6,7 and 8 in series for high set trip test.

n Power ON:

Switch ON the power supply, All LEDs will blink once and the display will show model number
(MC61C), Firmware version and CT rating. After this the relay will enter into current
measurement mode.

n Earth fault trip test:

Ensure the default settings in the relay is as shown in the setting form. Pass 2A (0.4A for 1A relay)
through the relay. Now the relay will start displaying the current in scrolling mode. Same time
earth fault trip LED will start flashing and will become permanently ON after 2 sec.

n Over current trip test:

Pass 10A (2A for 1A relay) through the relay. Now all the phase trip LEDs will start flashing
indicating the presence of fault. This will continue up to 2 sec and later all the phase trip LEDs will
become permanently ON and relay R1, R2,R3 and R4 will trip. Check the continuity between the
terminals 9-10, 11-12, 17-18 and 27-28 to ensure tripping of R1, R2, R3 and R4. Remove the
current and press "reset" button to reset the relay R1. Now LEDs will become OFF.

n High set trip test:

Set the high set setting (OCHS) as 2 times the rated current. Pass 10.5A(2.1A for 1A relay) through
the relay. Now all the LEDs will become ON and all relay (R1, R2, R3, and R4) will trip within 55
msec. Check the continuity between the terminals 9-10, 11-12, 17-18 and 27-28 to ensure
tripping of R1, R2, R3 and R4. Remove the current and press "reset" button to reset the relay R1.
Now LEDs will become OFF.

This completes the secondary current injection test. Disconnect auxiliary supply and other CT
connections. Fix the protective covers back on front panel and terminal block.

-27-
MEMORY MAP

28. MEMORY MAP


Read Parameters:
Address Parameter Word MF Remarks
30001 Trip Count OC 2 1 Input register
30003 OC Trip 1 Cause 2 1 Input register
Latest 15 Trips Due to Over Current (OC)
Note: 0 - NI1.3
1 - NI3
2 - VI
3 - EI
4 - D1
5 - D10
6 - D100
7 - HS
128 – No trip
The same is applicable for OC Trip cause 2 to OC Trip cause 15 and OC Trip 1 is the latest
Trip.
30005 R Phase Current 2 0.001 Input register
30007 Y Phase Current 2 0.001 Input register
30009 B Phase Current 2 0.001 Input register
30011 Earth Current 2 0.001 Input register
30013 Year & Month 2 Input register
Note: 1st Word contains year and 2nd Word contains Month.
The same is applicable for year & month Modbus address for OC Trip 2 to OC Trip 15.
30015 Day & Hour 2 Input register
st nd
Note: 1 Word contains Day and 2 Word contains Hour.
The same is applicable for Day & Hour Modbus address for OC Trip 2 to OC Trip 15.
30017 Minute & Second 2 Input register
st nd
Note: 1 Word contains Minutes and 2 Word contains Seconds.
The same is applicable for Minute & Second Modbus address for OC Trip 2 to OC Trip 15.

30019 OC Trip 2 Cause 2 1 Input register


30021 R Phase Current 2 0.001 Input register
30023 Y Phase Current 2 0.001 Input register
30025 B Phase Current 2 0.001 Input register
30027 Earth Current 2 0.001 Input register
30029 Year & Month 2 1 Input register
30031 Day & Hour 2 1 Input register
30033 Minute & Second 2 1 Input register

30035 OC Trip 3 Cause 2 1 Input register


30037 R Phase Current 2 0.001 Input register
30039 Y Phase Current 2 0.001 Input register
30041 B Phase Current 2 0.001 Input register
30043 Earth Current 2 0.001 Input register
30045 Year & Month 2 1 Input register

-28-
MEMORY MAP

30047 Day & Hour 2 1 Input register


30049 Minute & Second 2 1 Input register

30051 OC Trip 4 Cause 2 1 Input register


30053 R Phase Current 2 0.001 Input register
30055 Y Phase Current 2 0.001 Input register
30057 B Phase Current 2 0.001 Input register
30059 Earth Current 2 0.001 Input register
30061 Year & Month 2 1 Input register
30063 Day & Hour 2 1 Input register
30065 Minute & Second 2 1 Input register

30067 OC Trip 5 Cause 2 1 Input register


30069 R Phase Current 2 0.001 Input register
30071 Y Phase Current 2 0.001 Input register
30073 B Phase Current 2 0.001 Input register
30075 Earth Current 2 0.001 Input register
30077 Year & Month 2 1 Input register
30079 Day & Hour 2 1 Input register
30081 Minute & Second 2 1 Input register

30083 OC Trip 6 Cause 2 1 Input register


30085 R Phase Current 2 0.001 Input register
30087 Y Phase Current 2 0.001 Input register
30089 B Phase Current 2 0.001 Input register
30091 Earth Current 2 0.001 Input register
30093 Year & Month 2 1 Input register
30095 Day & Hour 2 1 Input register
30097 Minute & Second 2 1 Input register

30099 OC Trip 7 Cause 2 1 Input register


30101 R Phase Current 2 0.001 Input register
30103 Y Phase Current 2 0.001 Input register
30105 B Phase Current 2 0.001 Input register
30107 Earth Current 2 0.001 Input register
30109 Year & Month 2 1 Input register
30111 Day & Hour 2 1 Input register
30113 Minute & Second 2 1 Input register

30115 OC Trip 8 Cause 2 1 Input register


30117 R Phase Current 2 0.001 Input register
30119 Y Phase Current 2 0.001 Input register
30121 B Phase Current 2 0.001 Input register
30123 Earth Current 2 0.001 Input register
30125 Year & Month 2 1 Input register
30127 Day & Hour 2 1 Input register
30129 Minute & Second 2 1 Input register

-29-
MEMORY MAP

30131 OC Trip 9 Cause 2 1 Input register


30133 R Phase Current 2 0.001 Input register
30135 Y Phase Current 2 0.001 Input register
30137 B Phase Current 2 0.001 Input register
30139 Earth Current 2 0.001 Input register
30141 Year & Month 2 1 Input register
30143 Day & Hour 2 1 Input register
30145 Minute & Second 2 1 Input register

30147 OC Trip 10 Cause 2 1 Input register


30149 R Phase Current 2 0.001 Input register
30151 Y Phase Current 2 0.001 Input register
30153 B Phase Current 2 0.001 Input register
30155 Earth Current 2 0.001 Input register
30157 Year & Month 2 1 Input register
30159 Day & Hour 2 1 Input register
30161 Minute & Second 2 1 Input register

30163 OC Trip 11 Cause 2 1 Input register


30165 R Phase Current 2 0.001 Input register
30167 Y Phase Current 2 0.001 Input register
30169 B Phase Current 2 0.001 Input register
30171 Earth Current 2 0.001 Input register
30173 Year & Month 2 1 Input register
30175 Day & Hour 2 1 Input register
30177 Minute & Second 2 1 Input register

30179 OC Trip 12 Cause 2 1 Input register


30181 R Phase Current 2 0.001 Input register
30183 Y Phase Current 2 0.001 Input register
30185 B Phase Current 2 0.001 Input register
30187 Earth Current 2 0.001 Input register
30189 Year & Month 2 1 Input register
30191 Day & Hour 2 1 Input register
30193 Minute & Second 2 1 Input register

30195 OC Trip 13 Cause 2 1 Input register


30197 R Phase Current 2 0.001 Input register
30199 Y Phase Current 2 0.001 Input register
30201 B Phase Current 2 0.001 Input register
30203 Earth Current 2 0.001 Input register
30205 Year & Month 2 1 Input register
30207 Day & Hour 2 1 Input register
30209 Minute & Second 2 1 Input register

30211 OC Trip 14 Cause 2 1 Input register


30213 R Phase Current 2 0.001 Input register

-30-
MEMORY MAP

30215 Y Phase Current 2 0.001 Input register


30217 B Phase Current 2 0.001 Input register
30219 Earth Current 2 0.001 Input register
30221 Year & Month 2 1 Input register
30223 Day & Hour 2 1 Input register
30225 Minute & Second 2 1 Input register

30227 OC Trip 15 Cause 2 1 Input register


30229 R Phase Current 2 0.001 Input register
30231 Y Phase Current 2 0.001 Input register
30233 B Phase Current 2 0.001 Input register
30235 Earth Current 2 0.001 Input register
30237 Year & Month 2 1 Input register
30239 Day & Hour 2 1 Input register
30241 Minute & Second 2 1 Input register

Latest 15 Trips Due to Earth Fault (EF)

30243 Trip Count EF 2 1 Input register

30245 EF Trip 1 Cause 2 1 Input register


Note :- 0 - NI1.3
1 - NI3
2 - VI
3 - EI
4 - D1
5 - D10
6 - D100
7 - HS
128 - No Trip
The same is applicable for EF Trip cause 2 to EF Trip cause 15
30247 R Phase Current 2 0.001 Input register
30249 Y Phase Current 2 0.001 Input register
30251 B Phase Current 2 0.001 Input register
30253 Earth Current 2 0.001 Input register
30255 Year & Month 2 1 Input register
st nd
Note: 1 Word contains year and 2 Word contains Month.
The same is applicable for year & month Modbus address for EF Trip 2 to EF Trip 15.
30257 Day & Hour 2 1 Input register
st nd
Note: - 1 Word contains Day and 2 Word contains Hour.
The same is applicable for Day & Hour Modbus address for EF Trip 2 to EF Trip 15.
30259 Minute & Second 2 1 Input register
Note: - 1st Word contains Minutes and 2nd Word contains Seconds.
The same is applicable for Minute & Second Modbus address for EF Trip 2 to EF Trip 15.

30261 EF Trip 2 Cause 2 1 Input register


30263 R Phase Current 2 0.001 Input register
30265 Y Phase Current 2 0.001 Input register

-31-
MEMORY MAP

30267 B Phase Current 2 0.001 Input register


30269 Earth Current 2 0.001 Input register
30271 Year & Month 2 1 Input register
30273 Day & Hour 2 1 Input register
30275 Minute & Second 2 1 Input register

30277 EF Trip 3 Cause 2 1 Input register


30279 R Phase Current 2 0.001 Input register
30281 Y Phase Current 2 0.001 Input register
30283 B Phase Current 2 0.001 Input register
30285 Earth Current 2 0.001 Input register
30287 Year & Month 2 1 Input register
30289 Day & Hour 2 1 Input register
30291 Minute & Second 2 1 Input register

30293 EF Trip 4 Cause 2 1 Input register


30295 R Phase Current 2 0.001 Input register
30297 Y Phase Current 2 0.001 Input register
30299 B Phase Current 2 0.001 Input register
30301 Earth Current 2 0.001 Input register
30303 Year & Month 2 1 Input register
30305 Day & Hour 2 1 Input register
30307 Minute & Second 2 1 Input register

30309 EF Trip 5 Cause 2 1 Input register


30311 R Phase Current 2 0.001 Input register
30313 Y Phase Current 2 0.001 Input register
30315 B Phase Current 2 0.001 Input register
30317 Earth Current 2 0.001 Input register
30319 Year & Month 2 1 Input register
30321 Day & Hour 2 1 Input register
30323 Minute & Second 2 1 Input register

30325 EF Trip 6 Cause 2 1 Input register


30327 R Phase Current 2 0.001 Input register
30329 Y Phase Current 2 0.001 Input register
30331 B Phase Current 2 0.001 Input register
30333 Earth Current 2 0.001 Input register
30335 Year & Month 2 1 Input register
30337 Day & Hour 2 1 Input register
30339 Minute & Second 2 1 Input register

30341 EF Trip 7 Cause 2 1 Input register


30343 R Phase Current 2 0.001 Input register
30345 Y Phase Current 2 0.001 Input register
30347 B Phase Current 2 0.001 Input register
30349 Earth Current 2 0.001 Input register

-32-
MEMORY MAP

30351 Year & Month 2 1 Input register


30353 Day & Hour 2 1 Input register
30355 Minute & Second 2 1 Input register

30357 EF Trip 8 Cause 2 Input register


30359 R Phase Current 2 0.001 Input register
30361 Y Phase Current 2 0.001 Input register
30363 B Phase Current 2 0.001 Input register
30365 Earth Current 2 0.001 Input register
30367 Year & Month 2 1 Input register
30369 Day & Hour 2 1 Input register
30371 Minute & Second 2 1 Input register

30373 EF Trip 9 Cause 2 1 Input register


30375 R Phase Current 2 0.001 Input register
30377 Y Phase Current 2 0.001 Input register
30379 B Phase Current 2 0.001 Input register
30381 Earth Current 2 0.001 Input register
30383 Year & Month 2 1 Input register
30385 Day & Hour 2 1 Input register
30387 Minute & Second 2 1 Input register

30389 EF Trip 10 Cause 2 1 Input register


30391 R Phase Current 2 0.001 Input register
30393 Y Phase Current 2 0.001 Input register
30395 B Phase Current 2 0.001 Input register
30397 Earth Current 2 0.001 Input register
30399 Year & Month 2 1 Input register
30401 Day & Hour 2 1 Input register
30403 Minute & Second 2 1 Input register

30405 EF Trip 11 Cause 2 1 Input register


30407 R Phase Current 2 0.001 Input register
30409 Y Phase Current 2 0.001 Input register
30411 B Phase Current 2 0.001 Input register
30413 Earth Current 2 0.001 Input register
30415 Year & Month 2 1 Input register
30417 Day & Hour 2 1 Input register
30419 Minute & Second 2 1 Input register

30421 EF Trip 12 Cause 2 1 Input register


30423 R Phase Current 2 0.001 Input register
30425 Y Phase Current 2 0.001 Input register
30427 B Phase Current 2 0.001 Input register
30429 Earth Current 2 0.001 Input register
30431 Year & Month 2 1 Input register
30433 Day & Hour 2 1 Input register

-33-
MEMORY MAP

30435 Minute & Second 2 1 Input register

30437 EF Trip 13 Cause 2 1 Input register


30439 R Phase Current 2 0.001 Input register
30441 Y Phase Current 2 0.001 Input register
30443 B Phase Current 2 0.001 Input register
30445 Earth Current 2 0.001 Input register
30447 Year & Month 2 1 Input register
30449 Day & Hour 2 1 Input register
30451 Minute & Second 2 1 Input register

30453 EF Trip 14 Cause 2 1 Input register


30455 R Phase Current 2 0.001 Input register
30457 Y Phase Current 2 0.001 Input register
30459 B Phase Current 2 0.001 Input register
30461 Earth Current 2 0.001 Input register
30463 Year & Month 2 1 Input register
30465 Day & Hour 2 1 Input register
30467 Minute & Second 2 1 Input register

30469 EF Trip 15 Cause 2 1 Input register


30471 R Phase Current 2 0.001 Input register
30473 Y Phase Current 2 0.001 Input register
30475 B Phase Current 2 0.001 Input register
30477 Earth Current 2 0.001 Input register
30479 Year & Month 2 1 Input register
30481 Day & Hour 2 1 Input register
30483 Minute & Second 2 1 Input register
Maximum Current
30485 R Phase Current 2 0.001 Input register
30487 Y Phase Current 2 0.001 Input register
30489 B Phase Current 2 0.001 Input register
30491 Earth Current 2 0.001 Input register
Starting Current
30493 R Phase Current 2 0.001 Input register
30495 Y Phase Current 2 0.001 Input register
30497 B Phase Current 2 0.001 Input register
30499 Earth Current 2 0.001 Input register
Instantaneous Current
30501 R Phase Current 2 0.001 Input register
30503 Y Phase Current 2 0.001 Input register
30505 B Phase Current 2 0.001 Input register
30507 Earth Current 2 0.001 Input register
Note: If current is more than 9999A then, value 0x2d2d2d2d will be returned ( -----).

-34-
MEMORY MAP

Read Write parameters

Address Parameter Word MF Remarks


40001 OCLS 1 0.01 Holding register
Note: Setting range= 0.20 to 2.00
Incremental step= 0.01
40002 OC Char 1 1 Holding register
Note: Min value(0)
Max value (6)
0 - NI1.3
1 - NI3
2 - VI
3 - EI
4 - D1
5 - D10
6 - D100
40003 OC TMS 1 0.01 Holding register
Note: Setting range= 0.01 to 1.6
Incremental step= 0.01
40004 OCHS 1 0.01 Holding register
Note: Setting range= DSB, 0.2 to 40.0
Incremental step= 0.1
40005 OCTD 1 0.01 Holding register
Note: Setting range= DSB, 0.05, 0.1 to 2.00
Incremental step= 0.01
40006 EF LS 1 0.01 Holding register
Note: Setting range= 0.05 to 0.80
Incremental step= 0.01
40007 EF Char 1 1 Holding register
Note: Min value= 0
Max value= 6
0 - NI1.3
1 - NI3
2 - VI
3 - EI
4 - D1
5 - D10
6 - D100
40008 EF TMS 1 0.01 Holding register
Note: Setting range= 0.01 to 1.60
Incremental step= 0.01
40009 EFHS 1 0.01 Holding register
Note: Setting range= DSB, 0.05 to 20.0
Incremental step= 0.1
40010 EFTD 1 0.01 Holding register
Note: Setting range= DSB, 0.1 to 2.00
Incremental step= 0.01

-35-
MEMORY MAP

40011 T.RST 1 0.01 Holding register


Note: Setting range= DSB, 0.1 to 10.0
Incremental step= 0.1
40012 PH.CTR 1 1 Holding register
Note: Setting range = 1 to 9999
Incremental step= 1
40013 E.CTR 1 1 Holding register
Note: Setting range = 1 to 9999
Incremental step= 1
RTC Settings
40014 YEAR 1 1 Holding register
40015 MONTH 1 1 Holding register
40016 DAY 1 1 Holding register
40017 HOUR 1 1 Holding register
40018 MINUTE 1 1 Holding register
40019 SECOND 1 1 Holding register
CT Rating
40020 CT Rating 1 1 Holding register
Note: 0 - P1E1
1 - P5E1
2 - P1E5
3 - P5E5
Breaker Operating Time of Downstream Relay
40021 BOT 1 0.01 Holding register
Note: Setting range= 0.01 to 0.25
Incremental step= 0.01
RS485 Settings
40022 Node Address 1 1 Holding register
Note: Setting range= 1 to 247
Incremental step= 1
40023 Baud rate 1 1 Holding register
Note: 0 - 9600
1 - 4800
2 - 2400
40024 Parity 1 1 Holding register
Note: 0 - No parity
1 - Even parity
2 - Odd parity
Password
40025 Password 1 1 Holding register
Note:
1) Password is a Write Only parameter.
2) For changing (Write operation) the parameters, first password (user password or Master
password) has to be entered in logic address 40025, and then parameters will be
enabled for writing. Once the password is enabled idle time is 30 seconds and then
comes out of programming mode.

-36-
MEMORY MAP

COILS

Address Parameter Bit MF Remarks


Relay Output Contacts Configuration for Over Current (OC)
50001 OC STARTER R2 1 NA Coil
50002 OC STARTER R3 1 NA Coil
50003 OC STARTER R4 1 NA Coil

50004 OCLS R1 1 NA Coil


50005 OCLS R2 1 NA Coil
50006 OCLS R3 1 NA Coil
50007 OCLS R4 1 Coil

50008 OCHS R1 1 NA Coil


50009 OCHS R2 1 NA Coil
50010 OCHS R3 1 NA Coil
50011 OCHS R4 1 NA Coil
Note: 0 - Not Selected
1 - Selected
Relay Output Contacts Configuration for Earth Fault (EF)
50012 EF STARTER R2 1 NA Coil
50013 EF STARTER R3 1 NA Coil
50014 EF STARTER R4 1 NA Coil

50015 EFLS R1 1 NA Coil


50016 EFLS R2 1 NA Coil
50017 EFLS R3 1 NA Coil
50018 EFLS R4 1 NA Coil

50019 EFHS R1 1 NA Coil


50020 EFHS R2 1 NA Coil
50021 EFHS R3 1 NA Coil
50022 EFHS R4 1 NA Coil
Note: 0 - Not Selected
1 - Selected
Starter Configuration (OC STR) for Blocking Output
50023 LS 1 NA Coil
50024 HS 1 NA Coil
Note: 0 - Not Selected
1 – Selected
Starter Configuration (EF STR) for Blocking Output
50025 LS 1 NA Coil
50026 HS 1 NA Coil
Note: 0 - Not Selected
1 - Selected
50027 Reset 1 NA Coil
Note: 0 – Self Reset
1 - Hand reset

-37-
MEMORY MAP

Breaker Open/Close
Relay R3 Selection for
Breaker Open
50028 Functionality 1 NA Coil
Breaker open CMD
50029 (write only) 1 NA Coil
Note: If Relay R3 selected for Breaker Open Functionality & Breaker Open command is
received then Breaker will Open.
0 - Not Selected
1 - Selected
Relay R4 Selection for
Breaker Close
50030 Functionality 1 NA Coil
Breaker Close
50031 CMD(write only) 1 NA Coil
Note: If Relay R4 selected for Breaker Close Functionality & Breaker Close command is
received then Breaker will Close.
0 - Not Selected
1 - Selected
Blocking Input for Pilot Wire Co-ordination
50032 OC- LS 1 NA Coil
50033 OC- HS 1 NA Coil
50034 EF-LS 1 NA Coil
50035 EF-HS 1 NA Coil
Note: 0 - Not Selected
1 - Selected
Auto Doubling
50036 Auto Doubling 1 NA Coil
Note: 0 - Not Selected (Off)
1 - Selected (On)
Relay Output Contact Status
50037 R1 1 NA Coil
50038 R2 1 NA Coil
50039 R3 1 NA Coil
50040 R4 1 NA Coil
Note: 0 - De-energised State
1 - Energised State
Coil Addresses 50037 to 50040 are READ ONLY and do not require prior password write.
Digital input status
50041 D1 1 NA Coil
50042 D2 1 NA Coil
50043 D3 1 NA Coil
Note: 0 - Inactive
1 - Active
Coil Addresses from 50041 to 50043 are READ ONLY and do not require prior password write.

-38-
MEMORY MAP

50044 Relay test 1 NA Coil


50045 Reset relay 1 NA Coil
50046 Clear Trip data 1 NA Coil
Clear Maximum
50047 current 1 NA Coil
Note: Coil Addresses from 50044 to 50047 are WRITE ONLY.
Reset relay is same as Reset Key function. Relay reset will work only in
Hand reset mode.
1 - Execute respective action

Note:
1) Response timeout value 650 msec required for 50046 (Clear Trip Data) since 30 trip
records have to be erased from the non-volatile memory.
2) For all other parameters 300 msec response time out can be given.

-39-
PRODUCT ORDERING INFORMATION

10. ORDERING INFORMATION

CAT.NO. F51/F51N F50/F50N 4NO STD. 2NO-2NC Communication

MC31ANX4000 a a
MC31ANX2200 a a
MC61ANX4000 a a a
MC61ANX2200 a a a
MC61CNX4000 a a a a

-40-
WARRANTY
LARSEN & TOUBRO (L&T) warrants that the protective Relay model MC61C-nX will meet L&T's published
specifications and will be free from defects in workmanship and materials for a period of
12 months from the date of shipment. L&T's obligation under this warranty shall be limited to servicing
or replacing the defective parts provided that notice of such defects and satisfactory proof thereof is
given to L&T by it's customer within the warranty period.

This warranty does not cover any defect caused by accident, misuse, neglect alteration, modification
or substitution of any of the components or parts or any attempts at internal adjustment by
unauthorized service personnel.

Under no circumstances shall L&T be liable for any consequential damage, resulting injury, loss or
expense, directly or indirectly, arising from the use of this product.

This foregoing warranty is in lieu of all other warranties expressed or implied and is the sole and
exclusive remedy for any claim arising from the defect in the product.

DISCLAIMER

Sufficient care is taken to provide all information regarding the product but L&T does not claim any
responsibility for the damages caused by using the product directly or indirectly.

L&T Electrical & Automation

Manufactured by:

L&T Electrical & Automation


Larsen & Toubro Limited
KIADB Industrial Area
Hebbal , Hootagalli, Mysore 570018
Karnataka,INDIA
Website: www.lntebg.com & www.larsentoubro.com
Contact: Toll free number 1800 233 5858
e-mail : cic@lntebg.com

©2014 LARSEN & TOUBRO LIMITED

Das könnte Ihnen auch gefallen