Acquisition Modes
a) Enable
When RTU/FRTU/FPI is enabled, the data is scanned in normal fashion
and control command execution is allowed.
b) Disable
When RTU/FRTU/FPI is disabled, the data scanning & control execution is
disabled. This is equivalent to” delete from scan “of complete RTU.
c) Test /Maintenance
The SCADA/DMS system will be synchronised from the GPS based Time and
frequency system. The SCADA system shall synchronise the time of all connected
RTUs/FRTUs/FPI every 15 minutes (user configurable from 5 minutes to 24 hrs )
using time synchronisation message in the IEC 870-5-104/101 protocol
/NTP/SNTP. The servers /Workstations at SCADA/DMS control centre shall be
synchronised using NTP/SNTP . The time of DR centre shall also be synchronised
from the GPS based system installed in one of the SCADA/DMS control centre in
the state.
The SCADA/DMS System shall exchange data with ISR System & ISR System
shall be the nodal interface with all IT System. The Data Center, DR Center and
Customer Care Center under IT System, shall exchange data with the ISR System,
using Open Standards like CIM/XML & IEC 61968 Series Standards for Power
System, OPC, ICCP/TASE.2., ODBC
SECTION-2, CHAPTER-1 : SCADA FUNCTIONS page 6 of 17