CLIENT : DESIGN BY :
JOB NO. : DATE : REVIEW BY :
Combined Footing Design Based on ACI 318-19
ANALYSIS
DESIGN LOADS AT TOP OF FOOTING (IBC SEC.1605.3.2 & ACI 318 5.3.1)
SERVICE LOADS COL # 1 COL # 2 TOTAL
CASE 1 : DL + LL P = 23 k 30 k 53 k
(e = 8.33 ft, fr CL ftg )
CASE 2 : DL + LL + E / 1.4 P = -48 k 101 k 53 k
M = 5.0 ft-k 5.7 ft-k 10.7 ft-k
(e = 116.76 ft, fr CL ftg )
V = 6 k 6 k 11 k
CASE 3 : 0.9 DL + E / 1.4 P = -58 k 89 k 32 k
M = 5.0 ft-k 5.7 ft-k 10.7 ft-k
(e = 188.87 ft, fr CL ftg )
V = 6 k 6 k 19 k
FACTORED LOADS
CASE 1 : 1.2 DL + 1.6 LL Pu = 31 k 40 k 71 k
( eu = 5.00 ft, fr CL ftg )
CASE 2 : 1.2 DL + 1.0 LL + 1.0 E Pu = -74 k 134 k 60 k
Mu = 7.0 ft-k 8.0 ft-k 15.0 ft-k
( eu = 142.84 ft, fr CL ftg )
Vu = 8 k 8 k 16 k
CASE 3 : 0.9 DL + 1.0 E Pu = -87 k 118 k 32 k
Mu = 7.0 ft-k 8.0 ft-k 15.0 ft-k
( eu = 262.42 ft, fr CL ftg )
Vu = 8 k 8 k 16 k
CHECK OVERTURNING FACTOR (2018 IBC 1605.2.1, 1808.3.1, & ASCE 7-10 12.13.4)
MR / MO = 7.92 > F = 0.75 / 0.9 = 0.83 [Satisfactory]
Where MO = MLAT 1 + MLAT 2 + (VLAT 1 + VLAT 2) T - PLAT 1(L - L1) - PLAT 2L2 = 3027 9114 k-ft
Pftg = (0.15 kcf) T B L = 450 k, footing weight
Psoil = ws (Df - T) B L = 1440 k, soil weight
MR = PDL 1(L - L1) + PDL 2L2 + 0.5 (Pftg + Psoil) L = 72200 k-ft
CHECK SOIL BEARING CAPACITY (ACI 318 13.3.1.1)
Where 6e [Satisfactory]
P 1 L
, for e L
q MAX BL 6
2 P L
, for e
3B (0.5L e )
6
Mu
T 4 '
0.85 f c 1 1
MIN MIN 0.0018 ,
'
0.383b d 2 f c
d 3
f y
700
600
500
400
300
200 M
100
0
40
20
0
V
-20
-40
FOOTING MOMENT & SHEAR AT LONGITUDINAL SECTIONS FOR CASE 2
Section 0 0.5 L1 L1 left L1 right 0.2 S 0.4 S 0.6 S 0.8 S L2 left L2 right 0.5 L2 L
Xu (ft) 0 18.00 36.00 36.00 42.00 48.00 54.00 60.00 66.00 66.00 84.00 102.00
Mu,col (ft-k) 0 0 0 67 1,736 3,405 5,074 6,743 8,412 8,451 7,305 6,125
Vu,col (k) 0 0.0 0.0 -278.2 -278.2 -278.2 -278.2 -278.2 -278.2 65.6 65.6 65.6
Pu,surch (klf) 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75
Mu,surch (ft-k) 0 -122 -486 -486 -662 -864 -1094 -1350 -1634 -1634 -2646 -3902
Vu,surch (k) 0 13.5 27.0 27.0 31.5 36.0 40.5 45.0 49.5 49.5 63.0 76.5
Pu,ftg & fill (klf) 6.39 6.39 6.39 6.39 6.39 6.39 6.39 6.39 6.39 6.39 6.39 6.39
Mu,ftg & fill (ft-k) 0 -1035 -4141 -4141 -5636 -7361 -9317 -11502 -13917 -13917 -22544 -33241
Vu,ftg & fill (k) 0 115.0 230.0 230.0 268.4 306.7 345.1 383.4 421.7 421.7 536.8 651.8
qu,soil (ksf) 0.31 0.57 0.82 0.82 0.91 0.99 1.08 1.17 1.25 1.25 1.51 1.77
Mu,soil (ft-k) 0 480 2337 2337 3370 4649 6196 8035 10188 10188 18770 31017
Vu,soil (k) 0 -59.1 -153.0 -153.0 -192.0 -234.8 -281.5 -332.1 -386.5 -386.5 -572.8 -793.8
S Mu (ft-k) 0 -676 -2289 -2222 -1191 -172 859 1925 3049 3088 885 0
S Vu (kips) 0 69.4 104.1 -174.1 -170.2 -170.2 -174.1 -181.8 -193.4 150.3 92.5 0
4000
3000
2000
1000
0
-1000 M
-2000
-3000
200
100
0
-100
V
-200
-300
4000
3000
2000
1000
0
-1000 M
-2000
-3000
200
150
100
50
0
-50
-100 V
-150
-200
-250
DESIGN FLEXURE
Location Mu,max d (in) r min rreqD rmax smax(in) use rprovD
Top Longitudinal -2435 ft-k 45.37 0.0019 0.0030 0.0155 no limit 10 # 10 @ 9 in o.c., cont. 0.0031
Bottom Longitudinal 3088 ft-k 44.37 0.0019 0.0041 0.0155 18 13 # 10 @ 7 in o.c., cont. 0.0041
Bottom Transverse, be 1 ft-k / ft 43.42 0.0006 6.93E-06 0.0155 18 8 # 5 @ 12 in o.c. 0.0006
[Satisfactory]
CHECK FLEXURE SHEAR
Direction Vu,max fVc = 2 f b d (fc')0.5 check Vu < f Vc
Longitudinal 193 k 328 k [Satisfactory]
Transverse 0 k / ft 43 k / ft [Satisfactory]
CHECK PUNCHING SHEAR (ACI 318 13.2.7.2, 22.6.4.1, 22.6.4.3, & 8.4.2.3)
P u R 0.5 v M u b1 A P 2 b1 b 2 d
v u ( psi )
J v c ( psi ) 2 y f 'c
AP 1
v 1 d
d b3 d 2 b 2 2 b1 y MIN 2,
4
, 40
J 1 1 1
3 c b 0
6
1
b b1 3 b2
A
P b b
A f Bb e b 0 P , b1 c1 d , b 2 c 2 d
R u 1 2 d
Af
[Satisfactory]
ft, fr CL ftg )
ft, fr CL ftg )
ft, fr CL ftg )
ft, fr CL ftg )
ft, fr CL ftg )
ft, fr CL ftg )
(cont'd)
V
(cont'd)
[Satisfactory]
(cont'd)
PROJECT : PAGE :
CLIENT : DESIGN BY :
JOB NO. : DATE : REVIEW BY :
Seismic Design for Combined Footing, Based on ACI 318-19
DESIGN SUMMARY
CONCRETE STRENGTH fc' = 3 ksi
REBAR YIELD STRESS fy = 60 ksi
FOOTING WIDTH W = 90 in
FOOTING THICKNESS D = 48 in
DISTANCE BETWEEN COLUMNS L = 30 ft
ANALYSIS
CHECK GB SECTION REQUIREMENTS (ACI 18.6.2)
Ln=L - c1 = 28.50 ft > 4d= 14.58 ft [Satisfactory]
W/D= 1.88 > 0.3 [Satisfactory]
W = 90 in > 10 in [Satisfactory]
< c1+1.5D = 90 in [Satisfactory]