Protection Automation Control

PCS-902
Line Distance Relay

The PCS-902 provides comprehensive protection and control The PCS-902 employs a wide range of innovative patented
solutions for transmission lines with high-speed sub-cycle technologies, such as DPFC (Deviation Power Frequency
distance element. The PCS-902 is intended for application on Component) distance protection and unique power swing
overhead lines and underground cables with diverse voltage blocking releasing logic. Thus, guaranteeing accurate and
levels. These include series compensated, double-circuit, reliable operations.
heavily loaded, weak infeed (WI), short and long lines. It can
meet the requirements of single-pole or three-pole tripping; The PCS-902 is compatible with IEC 61850 station level and
it also provides single and/or three-pole auto-reclosing process level applications. It supports IEC 61850-8-1 MMS,
functions. The PCS-902 is suitable for single and dual-breaker GOOSE and IEC 61850-9-2 Sampled Value. The front panel
applications, providing optional dual CT inputs, dual breaker RJ-45 port is provided for testing and setting, allowing for
failure protections, dual breaker auto-reclosing and dual smoother commissioning and maintenance.
synchro-checks. Additionally, the relay integrates the remote/
local control of circuit breaker, disconnector and earth switch.

PCS-902

Figure 1 PCS-902 Functional Block Diagram

8
www.nrec.com/en

Stub differential protection is introduced to protect the T-zone in


Functions

Transmission Line
one-and-a-half breaker and ring breaker arrangements.
Protection and Control

Protection
• Five zone phase-to-phase distance protection (21P) • Three stages undervoltage protection (27P)
Directional, load encroachment, power swing blocking releasing Time characteristics is selectable between definite-time and
and unique low-voltage elements are provided for phase-to- inverse-time. Phase voltage or phase-to-phase voltage can be
phase distance protection. selected for protection calculation. “1-out-of-3” or “3-out-of-3”
logic can be selected for protection criterion.
• Phase-to-phase distance protection for pilot scheme (85)
The relay provides an independent zone for pilot scheme of • Three stages overvoltage protection (59P)
PUTT, POTT, Blocking, Unblocking, DTT & Zone Extension. Time characteristics is selectable between definite-time and
The scheme integrates current reversal logic, weak-infeed inverse-time. Phase voltage or phase-to-phase voltage can be
echo and open breaker echo. selected for protection calculation. “1-out-of-3” or “3-out-of-3”
logic can be selected for protection criterion.
• Five zone phase-to-ground distance protection (21G)
The reactance characteristic, directional, load encroachment, • One stage negative-sequence overvoltage protection (59Q)
power swing blocking releasing and unique low-voltage
elements are provided for phase-to-ground distance protection. • Three stages residual overvoltage protection (59G)
Stage 1 is definite-time characteristic, stage 2 and 3 can be
• Phase-to-ground distance protection for pilot scheme (85) selected as definite-time or inverse-time characteristic, only
The relay provides an independent zone for pilot scheme of VWDJHFDQEHGH¿QHGIRUWULSSXUSRVHRUDODUPSXUSRVH
PUTT, POTT, Blocking, Unblocking, DTT & Zone Extension.
The scheme integrates current reversal logic, weak-infeed • Four stage overfrequency protection (81O)
echo and open breaker echo. Frequency is calculated by using the positive sequence voltage.

• High-speed DPFC distance protection (21D) • Four stage underfrequency protection (81U)
Innovative Deviation of Power Frequency Component Frequency is calculated by using the positive sequence
(DPFC) distance protection quickly clears faults in a sub- voltage. The df/dt element is provided for the supervision of
F\FOH'3)&LVLPPXQHWRWKHORDGÀXFWXDWLRQZHDNLQIHHG underfrequency protection.
and power swing.
• Phase overcurrent protection during VT failure (50PVT)
• Pilot directional earth-fault protection (85) Independent phase overcurrent protection is automatically
The relay includes directional zero sequence comparison enabled to substitute the phase-to-phase distance protection,
element for earth faults. The pilot scheme integrates current which is blocked during VT failure.
reversal logic, weak-infeed echo and open breaker echo.
• Ground overcurrent protection during VT failure (50GVT)
• Four stages phase overcurrent protection (50/51P) Independent ground overcurrent protection is automatically
6HOHFWDEOHWLPHFKDUDFWHULVWLFV GH¿QLWHWLPHRULQYHUVHWLPH  enabled to substitute the phase-to-ground distance protection,
and directional elements (forward, reverse or non-directional) which is blocked during VT failure.
are provided. A harmonic blocking function is integrated to
• Switch-onto-fault (SOTF) logic
restrain each stage independently.
Switch-onto-fault logic is used to clear the faults during manual
• Four stages earth fault protection (50/51G) closing and auto-reclosing.
6HOHFWDEOHWLPHFKDUDFWHULVWLFV GH¿QLWHWLPHRULQYHUVHWLPH 
• Unique power swing blocking releasing logic (PSBR)
and directional elements (forward, reverse or non-directional)
The power swing blocking releasing logic prevents mal-
are provided. A harmonic blocking function is integrated to
operations during external faults in power swing situations. It
restrain each stage independently.
quickly clears the internal faults in power swing scenarios.
• Four stages negative-sequence overcurrent protection
• Out-of-step protection (78)
(50/51Q)
6HOHFWDEOHWLPHFKDUDFWHULVWLFV GH¿QLWHWLPHRULQYHUVHWLPH  • Broken conductor protection (46BC)
and directional elements (forward, reverse or non-directional) 7KH UDWLR RI QHJDWLYH WR SRVLWLYH VHTXHQFH FXUUHQW ǿǿ  LV
are provided. Stage 4 can be set to alarm. adopted to detect the broken conductor.

• Breaker failure protection for one or two breakers (50BF) • Dead zone protection (50DZ)
Breaker failure protection can be applied to single-breaker It is provided to clear the dead zone faults between CT and breaker.
and dual-breaker applications.
• Thermal overload protection (49)
• Stub differential protection (87STB) Thermal accumulation using thermal models is implemented for

9
Protection Automation Control

overload protection. Two stages for alarm purpose or tripping • Pilot communication channel supervision
purpose are provided.
• System frequency supervision
• Pole discrepancy protection (62PD) • Clock synchronization using IRIG-B, SNTP, PPS (Pulse-Per-
It can be initiated by three auxiliary contacts of phase- Second) and PPM (Pulse-Per-Minute) , IEEE1588
segregate circuit breaker, and it can select zero-sequence
current or negative-sequence current as auxiliary criterion.
Communication
• Reverse power protection (32R) • 2SWLRQDOVLQJOHRUGXDOSLORWFKDQQHOV ¿EHURSWLF FRPSO\LQJ
The reverse power protection monitors the direction of with G.703 and C37.94
DFWLYHSRZHUÀRZDQGSLFNVXSZKHQWKHPHFKDQLFDOHQHUJ\
• Up to four 10Base-T/100Base-TX copper Ethernet ports using
fails. This function can be used for operational shutdown
IEC 61850, DNP3.0 or IEC 60870-5-103 over TCP/IP
(sequential tripping) of the generator but also prevents
damage to the steam turbines. • Up to two 100Base-FX optical Ethernet ports using IEC 61850,
DNP3.0 or IEC 60870-5-103 over TCP/IP ( Sharing two copper
• Single and/or three-pole auto-reclosing (single-breaker or Ethernet ports)
dual-breaker) (79)
Single/three pole auto-reclosing is provided for single- and • Two RS-485 serial ports using IEC 60870-5-103
dual-breaker applications. Priority logic is integrated for the • One RS-485 serial port for clock synchronization
applications of one-and-a-half breaker and ring breaker
• Optional Sampling value and GOOSE communication module
arrangements.
with six optical Ethernet ports using IEC 61850-9-2 and IEC
• Remote/local control 61850-8-1 GOOSE
The control of circuit breaker, disconnector and earth switch
• Support of IEC 61850 Edition 2
can be implemented via communication, LCD menu and
binary inputs. User programmable interlocking logics are • Support of IEC 62439-3 PRP and HSR protocols
available by PCS-Explorer.
• Cyber security in accordance with NERC CIP

• Synchronism check (25)


Synchro-check can be used for auto-reclosing and manual User Interface
closing for single-breaker and dual-breaker. • HMI interface with large-size LCD and 9-button keypad on
the front panel
• Voltage and current drift auto adjustment.
The relay continually and automatically traces the voltage • Support setup up to 40 users and allow each user to own
and current drifts and adjusts the zero point to acquire different password and access authority
accurate measurements.
• Provide some function shortcuts key, which can be
FRQ¿JXUHGE\3&6([SORUHUDQGEHIXO¿OOHGE\FRPELQDWLRQ
• Frequency tracking.
key of devices' keypad, to execute some operation quickly.
Frequency tracking is provided to accommodate the
frequency shifts in power system. • One front RJ-45 port for testing and setting

• One RS-232 or RS-485 rear port for printer


Monitoring and Measurement
• Language selection – English + selected language
• Energy measurement (active and reactive energies for
import and export) • Assistant software - PCS-Explorer

• CT circuit failure supervision

• VT circuit failure supervision Features


• Fault phase selection • 7KHXQLTXH'3)&SURWHFWLRQSULQFLSOH¿UVWO\LQWURGXFHGE\
NR Electric, employs superimposed increscent quantities as
• Fault Locator with parallel-line compensation
protection criteria, which provides high speed fault clearance
• Self diagnostic DQGLVLPPXQHWRSRZHUVZLQJDQGORDGÀXFWXDWLRQ

• Event recorder including 1024 change-of-binary-input events,


• A unique two-out-two logic is adopted in hardware design to
1024 supervision events, 256 control logs and 1024 device
improve security. Coordinating with the redundant scheme,
logs
this solution improves both security and dependability of
• Disturbance recorder including 32 disturbance records with protection system. The two independent data acquisition
waveforms (The format is compatible with COMTRADE.) paths are provided to prevent mal-operation caused by

10
www.nrec.com/en

component failure. One works as a fault detector and the • &RPSUHKHQVLYHÀH[LELOLW\LVDFKLHYHGYLDPRGXODUKDUGZDUH

Transmission Line
other is designed for protection logic. Tripping outputs are design, scalable function library, programmable logics,

Protection
supervised by both data acquisition paths. configurable I/Os and definable LEDs. It allows users to
FUHDWHFXVWRPL]HGVFKHPHVIRUWKHVSHFL¿FSURMHFWV¿[HG
• 6HOIDGDSWLYHÀRDWLQJWKUHVKROGZKLFKRQO\UHÀHFWVGHYLDWLRQ /('VDQGGH¿QDEOHFRORU/('V *UHHQ<HOORZ5HG DUH
of power frequency components improves the sensitivity and provided.
UHOLDELOLW\GXULQJORDGÀXFWXDWLRQDQGV\VWHPGLVWXUEDQFH
• The relay is fully compatible with IEC 61850, including station
• The unique power swing blocking releasing logic can bus communication and process bus communication. It
properly supervise the distance protection during power provides up to 6 Ethernet ports for process bus with IEC 61850-
swing, which ensures the distance protection will operate 9-2 Sampled Value and IEC 61850-8-1 GOOSE, as well as up
correctly for internal faults during power swing, and prevents to 4 Ethernet ports for station bus with IEC 61850- 8-1 MMS.
distance protection from mal-operation during power swing.
• Powerful disturbance recording function is integrated in the
• Fast clearance of the faults within the protected zone is relay for post-fault analysis. Up to 32 disturbance records
achieved by this relay. The typical operating time is less than can be stored in non-volatile memory. Each report includes
10 ms for close-up faults, less than 15ms for medium-zone 250-cycle to 500-cycle waveform records with settable pre-
faults and less than 25ms for remote-end faults. fault waveform.

11